ATTACHMENT D CITY OF GRAND RAPIDS NEIGHBORHOOD STABILIZATION PROGRAM HOME INVESTMENT PARNERSHIPS PROGRAM ENERGY EFFICIENCY AND WATER CONSERVATION STANDARDS The following minimum energy efficiency and water conservation improvements shall be made to the Property: 1. High Efficiency Furnace/Boiler. All units relying on forced air space heating must have a 90%+ efficiency rated furnace. All units relying on hot water space heating must have a boiler with an AFUE efficiency rating of 85%+. All systems must be equipped with automatic “set-back” thermostats. 2. Attic insulation with Ventilation. Minimum R value of 38. Ventilation must meet current code and be split between low intake and high outlet. The split will be between 50/50 and 60/40 (Low/High). Appropriate baffles must be installed to allow free flow of air. Knob & Tube wiring in the attic must be replaced prior to covering with insulation. Balloon framed structures will require top sealing of interior walls open to the attic prior to adding insulation. 3. Exterior Sidewall insulation. All exterior wall cavities must be blown full. Knob & Tube wiring in exterior walls must be replaced prior to installation. If sidewall insulation was previously installed, the general contractor must certify in writing to the City the existence and adequacy of previously installed sidewall insulation. 4. Rim joist insulation. Insulate to R19 (minimum) and foam seal. 5. Outlet/Switch Box Insulation. Outlet/switchbox insulation must be installed on all such openings in exterior walls. 6. Pipe Insulation. Pipe insulation must be installed on all hot water pipes exposed in basements or crawl spaces. 7. High Efficiency Water Heater. If the water heater is to be replaced, a high efficiency water heater must be installed. 8. Appliances. All new appliances must be Energy Star rated. 9. Light Fixtures. All new light fixtures must be Energy Star compliant. All existing fixtures rated for standard 1- and 3-way light bulbs must be equipped with comparable compact fluorescent bulbs. 10. Toilets. All toilets must be a maximum of 1.6 gpf. 11. Low Flow Shower Heads / Faucets. Low flow shower heads (2.2 gpm) and low flow faucets or faucet aerators must be installed. COMDEV-89-445 (10/01/2009, ts) -1- City of Grand Rapids Energy Efficiency and Water Conservation Standards 12. Windows. All windows must be double glazed. Any replacement window must be Energy Star rated. If, due to Historic Preservation issues, windows are not replaced with double glazed sash, low e storm windows must be installed. 13. Blower Door Testing. Blower door testing shall be required. City Housing Rehabilitation Office staff will conduct the tests at no cost to the Developer. Envelope sealing is required. A minimum 10% decrease in air infiltration is required unless such a decrease results in fewer than 0.35 air changes per hour. If infiltration is less than 0.35 air changes per hour, provisions for make-up air must be installed. 14. Crawl Space Insulation: Unvented crawl spaces must be insulated with Kraft-faced fiberglass bats butted tightly together and weighted in place. A 6 mil plastic sheeting vapor barrier must be placed on the ground and secured to the walls prior to placing bats (alt: 1” foam may be used in place of fiberglass if walls are smooth). Crawl spaces vented to the exterior must be sealed off from conditioned basement spaces and insulated between the floor joists. The Developer shall provide the Property owner or renter with written instructions explaining how to use and maintain energy efficient appliances and improvements installed in the Property. COMDEV-89-445 (10/01/2009, ts) -2- City of Grand Rapids Energy Efficiency and Water Conservation Standards