Frankfurt (Germany), 6-9 June 2011 RT3b – André Smit, Siemens USA U.S. Distribution Feeder Automation Pilot Project We have developed a peer-to-peer feeder automation system using WiMAX and IEC61850 During the project we needed to develop new protection settings for the feeder We found that conventional settings of coordinated overcurrent relays was not possible The relay setting groups could not be adapted to all the different operating scenarios we faced We needed to find a solution that was less complicated with better performance Frankfurt (Germany), 6-9 June 2011 Traditional Feeder Operation Overcurrent protection operate and trip Utility receives a fault notification from a customer experiencing an outage Trouble desk dispatches a line crew to locate and isolate the fault Crew restores service to unaffected sections of line Crew effects repairs and restores feeder to normal operation Outage time could be measured in hours André Smit – U.S. – RT3b Frankfurt (Germany), 6-9 June 2011 Automation of the Distribution Feeder FLISR Fault Location, Isolation, and Service Restoration Circuit Breaker Recloser Switch Frankfurt (Germany), 6-9 June 2011 Feeder Automation Pilot Project Frankfurt (Germany), 6-9 June 2011 Automating the Distribution Feeder Operational Features to Consider Change open point based on loading Isolate line sections for maintenance Transfer to healthy source Circuit Breaker Recloser Frankfurt (Germany), 6-9 June 2011 Different curve shapes to deal with Relay protecting power transformer does not have same shape curve as fuse designed to protect small distribution feeder load Frankfurt (Germany), 6-9 June 2011 Affect when lowering the Isc The effect of moving 50 setting to indicate what happens when Isc is low. Little room to coordinate with 51 element. Cannot coordinate with 50 element as a higher Isc will cross both lines and both relays will trip. Frankfurt (Germany), 6-9 June 2011 Affect without low Isc being a factor If low Isc not a factor, more space to coordinate with 51 element and still stay above fuse. Frankfurt (Germany), 6-9 June 2011 3 Reclosers with Tolerance Affect Typical TCC curve showing high and low tolerances. (Used ±5% on pickup & time.) Not considering CT tolerance. Illustrates need for space between curves. Frankfurt (Germany), 6-9 June 2011 1 Recloser Only one recloser easy to fit between max fuse and feeder main breaker. Better coordination (more space) between all four devices. Frankfurt (Germany), 6-9 June 2011 One set of TCC curves of 16 sets Using four total setting groups ComponentName P1 50/51 Manufacturer SIEMENS 7SJ62/63/64, TOC ANSI 7SJ64X CT Ratio 600 / 5 A Settings Phase 51 (0.5-20.0 x CTR) 3 (360A) ANSI Extremely Inv. 2.58 50-1 (0.5-175 x CTR) 7.92 (950.4A) 50-1 Delay (0-60 Sec) 0.1 Match curves to data by color ComponentName P2 50/51 Manufacturer SIEMENS 7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 A Settings Phase 51 (0.05-2.5 x CTR) 0.39 (312A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 1.15 (920A) 50-1 Delay (0-60 Sec) 0.15 150 A 360 A 312 A 256 A 200 A 51 pickup markers Largest downstream fuse Feeder main breaker and three reclosers KEL 69KV T1B-OC ComponentName P3 50/51 Manufacturer SIEMENS 7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 A Settings Phase 51 (0.05-2.5 x CTR) 0.32 (256A) ANSI Extremely Inv. 0.45 50-1 (0.05-50.0 x CTR) 0.78 (624A) 50-1 Delay (0-60 Sec) 0.15 Upstream Transformer or Bus Main Breaker ComponentName P4 50/51 Manufacturer SIEMENS 7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 A Settings Phase 51 (0.05-2.5 x CTR) 0.25 (200A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 0.5 (400A) 50-1 Delay (0-60 Sec) 0.15 50 active only during reclose MAX FU 1-2 890 A 1308 A 1357 A 1386 A 2189 A 2189 A TCC Name: BKR KEL 69KV THRU TO OPEN P5 Current Scale x 1 Reference Voltage: 25000 March 31, 2011 9:54 PM Siemens Energy Automation, Wendell, NC Existing devices shown for reference. Instantaneous enabled only during reclose cycle. P1 50-1 delay is 0.10 sec due to longer opening time for breaker vs. recloser. Frankfurt (Germany), 6-9 June 2011 One set of TCC curves of 16 sets Using four total setting groups ComponentName P1 50/51 Manufacturer SIEMENS 7SJ62/63/64, TOC ANSI 7SJ64X CT Ratio 600 / 5 A Settings Phase 51 (0.5-20.0 x CTR) 3 (360A) ANSI Extremely Inv. 2.58 50-1 (0.5-175 x CTR) 7.92 (950.4A) 50-1 Delay (0-60 Sec) 0.1 Match curves to data by color ComponentName P2 50/51 Manufacturer SIEMENS 7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 A Settings Phase 51 (0.05-2.5 x CTR) 0.39 (312A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 1.15 (920A) 50-1 Delay (0-60 Sec) 0.15 150 A 360 A 312 A 256 A 200 A 51 pickup markers Largest downstream fuse Feeder main breaker and three reclosers KEL 69KV T1B-OC ComponentName P3 50/51 Manufacturer SIEMENS 7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 A Settings Phase 51 (0.05-2.5 x CTR) 0.32 (256A) ANSI Extremely Inv. 0.45 50-1 (0.05-50.0 x CTR) 0.78 (624A) 50-1 Delay (0-60 Sec) 0.15 Upstream Transformer or Bus Main Breaker ComponentName P4 50/51 Manufacturer SIEMENS 7SR224, TOC ANSI 7SR224 CT Ratio 800 / 1 A Settings Phase 51 (0.05-2.5 x CTR) 0.25 (200A) ANSI Extremely Inv. 0.48 50-1 (0.05-50.0 x CTR) 0.5 (400A) 50-1 Delay (0-60 Sec) 0.15 50 active only during reclose MAX FU 1-2 890 A 1308 A 1357 A 1386 A 2189 A 2189 A TCC Name: BKR KEL 69KV THRU TO OPEN P5 Current Scale x 1 Reference Voltage: 25000 March 31, 2011 9:54 PM Siemens Energy Automation, Wendell, NC Existing devices shown for reference. Instantaneous enabled only during reclose cycle. P1 50-1 delay is 0.10 sec due to longer opening time for breaker vs. recloser. Frankfurt (Germany), 6-9 June 2011 Difficulties in Coordinating Feeder Reclosers are in series on feeder and not located on branches Segments have different types of loads Curves for transformers are not as steep Demand changes by time of day and season and differently for each segment Melt/time characteristics for distribution fuses do not fit closely with substation transformer protection upstream Original system designed without new switching points Frankfurt (Germany), 6-9 June 2011 Difficulties in Coordinating Feeder High source impedance + long line = very low fault currents Substations located at the ends of the line, so source impedance is usually high; a long feeder—the best candidate for automation—adds to the impedance Severe limits caused by existing minimum current settings and low short circuit current (Isc) Low available Isc limits use of 50, or 50 with definite time Must include considerable allowance for high-impedance branch line faults causing Isc to be even lower Inrush current could be five times nominal current, therefore precluding the use of 50 element when Isc is low Frankfurt (Germany), 6-9 June 2011 How do we deal with these difficulties to protect an Automated Feeder? Setting Sheets Frankfurt (Germany), 6-9 June 2011 Our Solution Detect and isolate faults with a differential (87L) function Activate a 50/51 overcurrent curve on one device end and reclose on fault Diff Zone Diff Zone Primary Switch 1 Primary Switch 2 Primary Switch 3 87 87 87 87 87 87 Relay 1 Relay 2 Relay 3 Frankfurt (Germany), 6-9 June 2011 Performance Direct Fiber WiMAX 30 msec 80 msec Frankfurt (Germany), 6-9 June 2011 Automating the Distribution Feeder Locate using 87L Isolate using 87L & Restore Reclose using 50/51 Restore Frankfurt (Germany), 6-9 June 2011 New Protection for Automated Feeders Fast Selective Uncomplicated Minimal Disruption for customers Reclosers Feeder Breaker Transformer Frankfurt (Germany), 6-9 June 2011 Questions