DET NORSKE VERITAS
TYPE APPROVAL CERTIFICATE
CERTIFICATE NO. E-11358
This is to certify that the
Electric Power Cable
with type designation(s)
RFOU P1/P8, RFOU VFD with/without 3x distributed earth conductors, RFCU
Manufactured by
Draka Norsk Kabel - part of the Prysmian Group
DRAMMEN, Norway
is found to comply with
Det Norske Veritas' Rules for Classification of Ships, High Speed & Light Craft and Det Norske Veritas' Offshore Standards
IEC 60092-350 (2008-02)
IEC 60092-353 (2011-08)
IEC 60332-3-22 (2009-02)
IEC 60754-1/2 (1994-01/1997-04)
IEC61034-1/2 (2005-04/2005-04)
NEK TS 606 (2009-05) (P-types only)
Application
General power & Lighting. Special types with enhanced insulation class for VFD applications.
Flame retardant in bunch Cat. A. Halogen free. Low smoke.
Type
RFOU P1/P8
RFOU VFD with/without 3x distributed earth conductors
RFCU
Høvik, 2012-02-13
for Det Norske Veritas AS
Marit Laumann
Head of Section
Voltage class (kV)
0,6/1
0,6/1 (1,8/3)
0,6/1
Temp. class (°C)
90
90
90
This Certificate is valid until
2016-06-30
DNV local office:
Electrical Systems
Ivar Bull
Surveyor
This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
If any person suffers loss or damage which is proved to have been caused by any negligent act or omission of Det Norske Veritas, then Det Norske Veritas shall pay compensation to such
person for his proved direct loss or damage. However, the compensation shall not exceed an amount equal to ten times the fee charged for the service in question, provided that the maximum
compensation shall never exceed USD 2 million. In this provision "Det Norske Veritas" shall mean the Foundation Det Norske Veritas as well as all its subsidiaries, directors, officers,
employees, agents and any other acting on behalf of Det Norske Veritas.
DET NORSKE VERITAS AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.com
Form No.: TA 1411a Issue: October 2009
Page 1 of 5
Certificate No.: E-11358
File No.:
827.10
Job Id.:
262.1-002558-5
Product description
Type: RFOU P1/P8 0,6/1 kV & RFOU-VFD 0,6/1 kV & RFCU 0,6/1 kV
Construction:
Conductors:
Core insulation:
Inner covering:
Metal covering:
Outer sheath:
Tinned, stranded copper class 2
EPR
Extruded flame retardant halogen free compound
Tinned, Copper wire braid (O) or Galv. Steel wire braid (C)
SHF2 mud resistant according to IEC 60092-350 Annex F & Annex G.
RFOU P1/P8 0,6/1 kV
Number of
cores x
conductor
cross-section
2
mm
1 x 16
1 x 25
1 x 35
1 x 50
1 x 70
1 x 95
1 x 120
1 x 150
1 x 185
1 x 240
1 x 300
1 x 400
1 x 500
2 x 1,5/4
2 x 2,5/4
2 x 4/6
2 x 6/6
2 x 10/10
2 x 16/16
2 x 25/16
3 x 1,5/4
3 x 2,5/6
3 x 4/6
3 x 6/6
3 x 10/10
3 x 16/16
3 x 25/16
3 x 35/16
3 x 50/25
3 x 70/35
Overall
diameter
mm
13,0 ± 0,8
14,5 ± 0,8
16,0 ± 0,8
18,0 ± 0,8
20,5 ± 1,0
22,5 ± 1,0
25,0 ± 1,0
26,5 ± 1,0
29,0 ± 1,0
32,0 ± 1,5
35,5 ± 1,5
40,0 ± 2,0
43,5 ± 2,0
12,5 ± 0,8
13,5 ± 0,8
15,0 ± 0,8
16,0 ± 0,8
18,5 ± 0,8
21,0 ± 1,0
24,5 ± 1,0
13,0 ± 0,8
14,5 ± 0,8
15,5 ± 0,8
17,0 ± 0,8
19,0 ± 0,8
22,0 ± 1,0
26,0 ± 1,0
28,5 ± 1,0
33,5 ± 1,5
38,5 ± 1,5
Number of
cores x
conductor
cross-section
2
mm
3 x 95/50
3 x 120/60
3 x 150/75
3 x 185/95
3 x 240/120
3 x 2,5 + E
3x4+E
3x6+E
3 x 10 + E
3 x 16 + E
3 x 25 + E
3 x 35 + E
3 x 50 + E
3 x 70 + E
3 x 95 + E
3 x 120 + E
3 x 150 + E
3 x 185 + E
3 x 240 + E
4 x 1,5/4
4 x 2,5/6
4 x 4/6
4 x 6/6
4 x 10/10
4 x 16/16
4 x 25/16
4 x 35/16
4 x 50/25
4 x 70/35
4 x 95/50
Overall
diameter
mm
43,0 ± 2,0
47,0 ± 2,0
53,5 ± 2,5
59,0 ± 2,5
67,0 ± 3,0
15,5 ± 0,8
17,0 ± 0,8
18,5 ± 0,8
21,0 ± 1,0
24,0 ± 1,0
28,5 ± 1,0
31,5 ± 1,5
36,5 ± 1,5
41,5 ± 2,0
47,0 ± 2,0
52,0 ± 2,5
57,0 ± 2,5
64,0 ± 3,0
71,5 ± 3,5
15,0 ± 0,8
16,0 ± 0,8
17,0 ± 0,8
18,5 ± 0,8
21,0 ± 1,0
24,5 ± 1,0
28,5 ± 1,0
31,5 ± 1,5
37,0 ± 1,5
42,5 ± 2,0
47,5 ± 2,0
Number of
cores x
conductor
cross-section
2
mm
4 x 95/50
4 x 120/60
4 x 150/75
4 x 185/95
4 x 240/120
4 x 2,5 + E
4x4+E
4x6+E
4 x 10 + E
4 x 16 + E
4 x 25 + E
4 x 35 + E
4 x 50 + E
4 x 70 + E
5 x 1,5/6
5 x 2,5/6
7 x 1,5/6
7 x 2,5/6
12 x 1,5/10
12 x 2,5/10
19 x 1,5/10
19 x 2,5/10
27 x 1,5/10
27 x 2,5/16
37 x 1,5/16
37 x 2,5/16
Overall
diameter
mm
47,5 ± 2,0
52,5 ± 2,5
59,0 ± 2,5
65,5 ± 3,0
74,0 ± 3,5
17,0 ± 0,8
18,5 ± 0,8
20,0 ± 1,0
23,0 ± 1,0
26,0 ± 1,0
31,0 ± 1,5
35,0 ± 1,5
40,5 ± 2,0
45,5 ± 2,0
15,5 ± 0,8
17,0 ± 0,8
17,0 ± 0,8
18,0 ± 0,8
21,5 ± 1,0
23,5 ± 1,0
25,0 ± 1,0
27,0 ± 1,0
29,5 ± 1,0
32,0 ± 1,5
32,5 ± 1,5
36,0 ± 1,5
DET NORSKE VERITAS AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.com
Form No.: TA 1411a Issue: October 2009
Page 2 of 5
Certificate No.: E-11358
File No.:
827.10
Job Id.:
262.1-002558-5
RFOU-VFD 0,6/1 kV (1,8/3kV) with 3x symmetrical distributed earth conductors
Construction:
Conductors:
Earth conductors:
Core insulation:
Inner covering:
Electrostatic screen:
Metal covering:
Outer sheath:
Tinned, stranded copper class 2 or class 5
3x distributed earth conductors class 5
EPR
Extruded flame retardant halogen free compound
Cu/PETP-tape
Tinned, Copper wire braid (O)
SHF2 mud resistant according to IEC 60092-350 Annex F & Annex G.
Number of cores
x conductor
cross-section
2
mm
Overall
diameter
3 x 10 + 3 x 4
3 x 25 + 3 x 6
3 x 50 + 3 x 10
3 x 95 + 3 x 16
3 x 120 + 3 x 25
3 x 150 + 3 x 35
29,0 ± 1,0
33,5 ± 1,5
41,5 ± 2,0
51,0 ± 2,5
57,0 ± 2,5
60,5 ± 3,0
mm
RFOU-VFD 0,6/1 kV (1,8/3kV) with copper braid as earth conductor
Construction:
Conductors:
Core insulation:
Inner covering:
Electrostatic screen:
Metal covering:
Outer sheath:
Tinned, stranded copper class 2 or class 5
EPR
Extruded flame retardant halogen free compound
Cu/PETP-tape
Tinned, Copper wire braid (O)
SHF2 mud resistant according to IEC 60092-350 Annex F & Annex G.
Number of cores
x conductor
cross-section
mm2
Overall
diameter
3 x 4 / 10
3 x 6 /10
3 x 10 / 10
3 x 16 / 16
3 x 25 / 16
3 x 70 / 35
3 x 95 / 50
21,5 ± 1
23,5 ± 1
25 ± 1
29 ± 1
33 ± 1,5
43 ± 2
49 ± 2
mm
RFCU 0,6/1 kV
Number of
cores x
conductor
cross-section
mm2
1 x 16
1 x 25
1 x 35
1 x 50
Overall
diameter
mm
13,0 ± 1,0
15,0 ± 1,0
16,5 ± 1,0
18,5 ± 1,0
Number of
cores x
conductor
cross-section
mm2
1 x 70
1 x 95
1 x 120
1 x 150
Overall
diameter
mm
21,5 ± 1,5
23,5 ± 1,5
25,0 ± 1,5
27,5 ± 1,5
Number of
cores x
conductor
cross-section
mm2
1 x 185
1 x 240
1 x 300
Overall
diameter
mm
29,5 ± 1,5
33,5 ± 2,0
36,5 ± 2,0
DET NORSKE VERITAS AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.com
Form No.: TA 1411a Issue: October 2009
Page 3 of 5
Certificate No.: E-11358
File No.:
827.10
Job Id.:
262.1-002558-5
Number of
cores x
conductor
cross-section
mm2
2 x 1,5
2 x 2,5
2x4
2x6
2 x 10
2 x 16
3 x 1,5
3 x 2,5
3x4
3x6
3 x 10
3 x 16
3 x 25
3 x 35
3 x 50
3 x 70
3 x 95
Overall
diameter
Number of
cores x
conductor
cross-section
mm2
mm
13,0 ± 1,0
14,0 ± 1,0
15,5 ± 1,0
17,0 ± 1,0
18,5 ± 1,0
21,5 ± 1,5
14,0 ± 1,0
15,0 ± 1,0
16,0 ± 1,0
17,5 ± 1,0
19,5 ± 1,0
23,0 ± 1,5
26,5 ± 1,5
29,5 ± 2,0
34,0 ± 2,0
40,0 ± 2,5
44,0 ± 2,5
Overall
diameter
mm
Number of
cores x
conductor
cross-section
mm2
Overall
diameter
mm
3 x 120
48,5 ± 2,5
5 x 2,5
17,5 ± 1,0
3 x 150 + E
3 x 185 + E
3 x 240 + E
59,5 ± 3,0
65,0 ± 3,0
73,0 +/+3,0
7 x 1,5
7 x 2,5
17,5 ± 1,0
18,5 ± 1,0
4 x 1,5
4 x 2,5
4x4
4x6
4 x 10
4 x 16
4 x 25
4 x 35
4 x 50
4 x 70
4 x 95
15,0 ± 1,0
16,5 ± 1,0
17,5 ± 1,0
19,5 ± 1,0
21,5 ± 1,5
25,0 ± 1,5
29,0 ± 1,5
32,5 ± 2,0
38,0 ± 2,0
44,0 ± 2,5
48,5 ± 2,5
12 x 1,5
12 x 2,5
22,0 ± 1,5
24,0 ± 1,5
19 x 1,5
19 x 2,5
25,5 ± 1,5
27,5 ± 1,5
27 x 1,5
27 x 2,5
30,0 ± 2,0
32,5 ± 2,0
37 x 1,5
37 x 2,5
34,0 ± 2,0
37,5 ± 2,0
Application/Limitation
The requirements of SOLAS Amendments Chapter II-1, Part D, Reg. 45, 5.2 (provision to be taken to limit Fire
Propagation along Bunches of Cables or Wires) are fulfilled without any additional measures.
RFOU-VFD is designed for variable frequency drives.
Type Approval documentation
Tests carried out
Standard
IEC 60092-350
Issued
2008-02
IEC 60092-351
2004-04
IEC 60092-353
2001-04
IEC 60092-359
IEC 60332-1-2
1999-08
2004-07
IEC 60332-3-22
2009-02
IEC 60754-1
1994-01
IEC 60754-2
1999-07
IEC 61034-1/2
2005-04
General description
General construction and test methods of power, control and
instrumentation cables for shipboard and offshore applications
Insulating materials for shipboard and offshore units, power, control,
instrumentation, telecommunication and data cables
Single and multicore non-radial field power cables with extruded solid
insulation for rated Voltages of 1 kV and 3 kV
Sheathing materials for shipboard power and telecommunication cables
Tests on electric and optical fibre cables under fire conditions - Part 1-2:
Test for vertical flame propagation for a single insulated wire or cable
Tests on electric and optical fibre cables under fire conditions – Part 3-22:
Test for vertical flame spread of vertically-mounted bunched wires or
cables – Category A
Test on gases evolved during combustion of materials from cables –
Determination of the amount of halogen acid gas
Test on gases evolved during combustion of materials from cables –
Determination of the degree of acidity of gases evolved during the
combustion of materials taken from electric cables by measuring pH and
conductivity
Measurement of smoke density of cables
burning under defined conditions –
Test apparatus, procedure and requirements
Limitation
Bunch test
Category A
Low Halogen:
<0,5%
Halogen
Halogen free:
pH > 4,3
Conductivity
< 10µS
Low smoke
DET NORSKE VERITAS AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.com
Form No.: TA 1411a Issue: October 2009
Page 4 of 5
Certificate No.: E-11358
File No.:
827.10
Job Id.:
262.1-002558-5
Standard
NEK TS 606
Ed. 4
Issued
2009-05
On special request:
IEC 60092-350
2008-02
General description
Cables for offshore installations. Halogen-free and/or mud resistant.
Technical specification.
Limitation
Annex E: Procedure
8.9.1: Temperature requirements
Cold bend: 40°C
Cold impact: 35°C
Marking of product
DRAKA NORSK KABEL or DRAKA 01 or Prysmian 01 - RFOU P1/P8 or RFCU - size - 0,6/1 kV – IEC 60332-3-22 or
DRAKA NORSK KABEL or DRAKA 01 or Prysmian 01 - RFOU VFD – size - 0,6/1 (1,8/3)kV kV – IEC 60332-3-22.
Certificate retention survey
The scope of the retention/renewal survey is to verify that the conditions stipulated for the Type approval is
complied with and that no alterations are made to the product design or choice of materials.
The main elements of the survey are:
•
•
•
•
•
•
Inspection on factory samples, selected at random from the production line (where practicable)
Results from Production Sample Tests (PST) and Routine Tests (RT) checked
(if RT- and PST-test reports are not available, tests according to PST and RT to be carried out)
Review of type approval documentation
Review of possible change in design, materials and performance
Ensure traceability between manufacturer's product type marking and Type Approval Certificate.
Survey shall be performed at least every second year.
END OF CERTIFICATE