OIL INTERCEPTOR SIZING CALCULATION FOR GENERATOR ROOM:
The size of the separator shall be calculated from the following formula:
NS = (Qr + fx ⋅ Qs ) fd
Where:NS is the nominal size of the separator;
Qr is the maximum flow rate of rainwater, in l/s
Qs is the maximum flow rate of wastewater, in l/s
fd is the density factor for the relevant light liquid
fx is the impediment factor depending on the nature of the discharge.
The maximum rainwater flow rate has been considered as zero, as no rainwater contributes to
the diesel generator room drainage system.
For the maximum flow rate of waste water: Flow rate for one floor gully is calculated as per the equation:
𝑄𝑤𝑤 = 𝐾√∑ 𝐷𝑈
(As per BS EN 12056-2, gravity drainage system inside the buildings)
Qww = Waste water flowrate (l/s)
K = Frequency factor
ΣDU = Sum of discharge units
Frequency factor considered is 1.2 as per BS EN 12056-2, gravity drainage system inside the
buildings, Table 3 — Typical frequency factors (K)
For the two diesel generator rooms, a total of 2 floor drains have been provided; therefore,
the total discharge units have been calculated accordingly:
= 1.3 x 2
= 2.6 (As per BS EN 12056-2, gravity drainage system inside the buildings, Table 2 – Discharge
units (DU)
Therefore, total discharge flow rate =
𝑄𝑤𝑤 = 1.2√2.6
𝑄𝑤𝑤 = 1.93 𝑙/𝑠
𝑄𝑤𝑤 = 1.93 𝑙/𝑠 (Considered)
Implement factor fx=2 has been considered as per BS EN 858-2 Separator system for oil and
petrol, Table 2 – minimum impediment factor.
Density factor fd=1 has been considered as per BS EN 858-2 Separator system for oil and petrol,
Table 3 – density factor fd.
NS = (Qr + fx ⋅ Qs ) fd
= (2 x 1.93) x 1
= 3.86 l/s
= 61.18 GPM
= 61.18 x 1.1 GPM (Considering 10% safety)
= 67.30 GPM
Selection = 75.0 gpm