GroundMed DAQ/DMS Training Coimbra 6-12-2011 Andre Quintino Duarte Anibal T. de Almeida Joao Fong Summary 1. DAQ - Data Acquisition System 1.1. Hardware Installation 1.1.1. Devices’ Assemblage 1.1.2. Power Connections 1.1.3. Communication Connections 1.1.4. Sensors Connections 1.2. Software Installation 1.2.1. Software Configuration 1.2.2. Measuring Utility 2. DMS - Data Management System (NEW) 3. Further Development in Coimbra 4. Questions and Answers 5. Coimbra GroundMed facility visit Info All information available at: www.isr.uc.pt/~groundmed Info All information available at: www.isr.uc.pt/~groundmed 1. DAQ - Data Acquisition System 1. DAQ - Data Acquisition System National Instruments cRIO 9074 1. DAQ - Data Acquisition System National Instruments cRIO 9074 NI 9217 NI 9871 NI 9219 1. DAQ - Data Acquisition System DAQ 1. DAQ - Data Acquisition System DAQ Brunata Thermal Meters Pyranometer Carlo Gavazzi Meters Humidity Sensor Indoor/Outdoor Temperature Sensors 1. DAQ - Data Acquisition System D DAQ A System Q 1. DAQ - Data Acquisition System Septemes les DAQ Vallons, System France Oradea, Romenia DAQ System Coimbra, DAQ Portugal System Benedikt, DAQ Slovenia System Valencia, DAQ Spain System Barcelona, DAQ Spain System Padova, DAQ Italy System DAQ Athens, Greece System Internet Internet Internet Internet Internet Internet Internet Internet DMS Serve r Ground Med WebSit e 1.1. Hardware Installation 1.1.1. Device’s Assemblage 1.1. Hardware Installation 1.1.1. Device’s Assemblage Coimbra 1.1. Hardware Installation 1.1.1. Device’s Assemblage Barcelona 1.1. Hardware Installation 1.1.2. Power Connections 1.1. Hardware Installation 1.1.3. Communication Connections 1.1. Hardware Installation 1.1.3. Communication Connections Important: - Create an RS-485 network; - Use shield cable with 2 twisted pairs; - Connect shield to ground; - Connect a 120Ω resistor on the edges of the network; - All the devices on the network must have different addresses; - The order is not important. 1.1. Hardware Installation 1.1.3. Communication Connections 1.1. Hardware Installation 1.1.4. Sensors Connections 1.1. Hardware Installation 1.1.4. Sensors Connections Sensors: - Indoor Temperature Sensor; - Outdoor Temperature Sensor; - Pyranometer; - 2x Brunata (Flow Sensor and 2 Temperature Sensors each); - Current Transformers; - Humidity Sensor (Optional). 1.1. Hardware Installation 1.1.4. Sensors Connections 1.1. Hardware Installation 1.1.4. Sensors Connections Important: - Don’t mix Brunata Temperature Sensors; Brunata Display Unit Temperature Probes 1.1. Hardware Installation 1.1.4. Sensors Connections Important: - Don’t mix Brunata flow sensors; Flow sensor Brunata Volume Meter 1.1. Hardware Installation 1.1.4. Sensors Connections Important: - Each Brunata Display Unit has one and only one Volume Meter. Brunata Display Unit Brunata Volume Meter 1.1. Hardware Installation 1.1.4. Sensors Connections 1.2. Software Installation 1.2. Software Installation Download and Install in this order: 1. NI cRIO Drivers (about 1600MB)http://joule.ni.com:80/nidu/cds/view/p/id/2411/lang/e n; 2. RTAD Application Installer (about 10MB) http://zone.ni.com/devzone/cda/epd/p/id/5986;3. Asynchronous Message Communication (AMC) reference library (about 6MB) (Not required anymore) http://zone.ni.com/devzone/cda/epd/p/id/6091;4. Reference Library for Reading cRIO System Configuration Information (about 6MB) (Not required anymore)http://zone.ni.com/devzone/cda/epd/p/id/1717;5. GroundMed software from ISR available at: www.isr.uc.pt/~groundmed;6. GroundMed Configuration Utility;7. GroundMed Measurement Utility. 1.2. Software Installation 1.2.1. Software Configuration 1.2. Software Installation 1.2.1. Software Configuration Set cRIO Time Zone, Time & Date: 1. Load MAX (Measurement & Automation) on the computer;2. Click on Remote Systems, then the cRIO module available;3. On the right size, click below on Time Settings;4. Set your Time Zone, Date and Time;5. Click above on Save. 1.2. Software Installation 1.2.1. Software Configuration Demonstration 1.2. Software Installation 1.2.1. Software Configuration Run RT Application Deployment: Your cRIO Software to install 1) Press Settings under “Application Images”; 2) Browse to load the GroundMed downloaded image; 3) Press “Deploy”. 1.2. Software Installation 1.2.1. Software Configuration Demonstration 1.2. Software Installation 1.2.1. Software Configuration - 8 different demonstration sites Does this means 8 different software versions? 1.2. Software Installation 1.2.1. Software Configuration 1.2. Software Installation 1.2.1. Software Configuration 1.2. Software Installation 1.2.1. Software Configuration 1.2. Software Installation 1.2.2. Measuring Utility 1.2. Software Installation 1.2.2. Measuring Utility 1.2. Software Installation Demonstration 3. Further Development in Coimbra 3. Further Development in Coimbra 3. Further Development in Coimbra NI 9472 Finder Relay 20.21.9.024.4000 - 8 Sourcing Digital Outputs; - 24V Coil Voltage; - 6 to 30V range. - 250V AC Rated Voltag 3. Further Development in Coimbra 4. Questions and Answers 5. Coimbra GroundMed facility visit 5. Coimbra GroundMed facility visit Thank You Andre Quintino Duarte Anibal T. de Almeida Joao Fong