Denver Fire Department Fire Prevention Division PO Box 40385 Denver, CO 80204 p: 720.913.3474 f: 720.913.3596 www.denvergov.org/fire MICHAEL B. HANCOCK Mayor Facility/ General Information Electric Traction Elevator Safety Test Report Building Name: Manufacturer: Capacity: Address: State Reg #: Job/Contract#: City: Install Date: Duty: Zip: Rated Speed: Freight Loading Class: C1 C2 Circle One Acceptance Safeties Governor / Safety Date Tests Performed: Yes Pass Fail Speed at which Governor Tripped: Slack Rope Device (winding drum machines): Governor Rope Pull Through Force: NA Pass Fail Car Safety, No Load, Slow Speed: Pass Stop Switches: A B Fail Yes If "Yes" Inspector Must Sign Test Report Pass CW Safety, No Load, Slow Speed: Pass Fail No Pass Fail NA Pass Emergency Limits: Up: NA Fail Pass Fail Fail Pass Top of Car: Directional & Final Limits: Up: Pass Fail Broken Rope, Tape or Chain Switch Tested: No No in in Test Tag Installed: Stop Switch in Machine Room, Machine Space or Control Space: Down: Pass NA Pass Braking System (125% Rated Load): Pit: Yes Yes Car Slide Of Safety Jaws On Rail: CW Slide Of Safety Jaws On Rail: Type C Safety Buffer Oil Loss: Yes No In Car: Fail fpm Governor Tripping Speed Setting in Need of Adjustment: Governor Adjustments Sealed: Pass Fail NA Pass Fail C C3 Governor Overspeed Switch Tripping Speed: lbf Elevator out of Level after Safety Test: No Governor Tripping Speed: fpm Car Safety, Full Load, Rated Speed: CW Safety, No Load, Rated Speed: Freight Category 5 Tests and Witnessed Was Inspector Present: Mechanical and Visual Check of Governor Operation: Type of Safety: Safety Devices Category 1 Tests Passenger Pass Fail Fail Down: Pass Traction-Loss Detection Means: Ascending Car Overspeed Protection and Unintended Car Movement (no load / up direction): Broken Suspension Member & Residual Strength Detection Means: NA Pass No Fail Escape Hatch Contact: Pass Fail Yes NA Pass Fail Fail NA Pass Fail NA Pass Fail Fail E/E/PES Electrical Protective Devices Operate as intended: NA Pass Fail E/E/PES Written Procedure Provided: NA Yes No The person or firm maintaining the equipment shall provide a written checkout procedure and demonstrate that all E/E/PES electrical protective devices operate as intended. Buffers Type: Spring Solid Oil No Pass Fail Excessive Buffer Oil Leakage: Yes No CWT Buffer No Load, Rated Speed: Pass Fail Car Oil Buffer Return (90 sec): Pass Fail Test Tags Installed: Yes No Door Guides Secure: Yes No Power Doors Down Closing Force (Max 30lbf): Emergency Operation Phase I Recall: Logs Yes Car Buffer Rated Load, Rated Speed: CW Buffer Return (90 sec): Signatures Buffer Data Plate in Place: Closing Time: Proper Fuses Installed: Controller Clean: Pass Fail lbf sec Electronic Edge: Yes Yes Buffer Switch: Safety Edge: No No Jumpers Removed: NA Pass Fail NA Pass NA Pass Yes Relay(s) Visually Inspected: Fail Fail No Yes Door Interlocks/Gate Switch: Pass Fail Wire Connections Tight: Yes No No NA Pass Fail Phase I Fire Service Instruction Signage In Place: Yes No Phase II Operation: NA Emergency Communication: NA Pass Pass Fail Fail Phase II Fire Service Instruction Signage In Place: Alarm Bell: Pass Fail Emergency Lights: Yes Pass No Fail Standby or Emergency Power Operation: Logs Properly Maintained: Yes No Note: 125% of rated load not required NA Pass Fail Logs Updated with this Annual safety test: Yes No Fire service logs maintained: Yes No I certify all statements are true to the best of my knowledge and that all testing was performed according to The Elevator and Escalator Certification Act CRS § 9-5.5, Conveyance Regulations 7 CCR 1101-8 and adopted Codes. Mechanic Name: Company Name: Signature: Date: Inspector Name: Company Name: Signature: Date: StateLicense #: State License #: 6/24/13