Article 220 ● Branch-Circuit, Feeder, and Service Calculations 220.83 Existing Dwelling Unit This section shall be permitted to be used to determine if the existing service or feeder is of sufficient capacity to serve additional loads. Where the dwelling unit is served by a 120/240-volt or 208Y/120-volt, 3-wire service, it shall be permissible to calculate the total load in accordance with 220.83(A) or (B). (A) Where Additional Air-Conditioning Equipment or Electric Space-Heating Equipment Is Not to Be Installed. The following percentages shall be used for existing and additional new loads. 220.83 (2) 1500 volt-amperes for each 2-wire, 20-ampere smallappliance branch circuit and each laundry branch circuit covered in 210.11(C)(1) and (C)(2) (3) The nameplate rating of the following: a. All appliances that are fastened in place, permanently connected, or located to be on a specific circuit b. Ranges, wall-mounted ovens, counter-mounted cooking units c. Clothes dryers that are not connected to the laundry branch circuit specified in (2) d. Water heaters Load (kVA) Percent of Load The optional methods described in 220.83(A) and (B) allow an additional load to be supplied by an existing service. First 8 kVA of load at Remainder of load at 100 40 Calculation Example Load calculations shall include the following: (1) General lighting and general-use receptacles at 33 voltamperes/m 2 or 3 volt-amperes/ft 2 as determined by 220.12 (2) 1500 volt-amperes for each 2-wire, 20-ampere smallappliance branch circuit and each laundry branch circuit covered in 210.11(C)(1) and (C)(2) (3) The nameplate rating of the following: a. All appliances that are fastened in place, permanently connected, or located to be on a specific circuit b. Ranges, wall-mounted ovens, counter-mounted cooking units c. Clothes dryers that are not connected to the laundry branch circuit specified in item (2) d. Water heaters (B) Where Additional Air-Conditioning Equipment or Electric Space-Heating Equipment Is to Be Installed. The following percentages shall be used for existing and additional new loads. The larger connected load of air-conditioning or space-heating, but not both, shall be used. Load Percent of Load Air-conditioning equipment Central electric space heating Less than four separately controlled spaceheating units First 8 kVA of all other loads Remainder of all other loads 100 100 100 100 40 Other loads shall include the following: (1) General lighting and general-use receptacles at 33 voltamperes/m 2 or 3 volt-amperes/ft 2 as determined by 220.12 National Electrical Code Handbook 2011 An existing dwelling unit is served by a 100-ampere service. An additional load of a single 5-kVA, 240-volt air-conditioning unit is to be installed. Because the existing load does not contain heating or air-conditioning equipment, the existing load is calculated according to 220.83(A). The load of the existing dwelling unit consists of the following: General lighting: 24 ft 40 ft = 960 ft2 VA per ft2 Small-appliance circuits: 3 1500 VA Laundry circuit at 1500 VA Electric range rated 10.5 kW Electric water heater rated 3.0 kW Total existing load 2,880 VA 4,500 VA 1,500 VA 10,500 VA 3,000 VA 22,380 VA Solution STEP 1. Following the requirements of 220.83(A), calculate the existing dwelling unit load before adding any equipment: First 8 kVA of load at 100% 8,000 VA Remainder of load at 40%: 22,380 VA 8,000 VA = 14,380 VA 40% 5,752 VA Total load 13,752 VA (without air-conditioning equipment) 13,752 VA 240 V = 57.3 A STEP 2. Prepare a list of the existing and new loads of the dwelling unit. General lighting: 24 ft 40 ft = 960 ft2 VA per ft2 Small-appliance circuits: 3 1500 VA Laundry circuit at 1500 VA Electric range rated 10.5 kW Electric water heater rated 3.0 kW Added air-conditioning equipment Total new load 2,880 VA 4,500 VA 1,500 VA 10,500 VA 3,000 VA 5,000 VA 27,380 VA 133