Connecticut Energy Code Frederick F. Wajcs Senior Energy Engineer Northeast Utilities February 10, 2011 Brought to you by: Current Connecticut Energy Code 2006 International Energy Conservation Code (IECC) with ASHRAE/IESNA Standard 90.1-2004 as reference document 2 Next Connecticut Energy Code 2009 IECC With Standard 90.1-2007 as reference document Anticipated implementation: Second half 2011 3 Next Connecticut Energy Code Required for receipt of the American Recovery and Reinvestment Act (ARRA) funds ARRA also requires 90% compliance by December 2017 • www.energycodes.gov/arra/compliance_eval uation.stm • On site surveys anticipate participation of building officials, design professionals, contractors and suppliers 4 Compliance Checklists Commercial Building Data Collection Checklist ANSI/ASHRAE/IESNA Standard 90.1-2007 Date: Name of Evaluator(s): Building Name & Address: Conditioned Floor Area: Building Contact: Name: Compliance Approach: State: Phone: Prescriptive Trade-Off (Section 5.6) ft 2 Email: Performance (ECB Section 11) Jurisdiction: Building Use: Project Type: Office Retail Storage New Construction Education Lodging Addition Dining Renovation Public Health Residential Other Valuation (If Renovation): $ Complies Item Number Plan Review PR1 1 [4.2.2] Plans and/or specifications provide all information with which compliance can be determined for the building envelope and delineate and document where exceptions to the standard are claimed. PR2 1 [4.2.2] Plans and/or specifications provide all information with which compliance can be determined for the mechanical systems and equipment and delineate and document where exceptions to the standard are claimed. PR3 1 [4.2.2] Plans and/or specifications provide all information with which compliance can be determined for the service water heating systems and equipment and delineate and document where exceptions to the standard are claimed. PR4 1 [4.2.2] Plans and/or specifications provide all information with which compliance can be determined for the lighting and electrical systems and equipment and delineate and document where exceptions to the standard are claimed. Information provided should include interior and exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. PR5 1 [6.4.2] HVAC load calculations submitted. PR6 1 [7.4.01] Service water heating load calculations submitted. PR7 1 [6.7.2.4] Detailed instructions for HVAC systems commissioning included on the plans or specifications. PR8 1 [6.7.2.1] Construction documents require HVAC “as-built” drawings submitted within 90 days of system acceptance. PR9 [8.4.1.1, 1 8.4.1.2] Feeder and branch circuit load and sizing calculations provided that allow verification of voltage drop. PR10 [8.7.1 1 8.7.2] Construction documents require as-built drawings for electric power systems and O&M manual for electrical power systems and equipment. Additional Comments: Y N N/A Comments/Notes/Findings 5 2009 IECC Administration Applies to residential and commercial buildings Regulates the design and construction of buildings for the effective use of energy 6 2009 IECC Administration Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to provisions for new construction Change in occupancy or use • That increases either fossil fuel or electrical energy • Lighting shall comply when space changes from one lighting building area type to another 7 Exceptions Storm windows over existing fenestration and glass only replacement Cavities completely filled with insulation or not exposed Reroofing • Roofs without insulation in cavity and where sheathing or insulation is exposed shall comply Replacement of existing exterior door does not require installation of vestibule as long as existing vestibule is not removed Alteration that replaces less than 50% of luminaires in a space as long as installed interior lighting power is not increased Lamp and ballast replacement within existing luminaires as long as installed interior lighting power is not increased 8 Commercial Projects Shall Comply Entirely with Chapter 5 Or Entirely with Standard 90.1-2007 9 Construction Documentation Information Insulation material and their R-value Fenestration U-factors and SHGCs Area-weighted U-factor and SHGC calculations Mechanical system design criteria Mechanical and service water heating system and equipment types, sizes and efficiencies Economizer description Equipment and systems controls Fan motor horsepower and controls Duct sealing, duct and pipe insulation and location Lighting fixture schedule with wattage and control narrative Air sealing details 10 Envelope IECC, 90.1Residential and 90.1 NonResidential Requirements are essentially the same (except skylights) and more stringent than 2006 IECC 90.1 has requirements for semi-heated spaces Projects with vertical fenestration area (40%) or skylight area (3%) exceeding IECC allowances must use 90.1 IECC has no SHGC requirements for fenestration with projection factor ≥0.25 11 Mechanical Air cooled air conditioner & heat pumps • Efficiency requirements higher than 2006 IECC • 90.1 has IEER requirements for ≥65,000Btu/h Water & evaporatively cooled air conditioner • Efficiency requirements are mostly the same as 2006 IECC • 90.1 has IEER requirements Efficiency requirements for SPVAC and SPVHP in 90.1 12 Mechanical Compliance paths for water chillers • Path A for chillers expected to operate a significant time near full load conditions • Path B for chillers expected to operate a significant time at part load conditions Efficiency requirements for water chillers • kW/ton for water cooled • Higher full load values but lower part load values • Air cooled cannot be used for Path B compliance 13 Mechanical Some boilers have combustion efficiency & thermal efficiency requirements in 2009 IECC Efficiency requirements for boilers are generally higher in 90.1 Heat rejection equipment requirements are in 90.1 but not in IECC 14 Mechanical – Controls Zone thermostatic controls Off-hour • Setback/Shutdown • Optimum start (Systems >10,000 cfm) only in 90.1 • Exceptions for systems: <6,800 in IECC <15,000 in 90.1 15 Mechanical – Controls Ventilation system • Gravity dampers allowed on outside air supply & exhaust in buildings <3 stories • Gravity dampers allowed on stair and elevator shafts in buildings <3 stories in IECC • Motorized dampers required elsewhere and must have shutoff control • Ventilation fans Capability to reduce to minimum required in IECC Off-hour shutdown for fans >3/4 hp in 90.1 16 Mechanical - Controls Demand control ventilation for spaces >500 sf & design occupancy >40 persons/ 1,000 sf Single zone VAV for chilled water AHU ≥5 hp in 90.1 17 Mechanical Duct and pipe insulation requirements are different in IECC and 90.1 Duct sealing requirements Duct leakage tests 18 HVAC Completion Requirements Record drawings covered in 90.1 Operating manual Maintenance manual System balancing System commissioning for conditioned area >50,000 sf in 90.1 19 Mechanical Economizers • Air side ≥54,000 Btu/h in IECC Total capacity without economizers not to exceed 480,000Btu/h or 20% economizer capacity • Air side ≥135,000 Btu/h in 90.1 Fan power limitations in IECC and 90.1 Speed control on VAV fan motors ≥10 hp 20 Mechanical – Hydronic Systems Flow modulation (≥300,000 Btu/h for IECC) Speed control on variable flow systems (>50 hp Pumps in 90.1) Equipment isolation Temperature reset controls Two-way valves on hydronic heat pumps (>10 total pump system power in IECC) 21 Mechanical Energy recovery Exhaust hoods Radiant heating systems required for unenclosed spaces Hot gas bypass limitations 22 Service Water Heating Equipment efficiencies Pool heaters Pipe insulation Pool covers Heat traps Allowed for space heating in 90.1 23 Lighting Building area method lighting power densities in IECC and 90.1 Space-by-space method lighting power densities in 90.1 Meet lighting power densities requirements when replacing ≥50% of luminaires Exterior lighting power allowances 24 Lighting – Controls Automatic interior lighting shutoff in all spaces • Holiday scheduling included in IECC Space controls • Bi-level capability in IECC • Automatic controls in defined spaces in 90.1 • For each interior enclosed space Individual independent controls in daylight zones in IECC 25 Detailed Comparison On Connecticut Chapter of ASHRAE web page www.ctashrae.org Spreadsheet showing requirements in 90.1-2001, 90.1-2004 and 90.12007 Spreadsheet showing requirements in 2006 IECC, 2009 IECC and 90.12007 26 Training International Code Council training sponsored by State of Connecticut Office of Education and Data Management To register for : http://www.iccsafe.org/Education/C ourses/Pages/CT-Energy-list.aspx 27 Thank You! Fred Wajcs Senior Energy Engineer Conservation and Load Management 860-665-3286 wajcsff@nu.com 28