Zoning Application Zoning Application Agenda Application Overview --Benefits & Challenges with Zoning HVAC System Designs Conventional Vs Zoning Excess Air --Defining --Management Strategies ‹#› Copyright 2011 Trane Zoning Application Zoning is the intentional restriction of capacity (air flow) into a specific zone. Why Zoning and how can a customer benefit from zoning? Have you come across a zoning system that did not provide these benefits? ‹#› Copyright 2011 Trane Zoning Application Air Conditioning Contractors of America (ACCA) provides standards in designing HVAC system. There are standards for conventional systems and standards for zoning systems. Which manuals are mandatory? Manual J8 is required for the proper application & design of zoning systems. ‹#› Copyright 2011 Trane Zone Heat Gain Sensible Heat Gain Graph of Manual J8 BTU’s Software will show “Powered by Manual J” The yellow line represents a 30% buffer zone. Room temperature swings may be extreme if hourly load conditions exceed this buffer limit. The lower green line shows the average sensible heat gain. This is used to size the HVAC system The red line represents the actual hourly heat gain. Time Zone Heat Gain BTU’s Some applications will have extreme excursions. This is especially true for homes with large glass loads or condominiums (small interior loads with only one external wall). If zoning is applied, the duct size must be sized upon the red line peak excursion. Time Zoning Application The fundamentals remain the same: An accurate heat load calculation & proper duct design is critical. Zoning should never be applied to oversized systems or undersized ducting. The HVAC system is sized on _________ ________________ The duct system is sized on _________ ________________ ‹#› Copyright 2011 Trane Zoning Application The Basics Always start with a “common sense” approach when applying zoning. There are several tools out there to assist with calculations, but always stay focus on the obvious: •Rooms that are open to each other should be in the same zone. •With multiple story homes, each floor should be a zone. •Unique rooms (detached rooms or rooms with large glass loads) should be individually zoned. ‹#› Copyright 2011 Trane Zoning Application The Basics •Each zone must have a dedicated return path. •Each sensor must be in the air path of the zone it controls. •Never apply more zones than the equipment can handle. What happens with only the smallest zone calling. ‹#› Copyright 2011 Trane Zoning Application Daily Solar Load Shifts Room grouping from ACCA Manual RS Daily solar shifts ‹#› Copyright 2011 Trane Living Room W N Guest Room 1 E Add 1 Ad 2 Add 3 Office Dining Guest Room 2 Kitchen S Master Bed Zoning Application Seasonal Load Shifts Room grouping from ACCA Manual RS Seasonal load shifts and the 15% rule. ‹#› Copyright 2011 Trane Living room Guest room Guest room 73% C/H Ratio 63% C/H Ratio Add 1 Ad 2 109% C/H Ratio Dining Kitchen Add 3 Office 61% C/H Ratio Master Bed Zoning Application Excess Air What happens to a system when air flow is restricted? How can this reduction in air flow be managed? ‹#› Copyright 2011 Trane Zoning Application Excess Air Management Strategies Bypass Dump Variable Speed Air Flow Reduction Multi Capacity Systems Relief Over Blow Excess air must be managed based on worst case conditions! ‹#› Copyright 2011 Trane Zoning Application DST Thermal Limits ‹#› Copyright 2011 Trane Which is the smallest zone in heating? How much excess air must be managed? Which is the smallest zone in cooling? How much excess air must be managed? ‹#› Copyright 2011 Trane Zoning Application Understanding Bypass Supply Air Manual D informs us how to size the ducting to each zone. But how do I size a bypass duct? Mixed Air ‹#› Copyright 2011 Trane Return Air Zoning Application Calculating Bypass Supply Air Turn on the system with the smallest zone calling and the bypass damper wide open. Obtain two dry bulb temperature readings: Temp split from return & bypass air. Bypass Air Reading Mixed Air ‹#› Mixed Air Copyright 2011 Trane Reading Return Air Return Air Reading Temp split from return & mixed air. Zoning Application Understanding Bypass Taken from the install guide of a popular zoning system. Take a look at what happens with this much bypass. Mixed Air ‹#› Copyright 2011 Trane Return Air This is 75% bypass Temp splits with 36% bypass on a 4-ton cooling system. Temp splits with 64% bypass on a 4-ton cooling system. Temp Rise 30⁰ - 60⁰ 43% bypass on 80K 4ton drive furnace 18% bypass on 80K 4ton drive furnace Zoning Application What are the main advantages of Bypass? What are the main disadvantages of Bypass? ‹#› Copyright 2011 Trane Zoning Application $$$ Savings on Energy Bills? Will zoning deliver energy savings? “The benefit of a set-up / setback schedule depends on the cycle time. Long periods (days or weeks) of set-up / setback save energy. Short set-up / set-back periods (less than a day, maybe less than 16 hours) saves less energy, or may increase energy use.” ACCA Preliminary Manual Zr ‹#› Copyright 2011 Trane Zoning Application $$$ Savings on Energy Bills? 4-ton AC system ‹#› 10.6Copyright EER2011 Trane 9.7 EER 8.5 EER Zoning Application Variable Speed Air Flow Reduction A variable speed indoor unit can reduce air flow up to 30% in compressor only operation. This creates similar results as bypass but with some energy savings. Air flow reduction is the preferred method over bypass, but is not incorporated with gas furnaces or when resistant heat is in use. Air flow reduction and bypass may not be utilized at the same time. ‹#› Copyright 2011 Trane 1985 CFM at 0.7 static consumes 824 watts. A 30% air flow reduction will deliver1389 CFM. 1383 CFM = 396 Watts at 0.7 static. Even if static remains constant as dampers close, blower reduction assists with energy savings. ‹#› Copyright 2011 Trane Zoning Application Multi Capacity Systems Can multi capacity systems assist with zoning? ‹#› Copyright 2011 Trane Zoning Application Over blow Over blow makes the assumption that air will be redirected through the ducting as dampers close. ‹#› Copyright 2011 Trane Zoning Application Over blow This duct system is moving 600 FPM. How much air flow will this 8 inch duct deliver__________? Static pressure & velocity rates will increase as dampers close. How much air will this 8 inch duct deliver at 900 FPM? Can you count on over blow with a high static duct system? ‹#› Copyright 2011 Trane Zoning Application Setting Duct Size -- Weight What are some advantages of an oversized duct system with zoning? What are some disadvantages of an oversized duct system? Should the zone control system know the duct size to each zone? Why? Auto Zone Weighting or Manual Set up ‹#› Copyright 2011 Trane ‹#› Copyright 2011 Trane Zoning Application Setting Duct Size -- Weight A main duct is defined as any damper that controls more than one supply terminal. ‹#› Copyright 2011 Trane Zoning Application Time to add it all up Time to calculate a basic two zone single stage system with psc motor. But first, how will I obtain the following information. •The required air for each zone •The amount of excess air that must be managed •The maximum allowable bypass •The amount of over blow (if any) •The remaining amount of excess air ‹#› Copyright 2011 Trane 14” 1000 CFM @ 900 feet per minute 12” 700 CFM @ 900 feet per minute Blower set to deliver 1600 CFM. The bedroom is the only zone calling and requires 36% of this air flow. The bedroom requires ________ CFM. Cooling Mode Due to the limitations of the furnace, the maximum bypass is 18% which is ________ CFM. I need to find a home for the remaining ________ CFM. Factor in over blow. The 12 inch duct can handle 700 CFM at 900 FPM (700 – ______required by bedroom = ______ CFM of over blow). 1600 CFM – 700 into the zone – ______bypass = _______CFM (_____%) of excess air. How can we manage this excess air? 12” 700 CFM @ 900 feet per minute Blower set to deliver 1600 CFM. Cooling Mode The living room zone is the only zone calling and requires 64% of this air flow. The living room requires ________ CFM. Due to the limitations of the furnace, the maximum bypass is 18% which is ________ CFM. I need to find a home for the remaining ________ CFM. Factor in over blow. The 14 inch duct can handle 1000 CFM at 900 FPM (1000 – ______required by living room = ______ CFM of over blow). 14” 1000 CFM @ 900 feet per minute 1600 CFM – 1000 into the zone ______bypass = _______CFM (_____%) of excess air. How can we manage this excess air? Blower set to deliver 1275 CFM. The bedroom is the only zone calling and requires 43% of this air flow. The bedroom requires ________ CFM. Heating Mode Due to the limitations of the furnace, the maximum bypass is 18% which is ________ CFM. I need to find a home for the remaining ________ CFM. Factor in over blow. The 12 inch duct can handle 700 CFM at 900 FPM (700 – ______required by bedroom = ______ CFM of over blow). 1275 CFM – 700 into the zone – ______bypass = _______CFM (_____%) of excess air. How can we manage this excess air? 12” 700 CFM @ 900 feet per minute Blower set to deliver 1275 CFM. Heating Mode The living room zone is the only zone calling and requires 57% of this air flow. The living room requires ________ CFM. Due to the limitations of the furnace, the maximum bypass is 18% which is ________ CFM. I need to find a home for the remaining ________ CFM. Factor in over blow. The 14 inch duct can handle 1000 CFM at 900 FPM (1000 – ______required by living room = ______ CFM of over blow). 14” 1000 CFM @ 900 feet per minute 1275 CFM – 1000 into the zone – ______bypass = _______CFM (_____%) of excess air. How can we manage this excess air? Cooling mode bedroom calling. Cooling mode bedroom calling. Living room damper stop must be set to manage 612 CFM. 38% relief. 576 CFM is required based on conventional system design . 412 CFM is managed through over blow & bypass. Cooling mode living room calling. Cooling mode living room calling. 1024 CFM is required based on conventional system design. 288 CFM is managed by bypass. Bedroom damper stop must be set to manage 312 CFM. 20% relief. 14” 1000 CFM @ 900 feet per minute 12” 700 CFM @ 900 feet per minute Heating mode bedroom calling. Heating mode bedroom calling. Living room damper stop must be set to manage 345 CFM. 27% relief. 548 CFM is required based on conventional system design . 382 CFM is managed through over blow & bypass. Heating mode living room calling. Heating mode living room calling. 727 CFM is required based on conventional system design. 503 CFM is managed by over blow & bypass. Bedroom damper stop must be set to manage 45 CFM. 4% relief. 14” 1000 CFM @ 900 feet per minute 12” 700 CFM @ 900 feet per minute Living Room Damper Bedroom Damper Damper relief must be set for worst case conditions which is 38% for the cooling mode (only 27% required in heating mode). Damper relief must be set for worst case conditions which is 20% for the cooling mode (only 4% required in heating mode). The zone will receive 11% more air than is required during the heating mode. The zone will receive 16% more air than is required during the heating mode. Would a variable speed motor help? Why? Would multi capacity systems help? Why 14” 1000 CFM @ 900 feet per minute 12” 700CFM @ 900 feet per minute Would oversizing the duct system help? Moving from a 14 to a 16 inch duct allows for an additional 500 CFM of over blow. Moving from a 12 to a 14 inch duct allows for an additional 300 CFM of over blow. This reduces the bedroom cooling damper stop from 20% to 0%. This reduces the living room cooling damper stop from 38% to 20%. It reduces the bedroom heating damper stop from 4% to 0%. It reduces the living room heating damper stop from 27% to 4%. What are the risks of oversizing ducting? 16” 1500 CFM @ 900 feet per minute 14” 1000 CFM @ 900 feet per minute What happens as the number of zones increases? 8” 250 CFM @ 900 feet per minute 10” 410 CFM @ 900 feet per minute How well will a single stage system work on 4 zone application? 12” 700 CFM @ 900 feet per minute 8” 250 CFM @ 900 feet per minute What happens in a home with different zones at different temperatures? 68⁰ 8” 250 CFM @ 900 feet per minute 75⁰ 12” 700 CFM @ 900 feet per minute 77⁰ 10” 410 CFM @ 900 feet per minute 84⁰ 8” 250 CFM @ 900 feet per minute Zoning Application What are the chances any dealer / designer is going to go through all these steps? How many zoning systems are working properly? ‹#› Copyright 2011 Trane Zoning Application Bypass is a way to manage excess air. The downfall is it’s extremely difficult to configure and impossible to maintain consistency. The Comfortlink II / AccuLink zone system has the ability to manage excess air based on static pressure and discharge air temperature. •System configuration is simplified. •System performance is improved. •Homeowner comfort is maximized. ‹#› Copyright 2011 Trane Zoning Application The Comfortlink II / AccuLink zone system has two strategies for managing excess air: Stand Alone Relief or Temperature / Pressure Bypass. You can set these independently for heating & cooling modes. Cooling Mode ‹#› Heating Mode Relief Relief Temperature / Pressure Bypass Temperature / Pressure Bypass Copyright 2011 Trane Zoning Application Relief Based on the installation set up (manual or auto zone weighting), the zone control knows: •The size (weight) of each zone •The position of each damper •The blower speed (total air delivery) The zone control knows how much air is being delivered into each zone and how much excess air must be managed. ‹#› Copyright 2011 Trane Zoning Application Relief Once the zone control calculates the amount of excess air, it will distribute this air based on the following hierarchy: •Open dampers in all calling zones-up to 100% if necessary. •Open dampers (25% minimum) in the same mode zones that are not actively calling—up to 100% if necessary (an off zone is the same mode zone). •Open dampers (25% minimum) in opposing mode zones. ‹#› Copyright 2011 Trane Zoning Application Temperature / Pressure Control ‹#› Copyright 2011 Trane Zoning Application Temperature / Pressure Control The installation technician must pick a design static pressure when setting up the zone panel (from 0.4 to 1.0 inch of water column. The zone panel evaluates the system static pressure and discharge air temperature. Static pressure will increase as supply dampers close, and the zone panel will begin to open the bypass damper when the static reaches its configured target. ‹#› Copyright 2011 Trane Zoning Application Temperature / Pressure Control The ∆T from the return to the supply duct will increase as the bypass damper opens. The zone control will freeze the bypass damper and initiate the relief strategy when the supply temperature is within 4 degrees from the trip limit setting. ‹#› Copyright 2011 Trane Zoning Application Understanding Bypass Four zone single stage cooling system with PSC air handler. Supply Air Discharge Temperature Sensor All zones are set in cooling mode. Discharge temp sensor cut out is set at 42 degrees. Return Air Mixed Air Cooling Zone LV Damper Position Bypass enabling static pressure set point is 0.7 inches of water. Static Pressure Transducer Zone 1 Zone 2 Zone 3 Zone 4 0 0 0 0 0% 0% 0% 0% Zoning Application Understanding Bypass The thermostat came out of program mode. All zones have a load value of 100. Supply Air External static pressure is 0.5 and discharge air temperature is 60 degrees. What is the bypass damper doing ____________? What method of relief is being used _______________? Return Air Mixed Air Cooling Zone LV Damper Position Zone 1 Zone 2 Zone 3 Zone 4 100 100 100 100 100% 100% 100% 100% Zoning Application Understanding Bypass The house is cooling off and the dampers start to close. Supply Air External static pressure increases to 0.7 and discharge air temperature is 56 degrees. What is the bypass damper doing ____________? What method of relief is being used _______________? Return Air Mixed Air Cooling Zone LV Damper Position Zone 1 Zone 2 Zone 3 Zone 4 75 60 80 100 75% 60% 80% 100% Zoning Application Understanding Bypass The house continues to cool and dampers continue to close. Supply Air External static pressure reaches 0.8 and discharge air temperature is 52 degrees. What is the bypass damper doing ____________? What method of relief is being used _______________? Return Air Mixed Air Cooling Zone LV Damper Position Zone 1 Zone 2 Zone 3 Zone 4 60 40 60 100 60% 40% 60% 100% Zoning Application Understanding Bypass The house continues to cool and two dampers close. Supply Air External static pressure stabilized at 0.85 and discharge air temperature dropped to 45 degrees. What is happening with the bypass damper ____________? What method of relief is being used _______________? Return Air Mixed Air Cooling Zone LV Damper Position Zone 1 Zone 2 Zone 3 Zone 4 0 0 50 100 0% 0% 50% 100% Zoning Application Understanding Bypass The relief strategy is implemented. Supply Air External static pressure stabilized at 0.7 stabilizes at 48 degrees. What is happening with the bypass damper__________? How will the dampers react to relief__________________? Return Air Mixed Air Cooling Zone LV Damper Position Zone 1 Zone 2 Zone 3 Zone 4 0 0 50 100 0% 0% 100% 100% Zoning Application Understanding Bypass The relief strategy is exited. Supply Air External static pressure stabilized at 0.6 stabilizes at 52 degrees. What is happening with the bypass damper__________? How will the dampers react to relief__________________? Return Air Mixed Air Cooling Zone LV Damper Position Zone 1 Zone 2 Zone 3 Zone 4 0 25 50 100 0% 25% 50% 100% Zoning Application Time for a vote: Who wants to manually set up a zoning system? How will auto zone weighting make this easier? What are the benefits of intelligent relief? What are the benefits of T/P bypass? ‹#› Copyright 2011 Trane Zoning Application Summary: What steps must be taken when designing a zone system? 1) Consult with the homeowner and obtain their comfort desires. 2) ACCA Manual J8, S & D. Size the system based on average block load design. Size the ducting on peak demands. Do not oversize equipment. 3) ACCA Manual RS. Follow the guidelines when joining multiple rooms into zones. Never lose focus on the common sense approach. ‹#› Copyright 2011 Trane Zoning Application 4) What is the smallest zone and can the system manage the excess air. 5) Have the steps been taken to manage excess air (i.e. have you installed a Comfortlink II / AccuLink zoning system)? 6) Since the ducting is sized based on peak load conditions. Are the registers placed in a manner to mix air through the room at different velocity rates (ACCA Manual T)? 7) Follow through with the homeowner about system limitations and relief strategies. ‹#› Copyright 2011 Trane Questions? ‹#› Copyright 2011 Trane