Dry Chemicals

advertisement
CXS490 Dry
Chemical Systems
NFPA 17
 minimum requirements
 standard includes only essential to make standard
workable by skilled hands
 not applicable to installations prior to effective date
of standard
2
Dry Chemicals
 most systems pre-engineered or designed by
manufacturer
 most design details are proprietary
 used for applications such as vehicle systems
 dry chemical = powder mixture (very small
particles)
 powder suspended in gas, which permits the
distribution to the hazard
3
Dry Chemicals Sodium Bicarbonate
 NaHCO3 in use since 1920’s
 modified in 1960’s
• metal stearate additive enhances flow and prevents
caking
• silicone enhances compatibility with water based foam
 effective and cheap
 used on class B and C fires
 forms a soap-like surface on grease or cooking oil
fire - saponification, surface coating broken down
by heat
4
Dry Chemicals Potassium Based
introduced in 1960’s
potassium carbonate, KHCO3, Purple K
potassium Chloride, KCl, Super K
urea based potassium carbonate, KC2N2H3O3,
Monnex
 used on class B and C fires, best on class B




5
Dry Chemicals Multipurpose
 NH4H2PO4, monoammonium phosphate
 introduced in the 1950’s
 used on class B and C fires, and on class A
6
Dry Chemicals Multipurpose
 forms a molten residue to prevent oxygen from
contributing to combustion
 not effective on deep fat fryers and delicate
electrical equipment where temp is more than 250
F and humidity is more than 50%
 deposits are difficult to remove not to be used with
delicate electrical equipment
7
Dry Chemicals –
Properties Stability
 at low and ordinary temperatures
 additives may melt and cause sticking at higher
temperatures
 upper storage temp recommended 49 C or 120 F
 temp of 66 C or 150 F for short periods - 4 hours
8
Dry Chemicals –
Properties Stability
 at fire temps decompose and dissociate
 danger when mixing multipurpose (acidic) with
other dry chemicals (alkaline) releases free carbon
dioxide gas and causes caking
 extinguisher shells have been known to explode
 dry chemicals may react violently with other
chemicals
9
Dry Chemicals –
Properties
 commercial additives to improve storage, flow and
water repellency
 additives include metallic stearate, tricalcium
phosphate and silicones
 particle size 10 to 75 microns - 20 to 25 best,
beyond performance drops
 momentum gained from large particles will
transport smaller particles
10
Extinguishing
Properties
 Comparison on Class B fires – best to worst
 monnex
 potassim bicarbonate & chloride
 multipurpose
 sodium bicarbonate
11
Cautions




most effective on class B materials
can be used with class C - non conductive
transitory on class A
supplement with water
12
Advantages
 rapid knockdown of flame 2x as effective by weight
as CO2
 surface coating does not run down
13
Disadvantages
 surface coating
 cleanup
• can be cleaned up with hose but mixture may
have environmental impact
• could vacuum
 caking into solid block when exposed to humidity
14
Personnel Hazards
 nontoxic and noncarcinogenic
 acute effects include irritation of mucous
membranes and possibility of chemical burns to
skin, eyes and mucous membranes lining the
respiratory system
 temporary discomfort and irritating
15
Procedure for
Personnel Protection





Pre-discharge alarms
Signs
personnel training
egress analysis
provision of SCBA
16
Testing
 Regular testing ensures system functions as
designed/intended
17
Extinguishing
Mechanisms
 chain breaking - dry chemical thermally
decomposes and combines with the free radicals
and is major contributor
 smothering from carbon dioxide and release of
water vapour when agent heated
 cooling - decomposes endothermically
 radiation shielding is of some significance as cloud
of dry chemical shield the fuel from some of the
heat radiated by the flame
18
Extinguishing
Mechanisms - A
 smothering from metaphosphoric acid with
multipurpose dry chemical
19
System - Containers





placed as close as possible to the hazard
up to 3000 pounds
maximum, pressure at 130 F
protected from damage
reserve not required unless located in remote
location
 systems protecting multiple hazards require a
reserve supply
20
System – Expellant
Cylinders
 usually nitrogen, sometimes CO2
 mix with powder for ease of distribution to the
hazard, fluidization
21
System – Piping
 pipe withstand the pressures encountered;
resistant to chemical corrosion
 galvanized, stainless steel, copper or brass
 welded or rolled groove, schedule 10, 1/8 to 3
inches, up to 560 psig
 steel threaded or cut grooved couplings,
schedule 40, 1/8 to 4 inches, up to 500 psig, 6
to 8 inches ,up to 420 psig
 fluidized agent likely to settle & lose momentum;
remix chemical at each tee
22
System – Nozzles
 blow-off caps in dusty and oily environments
23
Sequence of Operation
24
Application Methods
Three basic application methods for dry chemical
piped systems:
Total flooding,
Local application - overhead.
Local application – tankside
Hazard characteristics determine most appropriate
method
25
Applications




liquified natural gas loading platforms
paint spray booths and dip tanks
transformer, generator and turbine protection
mining, conveyor and lubrication areas
26
Extinguishing Systems
Two types:


Engineered Systems
Pre-engineered Systems
Engineered Systems
Require:
 Individual design
 Calculations
 To determine the:
 Flow rates,
 Quantity of dry chemical,
 Number, size, location & pressure of nozzles,
 Size and length of the piping & fittings
Refer to NFPA 17 & listed design manual
Pre-Engineered
"Package" Systems
• Must conform with pre-determined parameters
•
Limits defined by testing and approval agencies
Ex: vehicle system.
Refer to:
•
•
NFPA 17 and
Manufacturer’s listed installation manual
Total Flooding
30
Total Flood Calculation
How much agent is required when space is 10 ft long by 10 ft
wide by 10 ft high?
The application rate is 0.077 lb/min/ft3
Minimum duration of discharge is 30 seconds
Total Flood Calculation
W = V x Ar x T
Volume = L x W x H = 10 x 10 x 10 = 1000 ft3
Ar = 0.0077 lb/min/ft3
T = 30 seconds = 0.5 min
W = V x Ar x T = 1000 x 0.077 x 0.5 = 38.5 lb
Compare with CO2:
W = V x Fv x Fc = 1000 x 0.063 x 1 = 63.0 lb
Total Flood Calculation
Number of Nozzles?
Each nozzle requires 500 ft3
Number = __V__ = 1000 = 2 nozzles minmum
500
500
Area per nozzle = 500 / H = 500 / 10 = 50 ft2
Space = L x W = √50 = 7.1 ft
L / 7.1 = W / 7.1 = 10 / 7.1 = 1.41 --> 2
Number of nozzle = 2 x 2 = 4 nozzles
Local Application
Overhead
• Based on "area protection" - dry chemical is
applied to areas from nozzles mounted
overhead.
• Hazard located in a large room or building where
total flooding application is inappropriate.
• Effective on such hazards as dip tanks, drain
boards, quench tanks, pipe coating,
manufacturing equipment and wax coaters
• Up to 80 sq. ft. (7.4 m2).
Local Application Tank-side
• Based on ‘area protection’
• Applied horizontally over the fire surface.
• Nozzles are mounted above liquid surface
• Minimize liquid splashing &
• To cover the complete surface of the tank
• Used for dip tanks, drain boards, quench
tanks or floor areas under machinery
• Up to 120 sq. ft. (11.1 m2)
Local Application Tank-side
Local Application
Combination
In some cases, combination of types
Examples: Quench Tank & Exhaust Duct System
Hand Hose
Lines
Consists of:
• Supply of dry chemical &
• Supply of expellant gas &
• One or more hand hose lines
• Deliver the dry chemical to the fire.
• These systems require trained personnel
Piping Method Tee
Splits


The expellent gas - usually nitrogen.
Gas/dry chemical mixture must be maintained
as fluidized, homogeneous mixture

Some tee split conditions will split mixture into
components - dry chemical and nitrogen.


Possibility of insufficient flow rate
Can result in failure to extinguish.
Piping Method Tee
Splits
Two methods to overcome separation
 Venturi ensures homogeneous mixture when
entering a tee
 Critical length (20 x pipe diameter) to allow
remixing of the dry chemical to occur after a
change in direction.
 Critical length more cumbersome but lower
pressure drop of the agent mixture
Piping Method Tee
Splits
Inspection &
Maintenance




Both must be provided
Suppression systems – mechanical
Need periodic care
Carried out in accordance with manufacturer’s
recommendations
42
Inspection I

Necessary to provide reasonable assurance
the fire suppression system is:




Fully charged and Operable
At regular intervals.
Recommended daily
Performed by the operator of the apparatus.
Inspection II
Visual observation system components
Inspection VI



Discharge during daily inspection not
recommended.
When inspections give concerns -> reliability
may be desirable to discharge the system
Discharge during training exercises &
certification inspections provide testing
opportunities
Maintenance I





To provide maximum assurance system will
operate effectively and safely,
Conducted at six-month intervals or
Earlier when indicated by an inspection
Very complex & detailed operation
including discharge of the system
Strict adherence to manufacturer’s
recommendation
Maintenance II

Nitrogen cylinder regulators tested
annually

Often performed by contract with outside
firm

If fire department personnel not certified to
perform the maintenance on a system

contractor recommended
Recharge
When necessary:
operator follow the manufacturer’s
recommendation in the operator’s manual
 Clean out the hoses and pipes
 Short bursts of nitrogen builds up pressure in
the hoses - making clean out more effective
end
of
Presentation
49
Download