NEC Code Calculations Fall 2015 22.525 Prof Thomas For these calculations, we are assuming we are located in Lowell, MA. 690.7 Maximum Voltage Why calculate this? To make sure cables, disconnects, overcurrent devices and other equipment are rated to handle the highest possible voltage the system could produce. Also, to make sure voltage should remain within max power point (MPP) range of inverter. Variables include minimum temperature, module specifications, and string size Note: it says to use Table 690.7 unless open-circuit voltage temperature coefficients are supplied by the manufacturer. If they are, then use those instead of the table. Since just about every manufacturer includes these temperature coefficients in their data sheets, Table 690.7 is seldom necessary. As temperature decreases, voltage increases. Hence, at ambient temperatures below 25° C, modules’ voltages will be greater than rated. Hence, it is necessary to correct for colder temperatures when calculating max system voltage. Example: SunPower X21 335/345 Modules Datasheet: Temp coefficient for open circuit voltage (TVOC) = -167.4 mV/°C To find the appropriate cold temperature to use, consult the ASHREA Fundamentals Handbook. Or, go on-line to this website and simply enter the city & state: www.solarabcs.org/about/publications/reports/expedited-permit/map/index.html 1 NEC Code Calculations Fall 2015 22.525 Prof Thomas ASHRAE temp for Lowell, MA: -18 °C Note: this is NOT the record cold temperature for Lowell. Rather, it is the “extreme annual mean minimum design dry bulb temperature”, meaning that 99% of the time, the temperature will be greater than this cold temperature. Hence, it is realistic and sufficient, per the informational note in the NEC in 690.7, to use this temperature for these calculations. (ASHRAE does not have these temperatures for every location, so use the one closest to the PV system’s site. In this example, we are using the temperature from Lawrence, MA.) Temperature difference (dT) between ASHRAE cold temp and STC temp: ππ = −18β − 25β = −43β Voltage increase because of temp below STC: ππ × πVOC = −43β × −0.1674 π = 7.20π β From table above, for 335W module, open circuit voltage: VOC = 67.9 V Expected voltage of module at cold temp: 67.9V + 7.2V = 75.1 V Assuming there are 7 modules per string: πππ₯ ππ¦π π‘ππ ππππ‘πππ = # ππ ππππ’πππ πππ π π‘ππππ × max ππππ’ππ π£πππ‘πππ = 7 × 75.1 = 536π For 1 or 2 family dwellings, max voltage shall be permitted up to 600 V. Other installations may have a max voltage up to 1000 V. 2 NEC Code Calculations Fall 2015 22.525 Prof Thomas Second example: Given: 12 Jinko 255P Modules per string in Sacramento, CA. Find max system voltage corrected for temperature. For the high temperature to use, again consult the ASHREA temp found here: www.solarabcs.org/about/publications/reports/expedited-permit/map/index.html Solution: VOC = 38.0V (TVOC) = -0.31%/°C (Note that this is a percentage!) ASHRAE temp for Sacramento, CA: -3 β ππ = −3β − 25β = −28β Increase in VOC for each module due to temp: ππ × πVOC × πππΆ = −28β × (−0.0031) 1 × 38.0π = 3.30π β 38.0V + 3.30V = 41.3V πππ₯ ππ¦π π‘ππ ππππ‘πππ = # ππ ππππ’πππ πππ π π‘ππππ × max ππππ’ππ π£πππ‘πππ = 12 × 41.3 = 496π 3 NEC Code Calculations Fall 2015 22.525 Prof Thomas 690.8 Circuit Sizing and Current Calculation of max circuit current. Here, we determine the max current that will be flowing from the PV array, through the combiner boxes and protection devices into the inverter. Start with short circuit current for PV module. In this case, using the 335 W module in the table above, ISC = 6.23 A. Then, per 690.8(A)(1), ISC must be multiplied by 1.25 to account for currents > ISC that can occur around solar noon on very sunny, cold days: πΌπππ₯1 = πΌππΆ × 1.25 = 6.23π΄ × 1.25 = 7.79 π΄ Remember, modules in a single string are connected in series, so the current flowing through each module is the same as the current flowing out of the string of modules. Thus, the max current calculated above is the current to plan for as the “PV Source Circuit Current”. Let’s assume there are two strings and their respective outputs are combined in a combiner box. The output current from this combiner box would therefore be twice the current from each string. Hence, the max current to plan for as the “PV Output Circuit Current” would be: πΌπππ₯2 = πΌπππ₯1 × ππ. ππ π π‘πππππ ππ ππππππππ = 7.79 π΄ × 2 = 15.6 π΄ Conductor Ampacity Calculations Why do this? Ampacity refers to the ability of a conductor to carry current safely. Higher ampacity means a higher current-carrying capability. We need to verify that the conductors in our PV systems will function safely under the conditions in which they will be used. Therefore, we need to compare their ampacity against the maximum currents we expect them to carry. The NEC says that “circuit conductors shall be sized to carry not less than the larger of 690.8(B)(1) or (2)”, so there are two ampacity calculations you have to make prior to selecting the right sized conductor. First calculation: 690.8(B)(1) simply says that the ampacity of a conductor must be equal to or greater than the max currents as calculated above (Imax1 and Imax2), multiplied by another 1.25. For this example, that means 7.79A X 1.25 = 9.74 A for the PV source conductors, and 15.6A X 1.25 = 19.5 A for the PV output circuit conductors. 4 NEC Code Calculations Fall 2015 22.525 Prof Thomas Second calculation: 690.8(B)(2) says to use the max currents calculated above after the application of adjustment and correction factors. This refers to corrections due to exposure to high temperatures (ampacity decreases as temperature increases). First, start with ambient temperature. Unlike max voltage, here we are concerned with high temperatures. One should use the ASHRAE temperature again, this time selecting the 2% average high temperature (it is below this temperature 98% of the time). You can find this temperature at the same website: www.solarabcs.org/about/publications/reports/expedited-permit/map/index.html For Lowell, this is 32β. If the PV system is on a roof, one then has to adjust this temperature higher, since the temperature on or just above the roof surface is considerably higher than ambient. Use table 310.15(B)(3)(c) “Ambient Temperature Adjustment for Raceways or Cables Exposed to Sunlight on or Above Rooftops” (Article 310 covers conductors for general wiring, into which PV system conductors fall). Let’s say our PV source and PV output currents flow through cables 4 inches above a roof. Per the table, we need to add 17β to the ambient temperature, or 32 + 17 = 49β. Okay, now we need to adjust a conductor’s ampacity based on this corrected ambient temperature. First, always use conductors with insulation types rated at least 90β-rated —standard practice in the PV industry. Then, go to table 310.15(B)(2)(a) “Ambient Temperature Correction Factors Based on 30β”, and enter the table using the temperature you just calculated above. In this example, that’s 49β. For that temperature, under the 90β conductor column, find the listed correction factor. Here, its 0.821. Now, take the max currents from 690.8(A) and divide them by this correction factor. In this example, that’s 7.79 A/0.82 = 9.50 A and 15.6 A/0.82 = 19.0 A. These are the minimum ampacities of the conductors after temperature correction. Okay, here’s a quick summary: Circuit PV Source PV Output 1 Method 1 (690.8(B)(1)) ISC X 1.25 X 1.25 9.74 A 19.5 A Method 2 (690.8(B)(2)) (ISC X 1.25)/temp correction factor 9.5 A 19.0 A You’ll get the same correction factor if you use table 690.31(E). 5 NEC Code Calculations Fall 2015 22.525 Prof Thomas Based on the results we can see that 690.8(B)(1) yields the higher currents, hence higher ampacity requirements. This is generally true in colder climates, but you always should check both methods to confirm this. Bottom line: you have to select a conductor with an ampacity greater than 9.74 A and 19.5 A for the source and output circuits, respectively. A quick glance at tables 310.15(B)(16) and 310.15(B)(17) will show you that even very small gauge wires meet these relatively low currents. For instance, say we are using copper 10 AWG USE-2 conductor for the PV source current, and copper 10 AWG THWN-2 for the PV output current (both 90β rated). Using table 310.15 (B)(17) for the USE-2 conductor (because the source circuit conductors are not in a raceway or cable but rather “in free air”), we find it has an ampacity of 55 A. Using table 310.15(B)(16) for the THWN-2 conductor (because after the combiner box, we are assuming it is now in a raceway), we find is has an ampacity of 40 A. However, there are two other factors to consider—overcurrent protection devices and voltage drop—before making a final decision on conductor sizing. 690.9 Overcurrent Protection Why do we need overcurrent protection? We do not want any equipment failing (because that will cause down time and lost production) nor do we want to cause any fires (because that will cause damage and potentially injury/death). Therefore, the NEC calls for protecting our circuits with appropriate devices. These are generally fuses and circuit breakers (CBs). With the exception of small arrays with only one or two strings, all PV systems will require overcurrent protection on both the dc and ac sides. These calculations are straightforward. 690.9 (B) states that “overcurrent device ratings shall be not less than 125 percent of the maximum currents calculated in 690.8 (A)”. The 125 percent is because PV conductors and overcurrent protection devices (OCPDs) are considered “continuous duty” equipment. Therefore, OCPDs must be rated at or above short circuit current times 1.25 times 1.25, or ISC X 1.56 for source circuits, and ISC X 1.56X # of strings for output circuits. For our example: Source circuit OCPDs must not be rated less than2: πΌππΆ × 1.56 = 6.23 × 1.56 = 9.72 π΄ Output circuit OCPDs must not be rated less than: Note that rounding caused a slight difference between multiplying by 1.56 vs. multiplying by 1.25 twice. Since we always round up to the highest integer, this is not a factor. 2 6 NEC Code Calculations Fall 2015 22.525 Prof Thomas πΌππΆ × 1.56 × # ππ π π‘πππππ ππ ππππππππ = 6.23 × 1.56 × 2 = 19.4 π΄ Article 240.6(A) lists standard size fuses and circuit breakers. The minimum size OCPD we need to use is the next standard size greater than the values calculated above, e.g., 10 A and 20 A fuses, respectively, for the source and output circuits (or 15 A and 20 A CBs, since the smallest standard size CB is 15 A). Usually, smaller means less expensive, so the minimum is generally what we go with. However, you cannot arbitrarily use a fuse or CB that has a larger rating than the rating of the conductors it is protecting. For example, if you have a conductor rated for 40 A, you cannot protect it with a fuse rated at 50 A—the wire would melt/catch on fire prior to the fuse failing! There is one more NEC condition to consider. Section 240.4 (D) lists maximum OCPD sizes for small conductors. This essentially adds a safety factor. For example, though a copper 12 AWG USE-2 conductor is rated at 30 A (table 310.15 (B)(16)), 240.4 (D)(5) states that it will be protected by an OCPD rated no greater than 20 A. Would this ever come into play? It could. Maybe an installer has some 25 A fuses he wants to use up on a job. He plans on using 12 AWG USE-2 conductor after the combiner box in a system using the panels in our example (hence max current = 19.4 A). The 25 A fuses meet the minimum requirements we calculated above, and the conductor’s ampacity is rated at 30 A, so he thinks he is good to go. BUT, section 240.4 (D)(5) says he has to use 20 A or smaller fuses for that size wire. Hence, he can’t use his extra 25 A fuses. Voltage Drop Calculations Why worry about this? Voltage drop means that the voltage at the end of a cable (relative to ground) is smaller than at the beginning. Since power is voltage times current, voltage drops result in lost power, which in turn means less energy produced. Hence, designers always need to minimize voltage drop when possible. How do you do that? Voltage drop is related to conductor cross-sectional area, which is proportional to the resistance of the conductor3. Smaller conductors have a greater voltage drop per linear foot than larger conductors. So, you can reduce voltage drop by minimizing the length of the conductor and/or increasing the size of the conductor. There will be physical constraints on the former and fiscal constraints on the latter. Good designers will strive to run conductors along the shortest distance between two points, e.g., placing a combiner box so that the “homeruns” from the strings to Voltage = current X resistance. For a given current, a lower resistance means a lower voltage. The thicker the conductor, the lower the resistance, and hence the lower the voltage drop across it. 3 7 NEC Code Calculations Fall 2015 22.525 Prof Thomas that combiner are as short as possible. Likewise, inverters should be sited so that runs between the combiner boxes to the inverter are also minimized. This is one reason to have an inverter sitting in the middle of a ground-mounted array, for instance. Finally, you’ll also need to consider the distance from the inverter to the grid interconnect. Higher voltages have lower drops per linear foot, too, so that is another thing to think about. Table 8 at the back of the NEC lists properties for conductors, including their resistance per linear foot (R in the formula below). Voltage drop in 2-wire dc or ac circuit, or a 3-wire single phase ac circuit, can be calculated using this formula: π£πππ‘πππ ππππ = 2×πΏ×π ×πΌ 1000 where: L = length of circuit (ft) R = resistance in Ohms per 1000 ft (see Chapter 9, Table 8 in NEC) I = load current (amps) We are always concerned with the maximum voltage drop, so we use the maximum current calculated above in this formula. Let’s say we are sticking with 10 AWG copper, coated conductor. Per Table 8, its R = 1.26 ohm/kft. The max current for the source circuit was found to be 7.79 A. Finally, let’s say we had to put the combiner box 50 feet away from the end of the strings, so L = 50 ft. π£πππ‘πππ ππππ = 2 × 50 × 1.26 × 7.79 = 0.98 π 1000 Thus, the voltage at the combiner box is about 1 V lower than when it left the string of modules. Since the maximum voltage calculated for a string was 535.7 V, a drop of 0.98 V is less than 0.2%, which is very small. So, we are not losing much power between the strings and the combiner boxes. Let’s say the inverter is 100 ft from the combiner box: π£πππ‘πππ ππππ = 2 × 100 × 1.26 × 15.6 = 3.93 π 1000 The voltage drop between the combiner box and the inverter is now 0.73% (i.e., 3.93V/535.7V = 0.0073). Add this to the drop between string and combiner box, and we have a voltage drop 0.93% or about 1%, which is acceptable. Not exceeding a 2% voltage drop on the dc side is the rule of thumb in the industry. Let’s look at an example of a poor design. Say a larger system—using the same modules and string size—has a PV output current of 195 A. Basically, there are 10 78 NEC Code Calculations Fall 2015 22.525 Prof Thomas module strings combined into a single combiner box (this is not uncommon—there are combiner boxes that have terminals for 16 strings…). Max system voltage is still 535.7 V. The inverter is 500 ft away from the combiner box. Also, let’s say that the conductor is coated 2/0 AWG copper THWN-2. It has an ampacity of 195 A (per Table 310.15(B)(16)) and a resistance of 0.101 ohm/kft (per Table 8). Using the voltage drop equation above: π£πππ‘πππ ππππ = 2 × 500 × 0.101 × 195 = 19.7 π 1000 19.7 V drop equates to a 3.7% voltage drop, which is generally considered too high (especially since we have not included the voltage drop in the PV source current). Power is voltage times current. So, leaving the combiner box, the power would be 535.7 V X 195 A = 104.5 kW. By the time it reaches the inverter, the power is now (535.7 – 19.7 V) X 195 A = 100.6 kW. This is of course a loss of 3.7%. To reduce this loss, the distance between the combiner box and inverter should be reduced, and/or a larger conductor with a lower resistance should be used. If moving the inverter is feasible, that is the first choice, since there is no cost to that whereas a larger conductor will cost more. One must also perform voltage drop calculations on the ac side, though these are usually lower, mainly because the distance between the inverter and load center is often only a few feet (installers like to place inverters right next to load centers if possible). Or, for larger systems, the inverters’ output tends to be at a higher voltage and/or 3-phase, so the output current in each conductor is proportionately lower. Based on the equation for voltage drop above, these lower inverter output currents translate into a lower AC voltage drop. (Incidentally, this is why power is transferred over long distances at such high voltages: hi-voltage means lower current, which then means lower power loss.) A Reality check on voltage drop. Let’s say that as a designer, you try to keep dc voltage drop to less than 2%. In your latest design, using the smallest conductor that meets the ampacity requirements discussed above, you find that you have a 2.3% voltage drop. Do you automatically select the next highest conductor to reduce this? Do you scrap your whole layout and start from scratch to try and reduce the conductor distances? Not necessarily. Remember, larger conductors cost more, so any savings from shaving 0.3% off the voltage drop may be offset by a higher installation cost. Also, how often will the system really be operating at such high power? In reality, very rarely, maybe only one or two hours per year, especially in a climate like Lowell’s. Therefore, the extra 0.3% voltage drop usually affects the system operating at lower power levels, and hence makes less of an impact. So, think twice about voltage drops and what to do about them. Your firm may well have a policy on what is acceptable. Also keep in mind that your firm may be contractually required to keep losses (including voltage drops) built into the design below a certain level. 9 NEC Code Calculations Fall 2015 22.525 Prof Thomas Conduit Sizing Calculations What’s this all about? Usually, conductors are collected and run inside of conduits (or raceways). This helps to protect them from the elements (including sunlight), and animals, and also keeps the arrays neat in appearance. However, due to the proximity of the conductors inside a conduit, their ampacities are also affected. Hence, we have to be aware of this when sizing conductors. Also, we can’t simply cram in as many conductors as possible into a conduit—there are limits to the number of individual conductors that can be installed in to a given diameter conduit. To be continued… 10