G&W Electric Company 3500 W. 127th Street Blue Island, IL 60406 USA Tel: 708.388.5010 Fax: 708.388.0755 www.gwelec.com ISO 9001:2008 Certified ISO 14001:2004 Certified G&W Fused Switch Information Sheet Important information regarding G&W switches equipped with 21.1V dry well fuse canisters G&W switches can be equipped with 21.1kV rated air insulated, non-load break dry well fuse canisters welded into an SF6 insulated tank. Switches can be equipped with a single fuse canister per phase or two fuse canisters per phase connected in parallel. The information below can be used for both of these switch types. ο· ο· ο· Continuous Current Ratings: The continuous current rating for each fuse canister, with solid links (G&W part number A1952 0019 C00) installed in place of fuses, is 160A. The current ratings provided by the fuse manufacturers assume the fuse canisters are installed in oil. SF6 cannot transfer heat as efficiently as oil and, because of this, some fuse designs may have their continuous current rating de-rated. The allowable continuous current with the fuse installed in an SF6 insulated fuse canister is provided for many commercially available fuses in the tables below. Parallel Fuse Canisters: Designs with parallel fuse canisters are used for applications where a higher continuous current is required. It is important to install fuses with the same voltage and current ratings into each canister. Doing so will effectively double the current rating per phase as compared to a switch equipped with one fuse canister per phase. Fuse Criteria: The following pages include a list of fuses that can be used with G&W switches equipped with 21.1kV dry well fuse canisters. Other fuses are useable provided they meet the criteria outlined below: - Maximum fuse length: 17.21” to end of mounting stud - Non-gassing type - Non-indicator style fuses - Nominal fuse diameter is 2.15” or less - Stud on each end of fuse is .623” in diameter and 1” long - Some fuse designs will have reduced current ratings because the fuse canister is installed inside an SF6 insulated tank. The equation below can be used to determine whether the fuse will have a reduced current rating. π·π − π ππ‘ππ πΆπππ‘πππ’ππ’π πΆπ’πππππ‘ ππ π ππ’π π = √ 32 πππ‘π‘π 1.5 π πΉπ’π π π ππ ππ π‘ππππ The continuous current of the fuse installed in an SF6 insulated fuse canister is the lesser of the current rating of the fuse or the result of the above equation. 2 The fuse resistance in the above equation must come from the fuse manufacturer. ο· Explanation of the notes used in the tables below Note 1: Each fuse has a range of resistances considered acceptable by the manufacturer. The range of de-rated continuous current in the tables below is calculated from this resistance range. The fuse’s actual de-rating can be determined by using the equation above and measuring its resistance in ohms. Note 2: G&W switches can be equipped with one fuse canister per phase or two (parallel) fuse canisters per phase. Designs with parallel fuse canisters are used for applications where a higher continuous current is required. Note 3: G&W switches can be equipped with one fuse canister per phase or two (parallel) fuse canisters per phase. Designs with parallel fuse canisters are used for applications where a higher continuous current is required. Each fuse has a range of resistances considered acceptable by the manufacturer. The range of de-rated continuous current in the tables below is calculated from this resistance range. The fuse’s actual de-rating can be determined by using the equation above and measuring its resistance in ohms. Cooper Power Systems Fuses for G&W 21.1kV rated fuse canisters Maximum Voltage Fuse Type ELX 23kV NX Catalog Number Factory labeled current Rating (Amps) Approximate De Rated Continuous Current (Amps) 3565003M11M 3 No De Rating required 3565006M11M 6 No De Rating required 3565008M11M 8 No De Rating required 3565012M11M 10 No De Rating required 3565010M11M 12 No De Rating required 3565018M11M 18 No De Rating required 3565020M11M 20 19-20 1 3565025M11M 25 20-24 1 3565030M11M 30 27-30 1 3565040M11M 40 27-31 1 (2) 3565025M11M installed in parallel 50 (both fuses) 40-48 (both fuses) 3 (2) 3565030M11M installed in parallel 60 (both fuses) 54-60 (both fuses) 3 (2) 3565040M11M installed in parallel 80 (both fuses) 54-62 (both fuses) 3 FA5H6 6 No De Rating required FA5H8 8 No De Rating required FA5H10 10 No De Rating required FA5H12 12 No De Rating required FA5H18 18 14-16 1 FA5H20 20 15-17 1 Notes 3 X-Limiter FA5H25 25 19-22 1 FA5H30 30 22-26 1 FA5H40 40 27-31 1 (2) FA5H25 installed in parallel 50 (both fuses) 38-44 (both fuses) 3 (2) FA5H30 installed in parallel 60 (both fuses) 44-52 (both fuses) 3 (2) FA5H40 installed in parallel 80 (both fuses) 54-62 (both fuses) 3 23F003-I 3 No De Rating required 23F006-I 6 No De Rating required 23F008-I 8 No De Rating required 23F010-I 10 No De Rating required 23F012-I 12 No De Rating required 23F018-I 18 16-18 1 23F020-I 20 16-18 1 23F025-I 25 20-22 1 23F030-I 30 23-26 1 23F040-I 40 28-31 1 23F050-DW 50 28-31 1 (2) 23F025-I installed in parallel 50 (both fuses) 40-44 (both fuses) 3 (2) 23F030-I installed in parallel 60 (both fuses) 46-52 (both fuses) 3 (2) 23F040-I installed in parallel 80 (both fuses) 56-62 (both fuses) 3 (2) 23F050-DW installed in parallel 100 (both fuses) 56-62 (both fuses) 3 Thomas and Betts Fuses for G&W 21.1kV rated fuse canisters Rated Max Factory labeled Fuse Voltage current Rating Type (kV) Catalog Number (Amps) Approximate DeRated Continuous Current (Amps) HTFX250006 6 No De Rating required HTFX250008 8 No De Rating required HTFX250010 10 No De Rating required HTFX250012 12 No De Rating required HTFX250018 18 No De Rating required HTFX250020 20 19-20 1 HTFX250025 25 24-25 1 HTFX250030 30 25-28 1 HTFX250040 40 29-32 1 HTFX250050 50 32-35 1 (2) HTFX250030 installed in parallel 60 (both fuses) 50-56 (both fuses) 3 (2) HTFX250040 installed in parallel 80 (both fuses) 58-64 (both fuses) 3 (2) HTFX250050 installed in parallel 100 (both fuses) 64-70 (both fuses) 3 FX 23 Notes