直流電源供應器 power Supply

advertisement
Common Equipment 2 :
DC power Supply
---MODEL LPS-305
Motech
Specifications
Model
MAX. OUTPUT POWER
OUTPUT VOLTAGE
Output Voltage
Setting Resolution
Max. output voltage
Dual tracking
Tracking deviation
OUTPUT CURRENT
Output Current
Setting Resolution
Max. output current
Dual tracking
Tracking deviation
LPS 305
165 WATTS
0 to +30V
10mV
+32V/-32V
0 to ±30V
±20mV
fixed 3.3/5V
0 to +2.5A
1mA
+3A/-3A
0 to ±2.5A
±5mA
3A
CL≒3.3A
CONSTANT VOLTAGE CHARACTERISTICS (at rated
output)
Line regulation(for change of AC
1mV
5mV
±10%)
Load regulation(for load change 0
2mV
10mV
100%)
Ripple/Noise rms (10Hz to 20MHz) 1.5mVrms 2mVrms
Ripple/Noise peak (10Hz to 20MHz) 10mVp-p
20mVp-p
200μs Typical
100 ppm/℃
Transient Response
Temperature Coefficient
CONSTANT CURRENT CHARACTERISTICS (at rated
output : ±2.5A )
Line regulation (for change of AC
15mA Typical
±10% )
Load regulation (for change from
short to
10mA Typical
full load )
Ripple/Noise rms (10Hz to
1mArms Typical
20MHz)
Ripple peak (p-p)(10Hz to 20MHz)Typical 5mAp-p
Temperature Coefficient
Display
Voltage Accuracy
200 ppm/℃
2×16 LCD with backlit;
Front Panel Status
Announciators with
beeper
±(0.2% of rdg+2 digits) ±2%
Current Accuracy
±(0.5% of rdg+5 digits)
Common Mode Voltage
± 240 Vdc
Temperature ranges Operating:
0℃ to 40℃, less than 80% RH;
Storage: -40℃ to 70℃, less than 80% RH
Front panel controls
+Vset
+Iset
+ output control
key.
-Vset
-Iset
- output control
key.
toggles the
tracking
mode on / off.
GDN Terminal
5V/3.3V Terminal
5V or 3.3V
output
selecting key.
+output terminal
-output terminal
OPERATION---Ex:+V setting
3.Set +V; key in number
1.Power on
4.Enter 5. output
on/off
Connect to load
LCD display message
Indicator of the independent
mode or tracking mode.
Indicator of CV mode or CC mode
Flashing cursor implies the unit
of + output (positive).
is working normally.
It will flash when the output is
enabled.
Indicator of CV mode or CC
mode of - output (negative).
It will flash when the output
is enabled.
Indicator of the selected output
5V or 3.3V.
It will flash when the output is
on.
Note: INDEP mode:+source & -source out put is
independent; Tracking Mode :+source & -source out
put will follow the +source setting.
Serial output
If the load is connected between the positive and negative
output terminals, the unit becomes a power
source which can supply twice as much voltage as the rated
output voltage.