265113S01 INTERIOR LIGHTING (Ameresco) [Ameresco] See 006290S01 to 006290S04 for ESCO Buildings List / Compliance Requirements. 1. INDOOR LIGHTING *Note: This standard is a design guideline for all new buildings and renovations. On LEED certified new building designs and on renovations designed to meet LEED-EB requirements, design exceptions may be taken to this standard if those are required for LEED designs and as long as the owner is aware (in writing) of the exceptions taken to meet LEED design requirements. For new installations or total fixture replacements, LED lighting should be considered as the first design option if LED equipment can satisfy the lighting requirements for the space. The lighting quality and payback need to be considerations in the design decision. 1.1. All general area lighting shall be LED fixtures or 2'x4' fixtures with T-8 (1" diameter) or T-5 (5/8” diameter) fluorescent lamps and energy efficient electronic ballast. Lamp Kelvin temperature shall be 4100 degrees and Color Rendering Index shall be 85 or higher. T12 and F32T8 lamps shall not be used. University has standardized on F28T8 lamps for these types of fixtures. 1.2. 1.3. 1.4. All new and replacement lighted "EXIT" signs shall be UL-924 approved, LED type, 2 watts or less, with red letters. Computer Labs, Libraries and similar areas to have indirect lighting to minimize glare and subsequently eye fatigue. If economics dictates, deep cell parabolic louvers may be used in lieu of indirect lighting. Can lights shall be LED fixtures or compact fluorescent by exception to item 1.1 above. Heat buildup shall be taken into consideration when using LED lamps in can lights. 2. LIGHTING BY AREA TYPE Light levels to be as follows and consistent with IES recommendations: 2.1. General Areas Corridors Stairs Average Footcandles (Maintained1) 20 20 Offices Mech. Rooms Computer Labs Libraries 502,3,5 20 100 100 Type area NOTES 1 Foot-candle levels calculations must have, associated with them, a spherical coordinate system or polar coordinate system. 2 Provide two (2) levels of illumination when possible. Provide dimmers when required. 3 Motion detectors 4 Motion detectors when safety permits. 5 Foot-candle illumination levels in office areas shall be measured at workstation surface with occupant in place. Task lighting may be used to provide illumination levels at work surface height supplementing overhead lighting system. 265113S01 INTERIOR LIGHTING (Ameresco) Dated: 12/2015 Applies to: All Projects University of Kentucky Page 1 of 3 265113S01 INTERIOR LIGHTING (Ameresco) 2.2. Classrooms Type area Art Rooms Drafting Rooms Home Economics Room, Sewing Home Economics Room, Cooking & Ironing Home Economics Room, Sink Activities, Note Taking Areas Laboratories Lecture Rooms, Audience Area Lecture Rooms, Demonstration Area Music Rooms, Simple Scores Music Rooms, Advanced Scores Recreation Areas Shops Sight Saving Rooms Study Halls Typing Average Footcandles (Maintained1) 50 50 50 50 50 100 50 50 30 50 30 100 50 50 50 2.3. Lighting by Task in Area School Task: Reading Spirit Duplicated Material Drafting, Bench work Lip Reading, Chalkboards, Sewing Average Footcandles (Maintained1) 50 100 75 50 NOTES 1 Foot-candle levels calculations must have, associated with them, a spherical coordinate system or polar coordinate system. 3. INDOOR SPECIALTY LIGHTING Review with owner in design phase of project and provide as designed. 265113S01 INTERIOR LIGHTING (Ameresco) Dated: 12/2015 Applies to: All Projects University of Kentucky Page 2 of 3 265113S01 INTERIOR LIGHTING (Ameresco) 4. GENERAL REQUIREMENTS FOR ALL LIGHTING 4.1. T12 and F32T8 lamps shall not be used. University has standardized on F28T8 lamps for these types of fixtures 4.2. All new construction and major renovation lighting shall meet the ANSI/ASHRAE/IESNA Standard 90.1-2007 requirements for efficiency. Refer to the most recent edition of the IES Handbook for recommended light levels for all interior locations and tasks. If design is specified as a LEED design, lighting design shall contribute to LEED certification as required. 4.3. All ballasts to be low noise type, sound rated "Class A" UL Listed with "Class P Thermal Protector”. 4.4. Unless specified otherwise, lighting to be industrial quality. 4.5. All lighting to be installed in accordance with UK Standards 16000-16999. 4.6. All lighting on emergency generator circuits shall be non re-strike type. 4.7. At minimum, all lighting provided to be "Energy Saving" low mercury type. 4.8. Do not provide radioactive lighting of any kind on University projects. 4.9. Install a 120 volt receptacle at floor level near each exit that has an exit sign. (Is this a requirement associated with an exit or exit signs?) 4.10. No quartz or mercury vapor lighting is to be added on the UK projects. 4.11. No incandescent lighting shall be added on the UK projects unless by written exception. Exception will be considered when energy efficient lamp varieties will not work for the application. 4.12. Lighting controllers shall be Lutron or equal and shall be interfaced with the building automation system (BAS). Lighting controllers should be BACnet MSTP or BACnet IP compliant to seamlessly interface with the BAS. 265113S01 INTERIOR LIGHTING (Ameresco) Dated: 12/2015 Applies to: All Projects University of Kentucky Page 3 of 3