lOMoARcPSD|71201273
E1 - asdasdad
Evapotranspiration (Bicol University)
Scan to open on Studocu
Studocu is not sponsored or endorsed by any college or university
Downloaded by sophia (pialorine268@gmail.com)
lOMoARcPSD|71201273
GENERAL NOTES:
150 X 150 X 150MM PB FOR EMERGENCY LOAD
1.
ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN
ACCORDANCE WITH THE PROVISION OF THE LATEST
EDITION OF THE PHILIPPINE ELECTRICAL CODE PEC 2017
RA 7920 WITH THE RULES AND REGULATION OF EXISTING
LOCAL AND NATIONAL AUTHORITIES CONCERNED IN THE
ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES
C:\Users\Admin\Desktop\CASA DISENO FILES\CASA DISENO\Untitled.png
6
150 X 150 X 150MM PB FOR NORMAL LOAD
PB
ref
9
1
LEGENDS:
a
S3a
7
PB
c
c
c
c
1
GFCI
Sa,b,g
c
a
pilot light
PENDANT LIGHT
PL
e
e
e
SERVICE ENTRANCE
GFCI
2
e
e
PL
g
e
e
ref
M
KILOWATT-HOUR METER
G
GENERATOR SET
ATS
AUTOMATIC TRANSFER SWITCH
150 X 150 X 150MM PULL BOX STUB OUT
NL FOR NORMAL
150 X 150 X 150MM PULL BOX STUB OUT
PB
EL FOR EMERGENCY
PB
3
PILOT LIGHT/
SECURITY LIGHT
SINGLE - REFRIGERATOR
OUTLET
DUPLEX CONVENIENT OUTLET
Sa
1-GANG SWITCH
Sab
2-GANG SWITCH
C:\Users\Admin\Desktop\CASA DISENO FILES\CASA DESINO PROJECTS\Makati Office Project\perspectives\ver 04\Enscape_2025-09-14-23-50-36.png
Sabc 3-GANG SWITCH
PERSPECTIVE
e
4.
ALL WIRES SHALL BE COPPER AND THERMOPLASTIC
INSULATION TYPE THHN/THWN, UNLESS OTHERWISE
INDICATED THE MINIMUM SIZE OF WIRES AND CONDUIT FOR
POWER AND LIGHTING LAYOUT SHALL BE 3.5MM2 THHN
20MM Ø (NORMAL DIAMETER) RESPECTIVELY, WIRE
INSULATION ARE GOOD FOR 600 VOLTS COLOR CODING:
LINE 1: RED
LINE 2: YELLOW
LINE 3: BLUE
NEUTRAL: BLUE
GROUND: GREEN
FLAT PANEL LIGHT
LIGHTING SWITCH LINE
a
Mountain view Subd., Filinvest II, Quezon City
Whatsapp & Viber no.: +639154691972
+639451936686 / +639154691972
casadiseno.1119@gmail.com
GFCI OUTLET
POWER LINE
SERVICE VOLTAGE TO THE BUILDING SHALL BE A:
400V,3-PHASE , 4-WIRE PLUS GROUND OR:
230V,1-PHASE,2WIRE PLUS GROUND, 60 HERTZ
3.
WIRING METHOD SHALL BE AS FOLLOWS:
A.
3.5MM STRANDED WIRE FOR POWER AND LIGHTING
OUTLET
B.
ELECTRICAL METALLIC TUBING (EMT); USING
COMPRESSION-TYPE CONNECTIONS
gfci
CIRCUIT BREAKER
S3g
2.
A.
B.
CIRCUIT HOMERUN
PANEL BOARD
Sc,d,e
c
WALL MOUNTED EMERGENCY LIGHT, TWIN
LED LIGHT, 3HR-DURATION , BATTERY
PACKED: NICKEL CADIUM
3-WAY SWITCH
e
e
b
e
4
NCGOC
New Change Group of Companies
b
d
d
d
d
d
d
d
CLIENT
d
PL
g
d
d
PROJECT:
d
PROPOSED
OFFICE FIT-OUT
b
Sf
5.
ALL MATERIALS TO BE USED AND EQUIPMENT TO BE
INSTALLED SHALL BE BRAND NEW AND MUST BE OF
APPROVED TYPE FOR BOTH PURPOSE AND LOCATED
INTENDED.
LOCATION:
b
Unit 2912- East Tower, The Stiles Enterprises Plaza,
Circuit Makati, Makati City
f
5
f
b
6.
ALL METALLIC CONDUITS, CABINETS AND EQUIPMENT
SHALL BE PROPERLY GROUNDED AND BONDED BY MEANS
OF COPPER STRAPS CONNECTION TO GROUND ROD SHALL
BE EXPOSED READILY ACCESSIBLE FOR INSPECTION
DOCUMENT TYPE:
f
f
PRELIMINARY PLAN FOR APPROVAL
BID DOCUMENT
PERMIT APPLICATION DOCUMENT
CONSTRUCTION DOCUMENT
ADDENDUM
b
7.
ALL ELECTRICAL WORKS HEREIN SHALL BE UNDER THE
DIRECT SUPERVISION OF A DULY LICENSED REGISTERED
ELECTRICAL ENGINEER OR A MASTER ELECTRICIAN.
8.
EXACT LOCATION OF ALL ELECTRICAL DEVICES TO BE
VERIFIED AT SITE AND ARE SUBJECT TO ARCHITECTS'/
ENGINEER'S APPROVAL.
E LIGHTING LAYOUT
1-4
SCALE
SHEET CONTENTS:
LIGHTING LAYOUT
POWER LAYOUT
SCHEDULE OF LOADS
RISER DIAGRAM
GENERAL NOTES
E POWER LAYOUT
2-4
1:50MTS
SCALE
1:50MTS
REVISIONS
DATE
9.
THE CONTRACTOR SHALL COORDINATE HIS WORK
WITH ALL TRADERS INVOLVED SO THAT THE EXACT
LOCATIONS AND QUANTITIES MAY BE OBTAINED FOR ALL
OUTLETS, APPARATUS, APPLIANCES AND EQUIPMENT.
10.
THE CONTRACT'S DRAWINGS. INSTRUCTION AND
TECHNICAL SPECIFICATION SHALL BE CONSIDERED AS ONE,
WHATEVER IS CALLED FOR BY ANY OF THE DOCUMENTS
SHALL BE IMPLEMENTED TO THE FULLEST EXTENT.
RA 9266, ARTICLE IV, SEC.33
MDP
PB NL
M
G DIESEL-FUELED-ENGINE
EL
GENERATOR SET
400Y/230V, 60Hz
50 AT, 100 AF, 400V,
3 POLE, MCCB, 18 KAIC
11.
EQUIPMENTS WITH BUILT-IN MALE PLUG MUST BE
COMPATIBLE WITH FEMALE EQUIPMENT INSTALLATION:
SWITCHES/CONVENIENCE OUTLETS / ACU OUTLETS /
TELEPHONE OUTLETS / CCTV PANEL BOARDS SHALL BE
FLUSH MOUNTED UNLESS OTHERWISE SPECIFIED.
12.
MOUNTING HEIGHTS:
A.
CONVENIENCE OUTLET
FLOOR LINE
B.
SWITCH OUTLET
FLOOR LINE
C.
ACU OUTLET
ACU UNIT
D.
TELEPHONE/CCTV OUTLET
FLOOR LINE
PB
4-8.0MM2 THWN, 1-5.5MM2 THWN
GROUNDING IN 32MM Ø IMC
ATS
1- EMERGENCY LIGHT, 6- PANEL
LIGHTS, 3- PENDANT LIGHT
- 0.30M ABOVE FINISH
1
20A
20A
7
2- EMERGENCY LIGHT, 8PENDANT LIGHT2
2
20A
30A
8
11- PENDANT LIGHT
3
20A
20A
9
2
2-3.5MM
- 1.50M ABOVE FINISH
2-3.5MM
2-3.5MM2
- LEFT HAND SIDE OF
ACU
2-5.5MM
1-SPECIAL OUTLET (REFRIGERATOR)
2-3.5MM
4
20A
20A
10
FCU
4- PANEL LIGHT2
5
20A
20A
11
SPARE
CONVENICE OUTLET2
6
20A
20A
12
SPARE
2-3.5MM
2-3.5MM
ELECTRICAL ENGINEER
2-3.5MM
11- PENDANT LIGHT2
2-3.5MM
-0.30M ABOVE FINISH
CONVENICE OUTLET
Drawings & specifications & other contract
documents duly signed, stamped or sealed as
instruments of service, are the intellectual property
and documents of the architect whether the object
of which they are made is executed or not.
It shall be unlawful for any person to duplicate or to
make copies of said documents for use in the
repetition of and for other projects or buildings,
whether executed party or in whole, without written
consent of architect or author of said documents
2-3.5MM
PRC Reg No.:
PTR No.:
TIN:
Place:
ARCHITECT:
EARL VINCENT C. ACIDRE
2-3.5MM
PRC Reg No.: 42062
TIN:
E SCHEDULE OF LOADS
3-4
SCALE
NTS
E RISER DIAGRAM
4-4
SCALE
NTS
500260036 Place:
DRAWN BY:
GM
DATE:
11/03/25
CHECKED BY: JMA
DATE:
10/03/25
APPROVED BY: JMA
DATE:
Downloaded by sophia (pialorine268@gmail.com)
PTR No.:
10/03/25
4256495
QUEZON CITY
SHEET NO.
EE-1