SINORIX CDT

advertisement
TM
SINORIX CDT
Product Presentation
Page 1
April 2010
Building Technologies
Nitrogen (N2) extinguishing agent
Characteristic of nitrogen (N2)
Room ambient
Agent:
clean
Nitrogen
79 %
Extinguishing principle:
displacement of Oxygen
After extinguishing
Nitrogen
89%
Approx.
Extinguishing concentration: min 30%
< 14.5% O2
Oxygen
Storage stage:
as expended gas
Effect on people:
harmless
21%
Oxygen 10-12%
(due to not having medical
effect on blood supply)
Page 2
April 2010
Building Technologies
Inert Gas Extinguishing
Inert gas systems aim to drop the O2 to between 10% and
14%. Ideally inert gas systems aim for ca. 12.5% O2
Page 3
April 2010
Building Technologies
SINORIX CDT 300 bar regulated
• Nitrogen: Main component of air, inert and odourless
• Extinguishing agent which works by reducing the oxygen level
(< 14%)
• Ecologically clean
ODP = 0 (Ozone Depletion Potential)
GWP = 0 (Global Warming Potential)
• Does not create breakdown products in contact with a
naked flame
•Siemens was the first to have the idea of using nitrogen as an
extinguishing agent
Page 4
April 2010
Building Technologies
SINORIX CDT 300 bar regulated
• 60 second discharge with extinguishing before the end of
the discharge.
• Pipework pressure < 100 bar
• Centralised system with optional directional
valves
• Modular system for protection of small enclosures
• Using 40.3% of nitrogen reduces oxygen level to 12.5%,
which equates to air breathed at an altitude of 3,500 m.
Page 5
April 2010
Building Technologies
Sinorix CDT: The best solution compared with gas blends
Unlimited access to natural gases
Not dependent on specialist suppliers
- Natural gas blends are available from only a limited number of
suppliers
No extra costs for an inert gas without extinguishing benefits
- No patent costs for N2, Ar and CO2
- The price of a gas blend is about 5 times that of a single gas
No CO2 in SINORIX CDT
(Unlike IG-541, which contain CO2)
Page 6
April 2010
Building Technologies
SINORIX CDT 300 bar regulated – Key points
• Excellent extinguishing performance for Class A, B and C fires
- best solutions for rapidly spreading fires
- excellent performance on liquid and gas fires
• Electrically non-conductive
- safe for electronic risk
• Using inert gas
- no residues after a discharge
• Excellent performance on deep-seated fires with a retention time
of 20 minutes
- suitable for archives
Page 7
April 2010
Building Technologies
SINORIX CDT Stability of nitrogen after discharge
O x yg e n C o n c e n tra tio n a fte r D is c h a rg e
O xyg en C oncen tration [V ol% ]
1 4 .0
1 3 .0
O 2 % o n 9 0 % ro o m h e ig h t
O 2 % o n 5 0 % ro o m h e ig h t
1 2 .0
O 2 % o n 1 0 % ro o m h e ig h t
m a x. O 2 le ve l a fte r C E A 4 0 0 8
1 1 .0
1 0 .0
0
60 120 180 240 300 360 420 480 540 600 660 720 780 840 900
T im e [s ]
110 m3 room/60 seconds discharge time
Page 8
April 2010
Building Technologies
SINORIX CDT 300 bar regulated
What does CDT mean?
Constant
Discharge
Technology
New constant (or regulated) flow technology:
Discharge pressure is almost constant, whatever the container
pressure.
Technology developed in house by Siemens SAS and manufactured
by Production Extinction Siemens SAS.
All the accessories too (e.g.: Pressure switch, Manual actuator, ….)
Page 9
April 2010
Building Technologies
SINORIX CDT
VFR 300S
Constant Discharge Valve
Quick connection
PRESCODEM 400/270
BOUT80-CDT
Equipped cylinders
Removable pressure gauge
and pressure switch
80L / 130 Kg 300 bar working pressure
Cône DIN 477
Pressure Gauge 0-400 bar
Transportatino without accesories
Pressure Switch 270 bar
TPED
Removable under pressure
Page 10
April 2010
Building Technologies
SINORIX CDT
VFR 300 S
Specifications
Gas
No perforation disc (OPEF).
Nitrogen or Argon
Soft opening of the valve
Pressure at 15°C
Outlet pressure
300 bar
60 bar to 40 bar
(60s discharge time)
Safety valve 95bars included
Outlet positioning left or right
No difference between master
and slave valve
Page 11
April 2010
Building Technologies
SINORIX CDT
VFR 300 S
1/8NPT port for pneumatic
driving
Interfaces
Standard outlet connection
(3/4’’ BSP) / FR16-type
Using of existing actuators
(COPIST, DEPYM, POUSSAX…)
Accessories
removable under pressure
Page 12
April 2010
Building Technologies
Comparison standard technology to CDT
Comparison mass flow rate standard/CDT
VFR 300 S
Flow rate
Results
Flow rate Std
Flow rate CDT
Time
Page 14
April 2010
Building Technologies
SINORIX CDT 300 bar regulated
Benefits of the SINORIX CDT 300 bar regulated system
Comparison for a protected volume of 450m3 and 3 mbar acceptable overpressure
Type of system
No. of
Total venting area
Service pressure upstream
80 litre containers
(in m2)
Restrictors/sector valves
(in bar)
Nitrogen system (Standard)
200 bar
15
0.89
PN220
10
0.89
PN360
10
0.31
PN100
Nitrogen system (Standard)
300 bar
Nitrogen system (CDT)
300 bar regulated
Page 17
April 2010
Building Technologies
SINORIX CDT 300 bar regulated
Benefits of the SINORIX CDT
regulated nitrogen system
SINORIX CDT regulated nitrogen
at least one third fewer containers
compared with a 200 bar system.
More than 50% less overpressure
venting area compared with an
unregulated system.
 pressure downstream of the valve
VFR300-S less than 100 bar.
Page 18
April 2010
Building Technologies
SINORIX CDT: A modular system
As well as centralised systems, SINORIX CDT also allows you the
option of modular systems
The benefits are:
• No pipework
• No nozzle orifice drilling calculation
• Installation in existing premises without disturbing the user
• Cost
Page 19
April 2010
Building Technologies
SINORIX CDT 300 bar regulated
Examples of applications of the CDT system:
• Computer room
• Anechoic chamber
• Electrical rooms
• Solvent storage
• Cold rooms
• Deep-seated fires
• etc…
Page 20
April 2010
Building Technologies
SINORIX CDT International Approvals
Nitrogen is recognised by the following organisations:
- Authorities and Laboratories:
VdS, LPC, FM, UL, CNPP, HK-FSD, etc
Agreement by the French Ministry of Health to the use of nitrogen
as an extinguishing agent in the presence of people
- Standards:
CEA 4007&4008/NFPA 2001/UL 2127/ISO & CEN 14520
Siemens introduced nitrogen
as an extinguishing agent on the international stage for 4
years
Page 21
April 2010
Building Technologies
SINORIX CDT - Approvals
The IEAG APSAD Gas
Committee issued a
favourable opinion on
Nitrogen 300 bar systems
since December 2004
More than 10000 bottles
installed since 02/2005
VdS approved S-number
+ G-numbers
Page 22
April 2010
Building Technologies
SINORIX CDT 300 bar regulated
All extinguishing systems using an inert agent need an
overpressure vent to avoid damage to the protected enclosure.
Even though the SINORIX CDT system uses a new constant flow
technology, reducing the venting area required by 70%, you must
still provide overpressure venting.
Siemens FR has developed its own overpressure vent
1 hour fire resistant
GRIFEU0,1
GRIPRO0,1
EVENT0,1
Page 23
April 2010
Building Technologies