Civil Engineering Design – Project II
Group number:
Student ID
Signature
First name
Surname
Rough contribution
(%)
We certify that the attached assignment/project is our own work and that any material drawn from
other sources has been acknowledged. This work has not previously been submitted for assessment in
any other unit or course. Copyright in assignments remains our property. We grant permission to the
University to make copies of assignments for assessment, review and/or record keeping purposes. We
note that the University reserves the right to check our assignment for plagiarism. Should the
reproduction of all or part of an assignment be required by the University for any purpose other than
those mentioned above, appropriate authorisation will be sought from us on the relevant form.
Students are expected to use their own knowledge and work for completing their submissions to ensure
their effective learning. If any AI tool is used, in any shape or form, for answering the questions or
writing the report, then it should be transparently acknowledged in the beginning of the report. It must
be clearly explained for which section(s) or question(s) AI tools have been used, to what extent, and
what AI tool was used. The report will then be graded based on its merits considering the use of AI in
it. The utilisation of AI tools without an acknowledgement, is likely to constitute an academic
misconduct.
ENS5190
1
ENS5190 Civil Engineering Design
PROJECT II (25% of the assessment of the unit)
Due: Wed May 14, 23:59
This is an online group submission through Turnitin page provided. Members need to indicate
a rough estimate of their contribution to the submission in percent (%). The group has the right
to deduct up to 100% of the contribution from those who join the group after the deadline,
and/or based on an individual’s relative contribution. I leave this to individual groups to decide.
Students are expected to use their own knowledge and work for completing their submissions
to ensure their effective learning.
If any AI tool is used, in any shape or form, for answering the questions or writing the report,
it must transparently be acknowledged in the beginning of the report. It must be clearly
explained for which section(s) or question(s) AI tools have been used, to what extent, and what
AI tool was used. The report will then be graded based on its merits considering the use of AI
in it. The utilisation of AI tools without an acknowledgement may constitute an academic
misconduct.
There may be a VIVA to reassess the understanding of individual group members after the
submission and the effectiveness of the group work. The assessment during VIVA will override
the original mark given to individuals/whole group. All group members are expected to be fully
conversant with their group submissions – with everything included in their submission. The
details of your calculations must be attached as an appendix to your submission.
ENS5190
2
Part I: Schematic Design (Preliminary Design) - (8 Marks out of 100 Total
Marks of the unit)
Great work on the Concept Design! The architects really liked the work you did. The Architect took
away the Concept Design, thought it through and now have proposed a column grid. Now this is where
the architect is looking to finetune the design. At the same time, this is where it gets really challenging
for us as engineers. This is the time where architects will look to stretch the boundaries a bit, and ask
us to provide solutions to meet their complex demands – but, this is our moment to shine! By applying
our engineering excellence, we can give our client what they need and help the architect achieve their
vision.
The architect has requested preliminary design options for both the roof and suspended floor.
Level 3 Lecture Theatre:
•
The client has said that they want a very large column free lecture theatre on Level 3. I can see
their logic – wouldn’t you just hate it, if you were in a lecture theatre and there was a column
right in front of you obstructing your view? Assuming we delete the columns on Grid B and C,
on Axes 4 and 5, you are to provide a preliminary design for both a truss and portal frame
option to support the roof. Only indicative depths of members/trusses are required. Comment
on the viability of these options and how any issues can be resolved. Assume a tributary width
of 6.0 m between frames (one page).
Ground Floor E-Gaming Space
•
ENS5190
The Client wants a column free space on the ground floor so they can create an e-gaming room.
Luckily the architect has allowed us to introduce an intermediate column (refer to elevation
below).
3
In the meantime, we are going to assume that you have come up with the below information for your
design:
Design Loading:
Floor Level
Super imposed dead load
Imposed load
Roof
1.0 kPa (Cladding);
0.15 kPa (Services);
0.35 kPa (Solar Panels)
0.25 kPa
Level 3
1.0 kPa (Access Floor);
1.0 kPa (Partitions & Services)
0.5 kPa (Ceiling)
5.0 kPa
Level 2
1.0 kPa (Access Floor);
1.0 kPa (Partitions & Services)
0.5 kPa (Ceiling)
5.0 kPa
Level 1
1.0 kPa (Access Floor);
1.0 kPa (Partitions & Services)
0.5 kPa (Ceiling)
5.0 kPa
Ground Floor
1.5 kPa
5.0 kPa
Location
Pressure
Windward Wall
+1.0 kPa
Leeward Wall
-0.6 kPa
Roof Pressure
1
Side Wall pressure
-1.1 kPa
2
Internal Pressure
-0.8 kPa
Ignore for this exercise
1
For the purposes of this exercise (and for simplicity) assume constant roof pressure regardless of whether you are considering
Upwind Slope or Downwind Slope.
2
For the purposes of this exercise (and for simplicity) assume constant side wall pressure ignoring the length effects on the
walls.
Seismic Loading Parameters
Super imposed dead load
Annual probability of exceedance
1/1000
Hazard Factor (Z)
Perth
Soil Type
Shallow Soil
EDC
III
Ductility Factor
2
ENS5190
4
You are to provide a preliminary design for a Post Tensioned Transfer beam. Assume the beam is 1000
mm deep x 1200 mm wide. You are allowed to design it either as a simply supported beam (spanning
13.5 m), or a 2-span continuous beam, taking the benefit of the continuity – as a competent engineer, I
will leave it to you to decide which option is better for this beam i.e. simply supported vs continuous
(support your option with some simple manual analyses and perhaps providing SFD and BMD – one
page).
It’s great that you have done the analysis for both options. We presented that to the architect.
Unfortunately, the architect advised there is not enough ceiling space to accommodate a deep beam
between grids C and D, i.e. they want to maximise their floor-to-floor height, so they want us to keep
the beam depth minimum. Moving forward, you are going to go ahead with the simply supported option,
for which you are to provide the below:
a. A suitable prestress force and thus number of 12.7 mm diameter ordinary strands to balance
100% of the total dead load acting on the beam. Assume a strand yield stress of 0.82fpb. Consider
any relevant losses and if needed, make reasonable assumptions. Adopt 4 tendons with 5 strands
each.
b. Check the stresses at transfer are within code limits.
c. Estimate the short and long term (after 30 years) mid-span deflection under G + 0.7Q.
d. Estimate the ultimate flexural strength of the below transfer beam.
For the above, assume beams are spaced at 6.0 m centres with a 150 mm thick slab spanning
between beams. Assume a parabolic tendon profile with a bottom cover of 150 mm at mid-span to
the centreline of tendons, and dead/live ends located at mid height. Concrete strength is 40 MPa at
maturity, and 22 MPa at transfer. The material properties are: Ec = 33 GPa, fc’ = 40 MPa, Ep = 205
GPa
Note: Calculations/justification is required for the preliminary phase.
ENS5190
5
Part II: Refined design (12 Marks out of 100 Total Marks of the unit)
Schematic Design is always quite hard! So well done on finishing it off. You are doing great.
Now, we need to finish everything else off!
Before we go too far, the client rang me 5 minutes ago and said the table you prepared in concept design
comparing the various materials has really got them thinking (great work being able to influence the
client like that). They are really concerned about the environment and climate change. So, they are
thinking of looking at a timber option.
1. Timber Design
Can you quickly design a typical bay using Glulam timber beam and Glulam columns? Below is what
they want:
ENS5190
6
Can you check if the following works?
• Glulam GL 13 Beam = 1000 mm deep x 450 mm wide
• Glulam GL 13 Column = 450 mm wide x 450 mm deep
As part of the analysis, check the following:
1) ULS Capacity (Bending, Shear for the beams; Axial for the column)
2) SLS Capacity (Short term and long-term deflections)
Assumptions:
•
•
•
Assume a 220 CLT floor spanning onto this beam with a tributary width of 6.0 m.
Assume the density of the CLT is 450 kg/m3.
Assume single span simply supported beams.
2. Lateral Stability - EQ
Now, let’s get into details. Let’s start designing the following:
Define the most three significant mode shapes of the structure in both x and y directions.
Evaluate the corresponding base shear of the structure and the design seismic load according to
the AS1170.4 based on the fundamental natural frequency for each direction. Use the concrete
lift core, as well as the braced bays as part of your lateral stability system. The client has already
told us where we can put the braces. I hope you remember it!
Assumptions:
1) For this analysis, ignore the transfer structure in the e-gaming room, and the roof column free
zone – you can assume the columns go all the way from roof to the foundation. Assume a fully
pinned structure.
2) Assume the structure is all timber, i.e. columns are all 450x450 mm; beams are all 1000x450
mm.
3) For the roof, assume the rafters are 650 mm deep x 450 mm wide GL13, with 120 CLT slab.
4) Use both the concrete cores and the braced bays as part of the stability system. You may also
use K braces as per below snapshot.
3. Lateral Stability - WIND
a. Horizontal load resisting system: This is to include a drawing showing wall bracing to transfer
the wind load to ground (both North-South and East-West wind directions to be considered).
You are to assume a fully pinned timber structure and provide outputs of the most critical
member of each type. You are then to design one of the braces for the most critical bracing
load.
b. Provide calculations showing all working. SpaceGass is to be used for the analysis with all
required output clearly shown (only for the critical members). All the load combinations used
in the model to be provided in your solutions – make a final comparison with what you
submitted in Project I and correct if needed. A 3D screenshot of the model is also to be included
in the report showing the most critical load combination used for the bracing member design.
c. You are required to state all the assumptions you make and provide all calculations to justify
your design.
Assumptions: The same as Item 2 above.
ENS5190
7
ENS5190
8
ENS5190
9
Part III: Construction Phase (5 Marks out of 100 Total Marks of the unit)
Great work on sending those drawings out for construction. The client is happy, and so is the architect.
Now your project is in construction. Well done!
This morning, I received a phone call from site – it was the contractor. As part of their construction
methodology, the contractor wants to stack construction material on our floor structure. The contractor
has advised me they are planning to load the structure with pallets of construction materials – they
weigh 2000 kg, and the floor plan each takes up is approximately 1.5 m x 1.5 m.
What should we tell them? Please give reasoning.
HINT: Think, loading criteria in the brief vs pressure loading applied here.
ENS5190
10