SNS COLLEGE OF ENGINEERING, COIMBATORE – 641 107. DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING TUTORIAL IV POWER SYSTEM ANALYSIS Date: 23.09.2015 1. The phase voltage across a certain load are given as Va=(176-j132)Volts, Vb=(-128-j96)Volts and Vc=(-160+j100)Volts. Compute positive, negative and zero sequence component of voltage. [Ans: Va1 = (163.24-j35.10)Volts, Va2=(50.1-j53.9)Volts, Vao = (-112-j128)Volts]. 2. A balanced delta connected load is connected to a three phase system and supplied to it is a current of 15 amps. If the fuse is one of the lines melts, compute the symmetrical components of line currents. [Ans: Ia1= (7.5+j4.33)Amps, Ia2= (7.5+j4.33)Amps, Ia0= 0 Amps.] 3. The symmetrical components of phase voltages in a 3Φ unbalanced system are Va0 = 10∟180° Volts, Va1 = 50∟0° Volts and Va2 = 20∟90° Volts. Find the phase voltages. [Ans:Va = 40+j20; Vb = -52.32-j 53.30; Vc = -17.68+j33.3] 4. Determine the symmetrical components of the unbalanced 3Φ currents Ia= 10∟0° Amps, Ib= 12∟230° Amps and Ic= 10∟130°. [Ans.: Ia1= 10.56∟0°; Ia2= 1.04∟37°; Ia0= 1.47∟-160°] 5. Draw the positive, negative and zero sequence network of the power system as shown in fig. 6. A 50MVA, 11KV, synchronous generator has a sub transient reactance of 20%.The generator supplies two motors over a transmission line with transformers at both ends as shown in fig. The motors have rated inputs of 30 and 15 MVA, both 10KV, with 25% sub transient reactance. The three phase transformers are both rated 60MVA, 10.8/121KV, with leakage reactance of 10% each. Assume zero sequence reactance for the generator and motors of 6% each. Current limiting reactors of 2.5 ohms each are connected in the neutral of the generator and motor number 2. The zero sequence reactance of the transmission line is 300 ohms. The series reactance of the line is 100 ohms. Draw the positive, negative and zero sequence networks.