ASME B31.3 Hydrostatic Test Summary Sheet
Purpose: Verify the integrity and leak tightness of a piping system after fabrication or modification and before being
placed into service.
Test Type
Test Fluid
Test Pressure
Test
Temperature
Hold Duration
Acceptance
Criteria
Hydrostatic
Water or other
compatible
nonhazardous liquid
suitable for the system
materials.
1.5 × Design
Pressure × (ST/SD)
At least 10°F (5°C)
above MDMT to
prevent brittle
fracture.
Maintain pressure
long enough for
complete
inspection
(typically ≥ 10
minutes).
No visible leakage
through welds,
joints, or
pressure-containing
components.
Test Pressure Calculation:
PT = 1.5 × Pdesign × (ST / SD)
Where: PT = test pressure at highest point, ST = allowable stress at test temperature, SD = allowable stress at design
temperature.
Preparation Requirements:
• System complete and ready for testing (welds complete, blinds installed).
• Instruments, relief valves, and expansion joints removed or isolated.
• Provide vents for filling and drains for emptying.
Alternative Tests:
• Pneumatic test: 1.1 × design pressure (incremental pressurization required).
• Leak test (if hydro/pneumatic not practical): soap-bubble or halogen detection.
Record of Test:
System Name:
Design Pressure (psig):
Test Pressure (psig):
Test Medium:
Test Temperature (°F):
Date:
Inspector: