Minutes - June 1, 2013 2013 MSJC Reinforcement & Connectors Subcommittee 2:30-5:30pm Coast Coal Harbour Hotel, Coal Harbour A Room, Vancouver BC 1. 2. 3. Welcome Attendance/Membership Voting members: David Biggs, Tom Corcoran, Terry Curtis, Matt Jackson, Mark McGinley, David McLean, Max Porter Others: John Swink, Andy Dalrymple, Andrew Geister, John McCall, Sarah Rogers, Paul Curtis, Art Schultz Announcements a. 2016 Committee and Chair announcements - incoming chair of R&C committee is Fernando Fonseca b. Executive Subcommittee 1. Volunteers needed to proofread 2013 final draft. Speak to Phil and Diane. 2. Provide changes to PC responses – any changes from results from Main 10. 3. Request Main 11 items. 4. Max Porter - editor. 5. This is last meeting of 2013 subcommittee. Official discharge is in fall but there will be no meeting. Subcommittee members should continue to vote; R&C will only have Minutes to approve. 6. Minutes of this meeting are due mid-July. 7. 2016 MSJC Meeting October 13-15, 2013 in Herndon, VA. c. Main 11 ballots due to editors June 10. Comments back by June 14. Ballots to Andy by June 17. 4. Approval of Fall 2012 Minutes - completed, previously approved by email vote Oct. 1, 2012. 5. Old Business: a. MAIN 08 RESULTS 08-R-012 Failed with 2 negatives + comments for new business Affirmative with Comment Richard,Bennett It seems like there should be a reference to the new Figure in the commentary. John,Chrysler Please correct diagram. The maximum 135 degrees that is indicated shows an angle that exceeds 135 degrees by a fair amount. Keith,Itzler The diagram is not a reasonable representation of masonry construction and could cause confusion. Going to the trouble of adding a diagram should make things clearer, this does not. Make the diagram applicable to masonry or consider omitting it. Negative Edwin,Huston I believe that the 135 degree bend DOES apply to the hooks at the ends of ties. There are well documented failures to buildings in Chile and in other locations where the hooks at the ends of the ties did not provide sufficient confinement. Rochelle,Jaffe 1. Although columns are required to have laterally tied longitudinal reinforcement, pilasters are not. Also, columns may be formed with brick units, not just block units. Delete the phrase “(pilaster/column block)”. 2. If masonry units are to be identified in the figure, the grout should also be identified. 08-R-015 Passed - done 08-R-016 Passed; 1 comment for new business Affirm with comment Rochelle Jaffe Relocate the arrow head for the 45 degree arrow so that it is not at the intersection of the arc and the dimension line. 08-R-019 Failed with 1 negative + 1 comment for new business Affirm with Comment Rochelle Jaffe Insert a comma after “respectively” in the last line of the commentary. Negative Jason Thompson Commentary references should be added to the list of commentary references, not the Code provisions of Section 1.4. Doing so can have the effect of making the provisions of these standards a mandatory requirement. 08-R-021 Passed; 1 comment for new business Affirm with Comment Rochelle Jaffe In the first sentence of the commentary, insert a comma after “necessary”. In the second-to-last sentence, insert “requirements” after “preheat”. 08-R-023 Failed with 1 negative + 1 comment for new business Affirm with Comment David Pierson I dont like the term edge cell or edge reinforcing bar. If we are referring to the end of a shear wall, this would be the end cell of the wall and the vertical bar in the end cell. It would be clearer if the anchorage had a figure in the code or commentary, and if we simply required a cross wire in the bed joint crossing the end web at the end of the wall (rather than the 3 inch return that is a bit confusing) Negative Mark McGinley Note in Section 9.1.8.3.2 - You have removed the requirement for a 1.3 limit on the actual strength of rebar if laid so that it is resisting flexure parallel to the bed joints. You have justified the relaxation of this requirement for joint reinforcement but not for rebar. If you can prove to me this can also be done for rebar, I will withdraw my negative. b. MAIN 09 RESULTS From Public Comments Daigle Item 09-R-012 Affirm w/comment 4 Negative 5 Affirmative with Comment Richard,Bennett I believe the Figure number should be Figure CC-9.3-1. We probably also need a reference to the Figure in the Commentary. I would suggest a sentence after the second sentence of the first paragraph of part (b) of commentary: The required configuration of the transverse reinforcement is shown in Figure CC-9.3-1. The minimum length of the splice may also need a little more work. For a #4 bar in the middle of an 8 inch CMU wall (fm=1500 psi), the required lap length is 14 inches if you do not have transverse reinforcement. If you have transverse reinforcement, then the 36db requires 18 inches. Granted putting in the tranverse reinforcement in this short of a lap length may not occur very frequently, but it could. Should we state that the lap length need not be required to be greater than that by Equation 9-16? Fernando,Fonseca #2 reinforcing bar is not used. Consider deleting the following part of the sentence: or 12 in. (305 mm) whichever is greater. The 36db requirement will always govern. Susan,Frey Why was the ASD 8.1.7.7.1.2 not similarly revised? It seems that the same editorial changes should be made there as well even if these occur in the next cycle. Arturo,Schultz Corcorans comment seems quite appropriate and should be addressed. Why specify the larger of 36db and 12 inches if the former will always be larger than he latter? Negative Eric,Johnson The ballot identified a valid comment from a subcommittee voter. I am voting negative because no response to the comment was presented. Jason,Thompson Item 09-R-012 Negative Delete the parenthetical PERPENDICULAR, adding the term transverse at the beginning of the requirement clarifies the intent. Delete this term from the commentary figure as well. Delete the 12 inch minimum requirement. This is not applicable to confined lap splices, only unconfined lap splices. The failure mode can change when lap splices are confined hence the 36db limit. The proposed commentary figure is potentially misleading as it shows the edge or corner of a wall. The confining reinforcement needs to be developed on both sides of the splice. It is possible to do this at a corner by turning the transverse bar around the corner, but as shown the figure seems to imply that the transverse bar simply stops an inch or two away from the splice on the right hand side. Charles,Tucker Corcoran’s comment is correct so why include the minimum 12 requirement? To resolve this negative, remove the last phrase or 12 in. (305mm), whichever is greater. There is also an extra period in the proposed last sentence following the subscript b. Rochelle Jaffe: 1. In the first sentence, either delete “within” or delete “or less” – these are redundant. 2. The phrase “reduced by” implies subtraction rather than multiplication. Need to keep the “multiplied by”. 3. In the figure, the as-drawn transverse reinforcement is obviously not fully developed on each side of the lapped bars because the lapped bars are shown at the end of the wall. Either show a hook on the transverse bars or revise the figure so that the lapped bars are in the middle of a wall. David,Pierson Below is how I would word this provision. Where transverse (perpendicular) reinforcement consisting of No. 3 (M#10) or larger bars is located in position along placed within the lap splice, and with at least one transverse bar is within 8 in. (203 mm) or less from of each end of the lap splice, the minimum length of lap splice for bars in tension or compression determined by Equation 9-16 shall be permitted to be reduced by multiplying the a confinement reinforcement factor, ξ. The clear space between the transverse bars and the lapped lap spliced bars shall not exceed 1.5 in. (38 mm) and the transverse bars shall be fully developed in grouted masonry. The reduced lap splice length shall not be less than 36db. or 12 in. (305 mm), whichever is greater. 1I agree with Corcoran – the 12” limit is not needed. 2“…is within 8 in. or less from each end…” is not good code language. “…is within 8 in. of each end…” is better 3I don’t like the phrase “lap spliced bars”. We are only talking about lap splices here, so “spliced bars” is adequate. 4“in position along the lap splice” sounds strange. “located within the lap splice” is better. Comments James,Farny Since you have added [within] to [8 in. or less], you no longer need [or less]: Where transverse (perpendicular) reinforcement consisting of No. 3 (M#10) or larger bars is in position along the lap splice, and at least one transverse bar is within 8 in. (203 mm) from each end of the lap splice,... Also, consider adding the 1.5 in. clear distance dimension between the lap-spliced bars in the figure. Daniel,Zechmeister I suggest to delete: in position along, and keep: placed within. Daigle Item 09-R-024 Affirm w/comment 2 Negative 2 Affirmative with Comment David,McLean Suggest improved wording as follows for Code 5.3.1.4 (e) Hooks at the end of a lateral tie fabricated using a No. 5 bar and smaller shall consist of a 135-degree bend plus a minimum 6 db extension, but not less than 2-1/2 in. (64 mm) at free end of bar. Rochelle,Jaffe Delete the comma after “smaller”, or better yet, rewrite as “For a No. 5 lateral tie bar or smaller, hooks at the ends shall consist of a 135 degree bend plus . . . “ Negative Richard,Bennett The way I read this is that 135 hooks are required. Why are 180 degree hooks not allowed? Jason,Thompson Item 09-R-024 Negative This is confusing. Is the No. 5 bar limit referring to the tie or the longitudinal reinforcement being tied? What does one do if they wanted to use a No. 6 bar (or larger) bar? The 135 degree hook at the termination of the tie isn’t necessary if the tie is overlapped on itself – for example a single tie encompassed the longitudinal bars twice before terminating. What if one wanted to use a circular tie? Comments Daniel,Zechmeister This is already in the Code, section 6.1.5 (c), why repeat it? Grant Item 09-R-025 Affirm w/comment 2 Negative 0 Affirmative with Comment Richard,Bennett I would suggest changing the titles of the previous sections to indicate that the previous sections are for bars. For example, Section 8.1.7.7.1 Lap splices perhaps should be changed to 8.1.7.7.1 Lap splices of bars in tension and compression 8.1.7.7.2 Welded splices changed to 8.1.7.7.2 Welded splices of bars in tension and compression 8.1.7.7.3 Mechanical splices changed to 8.1.7.7.3 Mechanical splices of bars in tension and compression 8.1.7.7.4 End-bearing splices changed to 8.1.7.7.4 End-bearing splices of bars in compression (as a side note, are endbearing splices used in masonry?). This changing of titles may become a moot point if these provisions are moved to Chapter 6. Rochelle,Jaffe In the last sentence of the Commentary, change “is” to “are”. Porter Item 09-R-034.1 Affirm w/comment 2 Negative 3 Affirmative with Comment David,Pierson Since all cross wires are cross wires - they are either diagonal or perpendicular - I would phrase it thusly: ...welded to perpendicular or diagonal cross wires. Scott,Walkowicz Editorially insert mortar bed joint between between wires in the and face shells because it seems the intent is to describe the joint reinforcement placement and it is impossible to place it in the face shells - it must go in the mortar in the bed joint.... Negative W.,McGinley Joint Reinforcement can also be used as principal flexural reinforcement for inplane and out-ofplane bending. The commentary needs to include this in its definition. Jason,Thompson Item 09-R-034.1 Negative Joint reinforcement is not required to have cross wires – consider single wire joint reinforcement used in veneers. By citing face shells and crack control, the commentary implies that joint reinforcement is only used with hollow concrete masonry units whereas is can be used with solid units, clay masonry, or glass block. Rochelle,Jaffe The proposed definition is inaccurate for several reasons: it omits some types of joint reinforcement that are permitted by MSJC, such as tab type; and it excludes single wire joint reinforcement which is required for veneer. The commentary to the proposed definition is also inaccurate because it limits joint reinforcement wires to being placed on face shells (of hollow units), but wires can also be placed in bed joints on solid units. Comments Daniel,Zechmeister Consider adding the following to the last sentence of the Commentary...vertical reinforcement, insulation or grout. Porter Item 09-R-034.2 Affirm w/comment 0 Negative 6 Negative Richard,Bennett I support the concept of moving the development and splice requirements to Chapter 6. This item needs to be coordinated with 09-R-025. That ballot item adds additional information on splicing of wires in tension. There is also an inconsistency between Code and Commentary. The Code requires a minimum of 9 inches development length for epoxy coated wire. The commentary says The 50 percent increase in development length does not apply to the 6 in. (152 mm) minimum. Spec Article 3.4 B.10.b requires a minimum 6-in. (152-mm) lap splices for joint reinforcement. Is there a reason that the minimum 6 inches is not included in the Code? The commentary to Section 6.1.7.1 refers to previous versions of the Code. The chances of us remembering to update this in the 2016 version are rather slim. I would suggest saying: Prior to 2013, the Code required the development of wires to be .... An editorial comment is that in 6.1.8, the b of db should be a subscript. David,McLean I voted negative on this item for 2 reasons: (1) in the proposed Code 6.1.8 Lap splice of wires, bars are included in the requirements. I believe this is an error. (2) In the proposed Code 6.1.8, shouldnt the lap splice for wires also include the minimum of 6 in. (in addition to 48 db) as required by Code 6.1.7? What if the wires are epoxy coated? David,Pierson The title of 6.1.8 is -Lap Splices of Wires -. Yet the provision references reinforcing bars and wires. As such it could be used to pre-empt the reduced splice lengths of 9.3.3.4(b), which could be less than 48db. Shouldnt 6.1.8 just be provisions for lap splices of wires? Jason,Thompson Item 09-R-034.2 Negative The proposed Section 6.1.8 references reinforcing bars. These provisions do not apply to bars. The design, construction, and prescriptive requirements phrase adds little. Just simplify to: The minimum lap splice for wire shall not be less than 48db. I’m not sure I understand the commentary statement that the 50% increase on lap length does not apply to the 6 inch minimum when the proposed code provision states 9 inches for epoxy wire. AAC masonry cannot accommodate bed joint reinforcement, but by moving these requirements to Chapter 6 implies that it can. Suggest adding new commentary language to clarify this or revising accordingly. Charles,Tucker 1) At the end of Section 6.1.8 the b in 48db should be a subscript. 2) There is a discrepancy between the Code and Commentary for Section 6.1.7. The Commentary says, The 50 percent increase in development length does not apply to the 6 in. (152 mm) minimum. yet the Code shows the minimum increased by 50 percent to 9 in. To resolve this negative rectifythis discrepancy. Rochelle,Jaffe 1. Although the title of proposed Section 6.1.8 is “Lap splices of wires”, the text also refers to bars. 2. Proposed Section 6.1.8 discusses lap splices “required by construction”, but the Code does not address requirements for wires “required by construction”. The Code addresses design. Do you mean for restraint of volume change stresses? 3. Because proposed Section 6.1.8 includes bars as well as wires, it is in direct conflict with Sections 8.1.7.7.1.1, 9.3.3.4, and 11.3.3.4. 4. Proposed Section 6.1.8 is in conflict with the Specification, because it requires wires to always be lapped 48db, but the Specification permits 6 inch laps. 5. Suggest rewriting Section 6.1.8 as: 6.1.8 Lap splices of wires — Lap splices for wirerequired by design in accordance with this Code shall be a minimum of 48db. Lap splices for wire required solely to resist volume change stresses shall be permitted to be 6 inches. 6. Delete the proposed commentary to Section 6.1.8. Other than the first sentence, which provides no additional information, the remainder belongs in the Specification or Specification Commentary (Article 3.4 C.1). Comments James,Farny In 6.1.7 commentary, first paragraph, last sentence, it says [The 50 percent increase in development length does not apply to the 6 in. (152 mm) minimum.]. I would like clarification on that because section 6.1.7 of the code says to use no less than 9 in. for epoxy-coated bars (a 50% increase over uncoated bars). Should the statement say that the 50% increase does not apply to the 6 in. or 9 in. length, respectively (uncoated, coated)? Seems like something is missing from statement as written. Daniel,Zechmeister I believe the proposed section 6.1.8 48db is in conflcit with the 6 inch minimum in the Specification. For a 9 gage wire, I believe, you will get 7.1 inches. Curtis Item 09-R-043 Passed-evaluate comments as new business Affirm w/comment Negative 2 2 were withdrawn Affirmative with Comment Richard,Bennett Commentary 8.1.7.3 reads: The 50 percent increase in development length does not apply to the 12 in. (305 mm) minimum. I would change to: The 50 percent increase in development length required for epoxy-coated bars does not apply to the 12 in. (305 mm) minimum. Or better yet, just move all of the commentary from 9.3.3.3 to 8.1.7.3. Arturo,Schultz In Code commentary section 8.1.7.7.1 bond stress failure should be replaced with bond failure. This should be an editorial change Daigle Item 09-R-062 Affirm w/comment 4 Affirmative with Comment Richard,Bennett Negative 6 Please show grout in the interior of the left column in Figure CC-5.3-1. We had an almost endless debate in Flexural, Axial, and Shear whether a hollow column was permitted, and if ties would be required on the interior of the bars if it was hollow. To avoid that debate, just show a solid column. Robert,Chittenden The sketches are missing a hook. It appears that the hoop has a hook at one end of the hoop bar and a straight end at the other end of the hoop bar - show both ends terminating with a hook. David,Pierson While I understand Jacksons negative, this provision is actually found in the code (which binds a designer but not a contractor). The tolerances that he seeks probably ought to be part of the specification (which binds a contractor if incorporated by reference into the construction documents). Also, the word -fathershould be -farther-. Rochelle,Jaffe In Figure CC-5.3-2, do not capitalize Clay. In Figure CC-5.3-1, suggest adding a note that CMU shells and webs need to be notched to accommodate the tie and its embedment in mortar or grout. “and/or” is an imprecise term that should be avoided in a Code. Suggest rewriting as “Lateral ties shall be placed embedded in either a mortar joint and/or in grout.” Jaffe_Rochelle_C_09-R-062.doc Negative John,Chrysler I agree with the Jackson Negative. I have seen this identical condition (very slight gap randomly between bars) become a big and unnecessary field issue. Keith,Itzler I agree with the negative voter. The requirements for direct contact should be vetted before rushing into the Code. Eric,Johnson I agree with the negative voter from Subcommittee. This item warrants further consideration. John,Tawresey This is an unnecessary restriction for masonry. It is common in masonry construction for column ties not in to be in direct contact with column longitudinal reinforcement. I know of no test data supporting the requirement. Moreover, calculations show that ties without direct contact prevent longitudinal bar bucking. This comment appears to be from a concrete person not a masonry person. Jason,Thompson Item 09-R-062 Negative The and/or isn’t the best code language. I also agree with the subcommittee negative that the direct contact reference is likely to be misconstrued in the field. Admittedly, I never interpreted the reference to ties in mortar joints the same way as the public commenter does, which seems to imply that the entire tie could be placed only on the face shell perimeter of the column – which I would agree it incorrect and effectively nullifies the confinement provided by the ties. The way I have interpreted this statement is reflect in the proposed Commentary Figure CC-5.3-1. Here the column may be constructed using units having reduced web heights (bond beam units), in which case the tie is located at some position within the height of course of units. Alternatively, the units can be all full height and the tie located at the top of the course – i.e., the mortar joint. In this case, portions of the tie are embedded in grout and portions are potentially embedded in mortar where the tie crosses a web or face shell. In this latter case, the diameter of the tie is limited based on the mortar joint thickness. Scott,Walkowicz I think this is a very important item to address, for us and for ACI 318. That being said, I didnt expect direct contact to be required but rather a small separation with some minor tolerance. Is there research that shows only direct contact works? Ill guarantee you that most longitudinal bar/tie bar intersections are not in perfect contact in most parts of the country and I agree with the subcommittee negative on the impracticality of requiring perfect contact at every long bar/tie bar interface. Was this coordinated with FAS and Seismic? When I asked respected researchers who are members of our committee the answers varied but seemed to indicate direct contact is desired by those who may be influenced by seismic concern where as some seismic minded persons and others who may focus less on seismic research seemed to think that some separation would be okay because the grout or mortar between the bar and the tie bar would be in compression and that the desired confinement would remain. Ill withdraw my negative if there is research that shows direct contact is the only effective way to confine column longitudinal bars. Or maybe there needs to be a two part requirement based on SDC or something like that, if that approach is supported by research. Thanks and I hope youll keep working on this! Comments James,Farny In 5.3.1.4 (c), typo in first sentence where provide should be provided: ...bar shall have lateral support provided by the corner of a lateral tie... Daniel,Zechmeister I agree with the negative voter. The Specification allows a +/- tolerance for the longitudinal bars based on the effective depth, d. Based on these tolerances every tie in a column would be a different size and have to be field measured after the longitudinal bars are placed. Also the matter is further complicated at the lap splices of longitudinal bars. Whitlock Item 09-R-109 Affirm w/comment 1 Negative 14 Affirmative with Comment Susan,Frey I agree that the terminolgy is a bit confusing. I do see headed anchor studs used in masonry construction. The intent is going in the right direction -- to cover both hooks and headed studs, but a clarifying sketch and industry standard terminology is in order for future consideration. Negative Jennifer,Bean Popehn I agree with Diagles and McLeans negative comments. Richard,Bennett The subcommittee negative by Daigle is persuasive. Robert,Chittenden Need to define what a headed deformed bar is and set forth the head parameters. The head must have sufficient strength AND stiffness to function similar to a bolt head or stud head. John,Chrysler I agree with the Subcommittee negative voters. Fernando,Fonseca How is a headed deformed bar manufactured? Will the manufacturing process change the material properties around the head so that the behavior of a headed deformed bar is different from the other devices mentioned in 8.1.7.1. I am sure how to calculate the tension or compression in the reinforcement that shall be developed on each side of a headed deformed bar. If such a calculation requires an equation to compute the development length of a headed deformed bar, where can we find such an equation? Keith,Itzler I agree with the negative voter. Terminology must be correct before changing the Code. Eric,Johnson I agree with the negative subcommittee voters. W.,McGinley I agree with McLean. They we do not need to introduce new headed bars into the code without research. David,McLean I vote negative on this item primarily because I think the use of headed bars in masonry will introduce numerous behavioral issues not currently covered by the MSJC provisions. Introducing this terminology in this one location is not appropriate. David,Pierson Unless - Headed Deformed Bar- is defined I would not want this in the code. Jason,Thompson Item 09-R-109 Negative Too many unresolved subcommittee negatives to warrant balloting this item. More technical fodder to consider: The MSJC contains provisions for development, hooks, and mechanical coupling – but nothing on headed bars. How does one use the MSJC provisions to detail development length with a headed bar? Is there a minimum size of head? Depending upon the location/orientation, the ability to adequately place and consolidate grout could become an issue. Charles,Tucker The subcommittee negative voters have valid points that should be addressed. The terminology should be consistent with design practice. To resolve this negative address the negatives from the subcommittee. Scott,Walkowicz First, we need to use the proper terms for each and every item that may be used in masonry and will be governed by our code - so lets determine if headed deformed bar is correct (it seems not) or if others like Headed Anchor Stud and Deformed Anchor Stud are correct then, second, lets properly evaluate whether each can be used in compression development and apply exclusions appropriately. Rochelle,Jaffe A “headed deformed bar” is not defined by MSJC or by ASTM. MSJC does not have design provisions for development of a “headed deformed bar”. Do not make the proposed change. Comments Daniel,Zechmeister I agree with the negative voters, what is a headed deformed bar? McLean Item 09-R-139 Affirm w/comment 2 Negative 1 Affirmative with Comment Richard,Bennett The requirement that the actual yield strength not be greater than 1.3 times the specified yield strength does not apply to all bars. It does not apply to reinforcement used for in-plane shear or flexural tension parallel to the bed joints. This should be clarified in the checklist. Jason,Thompson Item 09-R-139 Affirmative with Comment Not related to this proposed change directly…more to the 1.3 limit and a long-standing personal rant but not EVERYTHING is seismically-driven or in need of high levels of ductility. I’m OK with A615 steel for my structurally isolated, non-participating partition walls. And if this comment doesn’t get me banded from the Seismic Subcommittee, I have others. Negative Rochelle,Jaffe I agree with the concept of adding an item to the Mandatory Requirements Checklist, but the item as written fails to include Chapter 11, which has the same limitation on yield strength. Suggest rewriting as: “When deformed reinforcing bars are required by strength design (in accordance with Code Chapter 9 or Chapter 11), specify that the actual yield strength must not exceed the specified yield strength multiplied by 1.3.” Committee discussed item and Jaffe negative. Motion to find Jaffe’s negative persuasive. Vote 7-0-0. Motion passes. Motion to propose new item for Main 11: “When deformed reinforcing bars are required by strength design in accordance with Code Chapter 9 or Chapter 11, specify that the actual yield strength must not exceed the specified yield strength multiplied by 1.3.” Vote 7-0-0. Motion passes. Item will be carried to Andy as Main 11-R-139. Corcoran Passed-evaluate comments as new business Item 09-R-145 Affirm w/comment 2 Negative 0 Affirmative with Comment Susan,Frey The word bar is a bit obsolete. Our master specifications are modifying this terminology at this time to reflect ACI and ASTM terminology. Note the reinforcement seems to be the most common usage in many of those documents. Reinforcing steel is the next most commonly used and reinforcement bar is phasing out. I would also suggest that a future global change be made to all references in the document and would cover bars and wires unless a specific distinction need be made. My suggestion would be reinforcement. Scott,Walkowicz I thought our standard was to use reinforcement but this seems to work properly here.... Corcoran Item 09-R-190 Affirm w/comment 3 Negative 1 Affirmative with Comment John,Chrysler The first item of this ballot (heading) is also ballotted on 09-Q-117. The proposed Commentary addition is written as if it is directed to a designer rather than field personnel. Susan,Frey See comment for 09-R-145. Rochelle,Jaffe Chapter 11, Section 11.1.8.6, also limits the actual yield strength of bar reinforcement. Suggest revising the Commentary to Article 2.4A to reflect this fact. Also suggest including the term “strength design”. Negative Keith,Itzler I agree with the negative voters. Terminology should be correct before changing the Code. Motion to find Negative by Itzler non-germane. Vote 7-0-0. Motion passes. Will carry to Main committee meeting this evening to uphold determination as nongermane. Subsequently, Itzler withdrew his negative. b. 2013 Cycle Summary to date of Main Ballots Lead: Porter 05-R-001 Failed due to negatives 06-R-001A Passed 06-R-001B Had persuasive negatives Completed - Became Item 07-R-023. Lead McGinley: 05-R-002 Failed due to negatives 06-R-002 Negatives found non-persuasive Completed - Item passed. Lead: Curtis SC-R-003 balloted at subcommittee. Withheld from Main Carryover item for next cycle. Lead: Curtis R-004 balloted at subcommittee. Withheld from Main Carryover item for next cycle. Lead: Jackson R-005 balloted at SC and Main but was withdrawn because should have been CR item. Completed - item failed. Lead: McGinley R-006 discussed at subcommittee. Not balloted. Carryover item for next cycle. Lead: Korany 06-R-007 Failed due to negatives. Negatives found persuasive. Completed - item failed. Lead: Whitlock R-008 discussed at subcommittee. Not balloted. Carryover item for next cycle. Lead: Jackson 06-R-009 Failed due to negatives. Negatives were withdrawn. Completed - Item passed. Lead: Porter R-010 discussed at subcommittee. Not balloted. Carryover item for next cycle. Lead: Corcoran/McLean 06-R-011 passed. Completed - Item passed. Lead: Daigle 08-R-012 failed due to negatives Carryover item for next cycle. Lead: Corcoran 07-R-013 passed. Completed - Item passed. Lead: Corcoran 07-R-014 passed. Completed - Item passed. Lead: McGinley 07-R-015 failed due to negative. 08-R-015 passed. Completed - Item passed. Lead: McLean 07-R-016 passed. Completed - Item passed. Lead: Daigle 07-R-018 passed. Completed - Item passed. Lead: Grant 07-R-019 failed due to negative. 08-R-019 failed due to negative. Carryover item for next cycle. Lead: McGinley 07-R-020 failed due to negatives. Negative found persuasive. Completed - item failed. Lead: Jackson 07-R-021 failed due to negative. 08-R-021 passed. Completed - Item passed. Lead: Whitlock 07-R-022 passed. Completed - Item passed. Lead: Porter Carryover from R-001 07-R-023 failed due to negatives. 08-R-023 failed due to negative. Carryover item for next cycle. Lead: Grant 08-R-024 passed. Completed - Item passed. Lead: Curtis 07-R-025 passed. Completed - Item passed. Lead: Jackson 07-R-026 passed. Completed - Item passed. Lead: Grant 07-R-027 failed due to negative. Negative was withdrawn. Completed - Item passed. 6. New Business a. Responses to Ballot 09 Lead: Daigle 09-R-012 failed due to negatives. Action: The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed on Main Committee ballot 09-R-012. Persuasive negatives were received that could not be resolved. The topic will be carried over to the next cycle. Vote on proposed change 7-0-0. Change approved. Lead: Daigle 09-R-024 failed due to negatives. Action: The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed on Main Committee ballot 09-R-024. Persuasive negatives were received that could not be resolved. The topic will be carried over to the next cycle. Vote on proposed change 7-0-0. Change approved. Lead: Grant 09-R-025 Passed –Item completed. Action: Comments to be addressed in next cycle. The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed and approved on Main Committee ballot 09-R-025. Motion to update the response to reflect successful outcome of ballot. Lead: Porter 09-R-034.1 failed due to negatives. Action: To be addressed in next cycle. The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed on two Main Committee ballots 09-R-034.1 and 09-R-34.2. Persuasive negatives were received that could not be resolved. The topics will be carried over to the next cycle. Vote on proposed change 7-0-0. Change approved. Lead: Porter 09-R-034.2 failed due to negatives. Action: To be addressed in next cycle. See 09-R034.1 Vote on proposed change 7-0-0. Change approved. Lead: Curtis 09-R-043 Passed –Item completed. Action: Comments to be addressed in next cycle. The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed and approved on Main Committee ballot 09-R-043. Vote on proposed change 7-0-0. Change approved. Lead: Daigle 09-R-062 failed due to negatives. Action: The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed on Main Committee ballot 09-R-062. Persuasive negatives were received that could not be resolved. The topic will be carried over to the next cycle. Vote on proposed change 7-0-0. Change approved. Lead: Whitlock 09-R-109 failed due to negatives. Action: The Committee appreciates your comment and thanks you for submitting it for consideration. The subcommittee considered the comment and could not reach a consensus. The topic will be considered in the next cycle. Changes consistent with the comment were proposed on Main Committee ballot 09-R-109. Persuasive negatives were received that could not be resolved. The topic will be carried over to the next cycle. Vote on proposed change 7-0-0. Change approved. Lead: McLean 09-R-139 failed due to negative. Action: Revise and reballot for Main 011 The Committee appreciates your comment and thanks you for submitting it for consideration. However, we respectfully disagree as Commentary Section 9.1.8.3.1 states that the requirement that the actual yield strength shall not exceed 1.3 multiplied by the specified yield strength is to minimize the over-strength unintentionally incorporated into design. This criterion is a specific requirement of ASTM A706. While A615 does not have this requirement, many heats of A615 will meet the criterion. So while A706 reinforcement will always meet the requirement, A615 reinforcement may also meet the requirement. It would be the responsibility of the contractor to demonstrate compliance with the requirement if A615 reinforcement is being used. On the basis of the above discussion, the Committee is proposing only to add an item to the Specification Checklist on Main Committee ballot 09 11-R-139. Vote on proposed change 7-0-0. Change approved. Lead: Corcoran 09-R-145 Passed –Item completed. Action: Comments to be addressed in next cycle. The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed and approved on Main Committee ballot 09-R-145. Vote on proposed change 7-0-0. Change approved. Lead: Corcoran 09-R-190 failed due to negatives. Action: At Main Committee, Itzler withdrew his negative and the item passed. The Committee appreciates your comment and thanks you for submitting it for consideration. Changes consistent with the comment were proposed and approved on Main Committee ballot 09-R-190 b. Review all PC responses. Update responses affected by negatives and edits. 1. Subsequent to the subcommittee meeting, it was noted at Main Committeee that the response to PC 44 was incorrect. While 09-R-044 was balloted at subcommittee, there were concerns and it was not presented to Main Committee and will carry over the next cycle. 2. Subsequent to the subcommittee meeting, it was noted at Main Committeee that the response to PC 45 was incorrect. While 09-R-045 was balloted at subcommittee, there were concerns and it was not presented to Main Committee and will carry over the next cycle. c. 7. New items Additional Items to Rollover to 2016 Cycle a. Staggered bond beams. i. See Diane Throop email of 2-13-12 ii. ii. Biggs negative on 05-Q-006 a. Asks for evidence that non-contact lap splices will not cause cracking. However, non-contact lap splices are already allowed by the Code in Chapters 2 and 3, and in the Specification; we are not introducing anything new. Question: Are multiple non-contact splices appropriate or desirable? b. Addresses only one approach to detailing the stepped bond beam using specific values. We are not restricting bond beams to a single layer of reinforcement per course, nor are we dictating the spacing between bars. Those are details that must be designed by the A/E to meet the existing code requirements. We are just providing a generic description of what is involved; we are not providing design requirements that are included elsewhere in the Code/Specification. Question: Can stepped bond beams be detailed and constructed adequately? b. Comments from 05-R-001. Mark McGinley. c. See carryover items from R&C Item 5a. d. Use of joint reinforcement. Responses to comments from negatives on Main item 06-R-001B. Was this resolved by Main 07 and 08?? e. From Paul Curtis: I think this may be a problem because people consider the “length” as the distance of the anchor in its bent state. I have attached our RFQ file for the intersecting wall anchor. The code reads: Minimum size: 1/4” x 1 1/2” x 28” including 2” long 90-degree bend at each end to form U or Z shape. I interpreted the “including” being in addition to the 28” length. A possible fix: Minimum size: 1/4” x 1 1/2” x 24” long center to center of 2” long 90-degree bends at each end to form U or Z shape. I have had people order these in 28” lengths. I actually changed our catalog in 2007 when I noticed the 28” in the code! I now intend to switch this back to 24” for the length. Diane Throop was at the presentation I gave and I did mention this to her and told her I would send you an email. I have copied her in on this email. f. g. h. i. The use of high strength bars A722 (like prestress) in reinforced masonry. Using non-metallic reinforcement. Post-installed anchors. Veneer anchors and ties – design and corrosion protection. Coordinate with VG&E.