SECTION 16120 ELECTRICAL CABLES Display hidden notes to

SECTION 16120
ELECTRICAL CABLES
Display hidden notes to specifier. (Don't know how? Click Here)
Copyright 2013 - 2015 ARCAT, Inc. - All rights reserved
PART 1 GENERAL
1.1
SECTION INCLUDES
A.
Cabling for the following applications:
1.
Security and Control Cables:
a.
Type: Unshielded Multi-Conductor.
b.
Type: Shielded Multi-Conductor.
c.
Type: Unshielded Multi-Pair.
d.
Type: Shielded Multi-Pair.
e.
Type: Each Pair Shielded Multi-Pair
2.
Control Cables
a.
Type: Access Control: Profusion Unjacketed Bundle
b.
Type: Access Control: Jacketed Bundle
c.
Type: TIA/EIA-485, BACnet.
d.
Type: Echelon LonWorks® .
3.
Irrigation, Tracer, and Underground Lighting Cables.
a.
Irrigation & Tracer.
b.
Underground Lighting.
4.
HVAC & Thermostat Cables:
a.
Type: Hybrid Thermostat.
b.
Type: Thermostat.
c.
Type: Mini Split Tray Cables.
5.
Fire Alarm Cables:
a.
Type: Unshielded.
b.
Type: Shielded.
c.
Type: NYC LL5.
6.
Home Theater Cables:
a.
Type: Premium Speaker.
b.
Type: Standard Speaker.
7.
Multimedia Cables:
8.
Network & IP Cables:
a.
Type: Category 6A.
b.
Type: Category 6 Plus.
c.
Type: Category 6.
d.
Type: Shielded Category 6.
e.
Type: Category 5e.
f.
Type: Shielded Category 5e.
9.
Coaxial CATV and CCTV Cables:
a.
CATV Coaxial:
1)
Type: Quad-shielded
2)
Type: Dual-shielded.
b.
CCTV:
16120-1
1)
2)
1.2
1.3
1.4
1.5
Type: Coaxial.
Type: Coaxial and power.
RELATED SECTIONS
A.
Section 13700 - Security Access and Surveillance
B.
Section 13710 - Intrusion Detection.
C.
Section 13800 - Building Automation and Control.
REFERENCES
A.
Underwriter's Laboratories (UL):
1.
UL 13 - Power-Limited Circuit Cables.
2.
UL 444 - Communications Cables.
3.
UL 1277 - Electrical Power and Control Tray Cables with Optional Fiber Members
4.
UL 1424 - Cables for Power-Limited Fire-Alarm Circuits.
5.
UL 1838 - Low Voltage Landscape Lighting Systems.
B.
National Electric Code (NEC):
1.
Article 336.
2.
Article 725.
3.
Article 760.
4.
Article 800.
5.
Article 820.
SUBMITTALS
A.
Submit under provisions of Section 01300.
B.
Product Data: Manufacturer's data sheets and detail drawings for each product to be used,
including:
1.
Preparation instructions and recommendations.
2.
Storage and handling requirements and recommendations.
3.
Product literature.
4.
Installation methods.
C.
Manufacturers Certificates, if applicable: Certify product meet or exceed specified
requirements.
D.
Testing Agency Qualifications: Products listed by Underwriters Laboratories (UL) or
Electrical Testing Laboratories (ETL).
DELIVERY, STORAGE, AND HANDLING
A.
Deliver, store and handle materials and products in strict compliance with manufacturer's
instructions and recommendations and industry standards.
B.
Test cable upon receipt at project site.
1.
Test each UTP cable pair for shorts or opens.
2.
Test coaxial cables for shorts or opens.
C.
Store products indoors in manufacturer's or fabricator's original containers and packaging,
with labels clearly identifying product name and manufacturer. Protect from damage.
1.
Storage and handling of cables in ambient temperatures of 32 degrees F or less:
Allow cable to acclimate to room temperature for at least 24 hours before installation
to ensure optimal cable flexibility.
16120-2
1.6
PROJECT CONDITIONS
A.
Maintain environmental conditions (temperature, humidity, and ventilation) within limits
recommended by manufacturer for optimum results. Do not install systems under
environmental conditions outside manufacturer's recommended limits.
B.
Do not install UTP, coaxial, and low-voltage cables and connecting materials in wet work
areas. Area must be completely dry and temporary HVAC or other controlled systems must
be operating and maintaining proper temperature and humidity.
1.
Exceptions: Manufacturer's cable is indoor/outdoor rated.
a.
Water resistant coaxial cables.
b.
Water resistant UTP cables.
PART 2 PRODUCTS
2.1
2.2
MANUFACTURERS
A.
Acceptable Manufacturer: Honeywell Cable & Custom Electronics , which is located at: 7701
95th St.; Pleasant Prairie, WI 53158; Toll Free Tel: 800-222-0060; Tel: 262-947-0720 ; Fax:
262-947-0724 ; Email:request info (Daniel.Dunar@Honeywell.com);
Web:www.honeywellcable.com
B.
Substitutions: Not permitted.
C.
Requests for substitutions will be considered in accordance with provisions of Section
01600.
SECURITY AND CONTROL CABLES (ARTICLE 725/800)
A.
Unshielded Multi-Conductor Cables: Unshielded, copper conductors.
1.
General Purpose Rated: Polypropylene Insulation, PVC Jacket: CM, CL2, Sunlight
Resistant listed.
a.
Part No.: 1140, 24 AWG, 4 solid conductors.
b.
Part No.: 1101, 22 AWG, 2 solid conductors.
c.
Part No.: 1102, 22 AWG, 2 stranded conductors.
d.
Part No.: 1103, 22 AWG, 4 solid conductors.
e.
Part No.: 1104, 22 AWG, 4 stranded conductors.
f.
Part No.: 1105, 22 AWG, 5 stranded conductors.
g.
Part No.: 1106, 22 AWG, 6 solid conductors.
h.
Part No.: 1107, 22 AWG, 6 stranded conductors.
i.
Part No.: 1108, 22 AWG, 8 solid conductors.
j.
Part No.: 1109, 22 AWG, 8 stranded conductors.
k.
Part No.: 1110, 22 AWG, 10 solid conductors.
l.
Part No.: 1111, 22 AWG, 10 stranded conductors.
m.
Part No.: 1112, 22 AWG, 12 solid conductors.
n.
Part No.: 1113, 22 AWG, 12 stranded conductors.
o.
Part No.: 1118, 18 AWG, 2 stranded conductors.
p.
Part No.: 1138, 18 AWG, 2 solid conductors.
q.
Part No.: 1130, 18 AWG, 3 stranded conductors.
r.
Part No.: 1119, 18 AWG, 4 stranded conductors.
s.
Part No.: 1120, 18 AWG, 6 stranded conductors.
t.
Part No.: 1121, 18 AWG, 8 stranded conductors.
u.
Part No.: 1122, 18 AWG, 10 stranded conductors.
v.
Part No.: 1123, 18 AWG, 12 stranded conductors.
w.
Part No.: 1125, 16 AWG, 2 stranded conductors.
x.
Part No.: 1126, 16 AWG, 4 stranded conductors.
y.
Part No.: 1131, 14 AWG, 1 solid conductor.
16120-3
2.
3.
B.
z.
Part No.: 1127, 14 AWG, 2 stranded conductors.
aa.
Part No.: 1129, 12 AWG, 2 stranded conductors.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant listed.
a.
Part No.: 2101, 22 AWG, 2 solid conductors.
b.
Part No.: 2102, 22 AWG, 2 stranded conductors.
c.
Part No.: 2103, 22 AWG, 4 solid conductors.
d.
Part No.: 2104, 22 AWG, 4 stranded conductors.
e.
Part No.: 2105, 22 AWG, 5 stranded conductors.
f.
Part No.: 2106, 22 AWG, 6 stranded conductors.
g.
Part No.: 2109, 22 AWG, 12 stranded conductors.
h.
Part No.: 2114, 18 AWG, 2 stranded conductors.
i.
Part No.: 2115, 18 AWG, 4 stranded conductors.
j.
Part No.: 2116, 18 AWG, 6 stranded conductors.
k.
Part No.: 2117, 18 AWG, 8 stranded conductors.
l.
Part No.: 2118, 18 AWG, 10 stranded conductors.
m.
Part No.: 2119, 18 AWG, 12 stranded conductors.
n.
Part No.: 2121, 16 AWG, 2 stranded conductors.
o.
Part No.: 2122, 16 AWG, 4 stranded conductors.
p.
Part No.: 2123, 14 AWG, 2 stranded conductors.
q.
Part No.: 2124, 14 AWG, 4 stranded conductors.
r.
Part No.: 2125, 12 AWG, 2 stranded conductors.
Plenum Rated: Low Smoke PVC Insulation, Low Smoke PVC Jacket: CMP, CL2P,
FT6 listed.
a.
Part No.: 3101, 22 AWG, 2 solid conductors.
b.
Part No.: 3102, 22 AWG, 2 stranded conductors.
c.
Part No.: 3127, 22 AWG, 3 stranded conductors.
d.
Part No.: 3103, 22 AWG, 4 solid conductors.
e.
Part No.: 3104, 22 AWG, 4 stranded conductors.
f.
Part No.: 3106, 22 AWG, 6 stranded conductors.
g.
Part No.: 3107, 22 AWG, 8 stranded conductors.
h.
Part No.: 3108, 22 AWG, 10 stranded conductors.
i.
Part No.: 3109, 22 AWG, 12 stranded conductors.
j.
Part No.: 3114, 18 AWG, 2 stranded conductors.
k.
Part No.: 3134, 18 AWG, 2 solid conductors.
l.
Part No.: 3126, 18 AWG, 3 stranded conductors.
m.
Part No.: 3115, 18 AWG, 4 stranded conductors.
n.
Part No.: 3116, 18 AWG, 6 stranded conductors.
o.
Part No.: 3117, 18 AWG, 8 stranded conductors.
p.
Part No.: 3118, 18 AWG, 10 stranded conductors.
q.
Part No.: 3119, 18 AWG, 12 stranded conductors.
r.
Part No.: 3121, 16 AWG, 2 stranded conductors.
s.
Part No.: 3129, 16 AWG, 3 stranded conductors.
t.
Part No.: 3122, 16 AWG, 4 stranded conductors.
u.
Part No.: 3123, 14 AWG, 2 stranded conductors.
v.
Part No.: 3124, 14 AWG, 4 stranded conductors.
w.
Part No.: 3125, 12 AWG, 2 stranded conductors.
Shielded Multi-Conductor Cables: foil shielded with drain wire, copper conductors.
1.
General Purpose Rated: Polypropylene Insulation, PVC Jacket: CM, CL2, Sunlight
Resistant listed.
a.
Part No.: 1202, 22 AWG, 2 stranded conductors.
b.
Part No.: 1204, 22 AWG, 4 stranded conductors.
c.
Part No.: 1206, 22 AWG, 6 stranded conductors.
d.
Part No.: 1207, 22 AWG, 8 stranded conductors.
e.
Part No.: 1208, 22 AWG, 10 stranded conductors.
16120-4
2.
3.
C.
f.
Part No.: 1209, 22 AWG, 12 stranded conductors.
g.
Part No.: 1214, 18 AWG, 2 stranded conductors.
h.
Part No.: 1228, 18 AWG, 3 stranded conductors.
i.
Part No.: 1215, 18 AWG, 4 stranded conductors.
j.
Part No.: 1216, 18 AWG, 6 stranded conductors.
k.
Part No.: 1217, 18 AWG, 8 stranded conductors.
l.
Part No.: 1218, 18 AWG, 10 stranded conductors.
m.
Part No.: 1221, 16 AWG, 2 stranded conductors.
n.
Part No.: 1229, 16 AWG, 3 stranded conductors.
o.
Part No.: 1222, 16 AWG, 4 stranded conductors.
p.
Part No.: 1223, 14 AWG, 2 stranded conductors.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant listed.
a.
Part No.: 2201, 22 AWG, 2 solid conductors.
b.
Part No.: 2202, 22 AWG, 2 stranded conductors.
c.
Part No.: 2203, 22 AWG, 4 solid conductors.
d.
Part No.: 2204, 22 AWG, 4 stranded conductors.
e.
Part No.: 2206, 22 AWG, 6 stranded conductors.
f.
Part No.: 2207, 22 AWG, 8 stranded conductors.
g.
Part No.: 2208, 22 AWG, 10 stranded conductors.
h.
Part No.: 2209, 22 AWG, 12 stranded conductors.
i.
Part No.: 2214, 18 AWG, 2 stranded conductors.
j.
Part No.: 2215, 18 AWG, 4 stranded conductors.
k.
Part No.: 2216, 18 AWG, 6 stranded conductors.
l.
Part No.: 2217, 18 AWG, 8 stranded conductors.
m.
Part No.: 2218, 18 AWG, 10 stranded conductors.
n.
Part No.: 2219, 18 AWG, 12 stranded conductors.
o.
Part No.: 2221, 16 AWG, 2 stranded conductors.
p.
Part No.: 2222, 16 AWG, 4 stranded conductors.
q.
Part No.: 2223, 14 AWG, 2 stranded conductors.
r.
Part No.: 2224, 14 AWG, 4 stranded conductors.
Plenum Rated: Low Smoke PVC Insulation, Low Smoke PVC Jacket: CMP, CL2P,
FT6 listed.
a.
Part No.: 3201, 22 AWG, 2 solid conductors.
b.
Part No.: 3202, 22 AWG, 2 stranded conductors.
c.
Part No.: 3227, 22 AWG, 3 stranded conductors.
d.
Part No.: 3203, 22 AWG, 4 solid conductors.
e.
Part No.: 3204, 22 AWG, 4 stranded conductors.
f.
Part No.: 3206, 22 AWG, 6 stranded conductors.
g.
Part No.: 3207, 22 AWG, 8 stranded conductors.
h.
Part No.: 3208, 22 AWG, 10 stranded conductors.
i.
Part No.: 3209, 22 AWG, 12 stranded conductors.
j.
Part No.: 3214, 18 AWG, 2 stranded conductors.
k.
Part No.: 3226, 18 AWG, 3 stranded conductors.
l.
Part No.: 3215, 18 AWG, 4 stranded conductors.
m.
Part No.: 3276, 18 AWG, 5 stranded conductors.
n.
Part No.: 3216, 18 AWG, 6 stranded conductors.
o.
Part No.: 3217, 18 AWG, 8 stranded conductors.
p.
Part No.: 3218, 18 AWG, 10 stranded conductors.
q.
Part No.: 3221, 16 AWG, 2 stranded conductors.
r.
Part No.: 3222, 16 AWG, 4 stranded conductors.
s.
Part No.: 3223, 14 AWG, 2 stranded conductors.
t.
Part No.: 3224, 14 AWG, 4 stranded conductors.
Unshielded Multi-Pair Cables: Unshielded, twisted copper pairs.
1.
General Purpose Rated: Polypropylene Insulation, PVC Jacket: CM, CL2, Sunlight
16120-5
2.
3.
Resistant listed.
a.
Part No.: 1234, 22 AWG, 2 stranded conductor pairs.
b.
Part No.: 1235, 22 AWG, 3 solid conductor pairs.
c.
Part No.: 1238, 22 AWG, 6 solid conductor pairs.
d.
Part No.: 1245, 18 AWG, 2 stranded conductor pairs.
e.
Part No.: 1246, 18 AWG, 3 stranded conductor pairs.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant listed.
a.
Part No.: 2232, 22 AWG, 1 stranded conductor pair.
b.
Part No.: 2233, 22 AWG, 2 solid conductor pairs.
c.
Part No.: 2234, 22 AWG, 2 stranded conductor pairs, one pair shielded.
d.
Part No.: 2237, 22 AWG, 4 solid conductor pairs.
e.
Part No.: 2239, 22 AWG, 6 stranded conductor pairs.
Plenum Rated: Low Smoke PVC Insulation, Low Smoke PVC Jacket: CMP, CL2P,
FT6 listed.
a.
Part No.: 3246, 22 AWG, 2 stranded conductor pairs.
b.
Part No.: 3270, 22 AWG, 2 stranded conductor pairs, one pair shielded.
c.
Part No.: 3247, 22 AWG, 3 stranded conductor pairs.
d.
Part No.: 3248, 22 AWG, 4 stranded conductor pairs.
e.
Part No.: 3249, 22 AWG, 6 stranded conductor pairs.
D.
Shielded Multi-Pair Cables: foil shielded with drain wire, twisted copper pairs.
1.
General Purpose Rated: Polypropylene Insulation, PVC Jacket: CM, CL2, Sunlight
Resistant listed.
a.
Part No.: 1290, 18 AWG, 3 stranded conductor pairs.
b.
Part No.: 1291, 18 AWG, 4 stranded conductor pairs.
2.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant listed.
a.
Part No.: 2281, 22 AWG, 2 stranded conductor pairs.
b.
Part No.: 2283, 22 AWG, 3 stranded conductor pairs.
c.
Part No.: 2284, 22 AWG, 6 solid conductor pairs.
3.
Plenum Rated: Low Smoke PVC Insulation, Low Smoke PVC Jacket: CMP, CL2P,
FT6 listed.
a.
Part No.: 3281, 22 AWG, 2 stranded conductor pairs.
b.
Part No.: 3283, 22 AWG, 3 stranded conductor pairs.
c.
Part No.: 3285, 22 AWG, 6 stranded conductor pairs.
E.
Each Pair Shielded Multi-Pair Cables: Individually shielded with drain wire, twisted copper
pairs.
1.
General Purpose Rated: Polypropylene Insulation, PVC Jacket: CM, CL2, Sunlight
Resistant listed.
a.
Part No.: 1263, 22 AWG, 2 solid conductor pairs.
b.
Part No.: 1264, 22 AWG, 3 stranded conductor pairs.
c.
Part No.: 1266, 22 AWG, 3 stranded conductor pairs.
d.
Part No.: 1273, 22 AWG, 2 stranded conductor pairs.
e.
Part No.: 1274, 22 AWG, 3 stranded conductor pairs.
2.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant listed.
a.
Part No.: 2264, 22 AWG, 2 stranded conductor pairs.
b.
Part No.: 2266, 22 AWG, 3 stranded conductor pairs.
3.
Plenum Rated: Low Smoke PVC Insulation, Low Smoke PVC Jacket: CMP, CL2P,
FT6 listed.
a.
Part No.: 3262, 22 AWG, 1 stranded conductor pairs.
b.
Part No.: 3263, 22 AWG, 2 solid conductor pairs.
c.
Part No.: 3264, 22 AWG, 2 stranded conductor pairs.
d.
Part No.: 3266, 22 AWG, 3 stranded conductor pairs.
16120-6
e.
2.3
Part No.: 3267, 22 AWG, 4 solid conductor pairs.
CONTROL CABLES
A.
Access Control Cables: 4 components, Profusion unjacketed bundle.
1.
Part No.: 2195, Riser Rated, CMR, CL2R, FT4, Sunlight Resistant Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors.
c.
Component 3: 22 AWG, 2 stranded conductors.
d.
Component 4: 22 AWG, 4 stranded conductors.
2.
Part No.: 2295, Riser Rated, CMR, CL2R, FT4, Sunlight Resistant Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors, shielded.
c.
Component 3: 22 AWG, 2 stranded conductors, shielded.
d.
Component 4: 22 AWG, 4 stranded conductors, shielded.
3.
Part No.: 3195, Plenum Rated, CMP, CL2P, FT6 Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors.
c.
Component 3: 22 AWG, 2 stranded conductors.
d.
Component 4: 22 AWG, 4 stranded conductors.
4.
Part No.: 3295, Plenum Rated, CMP, CL2P, FT6 Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors, shielded.
c.
Component 3: 22 AWG, 2 stranded conductors, shielded.
d.
Component 4: 22 AWG, 4 stranded conductors, shielded.
B.
Access Control Cables: 4 components, Overall jacketed bundle.
1.
Part No.: 2196, Riser Rated, CMR, CL2R, FT4, Sunlight Resistant Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors.
c.
Component 3: 22 AWG, 2 stranded conductors.
d.
Component 4: 22 AWG, 4 stranded conductors.
2.
Part No.: 2296, Riser Rated, CMR, CL2R, FT4, Sunlight Resistant Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors, shielded.
c.
Component 3: 22 AWG, 2 stranded conductors, shielded.
d.
Component 4: 22 AWG, 4 stranded conductors, shielded.
3.
Part No.: 3196, Plenum Rated, CMP, CL2P, FT6 Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors.
c.
Component 3: 22 AWG, 2 stranded conductors.
d.
Component 4: 22 AWG, 4 stranded conductors.
4.
Part No.: 3296, Plenum Rated, CMP, CL2P, FT6 Listed.
a.
Component 1: 22 AWG, 6 stranded conductors, shielded.
b.
Component 2: 18 AWG, 4 stranded conductors, shielded.
c.
Component 3: 22 AWG, 2 stranded conductors, shielded.
d.
Component 4: 22 AWG, 4 stranded conductors, shielded.
C.
TIA/EIA-485, BACnet Cables: EIA-485, UL13, and UL444, NEC Article 725 and 800.
1.
Plenum Rated: FEP insulation, aluminum/mylar shield with drain wire, low smoke PVC
jacket.
a.
Part No.: 3319, 24 AWG, 1 stranded conductor pair, shielded.
b.
Part No.: 3323, 24 AWG, 1.5 stranded conductor pairs, shielded.
c.
Part No.: 3320, 22 AWG, 1 stranded conductor pair, shielded.
d.
Part No.: 3324, 22 AWG, 1.5 stranded conductor pairs, shielded.
e.
Part No.: 3328, 22 AWG, 2 stranded conductor pairs, shielded.
16120-7
f.
D.
2.4
2.5
Part No.: 3322, 18 AWG, 1 conductor pair, shielded.
Echelon LonWorks® Cables: Level IV, UL13, and UL444, NEC Article 725 and 800.
1.
Unshielded, Plenum Rated, CMP, CL2P, FT6 Listed: FEP insulation, low smoke PVC
jacket.
a.
Part No.: 3252, 22 AWG, 1 conductor pair.
b.
Part No.: 3253, 22 AWG, 2 conductor pairs.
2.
Shielded, Plenum Rated, CMP, CL2P, FT6 Listed: FEP insulation, aluminum/mylar
shield with drain wire, low smoke PVC jacket.
a.
Part No.: 3254, 22 AWG, 1 conductor pair, shielded.
b.
Part No.: 3255, 22 AWG, 2 conductor pairs, shielded.
3.
Unshielded, General Purpose Rated, CM, CL2, Sunlight Resistant Listed:
Polypropylene insulation, low smoke PVC jacket.
a.
Part No.: 1061, 22 AWG, 1 conductor pair.
b.
Part No.: 1062, 22 AWG, 2 conductor pairs.
4.
Shielded, General Purpose Rated, CM, CL2, Sunlight Resistant Listed: Polypropylene
insulation, aluminum/mylar shield with drain wire, low smoke PVC jacket.
a.
Part No.: 1063, 22 AWG, 1 conductor pair, shielded.
IRRIGATION, TRACER AND UNDERGROUND LIGHTING CABLES
A.
Irrigation and Tracer Cables: 600V direct burial rated, bare copper conductor, polyethylene
insulation.
1.
Part No.: 1301, 1 solid conductor, 18 AWG.
2.
Part No.: 1303, 1 solid conductor, 14 AWG.
3.
Part No.: 1304, 1 solid conductor, 12 AWG.
B.
Underground Lighting Cables: Two stranded bare copper conductors, PVC jacket.
1.
Compliance: 150V direct burial rated, UL 493 and UL 1838.
2.
Part No.: 1021, 2 stranded conductors, 14 AWG.
3.
Part No.: 1019, 2 stranded conductors, 12 AWG.
4.
Part No.: 1018, 2 stranded conductors, 10 AWG.
5.
Part No.: 1017, 2 stranded conductors, 8 AWG.
HVAC THERMOSTAT AND CONTROL CABLES
A.
Hybrid Thermostat Cables
1.
General Purpose Rated: Copper Conductors, Polypropylene Insulation, PVC Jacket,
CL2, Sunlight Resistant listed.
a.
Part No.: 6713, 5 conductors.
1)
18 AWG, 1 solid conductor.
2)
20 AWG, 4 solid conductors.
b.
Part No.: 6714, 6 conductors.
1)
18 AWG, 1 solid conductor.
2)
20 AWG, 5 solid conductors.
c.
Part No.: 6716, 8 conductors.
1)
18 AWG, 1 solid conductor.
2)
20 AWG, 7 solid conductors.
d.
Part No.: 6718, 10 conductors.
1)
18 AWG, 2 solid conductors.
2)
20 AWG, 8 solid conductors.
B.
Thermostat Cables: UL 13, NEC Article 725.
1.
General Purpose Rated: Copper Conductors, Polypropylene Insulation, PVC Jacket,
CL2, Sunlight Resistant listed.
a.
Part No.: 4701, 20 AWG, 2 solid conductors.
b.
Part No.: 4702, 20 AWG, 3 solid conductors.
16120-8
2.
C.
2.6
c.
Part No.: 4703, 20 AWG, 4 solid conductors.
d.
Part No.: 4704, 20 AWG, 5 solid conductors.
e.
Part No.: 4705, 20 AWG, 6 solid conductors.
f.
Part No.: 4706, 20 AWG, 7 solid conductors.
g.
Part No.: 4707, 20 AWG, 8 solid conductors.
h.
Part No.: 4709, 20 AWG, 10 solid conductors.
i.
Part No.: 4710, 18 AWG, 2 solid conductors.
j.
Part No.: 4711, 18 AWG, 3 solid conductors.
k.
Part No.: 4712, 18 AWG, 4 solid conductors.
l.
Part No.: 4713, 18 AWG, 5 solid conductors.
m.
Part No.: 4714, 18 AWG, 6 solid conductors.
n.
Part No.: 4715, 18 AWG, 7 solid conductors.
o.
Part No.: 4716, 18 AWG, 8 solid conductors.
p.
Part No.: 4717, 18 AWG, 9 solid conductors.
q.
Part No.: 4718, 18 AWG, 10 solid conductors.
r.
Part No.: 4719, 18 AWG, 12 solid conductors.
Plenum Rated: Copper conductors, low smoke PVC insulation, PVC jacket: CL2P
listed.
a.
Part No.: 4760, 18 AWG, 2 solid conductors.
b.
Part No.: 4761, 18 AWG, 3 solid conductors.
c.
Part No.: 4762, 18 AWG, 4 solid conductors.
d.
Part No.: 4763, 18 AWG, 5 solid conductors.
e.
Part No.: 4764, 18 AWG, 6 solid conductors.
f.
Part No.: 4766, 18 AWG, 8 solid conductors.
g.
Part No.: 4768, 18 AWG, 10 solid conductors.
Mini Split Tray Cables
1.
Bare Copper conductors, THHN, PVC jacket: Type TC, Direct Burial, Sunlight
Resistant Listed.
a.
Unshielded: Stranded bare copper conductors, PVC jacket.
1)
Part No.: 1070, 14 AWG, 4 stranded conductors.
2)
Part No.: 1073, 14 AWG, 7 stranded conductors.
3)
Part No.: 1068, 16 AWG, 4 stranded conductors.
FIRE ALARM CABLES
A.
Unshielded Multiconductor Cables: Copper conductors, UL 13, UL 1424, NEC Articles 725
and 760.
1.
General Purpose Rated: Polypropylene Insulation, PVC Jacket: FPL, CL2, Sunlight
Resistant listed.
a.
Part No.: 4101, 22 AWG, 4 solid conductors.
b.
Part No.: 4102, 22 AWG, 6 solid conductors.
c.
Part No.: 4103, 22 AWG, 8 solid conductors.
d.
Part No.: 4105, 22 AWG, 12 solid conductors.
e.
Part No.: 4106, 18 AWG, 2 solid conductors.
f.
Part No.: 4107, 18 AWG, 4 solid conductors.
g.
Part No.: 4108, 18 AWG, 6 solid conductors.
h.
Part No.: 4109, 18 AWG, 8 solid conductors.
i.
Part No.: 4111, 16 AWG, 2 solid conductors
j.
Part No.: 4112, 16 AWG, 4 solid conductors.
k.
Part No.: 4113, 14 AWG, 2 solid conductors.
l.
Part No.: 4114, 14 AWG, 4 solid conductors.
m.
Part No.: 4115, 12 AWG, 2 solid conductors.
2.
Riser Rated: Polypropylene Insulation, PVC Jacket: UL 13, UL 1424, and NEC Article
725 and 760, FPLR, CL2R, Sunlight Resistant listed.
a.
Part No.: 4301, 22 AWG, 4 solid conductors.
16120-9
3.
4.
B.
b.
Part No.: 4306, 18 AWG, 2 solid conductors.
c.
Part No.: 4307, 18 AWG, 4 solid conductors.
d.
Part No.: 4308, 18 AWG, 6 solid conductors.
e.
Part No.: 4310, 18 AWG, 10 solid conductors.
f.
Part No.: 4311, 16 AWG, 2 solid conductors.
g.
Part No.: 4312, 16 AWG, 4 solid conductors.
h.
Part No.: 4313, 14 AWG, 2 solid conductors.
i.
Part No.: 4314, 14 AWG, 4 solid conductors.
j.
Part No.: 4315, 12 AWG, 2 solid conductors, 12 AWG.
Plenum Rated: Low Smoke PVC Insulation, Low Smoke PVC Jacket: FPLP, CL2P
listed.
a.
Part No.: 4502, 22 AWG, 6 solid conductors.
b.
Part No.: 4506, 18 AWG, 2 solid conductors.
c.
Part No.: 4507, 18 AWG, 4 solid conductors.
d.
Part No.: 4508, 18 AWG, 6 solid conductors.
e.
Part No.: 4509, 18 AWG, 8 solid conductors.
f.
Part No.: 4511, 16 AWG, 2 solid conductors.
g.
Part No.: 4512, 16 AWG, 4 solid conductors.
h.
Part No.: 4513, 14 AWG, 2 solid conductors.
i.
Part No.: 4514, 14 AWG, 4 solid conductors.
j.
Part No.: 4515, 12 AWG, 2 solid conductors.
Direct Burial Rated: SRPVC Insulation, PVC Jacket, FPL, CL2, Sunlight Resistant,
Direct Burial listed.
a.
Part No.: 4156, 18 AWG, 2 stranded conductors.
b.
Part No.: 4157, 18 AWG, 4 stranded conductors.
c.
Part No.: 4158, 18 AWG, 6 stranded conductors.
d.
Part No.: 4159, 18 AWG, 8 stranded conductors.
e.
Part No.: 4151, 16 AWG, 2 stranded conductors.
f.
Part No.: 4153, 14 AWG, 2 stranded conductors.
g.
Part No.: 4154, 14 AWG, 4 stranded conductors.
Shielded Cables, foil shielded with drain wire, copper conductors.
1.
General Purpose Rated: Polypropylene Insulation, PVC Jacket: FPL, CL2, Sunlight
Resistant listed.
a.
Part No.: 4201, 22 AWG, 4 solid conductors.
b.
Part No.: 4202, 18 AWG, 2 solid conductors.
c.
Part No.: 4203, 18 AWG, 4 solid conductors.
d.
Part No.: 4204, 18 AWG, 6 solid conductors.
e.
Part No.: 4205, 18 AWG, 8 solid conductors.
f.
Part No.: 4206, 18 AWG, 2 solid conductors.
g.
Part No.: 4207, 18 AWG, 4 solid conductors.
h.
Part No.: 4208, 18 AWG, 2 solid conductors.
i.
Part No.: 4209, 18 AWG, 4 solid conductors.
j.
Part No.: 4210, 18 AWG, 2 solid conductors.
2.
Riser Rated: Copper conductors, Polypropylene Insulation, PVC Jacket, FPLR, CL2R,
Sunlight Resistant listed.
a.
Part No.: 4402, 18 AWG, 2 solid conductors.
b.
Part No.: 4403, 18 AWG, 4 solid conductors.
c.
Part No.: 4404, 18 AWG, 6 solid conductors.
d.
Part No.: 4405, 18 AWG, 8 solid conductors.
e.
Part No.: 4406, 16 AWG, 2 solid conductors.
f.
Part No.: 4407, 16 AWG, 4 solid conductors.
g.
Part No.: 4408, 14 AWG, 2 conductors.
h.
Part No.: 4409, 14 AWG, 4 solid conductors.
i.
Part No.: 4410, 12 AWG, 2 solid conductors.
3.
Plenum Rated: Copper Conductors, Low Smoke PVC Insulation, Low Smoke PVC
16120-10
Jacket: FPLP, CL2P listed.
a.
Part No.: 4601, 22 AWG, 4 solid conductors.
b.
Part No.: 4602, 18 AWG, 2 solid conductors.
c.
Part No.: 4603, 18 AWG, 4 solid conductors.
d.
Part No.: 4604, 18 AWG, 6 solid conductors.
e.
Part No.: 4606, 16 AWG, 2 solid conductors.
f.
Part No.: 4607, 16 AWG, 4 solid conductors.
g.
Part No.: 4608, 14 AWG, 2 solid conductors.
h.
Part No.: 4609, 14 AWG, 4 solid conductors.
i.
Part No.: 4610, 12 AWG, 2 solid conductors.
C.
2.7
NYC Local Law 5 Compliant Fire Alarm Cables: fluoropolymer insulation and jacket, FPLP,
NYC LL5 listed.
1.
Unshielded Cables:
a.
Part No.: 5500, 18 AWG, 1 solid conductor pair.
b.
Part No.: 5501, 18 AWG, 2 solid conductor pairs.
c.
Part No.: 5502, 16 AWG, 1 solid conductor pair.
d.
Part No.: 5503, 16 AWG, 2 solid conductor pairs.
e.
Part No.: 5504, 14 AWG, 1 solid conductor pair.
f.
Part No.: 5505, 14 AWG, 2 solid conductor pairs.
g.
Part No.: 5506, 12 AWG, 1 solid conductor pair.
2.
Shielded Cables: foil shielded with drain wire:
a.
Part No.: 5550, 18 AWG, 1 solid conductor pair.
b.
Part No.: 5551, 18 AWG, 2 solid conductor pairs.
c.
Part No.: 5552, 16 AWG, 1 solid conductor pair.
d.
Part No.: 5553, 16 AWG, 2 solid conductor pairs.
e.
Part No.: 5554, 14 AWG, 1 solid conductor pair.
f.
Part No.: 5555, 14 AWG, 2 solid conductor pairs.
g.
Part No.: 5556, 12 AWG, 1 solid conductor pair.
HOME THEATER CABLES
A.
Premium Speaker Cables: oxygen free copper conductors, UL 13 and UL 444, NEC Article
725 and 800.
1.
Riser Rated: PVC Insulation, PVC WaveFLEX Jacket, CMR, CL3R, Sunlight Resistant
Listed.
a.
Part No.: 5473, 16 AWG, 2 stranded conductors.
b.
Part No.: 5474, 16 AWG, 4 stranded conductors.
c.
Part No.: 5475, 14 AWG, 2 stranded conductors.
d.
Part No.: 5476, 14 AWG, 4 stranded conductors.
2.
Direct Burial: SRPVC Insulation, PVC Insulation, CM, CL3, Sunlight Resistant, Direct
Burial listed.
a.
Part No.: 5283, 16 AWG, 2 stranded conductors.
b.
Part No.: 5284, 16 AWG, 4 stranded conductors.
c.
Part No.: 5285, 14 AWG, 2 stranded conductors.
d.
Part No.: 5286, 14 AWG, 4 stranded conductors.
B.
Standard Speaker Cables: CM, CL3 listed, stranded copper conductors, polypropylene
insulation, PVC jacket, UL 13 and UL 444, NEC Articles 725 and 800.
1.
General Purpose Rated: Polypropylene insulation, PVC jacket, CM, CL3, Sunlight
Resistant listed:
a.
Part No.: 5250, 16 AWG, 2 stranded conductors.
b.
Part No.: 5251, 16 AWG, 4 stranded conductors.
c.
Part No.: 5252, 14 AWG, 2 stranded conductors.
d.
Part No.: 5253, 14 AWG, 2 stranded conductors.
e.
Part No.: 5254, 12 AWG, 2 stranded conductors.
16120-11
f.
2.8
2.9
Part No.: 5255, 12 AWG, 4 stranded conductors.
MULTIMEDIA CABLES (ARTICLE 725/800)
A.
Profusion Multimedia Cables: CM, CL2 listed, unjacketed, 2 coax cables tested to 3 GHz. UL
13 and UL 444, NEC Article 725 and 800.
1.
Part No.: 5060, RG6/U CCS quad shielded coax, Cat 5e tested to 350 MHz.
2.
Part No.: 5956, RG6/U BC quad shielded coax, Cat 6, 2 FDDI.
3.
Part No.: 5957, RG6/U BC quad shielded coax, Cat 6.
B.
Jacketed Multimedia Cables: CM, CL2 listed, cabled construction, coax cables tested to 3
GHz, Cat 5e cables tested to 350 MHz, UL 13 and UL 444, NEC Article 725 and 800.
1.
Part No.: 5050, RG6/U CCS quad shielded, 2 coax.
2.
Part No.: 5051, RG6/U CCS quad shielded, 2 coax, 2 FDDI.
C.
Genesis Series Catlink Dual Zip Cables: CM, CL2 listed, parallel zip construction, coax
cables tested to 3 GHz.
1.
Part No.: 5066, RG6/U CCS quad shielded, 2 coax.
2.
Part No.: 5067, RG6/U CCS dual shielded 60 percent, 2 coax, 2 FDDI, UL 13 and UL
444, NEC Article 725 and 800.
NETWORK & IP CABLES
A.
Category 6A Cables: Unshielded twisted copper pairs, dielectric spline between pairs: UL
13, UL 444, NEC Articles 800 and 725, verified to TIA/EIA-568-C.2 Cat 6A:
1.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant Listed:
a.
Part No.: 5193, Cat 6A (500 MHz.)
2.
Plenum Rated: FEP insulation, low-smoke PVC jacket: CMP, CL2P, FT6 listed:
a.
Part No.: 5393, Cat 6A (500 MHz.)
B.
Category 6 Plus Cables: Unshielded twisted copper pairs, dielectric spline between pairs: UL
13, UL 444, NEC Articles 800 and 725, verified to TIA/EIA-568-C.2 Cat 6:
1.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant Listed:
a.
Part No.: 5092, Cat 6 Plus (500 MHz.)
2.
Plenum Rated: FEP insulation, low-smoke PVC jacket: CMP, CL2P, FT6 listed:
a.
Part No.: 5102, Cat 6 (500 MHz.)
C.
Category 6 Cables: Unshielded twisted copper pairs: UL 13, UL 444, NEC Articles 800 and
725, verified to TIA/EIA-568-C.2 Cat 6:
1.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant Listed:
a.
Part No.: 6360, Cat 6 (350 MHz.)
2.
Plenum Rated: FEP insulation, low-smoke PVC jacket: CMP, CL2P, FT6 listed:
a.
Part No.: 6361, Cat 6A (350 MHz.)
D.
Shielded Category 6 Cables: Foil shielded twisted copper pairs (F/UTP), dielectric spline
between pairs: UL 13, UL 444, NEC Articles 800 and 725, verified to TIA/EIA-568-C.2 Cat 6:
1.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant Listed:
a.
Part No.: 5192, Shielded Cat 6 Plus (500 MHz.)
2.
Plenum Rated: FEP insulation, low-smoke PVC jacket: CMP, CL2P, FT6 listed:
a.
Part No.: 5392, Shielded Cat 6 (500 MHz.)
E.
Category 5e Cables: Unshielded twisted copper pairs: UL 13, UL 444, NEC Articles 800 and
725, verified to TIA/EIA-568-C.2 Cat 5e:
16120-12
1.
2.
3.
F.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant Listed:
a.
Part No.: 5078, Cat 5e (350 MHz.)
Plenum Rated: FEP insulation, low-smoke PVC jacket: CMP, CL2P, FT6 listed:
a.
Part No.: 5088, Cat 5e (350 MHz.)
Direct Burial Rated: Polypropylene insulation, LLDPE jacket: Direct Burial, Sunlight
Resistant, Wet Location Approved:
a.
Part No.: 5090, Cat 5e (350 MHz.)
Shielded Category 5e Cables: Foil shielded twisted copper pairs (F/UTP): UL 13, UL 444,
NEC Articles 800 and 725, verified to TIA/EIA-568-C.2 Cat 5e:
1.
Riser Rated: Polypropylene Insulation, PVC Jacket: CMR, CL2R, FT4, Sunlight
Resistant Listed:
a.
Part No.: 5178, Shielded Cat 6 Plus (500 MHz.)
2.
Plenum Rated: FEP insulation, low-smoke PVC jacket: CMP, CL2P, FT6 listed:
a.
Part No.: 5388, Shielded Cat 6 (500 MHz.)
2.10 COAXIAL CATV AND CCTV CABLES
A.
CATV Coaxial Cables: NEC Article 820 and 725.
1.
Quad-Shielded Broadband Coaxial Cables: Two 100 percent aluminum foil and two
aluminum braids, sweep tested to 3 GHz.
a.
General Purpose Rated: CATV, CL2, Sunlight Resistant listed:
1)
Part No.: 5027, RG6 solid copper center conductor.
2)
Part No.: 5007, RG6 solid copper covered steel center conductor.
3)
Part No.: 5008, 2xRG6, solid copper covered steel center conductor.
b.
Riser Rated: CATVR, CL2R, FT4, Sunlight Resistant listed:
1)
Part No. 5307, RG6 solid copper covered steel center conductor.
c.
Plenum Rated: CATVP, CL2P, FT6 listed:
1)
Part No. 5356, RG6 solid copper covered steel center conductor.
d.
Water Resistant Rated: CATV, Sunlight Resistant listed:
1)
Part No. 5106, copper covered steel center conductor.
2.
Dual-Shielded Broadband Coaxial Cables: 100 percent aluminum foil shield and
minimum 65% coverage aluminum braid shield, sweep tested to 3 GHz.
a.
General Purpose Rated: CATV, CL2, Sunlight Resistant listed:
1)
Part No.: 5018, RG11 solid copper covered steel center conductor.
2)
Part No.: 5304, RG6/U, 3 GHz, solid copper center conductor.
3)
Part No.: 5011, RG6 solid copper covered steel center conductor.
4)
Part No.: 5003, RG6 solid copper covered steel center conductor.
5)
Part No.: 5012, 2xRG6 solid copper covered steel center conductor.
b.
Riser Rated: CATVR, CL2R, FT4, Sunlight Resistant listed.
1)
Part No.: 5303, RG6 solid copper covered steel center conductor.
c.
Plenum Rated: CATVP, CL2P, FT6 listed
1)
Part No.: 5353, RG6 solid copper covered steel center conductor.
d.
Water Resistant Rated: CATV listed:
1)
Part No.: 5105, RG6 solid copper covered steel center conductor.
B.
CCTV Coaxial Cables: NEC Article 725.
1.
CCTV Coaxial Cables: solid copper center conductor, 95 percent braid shield.
a.
General Purpose Rated: CL2, Sunlight Resistant Listed:
1)
Part No.: 5002, RG6, copper braid shield.
2)
Part No.: 5001, RG59, copper braid shield.
3)
Part No.: 6501, RG59, copper clad aluminum braid shield.
b.
Riser Rated: CL2R, FT4, Sunlight Resistant Listed:
1)
Part No.: 5302, RG6, copper braid shield.
2)
Part No.: 5301, RG59, copper braid shield.
16120-13
c.
2.
Plenum Rated: CL2P, FT6 Listed:
1)
Part No.: 5352, RG6, copper braid shield.
2)
Part No.: 5351, RG59, copper braid shield.
d.
Water Resistant Rated: Sunlight Resistant Listed:
1)
Part No.: 5103, RG59, copper braid shield.
CCTV Coaxial and Power Cables: Solid copper center conductor, 95 percent braid
shield. Stranded copper power conductors.
a.
General Purpose Rated: CL2, Sunlight Resistant Listed:
1)
Part No.: 5119, RG6, copper braid shield.
2)
Part No.: 5013, RG59, copper braid shield.
3)
Part No.: 6508, RG59, copper clad aluminum braid shield.
b.
Plenum Rated: CL2P, FT6 Listed:
1)
Part No.: 5355, RG59, copper braid shield.
c.
Water Resistant Rated: Sunlight Resistant Listed:
1)
Part No.: 5104, RG59, copper braid shield.
PART 3 EXECUTION
3.1
3.2
EXAMINATION AND PREPARATION
A.
Inspect and prepare substrates using the methods recommended by the manufacturer for
achieving best result for the substrates under project conditions.
B.
Do not proceed with installation until substrates have been prepared using the methods
recommended by the manufacturer and deviations from manufacturer's recommended
tolerances are corrected. Commencement of installation constitutes acceptance of
conditions.
C.
If preparation is the responsibility of another installer, notify Architect in writing of deviations
from manufacturer's recommended installation tolerances and conditions.
INSTALLATION
A.
Installation of Pathways:
1.
Cable trays: UTP - Comply with NEMA and TIA/EIA-569-A-7.
2.
Comply with requirements for demarcation points, pathways, cabinets, and racks
specified in Division 16.
3.
Comply with TIA/EIA-569-A for pull box sizing and length of conduit and number of
bends between pull points.
4.
Comply with requirements in Division 16 for installation of conduits and raceways.
5.
Install manufactured conduit sweeps and long radius elbows whenever possible.
6.
Backboards: Install backboard with 96 inch dimension vertical. Butt adjacent sheets
tightly, and form smooth gap-free corners and joints.
B.
Installation Of Conductors And Cables: Comply with NECA 1.
1.
General Requirements for Cabling:
a.
Comply with TIA/EIA 568-C series for UTP installations
b.
Comply with BICSI manuals - Cable Termination Practices
c.
Install 110 style IDC termination hardware for UTP installations
d.
Cables may not be spliced except in the cases of coaxial, fire alarm, and
access control installations where splicing is necessary
e.
Secure and support cables at intervals not to exceed 30 inches and not more
than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and
terminals for all UTP installations
f.
Comply with Honeywell Cable Catalog's Technical Section for pull tensions and
minimum bend radius requirements for all cable installations
g.
Do not install bruised, cut, scored, deformed, or abraded cable.
16120-14
h.
2.
3.
4.
5.
Allow cables to reach room temperature before dereeling. Do not use heating
equipment such as heat lamps to make the cable more flexible.
i.
For proper cable pulling, refer to BICSI manuals, NSCA training manuals,
NICET training manuals, or Infocomm training manuals.
j.
Plenum cables may be installed in all portions of the building cable routing and
raceways. Do not install outdoor or riser rated cable in building plenum areas.
k.
Separation from EMI sources - Maintain adequate separation between
communications cables in ground metallic raceways and unshielded power
lines or electrical equipment.
1)
2.5 inches: Electrical equipment - rating less than 2kVA.
2)
6 inches: Electrical equipment - rating between 2-5kVA.
3)
12 inches: Electrical equipment - rating more than 5kVA.
l.
Separation from EMI sources - Maintain adequate separation between
communications cables in ground metallic raceways and power lines or
electrical equipment located in grounded metallic conduits or enclosures.
1)
No requirements: Electrical equipment - rating less than 2.5kVA.
2)
3 inches: Electrical equipment - rating between 2-5kVA.
3)
6 inches: Electrical equipment - rating more than 5kVA.
m.
Separation between communication cables and electrical motors/transformers,
5kVA or larger - minimum 48 inches.
n.
Separation between communication cables and fluorescent fixtures: Minimum 5
inches.
UTP installations:
a.
Comply with TIA/EIA 568-C series standards.
b.
Refer to BICSI Manuals
Coaxial Cabling Installations:
a.
Bend Radius: 10 times cable O.D.
b.
Maintain Impedance throughout the system: 75 Ohm cable - 75 Ohm
connectors.
c.
Pull Tension:
1)
RG59/U Coaxial Cables: Maximum 48 lbs.
2)
RG6/U Coaxial Cables: Maximum 69 lbs.
3)
RG11/U Coaxial Cables: Maximum 145 lbs.
d.
Make coaxial connections with approved connectors.
e.
Use appropriate tools to ensure proper connections.
f.
Outdoor Coaxial Installations: Install outdoor connections in enclosures that
comply with NEMA 250, Type 4X. Install water-sealed connectors. O-rings may
be required.
RS-485 Installation:
a.
Bend Radius: 4-6 times cable O.D.
b.
Pull Tension: Refer to cable specification data.
c.
Use approved crimp-on plug, terminal connections, or other connectors suitable
for data RS terminations.
Fire Alarm Cabling Installation:
a.
Comply with NECA 1 and NFPA 72.
b.
Wiring methods: Install wiring in metal raceway according to Division 16.
1)
Install plenum rated cable in environmental air spaces- Plenum spaces.
2)
Fire alarm circuits and equipment control wiring associated with the fire
alarm system shall be installed in a dedicated raceway system. This
system shall not be used for any other wire or cable.
c.
Outdoor: For Indoor/Outdoor fire alarm installations, use sunlight and moisture
resistant wire or cables.
d.
Wiring with Enclosures:
1)
Separate power-limited and non-power limited conductors as
recommended by manufacturer.
2)
Install conductors parallel or at right angles to sides and back of the
16120-15
enclosures.
Bundle, lace, and train conductors to terminal points with no excess.
Connect to terminal blocks all conductors that are terminated, spliced, or
interrupted in any enclosure associated with the fire alarm.
5)
Mark each terminal according to the system's wiring diagrams.
6)
Make all connections with approved crimp-on terminal spade plugs,
pressure type terminal blocks, or plug connectors.
Cable Taps: Use numbered terminal strips in junction, pull, outlet boxes, as well
as cabinets or equipment enclosures where circuit connections are made.
Color Coding: Color code fire alarm conductors differently from the normal
building power wiring. It is recommended, but not required that the fire alarm
cabling jacket be red. Special jacket striping may be used for easy identification
of the fire alarm wiring.
3)
4)
e.
f.
3.3
C.
Connections: Comply with requirements in Division 16.
D.
Firestopping: Comply with requirements in Division 7, TIA/EIA 569-A Firestopping Annex A
and BICSI TDMM.
E.
Grounding:
1.
For communication wiring, comply with ANSI-J-STD-607-A and BICSI TDMM Grounding, bonding, and electrical protection.
2.
For low voltage wiring and cabling, comply with requirements in Division 16.
F.
Identification: Identification of system components, wiring, and cabling comply with TIA/EIA
606-A, Division 16.
G.
Field Quality Control:
1.
Testing Agency: Engage a qualified testing agency to perform tests and inspections.
2.
Perform test and inspection of cables upon delivery.
3.
Testing and Inspection:
a.
Visually inspect cables for deformities.
b.
Visually inspect cable packaging for damage.
c.
Test for shorts or opens.
4.
UTP testing shall be required for end-to-end verification.
PROTECTION
A.
Protect installed products until completion of project.
B.
Touch-up, repair or replace damaged products before Substantial Completion.
END OF SECTION
16120-16