© ABB Ltd. - 1 01-04-06 - PRODUCT PRESENTATION VHA PANEL WITH HPA12 CIRCUIT BREAKER ABB © ABB Ltd - 2 VHA 12 PANEL Designed and type tested to meet requirements of IEC 298 & 694 / IS:3427 Air insulated indoor switchgear Metal clad construction Internal arc tested IP4X degree of protection externally and IP2X between compartments Independent exhaust vents for all HT compartments ABB © ABB Ltd - 3 VHA 12 PANEL Integral Earthing Switch optional Normal service conditions: Min ambient temp:-5oC, Max ambient temp:+40oC Up to 3000A in panel without forced cooling Quality System CertificationISO 9001 Environmental Management System- ISO 14001 ABB © ABB Ltd - 4 BREAKER COMPARTMENT Cassette mounted breaker with isolated position on cubicle front door Racking in/out of breaker from test to service position and vice-versa with cubicle door closed only Mechanical interlock to prevent racking in/out of breaker, when breaker is in closed position Live parts covered by automatic shutters when breaker is racked out ABB © ABB Ltd - 5 METERING COMPARTMENT Metering compartment with numerical/static/electromagnetic relays, indicating meters, lamp and control switches Protection and measuring apparatus customized as per requirement ABB © ABB Ltd - 6 CABLE AND CT COMPARTMENT Spacious construction to accommodate 1 set of CTs and 2 runs of cables Option of rear extension to accommodate extra CTs or cables Adequate height for cable termination ABB © ABB Ltd - 7 PT COMPARTMENT Withdrawable line PT provided in the breaker panel Removable fuses mounted on the PT Safety shutters between PT & Cable compartment close automatically on PT withdrawal ABB © ABB Ltd - 8 BUSBAR COMPARTMENT Spacious busbar compartment for adequate air clearances Option for busbar insulation available Option for shrouds on joints available ABB © ABB Ltd - 9 HPA BREAKER The HPA type circuit breaker is designed and tested to meet requirements of IEC 56 / IS : 13118 SF6 gas used as insulation and arc interruption medium Arc control and extinction achieved by puffer principle Capable of interrupting small magnetizing and capacitive currents ABB © ABB Ltd - 10 HPA BREAKER Features of operating mechanism O-C-O operation without recharging Closing spring charged by motor in less than 15secs Electrical anti-pumoing Provision for manual recharging Synchronisation and fast auto reclosure duty ABB HPA BREAKER The HPA series of CB are designed and type tested to meet the requirements of IEC-60056 / IS:1318 The HPA series of CB use SF6 gas as insulating and arc interruption medium Arc interruption and control are achieved by puffer principle Short arc duration followed by rapid dielectric recovery Long electrical life, as the interruption system develops low arc energy and contact wear is minimal Long mechanical life with study and proven operating © ABB Ltd - 11 mechanism - 10000 operations at no load - 10000 operations at rated current ABB © ABB Ltd - 12 HPA BREAKER Operationally safe and reliable in wide range of operating temperature -5o to +40o c Capable of interrupting small magnetizing and capacitive currents Compact design with relatively light weight construction Features of operating mechanism O-C-O operation without recharging closing spring charged by motor in less than 15 secs. electrical anti-pumping provision for manual recharging synchronization and fast auto-reclosure duty ABB © ABB Ltd - 13 VHA PANEL CROSS SECTIONAL DWG ABB VHA 12 PANEL © ABB Ltd - 14 TECHNICAL DETAILS Description Unit Rating Voltage kV 12 Frequency Hz 50 Current A 630, 1250, 1600, 2000, 2500, 3000, 4000 Short time withstand current (for 3 secs) kA 40 Peak withstand current kAp 100 Insulation level kVrms/kVp 28/75 WidthxDepthxHeight mm 800x1370x2340 Weight with breaker (approx.) kg 1000 Degree of Protection-Enclosure IP4X ABB HPA12 CIRCUIT BREAKER TECHNICAL DETAILS Description Unit Rating Voltage kV 12 Frequency Hz 50 Current A 1250, 1600, 2000, 2500, 3150 Breaking capacity kA 40 Short time withstand current (for 3 secs) kA 40 Peak withstand current kAp 100 Insulation level kVrms/kVp 28/75 Operating sequence © ABB Ltd - 15 Weight (approx.) O-3min-CO-3min-CO/ O-0.3secs-CO-3min-CO kg 190-225 ABB INSTALLATIONS OVER 25,000 PANELS INSTALLED MAJOR INSTALLATIONS AT: POWER PLANTS DISTRIBUTION UTILITIES STEEL PLANTS CEMENT PLANTS REFINERIES VARIOUS INDUSTRIES & INFRASTRUCTURE PROJECTS © ABB Ltd - 16 ABB SUCCESFULL INSTALLATIONS IN GENEARATIONS Major installations of VHA 12S +HPA POWER PLANT LOCATION SF6 SWGR INSTALLED MSEB ( CHANDRAPUR UNIT IV V &VII ,KORADI) (1989,95,99)- 593 NTPC ( VINDHYACHAL 500MW)(1995) - 248 NTPC ( TALCHER 4 X 500MW) (1999) - 451 APSEB ( RAYALSEEMA 2 X 210 MW) (1998) - 235 BSES DAHANU ( 2 X 250MW) (1994) - 163 MPEB SGTPS (1997) - 179 GIPCL (2 X 125 MW) (1996) - 110 © ABB Ltd - 17 Total SF6 panels installed in Generations in India - 4100Nos ABB’s market share in Generation is 70% !!! ABB HPA – Arc Interruption principle © ABB Ltd - 19 BBBBBBBB ABB