sprinkler protection in atrium spaces, is deluge an option?

advertisement

SPRINKLER PROTECTION IN ATRIUM SPACES,

IS DELUGE AN OPTION?

Ing. J.C. (Johan) Hoogeweg

DGMR, Netherlands

Fire Sprinkler International 2014

Introduction:

Objective:

To give an insight in the daily practice of a fire engineer regarding

High atrium spaces and sprinklers.

2 Fire Sprinkler International 2014

The problem? (1)

Architect:

• Empty atrium / no fire load

• Larger and higher (>40 m)

Users: no limits in usage:

• Seating area’s

• (Car) exhibition

• Service desks

• Shops

• Libraries

• Stages

3 Fire Sprinkler International 2014

The problem? (2)

Dutch building code:

• Fire compartiments (FC) max 1.000 m2, 60 minutes rating between FC’s:

• Atrium is > 1.000 m2

• Atrium is open with the surrounding floors (no walls/glass)

• Atrium wall is glass (60 minutes rating around 400-600 €/m2)

• In the past a atrium without fire compartments was acceptable if:

• Slow growing fire (max 25 m2 after 30 minutes)

• Smoke and heat venting

• However this is no longer generally accepted by the fire brigade

• Option: Sprinkler to control the fire

4 Fire Sprinkler International 2014

Sprinkler code limits

Code

EN 12845

FM global

NFPA 13

Max hight

12 meters

30 meters

15,3 meters remark

• Discussion if this is acceptable

(will K80 sprinklers control a fire?)

• Wet systems only

• Limited ceiling slope

• Lot of fire damage (fire and smoke) due to late activation

• Test reports are ‘secret’.

• Discussion if this is acceptable

5 Fire Sprinkler International 2014

Deluge Concept (1)

Concept:

• 100% based on existing sprinkler technology

• Apply water over the total area of the protected space

• Density the same as sprinkler code

(depends on hazard)

• System activated by fire detection system

• Sidewall sprinklers or sprinklers under the ceiling

6 Fire Sprinkler International 2014

Will it work (example case)?

Aspect

Hazard

Density

Design Area

Ceiling height

Activation

First sprinkler / system activated

Fire size

Fire controle

Real fire test

EN 12845: OH1

5 mm/min

72 m2

8 meters

Sprinkler head

18:34 [min:sec]*

Large

YES

Deluge concept

EN 12845: OH1

5 mm/min

Total atrium (>72 m2)

31 meters

Fire detection system

< 5 minutes

Smaller than sprinkler

YES

* source: VdS office OH1 fire test

7 Fire Sprinkler International 2014

Activation

• Activation by fire detection system

• reliable detection (false detection  water!)

• Always ‘double knock’ system

• Smoke detection and flame detection (all directions)

• Fire size:

• 0.25 m2

• Foam

8 Fire Sprinkler International 2014

Flame detection

ASD

Safegards

It’s a complex systems, accidental activation of the system is possible!

To prevent unwanted activation:

1) ‘Double knock’ fire detection

2) Delay in activation of the system (manual override)

Sample:

Detection time flame detection

Detection time smoke detection [3:00]

Max. delay time [4:00]

Activation time sprinkler (calculated/fire test) [7:00]

9 time

Fire Sprinkler International 2014

Sprinkler heads

Sprinkler heads:

• (EC) sidewall sprinklers

• (EC) pendent/upright sprinklers

• Listed/approved for risk (VdS/LPC/UL/CE)

• Glass bulb removed, after pressure test

10 Fire Sprinkler International 2014

Design Area (1)

Design area:

• Location 1: total atrium

• Location 2: normal design area sprinkler

(e.g. EN 12845 OH 72 m2)

• Location 3:

• Normal sprinklers + Deluge protection?

11 Fire Sprinkler International 2014

Design Area - Zoned systems

Limit water demand en water

Damage

Fire in zone A:

A+B activated

Fire in zone B:

B+C+D activated

• Advanced flame detection required (if possible)

• Not possible in square or round atriums

• More valves and piping required

12 Fire Sprinkler International 2014

Water management

In case of activation, water damage could be a issue:

• Water in elevator shafts/server rooms/storage  € € € € € € €

• Keep in mind:

• Water drains

• Barriers (2/3 cm is enough)

13 Fire Sprinkler International 2014

Deluge cases

Building

Police Academy, Apeldoorn

Hirsch building, store

Rijksmuseum, Amsterdam

Eneco HQ Rotterdam

Hilton Schiphol

14

Curved ceiling

Outside FM 3-26 / FM 2-0 scope

8 meter atrium

Architect: no sprinklers under glass roof

Protection of restaurant seating area

Existing roof structure

Atrium height: 25 m

Pre FM 3-26 K360

Atrium height: 42m

Case 1: Hilton Amsterdam Airport (1)

15 Fire Sprinkler International 2014

Case 1: Hilton Amsterdam Airport (2)

• Ceiling height: 42 meters

• 676 m2 (26*26 meters)

• ‘no limits’

• parking cars

• exhibitions

• stages

• Seating area’s

• Sprinkler code: NFPA 13

• Ordinary hazard group 2

16 Fire Sprinkler International 2014

Case 1: Hilton Amsterdam Airport (3)

Sprinkler design:

-Sidewall sprinklers only

-Design area sprinkler:

- 4,9 * 7,3 m

No coverage in the centre of the atrium

17 Fire Sprinkler International 2014

Case 1: Hilton Amsterdam Airport (4)

Solution: Sprinkler column

18

Case 1: Hilton Amsterdam Airport (5)

Design area atrium:

-3 columns

-24 sidewall sprinklers

19 Fire Sprinkler International 2014

Case 1: Hilton Amsterdam Airport (6)

Design area -atrium:

-24 sidewall sprinklers

-291 l/min/sprinkler

-Water demand:

-24 sprinklers * 291 l/min * 60 minutes *1.2 (hydraulic imbalance) =

503 m3

20 Fire Sprinkler International 2014

Case 2: Eneco World, Rotterdam

Position of flame detection

• Ceiling level: 25-35 m

• Horeca area

• Event area

• Sprinkler heads:

• Sidewall sprinklers

• In the koffee corner

21 Fire Sprinkler International 2014

Position of sprinkler heads

Conclusion

22

Is deluge THE solution: NO

Will deluge control a fire: same a sprinkler (maybe better)

Water damage: YES

Fire and smoke damage: Small

Is deluge A solution: in some cases?

Fire Sprinkler International 2014

Discussions

Questions, discussions?

23 Fire Sprinkler International 2014 jho@dgmr.nl

Download