ET Electric BV Middelkampseweg 10 5311 PC Gameren T 088 11 65 300 F 088 11 65 310 etelectric@etelectric.nl www.etelectric.nl A2XCWY YELLOW-line Underground cable with XLPE insulation an PVC sheath, screened Voltage Rating UO/U: 0,6/1kV Test Voltage Minimum laying temperature: Operating temperature: Maximum conductor temperature: Short circuit temperature: Bending radius: 4kV / 50Hz -5⁰C -50⁰C to +90⁰C 90⁰C 250⁰C/5 sec 12 x d Standards Standard: Core identification: Flammability test: IEC 60502 HD 308 S2 IEC 60332-1-2 Application Power distribution cable in power stations, industrial installation and switchgears, as well as in local mains. For fixe installation underground, in interior premises, cable ducts, in the open air and in water (as permitted by local building regulations) if protection against shock hazard in the event of mechanical damage or electrical screening is required. The concentric ceander conductor can be used as PE or PEN conductor and needs not be cut when assembling branch joints. Construction Aluminium conductor round stranded (RM) Core insulation (XLPE) Inner covering (EPDM) Concentric screen (bare copper wires applied with changing direction of lay) and counter helix copper tape Sheath (PVC black with three yellow lines UV resistance) Marking YELLOW-line A2XCWY [number of cores] x [core diameter] RM [screen diameter] 0.6/1kV CE IEC 60502 yyyy KABELS ● BOUWLAMPEN ● CONTACTMATERIAAL ● BOUWKASTEN Op alle aanbiedingen, overeenkomsten en werkzaamheden van ET Electric BV zijn de algemene voorwaarden van ET Electric BV van toepassing, welke voorwaarden onder nummer 6/2007 zijn gedeponeerd bij de Rechtbank te ’s-Gravenhage. ET Electric BV Middelkampseweg 10 5311 PC Gameren T 088 11 65 300 F 088 11 65 310 etelectric@etelectric.nl www.etelectric.nl YELLOWLINE measurements type insulation cores bedding outer sheath outer diameter weight (mm²) 3x16/10 3x25/16 3x35/16 3x50/16 3x70/25 3x95/35 3x120/35 3x150/50 3x185/70 3x240/75 (mm) 0,7 0,9 0,9 1,0 1,1 1,1 1,2 1,4 1,6 1,7 (mm) 1,5 1,5 1,5 1,5 1,8 1,8 2,1 2,1 2,1 2,4 (mm) 1,8 1,8 1,9 2,0 2,2 2,3 2,5 2,6 2,8 3,0 (mm) 22,0 25,4 28,8 32,3 37,1 41,2 45,9 49,8 55,6 62,0 (kg/km) 735 1000 1030 1285 1715 2235 2635 3105 3885 4715 max. tension during installation (kN) 1,95 3,05 3,95 5,30 7,55 10,30 12,55 16,00 20,15 25,35 4x10/6 4x16/10 4x25/16 4x35/16 4x50/16 4x70/25 4x95/35 4x120/35 4x150/50 4x185/70 4x240/75 0,7 0,7 0,9 0,9 1,0 1,1 1,1 1,2 1,4 1,6 1,7 1,5 1,5 1,5 1,5 1,8 1,8 2,1 2,1 2,1 2,4 2,4 1,8 1,8 1,9 2,0 2,1 2,3 2,5 2,6 2,7 3,0 3,2 20,3 23,6 27,6 31,3 35,7 40,4 45,8 50,1 54,4 61,5 68,0 745 825 1150 1225 1540 2070 2715 3190 3760 4735 5790 1,70 2,42 3,80 5,00 6,80 9,65 13,15 16,15 20,50 25,70 32,55 KABELS ● BOUWLAMPEN ● CONTACTMATERIAAL ● BOUWKASTEN Op alle aanbiedingen, overeenkomsten en werkzaamheden van ET Electric BV zijn de algemene voorwaarden van ET Electric BV van toepassing, welke voorwaarden onder nummer 6/2007 zijn gedeponeerd bij de Rechtbank te ’s-Gravenhage. ET Electric BV Middelkampseweg 10 5311 PC Gameren T 088 11 65 300 F 088 11 65 310 etelectric@etelectric.nl www.etelectric.nl Technical specifications type (mm²) 3x16/10 3x25/16 3x35/16 3x50/16 3x70/25 3x95/35 3x120/35 3x150/50 3x185/70 3x240/75 maximum resistance 20⁰C (mm) 1,910 1,200 0,868 0,641 0,443 0,320 0,253 0,206 0,164 0,125 4x10/6 3,080 4x16/10 1,910 4x25/16 1,200 4x35/16 0,868 4x50/16 0,641 4x70/25 0,443 4x95/35 0,320 4x120/35 0,253 4x150/50 0,206 4x185/70 0,164 4x240/75 0,125 * according DIN VDE 0276-603 maximum resistance 90⁰C (mm) 2,450 1,539 1,113 0,822 0,569 0,411 0,325 0,265 0,211 0,161 maximum current ground* (A) 76 113 136 159 197 236 269 302 342 397 maximum current air* (A) 63 104 128 152 194 239 278 316 365 430 short-circuit core 1 sec 90-250⁰C (kA) 1,50 2,35 3,29 4,70 6,58 8,93 11,28 14,10 17,39 22,56 short-circuit screen 1 sec 90-250⁰C (kA) 1,43 2,28 2,28 2,28 3,57 5,00 5,00 7,15 10,01 10,72 3,950 2,450 1,539 1,113 0,822 0,569 0,411 0,325 0,265 0,211 0,161 47 76 113 136 159 197 236 269 302 342 397 39 63 104 128 152 194 239 278 316 365 430 0,94 1,50 2,35 3,29 4,70 6,58 8,93 11,28 14,10 17,39 22,56 1,43 1,43 2,28 2,28 2,28 3,57 5,00 5,00 7,15 10,01 10,72 KABELS ● BOUWLAMPEN ● CONTACTMATERIAAL ● BOUWKASTEN Op alle aanbiedingen, overeenkomsten en werkzaamheden van ET Electric BV zijn de algemene voorwaarden van ET Electric BV van toepassing, welke voorwaarden onder nummer 6/2007 zijn gedeponeerd bij de Rechtbank te ’s-Gravenhage.