B1 Particular Technical Requirements 7518P01/FICHT-8865720-v1 Section VI-I 1. Data Sheets 7518P01/FICHT-8825852-v12 Section VI-1-2 220kV Transmission System 220 kV Switchyard Equipment Unit Required - SF6 Nominal voltage kV 220 Rated voltage kV 245 Rated frequency Hz 50 Rated phase to ground lightning impulse withstand voltage (peak) kV 1050 Rated power frequency short withstand voltage kV 460 Rated short-circuit breaking current kA 50 Rated short-circuit making current (peak) kA 125 Rated nominal current A 2000 Rated short-circuit duration s 1 Minimum creepage distance mm 6125 - 1.3 - 0-0.3s – C01 min – C0 or C0-15sC0 Maximum breaking time ms 60 Maximum making time ms 100 Offered Performance and Design Criteria Circuit Breakers for 220 kV System Circuit breaker type Manufacturer First pole-to-clear factor Rated operating sequence (three-phase auto reclosing) Number of tripping coils 2 Number of closing coils 1 Protection class - IP 55 single and three phase Auto reclosing Drive - 1 pole Type of drive - Spring type Power supply for drive V 110 DC Power supply for auxiliary contacts V 110 DC Power supply for heater V 220/380 AC yes/no yes Auto reclosure, single and three phase 7518P01/FICHT-8825852-v12 Section VI-1-3 220kV Transmission System 220 kV Switchyard Equipment Unit Required Offered Performance and Design Criteria Isolator with Two Grounding Switch, 220 kV Manufacturer Type outdoor Type of operation Earthing on both sides center break yes/no yes Nominal voltage kV 220 Rated voltage kV 245 Rated nominal current A 2000 Rated short time current Ith (1s) kA 50 Rated short-circuit making current Idyn (peak) kA 125 Rated phase-to-ground lightning impulse withstand voltage (peak) kV 1050 Rated power frequency short withstand voltage kV 460 Rated frequency Hz 50 Minimum creepage distance mm 6125 Protection class - IP 55 Drive - 1 or 3 pole Type of drive - Power supply for drive V Electric motor 110 DC Power supply for auxiliary contacts V 110 DC Power supply for heater V 220/380 AC Manual operating facility yes/no yes Isolator with one or two Grounding Switches, 220 kV Manufacturer Type outdoor Type of operation Earthing on one side center break yes/no yes Nominal voltage kV 220 Rated voltage kV 245 Rated nominal current A 2000 7518P01/FICHT-8825852-v12 Section VI-1-4 220kV Transmission System 220 kV Switchyard Equipment Unit Required Rated short time current Ith (1s) kA 50 Rated short-circuit making current Idyn (peak) kA 125 Rated phase-to-ground lightning impulse withstand voltage (peak) kV 1050 Rated power frequency shortwithstand voltage kV 460 Rated frequency Hz 50 Minimum creepage distance mm 6125 Protection class - IP 55 Drive - 1 or 3 pole Type of drive - Electric motor Power supply for drive V 110 DC Power supply for auxiliary contacts V 110 DC Power supply for heater V 220/380 AC Manual operating facility yes/no yes Offered Performance and Design Criteria Current Transformers, 220 kV Manufacturer Type outdoor Nominal voltage kV 220 Rated voltage kV 245 Rated secondary currents A 1 Class accuracy for metering - 0.2 Class accuracy for measurement - 0.5 Class accuracy for protection system - 5 P 20 7518P01/FICHT-8825852-v12 Section VI-1-5 220kV Transmission System 220 kV Switchyard Equipment Unit Required Offered Performance and Design Criteria Number of cores - metering 1 measuring 1 protection 4 Rated burden VA 50 Minimum creepage distance mm 6,125 - a)200 - 400 b)50 c)100 d)200 e)1000-2000 1/1/1/1/1/1 A Rating of protective cores VA 50 Rating of measuring cores VA 30 kV 1050 kV 460 kA 50 Nominal voltage kV 220 Rated voltage kV 245 - 220/0.1/0.1/ 0,1 kV 3 / 3 / 3 / 3 Capacity of main winding VA 100 Capacity of secondary winding VA 100 Accuracy class for metering - 0.2 Accuracy class for measuring - 0.5 Accuracy class for protection - 3P Minimum creepage distance mm 6125 Rated phase-to-ground lightning impulse withstand voltage (peak) kV 1050 Transformation ratio Rated phase to ground power frequency withstand voltage (peak) Rated power frequency withstand voltage (peak) Rated short time current Ith (1s) Voltage Transformers, 220 kV (capacitive) Manufacturer Type Transformation ratio 7518P01/FICHT-8825852-v12 Section VI-1-6 220kV Transmission System 220 kV Switchyard Equipment Unit Required kV 460 Nominal voltage kV 220 Rated voltage kV 198 Rated continuous voltage kV 20 Rated discharge current kA 10 Offered Performance and Design Criteria Rated power withstand voltage (peak) Lightning Arresters, 220 kV System Manufacturer Type 220 kV Lighting Arrester Discharge Counter Manufacturer Type outdoor Counter indication digital Protection class IP 55 Number per three arresters 1 Post Insulator, 220 kV Manufacturer Type Rated voltage kV 245 Rated phase to ground lightning impulse withstand voltage (peak) kV 1050 Rated power frequencywithstand voltage (peak) kV 460 Minimum creepage distance mm 6125 Conductor at 220 kV Switchyard Manufacturers - Type - Total cross-section mm2 Aluminum conductor acc. EN50182 Aluminum cross-section mm2 2 x 400 7518P01/FICHT-8825852-v12 Section VI-1-7 220kV Transmission System 220 kV Switchyard Equipment Unit Required Aluminum mm 400 Conductor diameter mm Conductor weight kg/m Offered Performance and Design Criteria Conductor design: number of strands x diameter Theoretical breaking force kN Ohmic resistance at 20°C /km Insulator String at 220 kV Manufacturers - Type - Insulating body material - Rated electromechanical or mechanical strength kN Max. shed diameter mm Installation height mm Nominal creepage distance mm Rated short-time withstand current kA Weight kg Dead-end and suspension strings Number of cap insulators per string Single string Pcs. Double string Pcs. Clamps/Dead-End Joints, 220 kV Manufacturers Type Cross-section 7518P01/FICHT-8825852-v12 Section VI-1-8 132 kV Transmission System 132 kV Switchyard Equipment Unit Required - SF6 Nominal voltage kV 132 Rated voltage kV 145 Rated frequency Hz 50 Rated phase to ground lightning impulse withstand voltage (peak) kV 650 Rated power frequency short withstand voltage kV 275 Rated short-circuit breaking current kA 40 Rated short-circuit making current (peak) kA 100 Rated nominal current A 1000 Rated short-circuit duration s 1 Minimum creepage distance mm 4000 - 1.3 - 0-0.3s – C01 min – C0 or C0-15sC0 Maximum breaking time ms 60 Maximum making time ms 100 Offered Performance and Design Criteria Circuit Breakers for 132 kV System Circuit breaker type Manufacturer First pole-to-clear factor Rated operating sequence (three-phase auto reclosing) Number of tripping coils 2 Number of closing coils 1 Protection class - IP 55 single and three phase Auto reclosing Drive - 1 pole Type of drive - Spring type Power supply for drive V 110 DC Power supply for auxiliary contacts V 110 DC Power supply for heater V 220/380 AC yes/no yes Auto reclosure, single and three phase 7518P01/FICHT-8825852-v12 Section VI-1-9 132 kV Transmission System 132 kV Switchyard Equipment Unit Required Offered Performance and Design Criteria Isolator with Two Grounding Switch, 132 kV Manufacturer Type outdoor Type of operation Earthing on both sides center break yes/no yes Nominal voltage kV 132 Rated voltage kV 145 Rated nominal current A 1250 Rated short time current Ith (1s) kA 40 Rated short-circuit making current Idyn (peak) kA 100 Rated phase-to-ground lightning impulse withstand voltage (peak) kV 650 Rated power frequency short withstand voltage kV 275 Rated frequency Hz 50 Minimum creepage distance mm 4000 Protection class - IP 55 Drive - 1 or 3 pole Type of drive - Power supply for drive V Electric motor 110 DC Power supply for auxiliary contacts V 110 DC Power supply for heater V 220/380 AC Manual operating facility yes/no yes Isolator with one or two Grounding Switches, 132kV Manufacturer Type outdoor Type of operation Earthing on one side center break yes/no yes Nominal voltage kV 132 Rated voltage kV 145 Rated nominal current A 1250 7518P01/FICHT-8825852-v12 Section VI-1-10 132 kV Transmission System 132 kV Switchyard Equipment Unit Required Rated short time current Ith (1s) kA 40 Rated short-circuit making current Idyn (peak) kA 100 Rated phase-to-ground lightning impulse withstand voltage (peak) kV 650 Rated power frequency shortwithstand voltage kV 275 Rated frequency Hz 50 Minimum creepage distance mm 4000 Protection class - IP 55 Drive - 1 or 3 pole Type of drive - Electric motor Power supply for drive V 110 DC Power supply for auxiliary contacts V 110 DC Power supply for heater V 220/380 AC Manual operating facility yes/no yes Offered Performance and Design Criteria Current Transformers, 132 kV Manufacturer Type outdoor Nominal voltage kV 132 Rated voltage kV 145 Rated secondary currents A 1 Class accuracy for metering - 0.2 Class accuracy for measurement - 0.5 Class accuracy for protection system - 5 P 20 7518P01/FICHT-8825852-v12 Section VI-1-11 132 kV Transmission System 132 kV Switchyard Equipment Unit Required Offered Performance and Design Criteria Number of cores - Metering 1 measuring 1 protection 4 Rated burden VA 50 Minimum creepage distance mm 4000 Transformation ratio - 300 100-200 1/1/1/1/1/1 A Rating of protective cores VA 50 Rating of measuring cores VA 30 kV 650 kV 275 kA 40 Nominal voltage kV 110 Rated voltage kV 245 - 132/0.1/0.1/ 0,1 kV 3 / 3 / 3 / 3 Capacity of main winding VA 100 Capacity of secondary winding VA 100 Accuracy class for metering - 0.2 Accuracy class for measuring - 0.5 Accuracy class for protection - 3P Minimum creepage distance mm 4000 Rated phase-to-ground lightning impulse withstand voltage (peak) kV 650 Rated power withstand voltage (peak) kV 275 Rated phase to ground power frequency withstand voltage (peak) Rated power frequency withstand voltage (peak) Rated short time current Ith (1s) Voltage Transformers, 132 kV (capacitive) Manufacturer Type Transformation ratio 7518P01/FICHT-8825852-v12 Section VI-1-12 132 kV Transmission System 132 kV Switchyard Equipment Unit Required Nominal voltage kV 132 Rated voltage kV 118 Rated continuous voltage kV 20 Rated discharge current kA 10 Offered Performance and Design Criteria Lightning Arresters, 132 kV System Manufacturer Type 132 kV Lighting Arrester Discharge Counter Manufacturer Type outdoor Counter indication digital Protection class IP 55 Number per three arresters 1 Post Insulator, 132 kV Manufacturer Type Rated voltage kV 145 Rated phase to ground lightning impulse withstand voltage (peak) kV 650 Rated power frequencywithstand voltage (peak) kV 275 Minimum creepage distance mm 4000 Conductor at 132 kV Switchyard Manufacturers - Type - Total cross-section mm2 Aluminum conductor acc. EN50182 Aluminum cross-section mm2 1 x 400 mm 400 Conductor design: number of strands x diameter Aluminum 7518P01/FICHT-8825852-v12 Section VI-1-13 132 kV Transmission System 132 kV Switchyard Equipment Unit Required Offered Performance and Design Criteria Conductor diameter mm Conductor weight kg/m Theoretical breaking force kN Ohmic resistance at 20°C /km Insulator String at 132 kV Manufacturers - Type - Insulating body material - Rated electromechanical or mechanical strength kN Max. shed diameter mm Installation height mm Nominal creepage distance mm Rated short-time withstand current kA Weight kg Dead-end and suspension strings Number of cap insulators per string Single string Pcs. Double string Pcs. Clamps/Dead-End Joints, 132 kV Manufacturers Type Cross-section 7518P01/FICHT-8825852-v12 Section VI-1-14 220kV Transmission System Power Transformers/Reactors Unit Required Data MVA 90/110 Performance and Design Criteria Bid Data 220/132/33kV Auto Transformer Maximum continuous rating (MCR) for the 3 phase units ONAN/ ONAF Number of Phases 3 Number of windings Auto plus stabilising Normal ratio of transformation at no load and at principle tap - HV/LV/TV kV 220/132/33 Corresponding highest system voltages kV 245/145/36 Corresponding lowest system frequency Hz 48 Minimum withstand voltages: Full wave impulse withstand 1050/650/170 of windings kVp 1050/650/170 of line terminal bushings kVp 460/275/70 Induced over voltage kV rms 38 Power frequency withstand of neutral kV rms Type of cooling ONAN/ONAF Minimum continuous rating MVA 90/110 Rating of tertiary windings MVA 30 External cooling medium - Air Altitude not exceeding m 2000 Air temperature not exceeding °C 42 In any one day °C 35 Average in one year °C 25 Top oil rise normal °C 50 Average ONAN winding rise °C 55 Average ONAF winding rise °C 55 °C 98 Service conditions: Average air temperature in any one year not exceeding: Maximum temperature: Maximum hot spot temperature at maximum continuous rating at yearly average ambient temperature 7518P01/FICHT-8825852-v12 Section VI-1-15 220kV Transmission System Power Transformers/Reactors Unit Required Data °C 140 Performance and Design Criteria Winding hot spot temperature on emergency overload not exceeding Bid Data Phase connections: (a) HV winding Star (b) LV winding Star (c) TV winding Delta (d) Vector group - HV/LV/TV YNa0d1 Short circuit withstand fault level at terminals of: 220 kV busbars kA 50 132 kV busbars kA 40 33 kV busbars kA 25 % 13 kV 33 - initially 200 kVA - future up to 400 kVA ratio ..... plus % 10 ratio ..... minus % 10 Impedance voltage at 75 °C and at normal tap and MCR between windings (% on HV Base): HV & LV % on HV base Delta connected tertiary winding (a) Nominal voltage (b) External load Total range of variation of on load transformation ratio (on HV side) as sl. no. 4: Size of steps 1.25 On load local, remote and supervisory electrical and hand operation Type of control Line drop compensation Yes Whether automatic control required and referenced voltage Yes, 110V, 50Hz Whether separate remote control panel required Estimated distance between remote control point and transformer 7518P01/FICHT-8825852-v12 Yes m See drawings Section VI-1-16 220kV Transmission System Power Transformers/Reactors Unit Required Data Nominal V 110 Maximum float voltage, V 125 Performance and Design Criteria Bid Data DC supply: Whether provision for supervisory control required, including AVR setting Whether marshalling kiosk required Number of transformers for which automatic control is to be suitable Yes Tankside Cubicle 1 (and provision for future 2nd) Terminations Bushing insulators or cable boxes on line and neutral terminals: i) HV line Bushings ii) Neutral Bushings iii) LV line Bushings iv) Tertiary winding Bushings BCT Particulars 400-200/1A, 60VA, 5P20. i) HV (220kV) Side: Core 1 & Core 2: Core 3 : ii) LV (132kV) Side: Core 1, Core 2 & Core 3: iii) Neutral Core 1: Ratio, burden and accuracy class shall be matched with WTI meter. 400-200/1A, 60VA, 5P20. 400/1A, 10VA, Cl 3.0 200-100400/1A, 60VA, 5P20 Accommodation on tank for outdoor weatherproof HV Yes neutral current transformers 7518P01/FICHT-8825852-v12 Section VI-1-17 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Required Data Bid Data 25 mm/kV of system rated (highest) Pollution category of outdoor bushing insulators voltage Cooling To suit transformer design Number of cooler banks required per transformer Rating of each cooler bank as percentage of total loss at CMR % 50 One fan in each group Standby cooling requirement General Type of oil preservation system Air Cell Maximum acceptable noise level 78 dBA Dimensions length mm wide mm weight mm Weight total kg transport kg Oil kg 7518P01/FICHT-8825852-v12 Section VI-1-18 220kV Transmission System Power Transformers/Reactors Unit Required Data - 3-phase oil immersed Applicable standards - IEC 60076, 60354 Rated power ONAN MVA 23 MVA Rated voltage kV/kV 220/33 Highest system voltage kV/kV 245 / 36 Hz 50 Vector group - YN0yn0 Impedance voltage (at rated power) % 13 Insulation - Uniform Type of cooling - ONAN/ONAF Performance and Design Criteria Bid Data Power transformer 220 /33kV /Type Manufacturer Country of origin Rated frequency Temperature rise at rated power over 40°C maximum ambient temperature: - oil (upper level) °C 50 Winding °C 60 460 / Rated power frequency withstand voltage HV/LV kV Rated lightning impulse withstand voltage HV/LV kVpeak 1050 / 650 / 200 Max. noise level (Lp) dB (A) 66 Max. no-load current % In 0.2 losses no loud kW losses at ONAN kW losses at ONAF kW Short circuit withstand 3s kA Impedance homopolar 275 50 /ph *external 7518P01/FICHT-8825852-v12 Section VI-1-19 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Required Data Bid Data connection primary air secondary cables Dimensions lenght mm wide mm height mm Weight Total kg transport kg oil kg On-load tap changer Type - Rated current A Resistor Rated short-time current Maximum kA 50 3 seconds kA 10 On-load tap changer - + 10x1,5% Installation mode - HV side Oper. 200.000 Rated operations duty (min.) 7518P01/FICHT-8825852-v12 Section VI-1-20 220kV Transmission System Power Transformers/Reactors Unit Required Data - 3-phase oil immersed Applicable standards - IEC 60076, 60354 Rated power ONAN MVA 23 MVA Rated voltage kV/kV 132/33 Highest system voltage kV/kV 145 / 36 Hz 50 Vector group - YN0yn0 Impedance voltage (at rated power) % 13 Insulation - Uniform Type of cooling - ONAN Performance and Design Criteria Bid Data Power transformer 132 /33kV /Type Manufacturer Country of origin Rated frequency Temperature rise at rated power over 40°C maximum ambient temperature: - oil (upper level) °C 50 Winding °C 60 Rated power frequency withstand voltage HV/LV kV 275 / 80 Rated lightning impulse withstand voltage HV/LV kVpeak 650 / 200 Max. noise level (Lp) dB (A) 66 Max. no-load current % In 0.2 losses no loud kW losses at ONAN kW losses at ONAF kW Short circuit withstand 3s kA Impedance homopolar 7518P01/FICHT-8825852-v12 40 /ph Section VI-1-21 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Required Data Bid Data connection primary air secondary cables Dimensions lenght mm wide mm height mm Weight Total kg transport kg oil kg On-load tap changer Type - Rated current A Resistor Rated short-time current Maximum kA 40 3 seconds kA 10 On-load tap changer - + 10x1,5% Installation mode - HV side Oper. 200.000 Rated operations duty (min.) 7518P01/FICHT-8825852-v12 Section VI-1-22 220kV Transmission System Power Transformers/Reactors Unit Required Data - Digital - IEC 60255 maximum ambient temperature for rated accuracy oC 55 maximum temperature by storage oC 60 maximum humidity % 80 - EN 50081 Performance and Design Criteria Bid Data General Relays: standard electromagnetic compatibility tests EN 50082-1 IEC 60255-6 insulation tests IEC 60255-5 IEC 60870-21 mechanical tests (vibration and shock stress) IEC 60255-21 IEC 60068-2 Other: all other Norms as specied on technical document - IEC W 1000 year 2 standard - IEC 60529 protection class - IP 52 pre-wired - Yes floor-mounted - Yes steel sheet thickness mm >2 maximum height mm 2000 maximum width mm 800 maximum depth mm 600 front-door material - Glass coloring - RAL 7035 switching capacity of output contacts manufacturer references Panels: HV line protections Differential protection (ANSI: 87L): 7518P01/FICHT-8825852-v12 Section VI-1-23 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Type - Manufacturer - Place of manufacture - Required Data Bid Data Rated values: frequency Hz 50 phase current A 1 V DC 110 ranges of values of restrained protection I/InO 0.05 – 2.00 ranges of values of unrestrained protection I/InO 0.5 – 35.00 ranges of times sec 0.00 – 30.00 auxiliary voltage Settings: Distance protection (ANSI: 21): Type - Manufacturer - Place of manufacture - Rated values: frequency Hz 50 phase current A 1 phase to phase voltage V 110 V DC 110 ranges of values Ohm 0.050 – 600 ranges of times sec 0.00 – 30.00 minimum number of independent impedance zones - 4 type of characteristic of teleprotection - PUTT, POTT trip mode - 1-/3 pole minimum number of autoreclose cycles (ARcycles) - 3 aux. voltage Settings: 7518P01/FICHT-8825852-v12 Section VI-1-24 220kV Transmission System Power Transformers/Reactors Unit Required Data - Yes - IEC 608705-103 9600 Performance and Design Criteria fault locator and event (disturbance) recorder Bid Data Remote communication: protocol transmission rate Baud Back-up overcurrent protection (ANSI: 50/51 &50N/51N): Type - Manufacturer - Place of manufacture - Rated values frequency Hz 50 phase current A 1 phase to phase voltage V 110 V DC 110 ranges of values A 0.10 – 35.00 ranges of times sec 0.00 – 30.00 minimum number of DTL stages for 50/51 - 2 minimum number of IDMT stages for 50/51 - 1 minimum number of DTL stages for 50N/51N - 2 minimum number of IDMT stages for 50N/51N - 1 aux. voltage Settings Transformer Differential Protection Manufacturer Type Ratings Secondary current A Rated frequency Hz DC supply V 7518P01/FICHT-8825852-v12 Section VI-1-25 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Required Data Bid Data Main Characteristics Range of operating coil settings % of C.T. rating Range of bias coil settings Recommended operating coil setting Recommended bias coil setting Number of bias coils Minimum sensitivity earth faults % of C.T. rating phase faults % of C.T. rating Maximum trough fault at which the protective equipment is stable with recommended settings: earth faults % of C.T. rating phase faults % of C.T. rating Maximum time delay between initiation of fault and energizing of breaker trip circuit 3 x IN 10xIN (ms) Communication Interfaces Protection functions Transformer Restricted Earth Fault Protection Manufacturer Relay type Tripping current range from – to X IN Tripping time range from – to ms Transformer Overcurrent and earth fault Protection 7518P01/FICHT-8825852-v12 Section VI-1-26 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Required Data Bid Data Manufacturer Relay type Tripping current range from - to x IN ms Tripping time range from - to x IN ms Tertiary winding protection Manufacturer Relay type Phase balance protection Manufacturer Relay type Reactor Differential protection (ANSI: 87T): Type - Manufacturer - Place of manufacture - Rated values frequency Hz 50 phase current A 1 V DC 110 ranges of values of restrained protection I/InO 0.05 – 2.00 ranges of values of unrestrained protection I/InO 0.5 – 35.00 ranges of times sec 0.00 – 30.00 aux. voltage Settings Settings CT supervision Operating time 7518P01/FICHT-8825852-v12 ms Section VI-1-27 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Required Data Bid Data Scheme burdens DC burden W AC burden Ohm Contact rating Make and carry for 0.2 s VA Break Operation indicator Insulation AC inputs (for 1 minute to all circuits and to case earth) High voltage impulse withstand voltage kV kV peak Back-up overcurrent protection (ANSI: 50/51 & 49): Type Manufacturer - Place of manufacture - Rated values frequency Hz 50 phase current A 1 phase to phase voltage V 110 V DC 110 ranges of values A 0.10 – 35.00 ranges of times sec 0.00 – 30.00 minimum number of DTL stages of 50/51 - 2 minimum number of IDMT stages of 50/51 - 1 aux. voltage Settings 0.1 – 4.0 k-factor of 49 time constant 49 min 1.0 – 999.0 Busbar protection 7518P01/FICHT-8825852-v12 Section VI-1-28 220kV Transmission System Power Transformers/Reactors Unit Performance and Design Criteria Required Data Bid Data Differential protection (ANSI: 87L): Type - Manufacturer - Place of manufacture - Rated values frequency Hz 50 phase current A 1 V DC 110 ranges of values of restrained protection I/InO 0.05 – 2.00 ranges of values of unrestrained protection I/InO 0.5 – 35.00 ranges of times sec 0.00 – 30.00 aux. voltage Settings CT supervision Operating time ms Scheme burdens DC burden W AC burden Ohm Contact rating Make and carry for 0.2 s VA Break Operation indicator Insulation AC inputs (for 1 minute to all circuits and to case earth) High voltage impulse withstand voltage 7518P01/FICHT-8825852-v12 kV kV peak Section VI-1-29 220kV Transmission System MV Switchgear Performance and Design Criteria Minimum requirements Unit Data - metalclad Offered Data 33kV switchgear manufacturer designation type insulation air nominal system voltage kV 33 highest value of system operating voltage kV 40,5 range of highest voltage for equipment (IEC 60071-1) rated frequency Hz 50 rated short-circuit current (3 s) kArms 31,5 rated lightning impulse withstand voltage kVpeak 170/ (185)* rated power frequency short duration withstand voltage kVrms 70/ (85)* kA 31,5 kApeak 80 busbar, sectionalizer A 1250 outgoing feeders A 600 incoming feeder from transformer A 1250 protection class (with closed door) - IP 3X rated operating cycle of circuit breaker - 0-0.3 sec.-C03 min.-C0 rated voltage of CB drive V 110 DC type of circuit breaker - vacuum type of current transformers - cast-resin insulated incoming feeder A 600-1250 outgoing feeders A 200-400 symmetrical breaking current short circuit making current rated current ratings of current transformers primary winding: accuracy class for measuring / metering 0.5 *external 7518P01/FICHT-8825852-v12 Section VI-1-30 220kV Transmission System MV Switchgear Performance and Design Criteria Minimum requirements Unit Data accuracy class for protection 5P20 type of voltage transformers inductive, cast-resin insulated ratings kV Data 30/0.1/0.1 3/3/3 accuracy class for protection 3P accuracy class for measuring / metering 0.5 7518P01/FICHT-8825852-v12 Offered Section VI-1-31 Station service transformers Unit Required Data Type - 3-phase hermetically sealed Applicable standard - IEC 60076 Rated apparent power kVA 160 Rated voltage HV/LV kV 33/0.4 Rated frequency Hz 50 Vector group - Dyn 11 Impedance voltage % 4 Off-load tap changer regulation - + 2x2,5% Type of cooling - ONAN Rated power frequency withstand voltage kV 70/ (85)* Rated lightning impulse withstand voltage kVpeak 170/ (185)* Performance and Design Criteria Bid Data Station service transformers 33/ 0.4 kV Type Manufacturer Country of origin *external 7518P01/FICHT-8825852-v12 Section VI-1-32 Substation Control and monitoring system Unit Required Data System availability % > 99,95 Meantime between failure h > 8750 Performance and Design Criteria Bid Data Substation control and monitoring system Automatic time synchronization at all nodes of the network Time resolution events Yes msec Fault indication LEDs on modules Spare < 10 Yes % 20 Station Bus IEC 61850-81 Protocol Transmission medium Transmission rate FOC MBit/s 100 V 110 Ethernet Switches Manufacturer Type Power supply from station battery Clock system Manufacturer Type Synchronization source Synchronization interval Station computer Manufacturer Type Power supply from station battery (DC-supply) 7518P01/FICHT-8825852-v12 Section VI-1-33 Substation Control and monitoring system Unit Required Data V 110 Performance and Design Criteria Bid Data Common bay unit Manufacturer Type Power supply from station battery (DC-supply) Interfaces to remote control centers Serial Interface IEC 60870-5-101 Transmission medium Data transmission rate Bit/s Serial Interface IEC 60870-5-104 Transmission medium Data transmission rate 9600 FOC MBit/s 10 Other serial Interface Transmission medium FOC Data transmission rate Operator workstations (HMI) Hardware Manufacturer Type Power supply from station battery via converter V AC 230 CPU Working memory Hard disk RAID-System DVD or Disk array External memory Operating system Screens Screen size Pixels 7518P01/FICHT-8825852-v12 2 TFT inch 20 1280 x 1024 Section VI-1-34 Substation Control and monitoring system Unit Required Data Exchange of display (first reaction) sec. <1 Presentation of a binary change in the process display sec. < 0.5 Presentation of an analogue change in the process display sec. <1 From order to process output sec. < 0.5 From order to updating the display sec. < 1.5 Performance and Design Criteria Bid Data MMI-Software Manufacturer Type System Performance Hardcopy printer Number of printers Power supply from station battery via converter Format 1 V AC 230 DIN A3 Color Yes Pages / min. > 12 Presentation of an analogue change in the process display sec. <1 From order to process output sec. < 0.5 From order to updating the display sec. < 1.5 Event printer Number of printers Power supply from station battery via converter Format Color 1 V AC 230 DIN A4 No Pages / min. Service and Analysis System Hardware Manufacturer 7518P01/FICHT-8825852-v12 Section VI-1-35 Substation Control and monitoring system Unit Required Data V AC 230 Performance and Design Criteria Bid Data Type Power supply from station battery via converter CPU Working memory Hard disk External memory DVD Operating system Screens Screen size 1 TFT inch 20 Pixels 1280 x 1024 Service and Analysis Software Manufacturer Type Service unit Hardware Laptop Manufacturer Type Power supply V AC 230 CPU Working memory Hard disk Operating system External memory Screen size Pixels DVD inch 14 1280 x 1024 Service Software Manufacturer Type Panels 7518P01/FICHT-8825852-v12 Section VI-1-36 Substation Control and monitoring system Unit Performance and Design Criteria Required Data Pre-wired Yes Floor-mounted Yes Steel sheet thickness mm Protection class Bid Data >2 IP 52 Maximum height mm 2000 Maximum width mm 800 Maximum depth mm 600 Front-door material glass Coloring RAL 7035 Bay control units (IEDs) for high voltage application Manufacturer Type Power supply from station battery (DC-supply) V Protocol 110 IEC 61850 Other protocols Bay control units (IEDs) for middle voltage application Manufacturer Type Power supply from station battery (DC-supply) Protocol V 110 IEC 61850 Other protocols 7518P01/FICHT-8825852-v12 Section VI-1-37 Unit Optical Telecommunication Equipment Performance and Design Criteria Required Data Bid Data ODF Manufacturer - Type - Number of fiber interconnections - 96 Connector loss dB/ connector < 0.5 Screw on type connectors - yes designed for 19” cubicles - yes SDH Multiplexer and Access Multiplexer General Manufacturer of n x 2 MBit multiplexer equipment - terminal equipment - Type(s) of n x 2 MBit multiplexer - terminal equipment - Maximum extension of transmission capacity of individual terminal by adding plug in cards. - Ditto. for multiplexer based on 2 MBit-hierarchy. - Maximum extension for multiplexer and terminal equipment racks. - Protection class(es) of terminal equipment racks. - Construction Requirements Operating principle of amplifiers: optical - optical (bit rate insensitive) - Yes STM - 1 MBit/s 155 STM - 4 MBit/s 622 Operating range of fibre optic terminals. Operating principle of optical transmitter. 7518P01/FICHT-8825852-v12 Section VI-1-38 Unit Optical Telecommunication Equipment Performance and Design Criteria Required Data Bid Data Optical Parameters Nominal operating wavelength. Remaining overall system margin at start of life/end of life. Receiver sensitivity (at BER of 10-10) at start of life/end of life. Transmission Parameters Bit error rate (path including terminals) at n x 2 MBit/s - <1 x 10-10 Jitter performance n x 2 MBit/s Accuracy of internal clock acc. to G.823 ppm Line code (optical) Line code (electrical) ITU/CCITT standards (PCM equipment) 7518P01/FICHT-8825852-v12 Section VI-1-39 Unit Required Data mm x mm 96 x 96 Accuracy class - 1.0 Operating principle - moving coil - 0.5 % 0.3 Metering Equipment Performance and Design Criteria Bid Data Measuring instruments for (Volt, Ampere, Watt, Var, cos phi etc.) Size Meters (internal) Accuracy class Meters (Billing) Max. error Number of tariffs 4 Selectable recording interval min 1-60 15 minutes interval days 45 And for No's channel No. 8 Battery capacity days 32 Optical port - yes Serial port RS-232-C - yes years 5 s 0.5 Storage capacity for: Internal clock: battery capacity Max. error per month ST-PCQ data analysis software of Sangamo Software Programmer/Retriever Type - ST-RP or TELXON PTC-790 Batteries - rechargeable RS-232-C accessory module - yes Optical port accessory module - yes 7518P01/FICHT-8825852-v12 Section VI-1-40 Unit Required Data % 0.5 Output current mA 4-20 Auxiliary voltage Vdc 125 Max. Power consumption VA 1 Metering Equipment Performance and Design Criteria Bid Data Transducers Accuracy Measuring Instruments Voltmeter Manufacturer - Type - Size mm x mm Scale degree Accuracy class Power consumption VA Operating principle - Electro-mechanical - yes/no Electronic - yes/no Ampere meter Manufacturer - Type - Size mm x mm Scale degree Accuracy class Power consumption VA Operating principle - Electro-mechanical - yes/no Electronic - yes/no 7518P01/FICHT-8825852-v12 Section VI-1-41 Metering Equipment Unit Performance and Design Criteria Required Data Bid Data Watt meter Manufacturer - Type - Size mm x mm Scale degree Accuracy class - Power consumption VA Operating principle - Electro-mechanical - yes/no Electronic - yes/no VAR meter Manufacturer - Type - Size mm x mm Scale degree Accuracy class - Power consumption VA Operating principle - Electro-mechanical - yes/no Electronic - yes/no Meters (internal) Watt-hour meter Manufacturer - Type - Size mm x mm Accuracy class - Power consumption VA Operating principle - Electro-mechanical - 7518P01/FICHT-8825852-v12 yes/no Section VI-1-42 Metering Equipment Unit Required Data - yes/no Performance and Design Criteria Electronic Bid Data VAR hour meter Manufacturer - Type - Size mm x mm Accuracy class - Power consumption VA Operating principle - Electro-mechanical - yes/no Electronic - yes/no 7518P01/FICHT-8825852-v12 Section VI-1-43 0.4 kV Installations Unit Required Data Applicable standards - IEC 60439, 60947 Type - fixed units Rated voltage V 400 Frequency Hz 50 Rated short-circuit current for 1 s kA 50 Test voltage kV 2.5 Type of circuit breaker driving mechanism - Handoperated Secondary current of current transformer A 1 Protection class - IP 41 Performance and Design Criteria Bid Data 0.4 kV Installations 7518P01/FICHT-8825852-v12 Section VI-1-44 110 V DC Equipment Unit Required Data - IEC 60439, 60947 - fix mounted components P and N Insulated Rated voltage DC V 110 Test voltage V 1500 Type of load break switch/circuit breaker - hand-operated Protection class - IP 41 K 110 Battery type - NiCd Applicable standard - IEC 60623 Rated voltage V 110 - parallel standby Ah 250 - Thyristor controlled Input voltage (three-phase) V 400 + 10% Rated DC voltage V 110 Maximum DC voltage V 132 Residual ripple % <1 Type of cooling - self-ventilating Protection class of cubicle - IP 41 Performance and Design Criteria Bid Data 110 V DC Equipment Applicable standards Type of distribution board Busbar Min. insulation resistance Type of operation Rated capacity (for 10 hours discharge time) Battery charger type 7518P01/FICHT-8825852-v12 Section VI-1-45 240 V AC Uninterruptible Power Supply Unit Performance and Design Criteria Required Data Bid Data Static UPS General data Manufacturer Applicable standards Rated power at … °C ambient temperature IEC 62040 kVA/ °C 120 / 40 kW 96 Type of cooling - AN Protection class of cubicle IP 20 Rated voltage, input V 3x400/230 Rated voltage, output V 400/230 Voltage control % < +/- 1 Frequency Hz 50 Frequency stability Hz +/- 0,05 Frequency stability with auto-pulsing % +/- 0,1 Active power 125 % - 10 min 150 % - 60 s Overload capability Max. power loss at rated load W Acoustic level on 100 % load dB(A) < 63 (in 1m) Efficiency at 75 - 100 % linear load, at 75 - 100 % nonlinear load % Total Harmonic Distortion of Current (THDI) % <9 Static transfer switch yes / no yes Network card yes / no yes Interfaces: RS-232, RJ 45, ModBus alternative ProfiBus yes / no yes Relais cards for operating and malfunction messages yes / no yes Dimensions: - height mm - width mm - depth mm Total weight kg 7518P01/FICHT-8825852-v12 > 95 > 93 Section VI-1-46 240 V AC Uninterruptible Power Supply Unit Required Data Manufacturer - - Type - - Power supply - TN-S 400 V ± 10 % 50 Hz ± 2 % Rated voltage DC V - Rated current DC A - Maximum ambient temperature for operating at rated current °C - static (0 – 100 % of rated current) % ± 0,5 dynamic % - Residual undulation w/o battery % ss 5 Constance of the direct current % - % ss - Funkentstörung - IEC 61000-6-2 criterion A Type of cooling - self ventilating Efficiency % - Power factor - - Batterie type (maintenance free) - OPzS Rated voltage V - Ah - h 8 Performance and Design Criteria Bid Data Rectifier data Constance of the output voltage: Current undulation Batterie data Count of cells Rated capacity (C10, 1,8V/Cell, 20 °C) Discharge time 10 years at 20 °C Life period of the battery Weight kg Dimensions: mm 7518P01/FICHT-8825852-v12 Section VI-1-47 240 V AC Uninterruptible Power Supply Unit Performance and Design Criteria - height - width mm - depth mm Required Data Battery mounted in cubicle / on racks yes Drip pan for electrolyte yes Battery junction box yes Bid Data Inverter data: Input voltage V DC 110 ± 15 % Rated power kVA 120 °C - power factor range (ind. to cap.) - - Output voltage V TN-S system 400 / 230 Output frequency Hz 50 ± 1 % linear load % <2 nonlinear load % - for 10 min. x IN 1,25 for 60 sec. x IN 1,5 static % <2 dynamic (100 % load changes) % < 10 Efficiency (at cos = 0,8) % - Funkentstörung - IEC 61000-6-2 criterion A Static transfer switch yes / no yes Manual bypass switch yes / no yes Noise level at 1 m distance (any range 0 % till 100 % rated current) dB(A) 60 - IP 31 Maximum ambient temperature for operating at rated current. Distortion factor: Overload capability: voltage tolerance: Protection class 7518P01/FICHT-8825852-v12 Section VI-1-48 240 V AC Uninterruptible Power Supply Unit Required Data Type of cooling - self ventilating Manual transfer yes / no yes Performance and Design Criteria 7518P01/FICHT-8825852-v12 Bid Data Section VI-1-49 Cable Equipment Unit Performance and Design Criteria Required Data Bid Data 33 kV power cables, single-core Applicable standards Type IEC 60502 - XLPE Specified voltage E0/E kV 21/35 Highest system voltage kV 35 Rated frequency Hz 50 Test voltage kV 52.5 - Cooper mm approx.15 x d Conductor kA 16 Screen kA 10 Conductor material Bending radius (single core cables) Rated short circuit current (1 s.) 0.4 kV power cables, four-core Applicable standards Type IEC 60502 - PVC Specified voltage E0/E kV 0.6/1 Highest system voltage kV 0.44 Rated frequency Hz 50 Test voltage kV 2.5 - Cooper mm approx.15 x d Conductor kA 25 Screen kA 15 Conductor material Bending radius (single core cables) Rated short circuit current (1 s.) 7518P01/FICHT-8825852-v12 Section VI-1-50 Earthing System Unit Required - IEEE 80, IEC 60621 mm2 70 - by compression mm 8 Bid Data Performance and Design Criteria Earthing System Applicable standards Size of standards copper conductor Mode of connection Diameter of round copper rods for lightning protection IEC 60950 yes To be verified by CONTRACTO R Equipotential Bonding Power and Lighting Installation Subdistribution boards Type - Fixed Rated voltage V 400/230 Rated frequency - 50 kV 2.5 Test voltage Degree of protection IP41/IP54 Lighting fixtures indoor fluorescent W 1 x 58/2 x 58 indoor halogen W 1 x 250/1 x 400 outdoor high-pressure mercury W 400 - CEE form Power and domestic sockets Type Installation mode power socket combination - domestic sockets - Surface - IP54 Degree of protection 7518P01/FICHT-8825852-v12 Section VI-1-51 2. Annex 3. Forms and Procedures