1) What is a reasonable, average summertime humidity and temperature of
outdoor air?
The team found the average daytime temperature in the summer could be reasonably
estimated at 85o F. The average relative humidity would be reasonably summarized to
70%
2) How much water must be removed from an average size load of laundry in the
dryer?
The team found the average clothes dryer removes about 10 lbm of water per cycle
3) How much air flows through the dryer during the drying cycle?
The team found the average air flow through a dryer is estimated to 150 ft3/m.
4) How much energy must be used to move the water from the liquid phase in the
clothes to the vapor phase in the already hot, humid outdoor air?
The team found the average attic air temperature estimated to be 95o F. in Figure 1 a
mass balance of water is able to be found:
𝑚𝑎 𝜔1 + 𝑚𝑤 = 𝑚𝑎 𝜔2
𝑚𝑤 = 𝑚𝑎 (𝜔2 − 𝜔1 )
An energy balance is also able to be found from this system:
𝑚𝑎 ℎ1 + 𝑄𝑖𝑛 + 𝑚𝑤 ℎ𝑤 = 𝑚𝑎 ℎ2
Substituting the mass balance into the energy balance gives:
𝑚𝑎 ℎ1 + 𝑄𝑖𝑛 + 𝑚𝑎 (𝜔2 − 𝜔1 )ℎ𝑤 = 𝑚𝑎 ℎ2
And solving for Qin:
𝑄𝑖𝑛 = 𝑚𝑎 [ℎ2 − ℎ𝑤 (𝜔2 − 𝜔1 ) − ℎ1 ]
Using these equations 𝜔1 can be found using 𝜔1 = 0.622𝜙1𝑝𝑠𝑎𝑡@80𝑜𝐹𝑃1 −
𝑝𝑠𝑎𝑡@80𝑜𝐹. Assuming the air outside has a temperature of 85o F and a relative humidity
of 70% the psychometric chart h2 and specific volume can be found.
The mass of air can be found by diving the volumetric flowrate by the time of a cycle
and then diving that by the specific volume.
Tap water can be used to find hw (Table A-4E @ 65o F).
𝑚
𝜔2 can be found using 𝜔2 = 𝜔1 + 𝑚𝑤 . Using a relative humidity of 90% for the exiting
𝑎
air and 𝜔2 , h2 can be found.
Q is found by plugging in each value as described above which comes out to 10085.9
BTU.
Figure 1: Simplified Dryer Diagram
5) If indoor, cooled, conditioned air is use as the source air to the dryer, outdoor
air will come into the home because the dryer pushes the humidified air outdoors
after it has been used to remove some water from the clothes being
dried. Assuming a reasonable coefficient of performance for the home air
conditioner, how much energy must be used in re-conditioning the outdoor air
pulled into the home from outdoors while drying the load of clothes?
Indoor air can be taken as 70o F at a relative humidity of 50% and 25 BTU/lbm air.
The mass of air and mass of water stay the same between Q4 and Q5. The main
difference is the air is run through a conditioning cycle first before being used in the
dryer. Using Figure 2 another mass balance is able to be found:
𝑚𝑎 𝜔1 = 𝑚𝑎 𝜔2 + 𝑚𝑤
𝑚𝑤 = 𝑚𝑎 (𝜔1 − 𝜔2 )
An energy balance is also able to be found from this system:
𝑚𝑎 ℎ1 = 𝑄𝐿 + 𝑚𝑤 ℎ𝑤 + 𝑚𝑎 ℎ2
Substituting the mass balance into the energy balance gives:
𝑚𝑎 ℎ1 = 𝑄𝐿 + 𝑚𝑎 (𝜔1 − 𝜔2 )ℎ𝑤 + 𝑚𝑎 ℎ2
And solving for Qin:
𝑄𝐿 = 𝑚𝑎 [ℎ1 − ℎ𝑤 (𝜔1 − 𝜔2 ) − ℎ2 ]
Using A4-E hw can be found using T2.
Figure 2: Simplified Airconditioning Diagram
6) With indoor air, how much energy must be used by the dryer to move water
from the liquid phase in the clothes to the vapor phase in the indoor, conditioned
air?
The calculation for this question is the same as the calculations for question #4. The
difference is that for this question we used the indoor air instead of the outdoor air. This
air can absorb more moisture due to a lower humidity however it is also cooler air which
means it must be heated up more to by used in the drying process. The result of our
calculations showed that the dryer would require 12,087 BTU of energy.
7) Results
We concluded that assuming you run the washer three times per week, and there are
about 12 weeks in the summer. You would save approximately 9.80$ per summer, put in
different terms, this would be about 1.09 Big Zax Snaks a year. It might be worth it but it
would take at least a couple of summers to recover the costs.