Time–Domain solutions of Transmission Line Equation The partial–differential equations of a lossless line are v ( z, t ) i ( z, t ) L z t i ( z, t ) v ( z, t ) C z t These gives as 2 v ( z, t ) 2 v( z, t ) LC z 2 2t 2i ( z, t ) 2i ( z, t ) LC z 2 2t Solutions to the above equations are z z v ( z , t ) f (t ) f (t ) v v z z i ( z, t ) YO [ f (t ) f (t )] v v Where v 1 LC and Z0 1 Y0 L C z f (t ) v represents a wave traveling in the +z direction , where z f (t ) v is a wave traveling in the –z direction. Boundary conditions at the Source End A semi-infinite line driven by a generator with internal resistance The line has no voltage nor current anywhere on it (z>0) at t=0. We are interested in determining the voltage and current waves along the line for t 0 z 0. The voltage – current relation is simply VS (t ) I1 (t ) RS V1 (t ) for t 0 z 0. Note that z z V1 ( z, t ) f (t ) f (t ) |Z 0 v v z z I 1 ( z, t ) YO [ f (t ) f (t )] |Z 0 v v No wave travels in the –z direction and f (t ) 0 . We then have I1 (t ) YO f (t ) Rs V1 ( z ) f (t ) This gives us V1 ( z ) f (t ) VS ( t ) 1 Y0 RS Vs I1(t) V1(t) Z0 t0 Equivalent circuit for input condition at z=0 for t 0 The equivalent circuit is shown on the right side Terminated transmission lint with transient input Rs I1(t) I(0,t) + V(0,t) V1(t) Vs Ir(t) V(l,t) L,C - + Vr(t) - Z=0 Z=l We assume that the generator voltage is zero and that the line and load are not energized at time 0<t< l we have v VS (t ) I1 (t ) RS V (0, t ) f (t ) I1 (t ) I (0, t ) Y0 f (t ) This leads to the following result f (t ) VS ( t ) 1 YO RS At the load for 0<t< l v z= l , we have l l V (l , t ) f (t ) f (t ) v v l l I (l , t ) YO [ f (t ) f (t )] v v The essential boundary conditions at the load are then simply V (l , t ) Vr (t ) I (l , t ) I r (t ) By solving the above equation, we first obtain l l f (t ) f (t ) Z 0 I (l , t ) v v We then get l V ( l , t ) Vr ( l , t ) 2 f ( t ) Z 0 I r ( l , t ) v The above equation is extremely important . It says that the transmission line l 2 f (t ) v behaves with respect to any termination like a voltage source in series with an impedance Ir(t)= I(l,t) Z0 I1(t) 2V+(l,t)= 2f+(t-l/v) Z0 + Vr(t)=V(l,t) Zr - Equivalent circuit at a termination Solving the above circuit , we may obtain the terminal voltage Vr (t ) The reflected wave at the load is l l f (t ) Vr (t ) f (t ) v v Note that l f (t ) 0 v if Z0 Z r . The reflected wave l f (t ) v will travel back to the source end and it reach the source end at time t 2l v .In particular it carries information about the load. At the source end , we have the following boundary conditions. VS (t ) I1 (t ) RS V1 (t ) V (0, t ) f (t ) f (t ) I1 (t ) I (0, t ) Y0 [ f (t ) f (t )] The above two equations yield VS (t ) I1 (t ) RS 2 f (t ) Z 0 I1 (t ) It says that as for as the input generator circuit is concerned , the line behaves like a voltage generator 2 f (t ) in series with a resistance Z 0 . The equivalent circuit at the source end now is as followings. Rs I1(t) Z0 + + Vs(t) 2f-(t) V1(t) - - We get I 1 (t ) VS ( t ) 2 f (t ) RS Z 0 RS Z 0 f (t ) Z 0 I (l , t ) f (t ) or f (t ) VS ( t ) R Z0 ( S ) f (t ) 1 RS Y0 RS Z 0 The first term in f (t ) is the incident wave due to source Second term is due to the reflection of f (t ) VS (t ) , the Example: An open transmission line RS VS L,C (Z0) Z=0 Z=l A DC voltage source is connected to an open transmission line and the circuit is under steady state condition . We have z z v ( z , t ) f (t ) f (t ) v v z z i ( z, t ) YO [ f (t ) f (t )] v v Since the transmission line is open circuited at z l , we have i ( z, t ) 0 v( z, t ) VS for 0 z l These conditions yield z z V f (t ) f (t ) S v v 2 This indicates that two waves having amplitude VS 2 travel along the transmission line in the opposite directions. Example: D-C voltage applied to a shorted line RS L,C (Z0) V0 Z=0 Z=l At t=0 , the switch is closed , we obtain the following voltage on the line. V0 Z Z=vt Once the traveling wave reaches the load , we have IR Z0 2V0 As a result , the current I R at the load end is IR 2Vo Z0 The overall current at the load end is IR 4V0/Z0 2V0/Z0 t 3T T where T l v Example: Capacitive – terminated transmission line Z0 U-1(t) L,C (Z0) Z=0 C Z=l The source is a unit step For 0<t< l , we obtain v z 1 z f (t ) u (t ) v 2 v At t l v this wave reaches the load and the conditions are as following Z0 Ir(t) 2f+= U-1(t-l/v) C + Vr(t) - l Vr ( t ) u ( t ) Z 0 I r ( t ) v I r (t ) C dVr (t ) dt Solving the equation , we get z ( t ) / Z 0C l Vr (t ) u (t )(1 e v ) v The incident wave z 1 z f (t ) u (t ) will v 2 v generate a reflected wave at z= l , which is z l l 1 ( t ) / Z 0C f (t l ) Vr (t ) f (t ) u (t )( e v ) v v 2 For values of z< l , f is delayed from its form by the time (l z ) / v . Therefore it becomes 2l z f ( z, t ) u (t ( t ) / Z 0C 2l z 1 )( e v v ) v v 2 Line voltage versus distance and time is as follows. IR IR 1 1 1/2 1/2 z 0 z 0 l l 0<t< l / v l / v <t< 2l / v IR 1 1/2 z 0 l 2l / v <t< 3l / v Example: An open circuited transmission line fed by a current source with an internal conductance G . I(t) + V(z,t) - G lossless Z0 Z=0 Z=l If an input to the line is of the form I (t ) u (t ) sin w0 t w0 2 4T 2T T l /v The line is a quarter – wave length long . u (t ) is a unit step function Then the voltage in the signal line is z z V ( z, t ) (G Y0 ) 1 n [u (t 2nT ) sin( w0 t n w0 ) v v n 0 z z u (t ( 2n 2)T ) sin( w0 t ( n 1) w0 )] v v V(0,t) -1 (G+Y0) t 0 2T 4T 6T 8T 10T V(0,t) 0 t 2T