NFPA Circuits & Pathways by Dan Horon Cadgraphics Incorporated RescueLogic.com History In the 2007 Edition, the Style Tables had become outdated. They were prescriptive, and prevented new technologies. Understanding them required a fire alarm engineer. History Even though they were less complex than previous Editions, different tables represented types of circuits. History Even though they were less complex than previous Editions, different tables represented types of circuits. History Throughout the years that Style Tables were in Code, the older terms Class A and Class B never went away. Everyone working in fire alarm knew Class B as being a single supervised circuit, and that Class A has an additional redundant path. History In the 2010 Edition, we worked to replace the tables with simple, easy to understand language. Basically, fire alarm tradition: 1) requires a system to monitor itself for integrity; and 2) recommends -- but not requires -- redundant paths. History In the 2010 Edition, Class B is described in basic terms. History In the 2010 Edition, simple performance-based language also describes circuits that had never fit as Class A or B, even though they had been commonplace in fire alarm systems. History Class 7, the most fault-tolerant, but also most expensive type of circuit is now called Class X. Isolator modules are added to prevent a short-circuit from affecting equipment. History The Annex of the 2010 Edition explains the pathway Classes, and gives examples. More dramatically, it explains that a single ground fault does not need to be reported if it does not affect the circuit. Current Then, in the 2013 Edition, we added back the prescriptive requirement to report a single ground. Approved Fire Alarm Pathway One familiar type of Class B pathway has wires with direct current, and a resistor at the last device. The end-of-line resistor offers a level of assurance that the all wires are connected to the intended device. (+) (-) (+) (-) End-of-Line Resistor End-of-Line Resistor FACP Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway If a short occurs at any point on a Class B notification appliance pathway, the entire circuit becomes inoperable. (+) (-) X (+) (-) End-of-Line Resistor End-of-Line Resistor FACP Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway If an open occurs at any point on a Class B initiating device circuit, every device thereafter is inoperable. This is true even when a smoke detector is removed for maintenance. (+) (-) (+) (-) End-of-Line Resistor End-of-Line Resistor FACP Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway Class B pathways report a single ground connection because, a second ground may connection occur at some point later, and act like a short-circuit. On a Class B IDC, a short-circuit means alarm! (+) (-) (+) (-) End-of-Line Resistor End-of-Line Resistor FACP Wire touching ground Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway Class B pathways report a single ground connection because, a second ground connection may occur at some point later, and act like a short-circuit. On a Class B IDC, a short-circuit means alarm! (+) (-) (+) (-) End-of-Line Resistor End-of-Line Resistor FACP Two wires touching ground Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway Class B pathways report a single ground connection because, a second ground connection may occur at some point later, and act like a short-circuit. And, on a Class B IDC, a shortcircuit means alarm! (+) (-) (+) (-) End-of-Line Resistor End-of-Line Resistor FACP Two wires touching ground Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway Up to this point, we’ve seen the required methods of monitoring wires. We don’t know if any device is actually functional, but we can be reasonably certain the intended wires are connected. (+) (-) (+) (-) End-of-Line Resistor End-of-Line Resistor FACP Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway The Class B, multi-drop signaling line circuit gives each device a numerical address, and the control unit can communicate with all attached devices on just two wires in parallel. (+) End-of-Line Resistor (-) (+) (-) 001 002 003 004 Multi-drop End-of-Line Communications Resistor FACP 101 Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway An open on a Class B multi-drop SLC reports a trouble if the control unit cannot communicate with every device. (+) End-of-Line Resistor (-) (+) (-) FACP 001 002 003 004 Multi-drop Communications X 101 Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway For decades, smart systems have been sold as an improvement over conventional fire alarm systems. AHJs can see the obvious improvement that communication with each device provides. Yet, minimum Code requirements do not require operational capability of each device to be known. We only require the wires to be monitored. (+) End-of-Line Resistor (-) (+) (-) 001 002 003 004 Multi-drop Communications FACP 101 Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway Shorting the two wires at any point stops communication with every device. Not an indication of alarm as with an IDC, a short on the Class B multi-drop SLC reports a trouble. (+) End-of-Line Resistor (-) (+) (-) 001 002 003 004 Multi-drop Communications FACP X 101 Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway While every device is attached to the same two wires, a single ground reports a trouble. But, the single ground is not allowed to impact communications. (+) End-of-Line Resistor (-) (+) (-) 001 002 003 004 Multi-drop Communications FACP 101 Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Approved Fire Alarm Pathway A second ground on a Class B, multi-drop signaling line circuit stops all communication, as it is a short-circuit. (+) End-of-Line Resistor (-) (+) (-) 001 002 003 004 Multi-drop Communications FACP Version 3 Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Comparison 1 Every single connection on an Ethernet network is required by IEEE 802 (an ANSI standard) to be galvanically isolated. Traditional Fire Alarm Report a single ground A single ground must report even if it has no impact on communication. Wireless or fiber optic paths are excepted because they cannot be grounded, but IEEE 802 isolation means nothing. Cat 5/6 Ethernet A ground has no impact on IEEE 802 equipment. Every connection is galvanically isolated, which prevents propagation of transients, shorts, and grounds. (IEEE 802 is a verifiable ANSI Standard that can be referenced in Code.) Comparison 2 Class A and X paths have exactly two paths that will work if the other fails. A mesh network usually has more than two paths, not knowing exactly where a failure might occur. Redundant paths Traditional Fire Alarm Cat 5/6 Ethernet Redundant paths do not exist unless they are separately monitored for integrity. We must know the status of opens, grounds, and shorts on every connected wire. A mesh network design remains operational even after segments fail. Critical paths have redundancy, and failures of essential equipment report to responsible personnel. Comparison 3 Buildings are increasingly dependent on the network infrastructure. Traditional Fire Alarm Building networks No fire alarm equipment should ever be connected to a building network infrastructure. Building networks are not as reliable as traditional fire alarm systems. Cat 5/6 Ethernet Building networks are a new infrastructure. Modern building systems have standardized on LANs, WANs, and VLANs to interconnect intelligent equipment. A pair of parallel wires connected to multiple addresses is inherently unreliable. Wiring Comparison Every single connection on an Ethernet network is required by IEEE 802 (an ANSI standard) to be galvanically isolated. Wiring Traditional Fire Alarm Cat 5/6 Ethernet Terminations Wire nuts, junction boxes, Encased cables, RJ45 ends stripped wires, screw terminals Length Wire length is only limited when voltage drop and capacitance prove communication failure. The same wires touch every device in parallel. Like an old party-line telephone system, all devices talk on the same wires. Paralleled Version 1 Segmented every 300 feet or less. Packets are refreshed by forwarding equipment. Multi-layer design. Each device is an individually addressable endpoint. Devices are not physically wired in parallel with each other. Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Proposed Fire Alarm Pathway Network equipment can be thought of in two basic categories: Data Endpoints and Data Forwarding Equipment. Data Endpoint Version 1 Data Forwarding Dan Horon © 2013 DanHoron@RescueLogic.com Data Endpoints Permission required for distribution. Category 5 Ethernet Cable In between Data Endpoints and Data Forwarding Equipment, a standardized cable is used. ‘Cat 5’ is an example. Transmit Data Data Endpoint generates Receive or acts Data on alarm events IEEE requires 1 2 3 4 5 6 7 8 Transmit Data + Transmit Data Receive Data + NC NC Receive Data NC NC IEEE requires galvanic isolation on each pair of wires Version 1 Data Forwarding 1 2 3 4Network hub 5or switch that 6 7forwards data 8to endpoints galvanic isolation on each pair of wires Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Category 5 Ethernet Cable Each Cat 5 cable is galvanically isolated at each end, inside the equipment. The isolation helps prevents transient grounds and shorts on one cable from affecting other components. Transmit Data Data Endpoint generates Receive or acts Data on alarm events IEEE requires galvanic isolation on each pair of wires Data Endpoint 1 2 3 4 5 6 7 8 Transmit Data + Transmit Data Receive Data + NC NC Receive Data NC NC IEEE requires Cat 5 Cable Four wires are used for data transmission generates or acts on alarm events Version 1 Data Forwarding 1 2 3 4Network hub 5or switch that 6 7forwards data 8to endpoints galvanic isolation on each pair of wires Data Forwarding Network hub or switch that forwards data to endpoints Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. If Transmit Data (+) and (–) or Receive Data (+) and (-) are shorted together, communication stops. In fire alarm systems, a fault condition must be reported within 200 seconds. Transmit Data Receive Data IEEE requires 1 2 3 4 5 6 7 8 Transmit Data + Transmit Data Receive Data + NC NC Receive Data NC NC X IEEE requires galvanic isolation on each pair of wires galvanic isolation on each pair of wires Data Endpoint Data Forwarding generates or acts on alarm events Version 1 1 2 3 4 5 6 7 8 Network hub or switch that forwards data to endpoints Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. A ground connection on any one signal wire does not block communication. IEEE requires isolation at each end of every Cat 5 cable. Every data packet is checked for errors and re-transmitted until verified. Transmit Data Receive Data IEEE requires 1 2 3 4 5 6 7 8 Transmit Data + Transmit Data Receive Data + NC NC Receive Data NC NC IEEE requires galvanic isolation on each pair of wires galvanic isolation on each pair of wires Data Endpoint Data Forwarding generates or acts on alarm events Version 1 1 2 3 4 5 6 7 8 Network hub or switch that forwards data to endpoints Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. A second ground connection, on the other wire of a matched pair, will impair communication if it causes a short. A fault condition must be reported within 200 seconds. Transmit Data Receive Data IEEE requires 1 2 3 4 5 6 7 8 Transmit Data + Transmit Data Receive Data + NC NC Receive Data NC NC IEEE requires galvanic isolation on each pair of wires galvanic isolation on each pair of wires Data Endpoint Data Forwarding generates or acts on alarm events Version 1 1 2 3 4 5 6 7 8 Network hub or switch that forwards data to endpoints Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Again, each Cat 5 cable is galvanically isolated. Grounds and shorts have no direct path of electrical connection to other equipment or devices. Transmit Data Receive Data IEEE requires 1 2 3 4 5 6 7 8 Transmit Data + Transmit Data Receive Data + NC NC Receive Data NC NC IEEE requires Data Endpoints galvanic isolation on galvanic isolation on each pair of wires each pair of wires Data Endpoint Data Forwarding generates or acts on alarm events Version 1 1 2 3 4 5 6 7 8 Network hub or switch that forwards data to endpoints Dan Horon © 2013 DanHoron@RescueLogic.com Permission required for distribution. Here Goodyou network can see design a potential prevents vulnerability. a fault on any If asingle singlecable path were from making to become more impaired, than one multiple device data inoperable. endpoints would not communicate with essential equipment. Data Endpoint Version 1 Data Forwarding Dan Horon © 2013 DanHoron@RescueLogic.com Data Endpoints Permission required for distribution. A proposed Class N path would require alternate communication pathways whenever more than one device would be impacted by a fault. Data Endpoint Version 1 Data Forwarding Equipment Dan Horon © 2013 DanHoron@RescueLogic.com Data Endpoints Permission required for distribution. Class N Ethernet cables do not report grounds. Therefore, to allow Ethernet network wiring in the Code: • Any segment of a path that affects more than one device must be the equivalent of Class X. • Equivalent of Class B paths may be used when only one device is dependent on the path.