Public Courses In-House Courses Operator Training Benefits of Having Side Water-Draw in a Condensate Stabilizer Column – Part 1 This tip will investigate the benefits of having a water-draw in a condensate stabilizer. It will use a commercial simulation software to simulate the performance of an operating stabilizer. In order to take into account the non-ideality of water, the tip will perform three-phase (vapor, liquid hydrocarbon, and aqueous phases) Like calculations on the trays with excessive water rates. Specifically, it will study the impact of feed water rate in the raw condensate stream on the reboiler and condenser duties. It will also study water removal by waterdraw pan, and the optimum location of water-draw tray in the column. For a case study the tip will determine the optimum location of water-Draw tray by maximizing water removal from water-draw tray and minimizing the reboiler and condenser duties. 0 If the vapor – liquid equilibrium conditions in the distillation tower allow the water entering the column with the feed to leave in either the bottom product or in the overhead distillate product, then no special provisions are needed to remove the water from the fractionator. A key exception here is the probability of free water accompanying the feed stream due a malfunctioning upstream three-phase feed separator. If the distillate product is a liquid and the water condenses along with the distillate and reflux streams then the overhead accumulator can be configured as a three-phase separator. A more difficult situation exists if the water condenses within the tower because the overhead temperature is too cool and the bottoms temperature is too hot to allow the water to leave in the product streams. The most common example of this condition is found in the condensate stabilizer. Liquid water build-up can reduce capacity and, depending on the fluid composition, promote corrosion. Eventually the water build-up will cause the tower to flood and a major disruption in tower operation results as the water leaves the column. Once the water has left the column, operation will return to normal until the cycle repeats and the water build-up once again produces a flooding condition. The time between cycles can be anywhere from hours to weeks depending on the amount of water entering the stabilizer. One solution to the water build-up condition is to provide a water draw pan on the trays where liquid water is expected to condense. Figure 1 [1] is an example of a water draw for a tray-distillation column. The water draw pan is not sized to provide a good separation between water and hydrocarbon liquid so the fluid leaving the column is routed to an adequately sized liquid-liquid separator where the water is removed for further processing and the hydrocarbon liquid is routed back to the distillation column [2]. Figure 1. Water Draw Tray Arrangement [1] Case Study Table 1 presents the compositions (mol %) of a raw condensate mixture studied. This table also presents the required heavy end properties (Molecular Weight, Specific Gravity, and Volume Average Boiling Point) and the conditions of the feed stream. Search English TOTM Home Spanish TOTM Home Archives August 2022 July 2022 June 2022 March 2022 February 2022 September 2021 August 2021 July 2021 May 2021 April 2021 March 2021 February 2021 January 2021 December 2020 November 2020 October 2020 September 2020 August 2020 July 2020 June 2020 May 2020 April 2020 March 2020 February 2020 January 2020 December 2019 November 2019 October 2019 September 2019 August 2019 July 2019 June 2019 May 2019 April 2019 March 2019 February 2019 January 2019 December 2018 November 2018 October 2018 September 2018 August 2018 July 2018 June 2018 May 2018 April 2018 March 2018 February 2018 January 2018 December 2017 November 2017 October 2017 September 2017 August 2017 July 2017 Figure 2 presents a simplified process flow diagram for the case study. The tip utilized the front mixer to vary the feed water rate for the simulation purpose only. The use of the heat exchanger (HEX) will lower the reboiler and condenser duties. Table 2 presents the stabilizer column specifications. Note the difference between water draw from within the column and water drain from the V-4 reflux drum. June 2017 May 2017 April 2017 March 2017 February 2017 January 2017 December 2016 November 2016 October 2016 September 2016 August 2016 July 2016 June 2016 May 2016 April 2016 March 2016 February 2016 January 2016 December 2015 November 2015 October 2015 September 2015 August 2015 July 2015 June 2015 May 2015 April 2015 March 2015 February 2015 January 2015 December 2014 November 2014 October 2014 September 2014 August 2014 Figure 2. A simplified stabilizer column with side water-draw July 2014 June 2014 Based on the information in Tables 1 and 2, and the process flow diagram of Figure 2, the tip performed simulation using the Soave-Redlich-Kwong (SRK) equation of state [3] in ProMax [4] software. May 2014 April 2014 March 2014 February 2014 January 2014 December 2013 November 2013 October 2013 September 2013 August 2013 July 2013 June 2013 May 2013 April 2013 March 2013 February 2013 January 2013 Simulation Results: Figure 3 present the simulation results for the base case without side water-draw. The total water rate on the x-axis represents the sum of water rates in the vapor, light liquid (mostly hydrocarbons), and heavy liquid (mostly water) phases at any given tray in the column. The feed water range is from 940 to 1500 lbmole/d (427 to 1500 kmol/d). If the feed water is less than 940 lbmole (427 kmol/d) no heavy liquid (aqueous) phase is formed inside the column and water side draw rate will be zero. Figure 3 indicates if the feed water rate increases above 1200 lbmole/d (545 kmol/d), the maximum total water rate location shifts from tray 11 down to 18. In an actual plant a free water knockout drum (three-phase separator) ahead of the stabilizer removes the excess water to minimize the heating requirement. The feed water rate above 1200 lbmole/d (545 kmol/d) to the stabilizer column is unrealistic and shown here only for demonstration purposes. In addition to the base case, the tip simulated two cases with the side water-draw located at tray number 7 or 8. Table 3 presents the summary of simulation results for the base case and the two cases with side water-draw. For the base case without the water draw, at higher feed water rate some of the water leaves with stabilized condensate (C5+). December 2012 November 2012 October 2012 September 2012 August 2012 July 2012 June 2012 May 2012 April 2012 March 2012 February 2012 January 2012 December 2011 November 2011 October 2011 September 2011 August 2011 July 2011 June 2011 May 2011 April 2011 March 2011 February 2011 January 2011 December 2010 November 2010 October 2010 September 2010 August 2010 Figure 3. Total water molar rate profile in the stabilizer column without side water-draw as a function water rate in the feed July 2010 June 2010 May 2010 April 2010 March 2010 February 2010 January 2010 December 2009 November 2009 October 2009 September 2009 August 2009 July 2009 June 2009 May 2009 April 2009 March 2009 February 2009 January 2009 December 2008 November 2008 October 2008 September 2008 August 2008 July 2008 June 2008 May 2008 April 2008 March 2008 February 2008 January 2008 December 2007 November 2007 October 2007 September 2007 August 2007 July 2007 June 2007 May 2007 April 2007 March 2007 February 2007 January 2007 December 2006 Figure 4a indicates that the presence of side water-draw at tray 7 shifts the maximum total water rate from tray 10 (Figure 3) to 6 for lower feed water rates and from tray 18 (Figure 3) to 10 for higher feed water rates, respectively. Figures 4a and 4b also indicate that the side water-draw at tray 7 removes water effectively for low feed water rates. As shown in Table 3, at higher feed water rate, the reboiler and condenser duties decrease considerably compared to the base case. Table 3 also indicates that the HEX (feed-bottoms exchanger) duty remains the same for all three cases because there was no material change in its flows and temperatures. November 2006 October 2006 September 2006 August 2006 July 2006 June 2006 May 2006 April 2006 March 2006 February 2006 January 2006 December 2005 November 2005 October 2005 September 2005 August 2005 July 2005 June 2005 Complete Archives Figure 4a. Total water molar rate profile in the stabilizer column with side water-draw at tray 7 as a function water rate in the feed (full range) Topics Gas Processing Mechanical Pipeline Process Facilities Process Safety Refining Reliability Engineering Supply Chain Management Uncategorized Water and Corrosion Meta Log in Entries feed Comments feed WordPress.org Figure 4b. Total water molar rate profile in the stabilizer column with side water-draw at tray 7 as a function water rate in the feed (lower range) In order to maximize water removal for higher feed water rate, the tip moved the side water-draw from tray 7 to 8. Table 3 clearly indicates that water-draw at tray 7 give higher water recovery percent for lower feed water rates up to 1200 lbmole/d (545 kmol/d) and water-draw at tray 8 give higher water recovery for higher feed water rate. Figure 5 presents the total water flow rate profile within the column with side water-draw at tray 8 as a function of feed water rate. This figure demonstrates the effectiveness of the side water-draw. Figure 5. Total water molar rate profile in the stabilizer column with side water-draw at tray 8 as a function water rate in the feed (higher range) Figure 6 presents the water recovery percent of the feed water as a function of the feed water rate for the three cases considered. For the base case without the side water-draw some of the excess water leaves the column with the C5+ stream. For this case, the excess feed water rate also increases the reboiler and condenser duties. These increases are indicative of the increased internal vapor traffic necessary to carry the water vapor out of the tower. Like Figures 7 and 8, Figure 6 also shows the effectiveness of side water-draw and the impact of side water-draw location. Figure 6. Water recovery (%) as a function of the feed water rate Figure 7. Reboiler duty as a function of the feed water rate Figure 8. Condenser duty as a function of the feed water rate Conclusions: The simulation results for the three case studies demonstrated the effectiveness of side water-draw and the importance of water draw location in the column. Based on the results obtained, this tip presents the following observations. 1. Commercial simulators using special convergence algorithms and thermodynamic packages are able to predict the presence of two liquid phases within distillation columns. The calculations are difficult to converge and it is difficult to predict the exact location of the liquid water phase. Therefore, it is advisable to install liquid water draw trays in two or three locations around the tray predicted by the simulator. 2. Install properly sized free water knockout (three phase separator) separator to minimize the feed water rate to the stabilizer column. This assures easier/less troublesome operation with lower utility (reboiler and condenser duties) cost. 3. Side water-draw removes water/aqueous phase effectively and reduces the reboiler duty and condenser duty. 4. The optimum location of the side-draw depends on the feed water rate. 5. This tip determined the optimum location of water-draw try by maximizing liquid water removal and minimizing the reboiler and condenser duties. 6. The side water-draw has no impact on the heat exchanger upstream of the stabilizer column. 7. As shown In Table 3, the topmost condenser duties for the three cases are 14.67, 9.00 and 8.49 MMBtu/hr (4.3, 2.64, and 2.49 MW), respectively. Since fundamentally at a fixed overhead product rate, condenser pressure and temperature the water vapor content is fixed. Thus a greater total overhead flow is needed to transport water as vapor out of the column to be condensed into the reflux drum and removed. Greater total overhead means larger condenser duty. It also requires a commensurately larger reboiler duty. With a lot of water entering the tower the condenser and reboiler might not be big enough to do the job. Part 2 (follow-up of this tip) will investigate the variation of water partial pressure along the column and the changes in operating variables. To learn more about similar cases and how to minimize operational problems, we suggest attending our G4 (Gas Conditioning and Processing), G5 (Advanced Applications in Gas Processing), P81 (CO2 Surface Facilities), and PF4 (Oil Production and Processing Facilities), courses. PetroSkills offers consulting expertise on this subject and many others. For more information about these services, visit our website at http://petroskills.com/consulting, or email us at consulting@PetroSkills.com. By: Dr. Mahmood Moshfeghian Reference: 1. Campbell, J.M., Gas Conditioning and Processing, Volume 2: The Equipment Modules, 9th Edition, 2nd Printing, Editors Hubbard, R. and Snow–McGregor, K., Campbell Petroleum Series, Norman, Oklahoma, 2014. 2. Lieberman, N. P. ; “Troubleshooting Process Operation – 13,” Oil and Gas Journal, p. 100– 102, Feb 16, 1981. 3. Soave, G., Chem. Eng. Sci. 27, 1197-1203, 1972. 4. ProMax 3.2, Bryan Research and Engineering, Inc, Bryan, Texas, 2016. 0 Like Did you enjoy this post? Do you have a question? Leave us a Comment below! Want to read more articles like this? Subscribe to our RSS Feed or visit the Tip of the Month Archives for past articles. Posted on April 6, 2016 at 9:35 am 2 comments Categories: Gas Processing, Process Facilities Recieve new post updates: Entries (RSS) Recieve follow up comments updates: RSS 2.0 Written by admin View all posts by: admin « Previous post Next Post » 2 responses to “Benefits of Having Side Water-Draw in a Condensate Stabilizer Column – Part 1” 1. Benefits of Having Side Water-Draw in a Condensate Stabilizer Column – Part 2 | Campbell Tip of the Month says: May 2, 2016 at 10:59 am […] tip is the follow up to the April 2016 Tip of the Month (TOTM) which investigated the benefits of having a waterdraw in a condensate stabilizer column. It will […] 2. Ivan Wilson says: May 3, 2016 at 2:06 am What are splt-100 specifications? is it like Hysys splitter? Dr. Mahmood Moshfeghian says: May 25, 2016 at 4:00 pm Ivan: Yes, Split-100 is a stream splitter. 76.5 % of stream 104 goes to stream 105 and the rest goes to stream 8. 3. Beneficios de Tener una Corriente Lateral de Extracción de Agua en un Columna Estabilizadora de Condensados – Parte – 2 | Campbell Tip of the Month – Spanish says: May 5, 2016 at 4:43 pm […] previo será un seguimiento del previo de Abril 2016, el cual investigó los beneficios de tener una corriente lateral en una columna estabilizadora. Se […] 4. Despojo de Agua en una Columna Estabilizadora Sin-Reflujo – Parte 3 | Campbell Tip of the Month – Spanish says: January 12, 2017 at 2:07 pm […] M., April 2016 tip of the month, PetroSkills | John M. Campbell, […] Training Helpful Links Company Information Public Courses In-House Courses Operator Training Online Course Previews HGPA Educational Sessions Course Schedule Oil and Gas Training Facilities Engineering Training Liquefied Natural Gas Training Petroleum Engineering Courses Request Information Consulting Services Tip of the Month Campbell Forums Conversion Tool John M. Campbell & Co. Books GCAP Software GCAP Mobile Continuing Education Credits Follow us on Twitter Contact Us About Us Job Postings Testimonials Download Catalog (PDF) Request Catalog Instructor Bios FAQ Links Kindle Disclaimer © John M. Campbell & Co. 1215 Crossroads Blvd. Suite 230 Norman, OK. 73072
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )