PROPOSED Regional Technical Forum Air Source Heat Pump Commissioning, Controls, and Sizing Specification Adopted: May 12, 2015 Measure Specification This document details the measure specification for the RTF Heat Pump Commissioning, Controls, and Sizing measure for single family and manufactured homes. When installing a new single-speed or twospeed central air source heat pump, heat pump should be installed in accordance with this specification. The sunset date for this measure is March 31, 2016. 1 Component Measure Identifiers Baseline Specification Heating zones Current Practice Implementation and Product Standards Heat pumps must be new and rated by Air-Conditioning, Heating and Refrigeration Institute The heat pump shall be sized within a heating balance point of 30°F or lower Additional Notes Check heat pump is new and rated by AHRI The recommended method and form for calculations and selection are available in the ACCA Manuals J and S. Component U-values and F-values used in the heat loss and heat gain coefficients shall reflect the actual construction of the building and be generally consistent with those found in ACCA Manual J 8th Edition, or later. A natural infiltration rate of 0.5 or 0.8 air changes per hour shall be used for houses built after 1980 or before 1980, respectively, in sizing calculations unless a house (de)pressurization test has been performed and an estimate is made using the result. Where available, the results of duct pressurization testing shall be used to estimate the duct system efficiency used in sizing calculations. If a duct pressurization test has not been performed on the house, a default duct system loss of 25% shall be used. Exception: If the air handler and all ductwork are within the thermal envelope of the house, 0% shall be used as the duct system loss in sizing calculations. Sizing for cooling load is outside the scope of this specification. If the cooling loads justify a larger unit, than the minimum size required based on the heating sizing process, the larger unit should be installed 2 Delivery Verification Checklist Check for correct heating zone n/a Check contractor used specification Implementation and Product Standards (cont) 3 Auxiliary heat shall be controlled in the following manner depending on system type: Single stage OR multi stage without air temperature sensor control: Auxiliary heat shall be controlled in such a manner that it does not engage when the outdoor air temperature is above 35°F, except when supplemental heating is required during a defrost cycle or when emergency heating is required during a refrigeration cycle failure Multi stage with air temperature sensor control: Auxiliary heat shall be controlled in such a manner that it does not engage when the supply air temperature is above 85°F Thermostats for both heating and cooling shall have a manual changeover feature or heating/cooling lockout Temperature change across indoor coil after 10 minutes of heating operation shall be at or above the temperature split in Table 1 below If a low ambient temperature compressor cutout option is installed, it shall not cutout the compressor at temperatures above 5°F Air flow across the indoor coil shall be either: As specified in the heat pump manufacturer’s literature If not specified in the literature, ≥ 325 CFM per 12,000 Btu/hr output at AHRI rating conditions (at 47°F) Approved measurement methods include using a TrueFlow plate or using the duct pressurization fan matching method per plate or fan manufacturer’s instructions. Implementation and Product Standards (cont) The total external static pressure acting on the system air handler shall not exceed 0.8 in of water (200 Pa) after the new heat pump is installed Table 1: Minimum Temperature Split (°F) CFM per Ton Outdoor Temperature (°F) 300 350 400 450 5 13 11 10 9 10 15 13 11 10 15 17 15 13 11 20 19 17 15 13 25 20 18 16 14 30 21 19 17 15 35 23 21 18 16 40 25 23 20 18 45 28 25 22 20 50 31 27 24 22 55 34 29 26 23 60 36 31 28 25 65 38 33 29 26 4 Recommendations for Commissioning Controls and Sizing Programs The following sections provide additional guidance to support commissioning, controls, and sizing programs. These additional recommendations are not included in the RTF measure specification. However, the RTF recognizes these as best practices for commissioning, controls and sizing. 1. Auxiliary Heat Sizing. Installed auxiliary heat capacity shall not exceed 125% of the heating design load. a. The recommended ASHRAE winter design temperature and cooling design temperature for the nearest weather station representative of the installation shall be used. Exception: If State or Local code specifies a design temperature, the State or Local code design temperature value shall be used. a. . 2. Penetrations. Refrigerant piping passing through openings in the unit cabinet or the building structure shall be properly sealed. 3. Compliance with Applicable Codes and Manufacturer Requirements. Installation must comply with all applicable codes and be installed according to the manufacturer’s specifications, including, but not limited to, those for sizing, airflow, protective devices, equipment placement, refrigerant piping, refrigerant charge, condensate management, and fossil fuel back-up systems. 4. 5