G&W Electric Company 3500 W. 127th Street Blue Island, IL 60406 USA Tel: 708.388.5010 Fax: 708.388.0755 www.gwelec.com ISO 9001:2008 Certified ISO 14001:2004 Certified G&W Fused Switch Information Sheet Important information regarding G&W switches equipped with 8.3kV dry well fuse canisters G&W switches can be equipped with 8.3kV rated air insulated, non-load break dry well fuse canisters welded into an SF6 insulated tank. Switches can be equipped with a single fuse canister per phase or two fuse canisters per phase connected in parallel. The information below can be used for both of these switch types. ο· ο· ο· Continuous Current Ratings: The continuous current rating for each fuse canister, with solid links (G&W part number A1952 0019 A00) installed in place of fuses, is 160A. The current ratings provided by the fuse manufacturers assume the fuse canisters are installed in oil. SF6 cannot transfer heat as efficiently as oil and, because of this, some fuse designs may have their continuous current rating de-rated. The allowable continuous current with the fuse installed in an SF6 insulated fuse canister is provided for many commercially available fuses in the tables below. Parallel Fuse Canisters: Designs with parallel fuse canisters are used for applications where a higher continuous current is required. It is important to install fuses with the same voltage and current ratings into each canister. Doing so will effectively double the current rating per phase as compared to a switch equipped with one fuse canister per phase. Fuse Criteria: The following pages include a list of fuses that can be used with G&W switches equipped with 8.3kV dry well fuse canisters. Other fuses are useable provided they meet the criteria outlined below: - Maximum fuse length: 10.11” to end of mounting stud - Non-gassing type - Non-indicator style fuses - Nominal fuse diameter is 2.15” or less - Stud on each end of fuse is .623” in diameter and 1” long - Some fuse designs will have reduced current ratings because the fuse canister is installed inside an SF6 insulated tank. The equation below can be used to determine whether the fuse will have a reduced current rating. π·π − π ππ‘ππ πΆπππ‘πππ’ππ’π πΆπ’πππππ‘ ππ π ππ’π π = √ 32 πππ‘π‘π 1.5 π πΉπ’π π π ππ ππ π‘ππππ The continuous current of the fuse installed in an SF6 insulated fuse canister is the lesser of the current rating of the fuse or the result of the above equation. The fuse resistance in the above equation must come from the fuse manufacturer. 2 ο· Explanation of the notes used in the tables below Note 1: Each fuse has a range of resistances considered acceptable by the manufacturer. The range of de-rated continuous current in the tables below is calculated from this resistance range. The fuse’s actual de-rating can be determined by using the equation above and measuring its resistance in ohms. Note 2: G&W switches can be equipped with one fuse canister per phase or two (parallel) fuse canisters per phase. Designs with parallel fuse canisters are used for applications where a higher continuous current is required. Note 3: G&W switches can be equipped with one fuse canister per phase or two (parallel) fuse canisters per phase. Designs with parallel fuse canisters are used for applications where a higher continuous current is required. Each fuse has a range of resistances considered acceptable by the manufacturer. The range of de-rated continuous current in the tables below is calculated from this resistance range. The fuse’s actual de-rating can be determined by using the equation above and measuring its resistance in ohms. Cooper Power Systems Fuses for G&W 8.3kV rated fuse canisters Maximum Voltage Fuse Type NX 4.3kV X-Limiter Catalog Number Factory labeled current Rating (Amps) Approximate De Rated Continuous Current (Amps) FA1H18 18 No De Rating required FA1H25 25 No De Rating required FA1H35 35 No De Rating required FA1H45 45 No De Rating required FA1H50 50 No De Rating required FA1H65 65 No De Rating required FA1H75 75 71-75 1 FA1H100 105 87-100 1 (2) FA1H65 installed in parallel 130 (both fuses) No De Rating required (2) FA1H75 installed in parallel 150 (both fuses) 142-150 (both fuses) 3 (2) FA1H100 installed in parallel 210 (both fuses) 174-200 (both fuses) 3 43F008-I 8 No De Rating required 43F010-I 10 No De Rating required 43F012-I 12 No De Rating required 43F018-I 18 No De Rating required 43F025-I 25 No De Rating required 43F035-I 35 No De Rating required 43F045-I 45 39-43 43F050-I 50 No De Rating required 43F065-I 65 No De Rating required 43F075-I 75 66-73 Notes 1 1 3 NX 5.5kV X-Limiter 8.3kV NX 43F100-I 100 77-85 1 (2) 43F065-I installed in parallel 130 (both fuses) No De Rating required 2 (2) 43F075-I installed in parallel 150 (both fuses) 132-146 (both fuses) 3 (2) 43F100-I installed in parallel 200 (both fuses) 154-170 (both fuses) 3 FA2H6 6 No De Rating required FA2H8 8 No De Rating required FA2H10 10 No De Rating required FA2H12 12 No De Rating required FA2H18 18 No De Rating required FA2H20 20 No De Rating required FA2H25 25 No De Rating required FA2H35 30 No De Rating required FA2H45 40 No De Rating required FA2H50 50 No De Rating required FA2H65 65 No De Rating required FA2H75 75 71-75 1 (2) FA2H45 installed in parallel 80 (both fuses) No De Rating required 2 (2) FA2H50 installed in parallel 100 (both fuses) No De Rating required 2 (2) FA2H65 installed in parallel 130 (both fuses) No De Rating required 2 (2) FA2H75 installed in parallel 150 (both fuses) 142-150 (both fuses) 3 55F008-I 8 No De Rating required 55F010-I 10 No De Rating required 55F012-I 12 No De Rating required 55F018-I 18 No De Rating required 55F020-I 20 No De Rating required 55F025-I 25 No De Rating required 55F030-I 30 No De Rating required 55F040-I 40 No De Rating required 55F050-I 50 No De Rating required 55F065-I 65 60-65 1 55F075-I 75 67-74 1 (2) 55F040-I installed in parallel 80 (both fuses) No De Rating required 2 (2) 55F050-I installed in parallel 100 (both fuses) No De Rating required 2 (2) 55F065-I installed in parallel 130 (both fuses) 120-130 (both fuses) 3 (2) 55F075-I installed in parallel 150 (both fuses) 134-148 (both fuses) 3 FA3H1 1.5 No De Rating required FA3H3 3 No De Rating required FA3H4 4.5 No De Rating required FA3H6 6 No De Rating required FA3H8 8 No De Rating required FA3H10 10 No De Rating required 4 FA3H12 12 No De Rating required FA3H18 18 No De Rating required FA3H20 20 No De Rating required FA3H25 25 No De Rating required FA3H30 30 No De Rating required FA3H40 40 No De Rating required 83F003-I 3 No De Rating required 83F006-I 6 No De Rating required 83F008-I 8 No De Rating required 83F010-I 10 No De Rating required 83F012-I 12 No De Rating required 83F018-I 18 No De Rating required 83F020-I 20 No De Rating required 83F025-I 25 No De Rating required 83F030-I 30 No De Rating required 83F040-I 40 37-40 1 83F050-DW 50 42-47 1 (2) 83F030-I installed in parallel 60 (both fuses) No De Rating required 2 (2) 83F040-I installed in parallel 80 (both fuses) 74-80 (both fuses) 3 (2) 83F050-DW installed in parallel 100 (both fuses) 84-94 (both fuses) 3 3563003M11M 3 No De Rating required 3563006M11M 6 No De Rating required 3563008M11M 8 No De Rating required 3563010M11M 10 No De Rating required 3563012M11M 12 No De Rating required 3563018M11M 18 No De Rating required 3563020M11M 20 No De Rating required 3563025M11M 25 No De Rating required 3563030M11M 30 No De Rating required 3563040M11M 40 37-40 1 3563050M11M 50 44-50 1 (2) 3563030M11M installed in parallel 60 (both fuses) No De Rating required 2 (2) 3563040M11M installed in parallel 80 (both fuses) 74-80 (both fuses) 3 (2) 3563050M11M installed in parallel 100 (both fuses) 88-100 (both fuses) 3 X-Limiter 8.3kV ELX Cutler Hammer Fuses for G&W 8.3kV rated fuse canisters Fuse Type Rated Max Voltage (kV) Catalog Number Factory labeled current Rating (Amps) CX 4.3 4CX-18C 18 Approximate De-Rated Continuous Current (Amps) No De Rating required Notes 5 CX CX 5.5 8.3 4CX-25C 25 No De Rating required 4CX-35C 35 No De Rating required 4CX-45C 45 No De Rating required 4CX-50C 50 No De Rating required 4CX-60C 60 57-60 1 4CX-65C 65 59-65 1 4CX-75C 75 65-72 1 4CX-80C 80 70-80 1 4CX-100C 100 79-88 1 (2) 4CX-60C installed in parallel 120 (both fuses) 114-120 (both fuses) 3 (2) 4CX-65C installed in parallel 130 (both fuses) 118-135 (both fuses) 3 (2) 4CX-75C installed in parallel 150 (both fuses) 130-144 (both fuses) 3 (2) 4CX-80C installed in parallel 160 (both fuses) 140-160 (both fuses) 3 (2) 4CX-100C installed in parallel 200 (both fuses) 158-176 (both fuses) 3 5CX-10C 10 No De Rating required 5CX-12C 12 No De Rating required 5CX-18C 18 No De Rating required 5CX-20C 20 No De Rating required 5CX-21C 21 No De Rating required 5CX-25C 25 No De Rating required 5CX-30C 30 No De Rating required 5CX-35C 35 No De Rating required 5CX-40C 40 No De Rating required 5CX-50C 50 No De Rating required 5CX-60C 60 52-60 1 5CX-65C 65 59-65 1 5CX-75C 75 66-73 1 (2) 5CX-40C installed in parallel 80 (both fuses) No De Rating required 2 (2) 5CX-50C installed in parallel 100 (both fuses) No De Rating required 2 (2) 5CX-60C installed in parallel 120 (both fuses) 104-120 (both fuses) 3 (2) 5CX-65C installed in parallel 130 (both fuses) 118-130 (both fuses) 3 (2) 5CX-75C installed in parallel 150 (both fuses) 132-146 (both fuses) 3 8CX-3.5C 3.5 No De Rating required 8CX-4C 4 No De Rating required 8CX-4.5C 4.5 No De Rating required 8CX-6C 6 No De Rating required 8CX-7C 7 No De Rating required 8CX-8C 8 No De Rating required 8CX-10C 10 No De Rating required 8CX-12C 12 No De Rating required 8CX-15C 15 No De Rating required 6 8CX-18C 18 No De Rating required 8CX-20C 20 No De Rating required 8CX-25C 25 No De Rating required 8CX-30C 30 No De Rating required 8CX-35C 35 33-35 8CX-40C 40 No De Rating required (2) 8CX-25C installed in parallel 50 (both fuses) No De Rating required 2 (2) 8CX-30C installed in parallel 60 (both fuses) No De Rating required 2 (2) 8CX-35C installed in parallel 70 (both fuses) 66-70 (both fuses) 3 (2) 8CX-40C installed in parallel 80 (both fuses) No De Rating required 2 1 Thomas and Betts Fuses for G&W 8.3kV rated fuse canisters Fuse Type FX Rated Max Voltage (kV) 10 Catalog Number Factory labeled current Rating (Amps) Approximate De-Rated Continuous Current (Amps) HTFX230003 3 No De Rating required HTFX230006 6 No De Rating required HTFX230008 8 No De Rating required HTFX230010 10 No De Rating required HTFX230012 12 No De Rating required HTFX230018 18 No De Rating required HTFX230020 20 No De Rating required HTFX230025 25 No De Rating required HTFX230030 30 No De Rating required HTFX230040 40 No De Rating required HTFX230050 50 45-50 1 (2) HTFX230030 installed in parallel 60 (both fuses) No De Rating required 2 (2) HTFX230040 installed in parallel 80 (both fuses) No De Rating required 2 (2) HTFX230050 installed in parallel 100 (both fuses) 90-100 (both fuses) 3 Notes