Color profile: Generic CMYK printer profile Composite Default screen ACCESSIBILITY TABLE 1109.12.2 ACCESSIBLE CHECK-OUT AISLES MINIMUM NUMBER OF ACCESSIBLE CHECK-OUT AISLES OF EACH FUNCTION 1 to 4 1 5 to 8 2 9 to 15 3 Over 15 3, plus 20% of additional aisles 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Exception: Accessible windows are not required in bathrooms or kitchens. 1109.14 Recreational and sports facilities. Recreational and sports facilities shall be provided with accessible features in accordance with Sections 1109.14.1 through 1109.14.4. 1109.14.1 Facilities serving a single building. In Group R-2 and R-3 occupancies where recreational facilities are provided serving a single building containing Type A units or Type B units, 25 percent, but not less than one, of each type of recreational facility shall be accessible. Every recreational facility of each type on a site shall be considered to determine the total number of each type that is required to be accessible. 1109.12.4 Food service lines. Food service lines shall be accessible. Where self-service shelves are provided, at least 50 percent, but not less than one, of each type provided shall be accessible. 1109.12.5 Queue and waiting lines. Queue and waiting lines servicing accessible counters or check-out aisles shall be accessible. 1109.14.2 Facilities serving multiple buildings. In Group R-2 and R-3 occupancies on a single site where multiple buildings containing Type A units or Type B units are served by recreational facilities, 25 percent, but not less than one, of each type of recreational facility serving each building shall be accessible. The total number of each type of recreational facility that is required to be accessible shall be determined by considering every recreational facility of each type serving each building on the site. 1109.13 Controls, operating mechanisms and hardware. Controls, operating mechanisms and hardware intended for operation by the occupant, including switches that control lighting and ventilation and electrical convenience outlets, in accessible spaces, along accessible routes or as parts of accessible elements shall be accessible. Exceptions: 1109.14.3 Other occupancies. All recreational and sports facilities not falling within the purview of Section 1109.14.1 or 1109.14.2 shall be accessible. 1. Operable parts that are intended for use only by service or maintenance personnel shall not be required to be accessible. 1109.14.4 Recreational and sports facilities exceptions. Recreational and sports facilities required to be accessible shall be exempt from this chapter to the extent specified in this section. 2. Electrical or communication receptacles serving a dedicated use shall not be required to be accessible. 3. Where two or more outlets are provided in a kitchen above a length of counter top that is uninterrupted by a sink or appliance, one outlet shall not be required to be accessible. 1109.14.4.1 Bowling lanes. An accessible route shall be provided to at least 5 percent, but no less than one, of each type of bowling lane. 4. Floor electrical receptacles shall not be required to be accessible. 1109.14.4.2 Court sports. In court sports, at least one accessible route shall directly connect both sides of the court. 5. HVAC diffusers shall not be required to be accessible. 6. Except for light switches, where redundant controls are provided for a single element, one control in each space shall not be required to be accessible. 1109.14.4.3 Raised boxing or wrestling rings. Raised boxing or wrestling rings are not required to be accessible. 7. Access doors or gates in barrier walls and fences protecting pools, spas and hot tubs shall be permitted to have operable parts of the release of latch on self-latching devices at 54 inches (1370 mm) maximum and 48 inches minimum above the finished floor or ground, provided the self-latching devices are not also self-locking devices, operated by means of a key, electronic opener, or integral combination lock. 1109.14.4.4 Raised refereeing, judging and scoring areas. Raised structures used solely for refereeing, judging or scoring a sport are not required to be accessible. 1109.14.4.5 Raised diving boards and diving platforms. Raised diving boards and diving platforms are not required to be accessible. 2006 INTERNATIONAL BUILDING CODE® 246 11_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\11_ibc_2006.vp Thursday, December 08, 2005 9:37:16 AM 12 ➡ TOTAL CHECK-OUT AISLES OF EACH FUNCTION 1109.13.1 Operable window. Where operable windows are provided in rooms that are required to be accessible in accordance with Sections 1107.5.1.1, 1107.5.2.1, 1107.5.3.1, 1107.5.4, 1107.6.1.1, 1107.6.2.2.1 and 1107.6.4.1, at least one window in each room shall be accessible and each required operable window shall be accessible. Color profile: Generic CMYK printer profile Composite Default screen ACCESSIBILITY SECTION 1110 SIGNAGE 1110.1 Signs. Required accessible elements shall be identified by the International Symbol of Accessibility at the following locations: 1. Accessible parking spaces required by Section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessible areas of refuge required by Section 1007.6. 4. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location. 5. Accessible entrances where not all entrances are accessible. 6. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 7. Unisex toilet and bathing rooms. 8. Accessible dressing, fitting and locker rooms where not all such rooms are accessible. 1110.2 Directional signage. Directional signage indicating the route to the nearest like accessible element shall be provided at the following locations. These directional signs shall include the International Symbol of Accessibility: 1. Inaccessible building entrances. 2. Inaccessible public toilets and bathing facilities. 3. Elevators not serving an accessible route. 4. At each separate-sex toilet and bathing room indicating the location of the nearest unisex toilet or bathing room where provided in accordance with Section 1109.2.1. 5. At exits and elevators serving a required accessible space, but not providing an approved accessible means of egress, signage shall be provided in accordance with Section 1007.7. 1110.3 Other signs. Signage indicating special accessibility provisions shall be provided as shown: 1. Each assembly area required to comply with Section 1108.2.6 shall provide a sign notifying patrons of the availability of assistive listening systems. Exception: Where ticket offices or windows are provided, signs are not required at each assembly area provided that signs are displayed at each ticket office or window informing patrons of the availability of assistive listening systems. 2. At each door to an egress stairway, exit passageway and exit discharge, signage shall be provided in accordance with Section 1011.3. 3. At areas of refuge, signage shall be provided in accordance with Sections 1007.6.3 through 1007.6.5. 4. At areas for assisted rescue, signage shall be provided in accordance with Section 1007.8.3. 2006 INTERNATIONAL BUILDING CODE® 11_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\11_ibc_2006.vp Thursday, December 08, 2005 9:37:16 AM 247 13 Color profile: Generic CMYK printer profile Composite Default screen 2006 INTERNATIONAL BUILDING CODE® 248 11_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\11_ibc_2006.vp Thursday, December 08, 2005 9:37:16 AM 14 Color profile: Generic CMYK printer profile Composite Default screen CHAPTER 12 INTERIOR ENVIRONMENT 1203.2.1 Openings into attic. Exterior openings into the attic space of any building intended for human occupancy shall be covered with corrosion-resistant wire cloth screening, hardware cloth, perforated vinyl or similar material that will prevent the entry of birds, squirrels, rodents, snakes and other similar creatures. The openings therein shall be a minimum of 1/8 inch (3.2 mm) and shall not exceed 1/4 inch (6.4 mm). Where combustion air is obtained from an attic area, it shall be in accordance with Chapter 7 of the International Mechanical Code. SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions, surrounding materials and rodent proofing associated with the interior spaces of buildings. SECTION 1202 DEFINITIONS 1203.3 Under-floor ventilation. The space between the bottom of the floor joists and the earth under any building except spaces occupied by a basement or cellar shall be provided with ventilation openings through foundation walls or exterior walls. Such openings shall be placed so as to provide cross ventilation of the under-floor space. 1202.1 General. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. SUNROOM ADDITION. A one-story addition added to an existing building with a glazing area in excess of 40 percent of the gross area of the structure’s exterior walls and roof. THERMAL ISOLATION. A separation of conditioned spaces, between a sunroom addition and a dwelling unit, consisting of existing or new wall(s), doors and/or windows. 1203.3.1 Openings for under-floor ventilation. The minimum net area of ventilation openings shall not be less than 1 square foot for each 150 square feet (0.67 m2 for each 100 m2) of crawl-space area. Ventilation openings shall be covered for their height and width with any of the following materials, provided that the least dimension of the covering shall not exceed 1/4 inch (6 mm): SECTION 1203 VENTILATION 1. Perforated sheet metal plates not less than 0.070 inch (1.8 mm) thick. 1203.1 General. Buildings shall be provided with natural ventilation in accordance with Section 1203.4, or mechanical ventilation in accordance with the International Mechanical Code. 2. Expanded sheet metal plates not less than 0.047 inch (1.2 mm) thick. 3. Cast-iron grilles or gratings. 1203.2 Attic spaces. Enclosed attics and enclosed rafter spaces formed where ceilings are applied directly to the underside of roof framing members shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain and snow. Blocking and bridging shall be arranged so as not to interfere with the movement of air. A minimum of 1 inch (25 mm) of airspace shall be provided between the insulation and the roof sheathing. The net free ventilating area shall not be less than 1/150 of the area of the space ventilated, with 50 percent of the required ventilating area provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet (914 mm) above eave or cornice vents with the balance of the required ventilation provided by eave or cornice vents. Exception: The minimum required net free ventilating area shall be 1/300 of the area of the space ventilated, provided a vapor retarder having a transmission rate not exceeding 1 perm in accordance with ASTM E 96 is installed on the warm side of the attic insulation and provided 50 percent of the required ventilating area provided by ventilators located in the upper portion of the space to be ventilated at least 3 feet (914 mm) above eave or cornice vents, with the balance of the required ventilation provided by eave or cornice vents. 2006 INTERNATIONAL BUILDING CODE® 12_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\12_ibc_2006.vp Wednesday, December 07, 2005 10:55:19 AM 4. Extruded load-bearing vents. 5. Hardware cloth of 0.035 inch (0.89 mm) wire or heavier. 6. Corrosion-resistant wire mesh, with the least dimension not exceeding 1/8 inch (3.2 mm). 1203.3.2 Exceptions. The following are exceptions to Sections 1203.3 and 1203.3.1: 1. Where warranted by climatic conditions, ventilation openings to the outdoors are not required if ventilation openings to the interior are provided. 2. The total area of ventilation openings is permitted to be reduced to 1/1,500 of the under-floor area where the ground surface is treated with an approved vapor retarder material and the required openings are placed so as to provide cross ventilation of the space. The installation of operable louvers shall not be prohibited. 3. Ventilation openings are not required where continuously operated mechanical ventilation is provided at a rate of 1.0 cubic foot per minute (cfm) for each 50 square feet (1.02 L/s for each 10 m2) of crawl-space 249 1 Color profile: Generic CMYK printer profile Composite Default screen INTERIOR ENVIRONMENT floor area and the ground surface is covered with an approved vapor retarder. 4. Ventilation openings are not required when the ground surface is covered with an approved vapor retarder, the perimeter walls are insulated and the space is conditioned in accordance with the International Energy Conservation Code. 5. For buildings in flood hazard areas as established in Section 1612.3, the openings for under-floor ventilation shall be deemed as meeting the flood opening requirements of ASCE 24 provided that the ventilation openings are designed and installed in accordance with ASCE 24. 1203.4 Natural ventilation. Natural ventilation of an occupied space shall be through windows, doors, louvers or other openings to the outdoors. The operating mechanism for such openings shall be provided with ready access so that the openings are readily controllable by the building occupants. 1203.5 Other ventilation and exhaust systems. Ventilation and exhaust systems for occupancies and operations involving flammable or combustible hazards or other contaminant sources as covered in the International Mechanical Code or the International Fire Code shall be provided as required by both codes. SECTION 1204 TEMPERATURE CONTROL 1204.1 Equipment and systems. Interior spaces intended for human occupancy shall be provided with active or passive space-heating systems capable of maintaining a minimum indoor temperature of 68°F (20°C) at a point 3 feet (914 mm) above the floor on the design heating day. Exception: Interior spaces where the primary purpose is not associated with human comfort. 1203.4.1 Ventilation area required. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. SECTION 1205 LIGHTING 1203.4.1.1 Adjoining spaces. Where rooms and spaces without openings to the outdoors are ventilated through an adjoining room, the opening to the adjoining room shall be unobstructed and shall have an area of not less than 8 percent of the floor area of the interior room or space, but not less than 25 square feet (2.3 m2). The minimum openable area to the outdoors shall be based on the total floor area being ventilated. 1205.1 General. Every space intended for human occupancy shall be provided with natural light by means of exterior glazed openings in accordance with Section 1205.2 or shall be provided with artificial light in accordance with Section 1205.3. Exterior glazed openings shall open directly onto a public way or onto a yard or court in accordance with Section 1206. Exception: Exterior openings required for ventilation shall be permitted to open into a thermally isolated sunroom addition or patio cover provided that the openable area between the sunroom addition or patio cover and the interior room shall have an area of not less than 8 percent of the floor area of the interior room or space, but not less than 20 square feet (1.86 m2). The minimum openable area to the outdoors shall be based on the total floor area being ventilated. 1205.2.1 Adjoining spaces. For the purpose of natural lighting, any room is permitted to be considered as a portion of an adjoining room where one-half of the area of the common wall is open and unobstructed and provides an opening of not less than one-tenth of the floor area of the interior room or 25 square feet (2.32 m2), whichever is greater. 1205.2 Natural light. The minimum net glazed area shall not be less than 8 percent of the floor area of the room served. Exception: Openings required for natural light shall be permitted to open into a thermally isolated sunroom addition or patio cover where the common wall provides a glazed area of not less than one-tenth of the floor area of the interior room or 20 square feet (1.86 m2), whichever is greater. 1203.4.1.2 Openings below grade. Where openings below grade provide required natural ventilation, the outside horizontal clear space measured perpendicular to the opening shall be one and one-half times the depth of the opening. The depth of the opening shall be measured from the average adjoining ground level to the bottom of the opening. 1205.2.2 Exterior openings. Exterior openings required by Section 1205.2 for natural light shall open directly onto a public way, yard or court, as set forth in Section 1206. Exceptions: 1203.4.2 Contaminants exhausted. Contaminant sources in naturally ventilated spaces shall be removed in accordance with the International Mechanical Code and the International Fire Code. 1. Required exterior openings are permitted to open into a roofed porch where the porch: 1.1. Abuts a public way, yard or court. 1203.4.2.1 Bathrooms. Rooms containing bathtubs, showers, spas and similar bathing fixtures shall be mechanically ventilated in accordance with the International Mechanical Code. 1.2. Has a ceiling height of not less than 7 feet (2134 mm). 1.3. Has a longer side at least 65 percent open and unobstructed. 1203.4.3 Openings on yards or courts. Where natural ventilation is to be provided by openings onto yards or courts, such yards or courts shall comply with Section 1206. 2. Skylights are not required to open directly onto a public way, yard or court. 2006 INTERNATIONAL BUILDING CODE® 250 12_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\12_ibc_2006.vp Wednesday, December 07, 2005 10:55:20 AM 2 Color profile: Generic CMYK printer profile Composite Default screen INTERIOR ENVIRONMENT 1205.3 Artificial light. Artificial light shall be provided that is adequate to provide an average illumination of 10 foot-candles (107 lux) over the area of the room at a height of 30 inches (762 mm) above the floor level. 1205.4 Stairway illumination. Stairways within dwelling units and exterior stairways serving a dwelling unit shall have an illumination level on tread runs of not less than 1 foot-candle (11 lux). Stairs in other occupancies shall be governed by Chapter 10. 1205.4.1 Controls. The control for activation of the required stairway lighting shall be in accordance with the ICC Electrical Code. 1205.5 Emergency egress lighting. The means of egress shall be illuminated in accordance with Section 1006.1. 1207.2 Air-borne sound. Walls, partitions and floor/ceiling assemblies separating dwelling units from each other or from public or service areas shall have a sound transmission class (STC) of not less than 50 (45 if field tested) for air-borne noise when tested in accordance with ASTM E 90. Penetrations or openings in construction assemblies for piping; electrical devices; recessed cabinets; bathtubs; soffits; or heating, ventilating or exhaust ducts shall be sealed, lined, insulated or otherwise treated to maintain the required ratings. This requirement shall not apply to dwelling unit entrance doors; however, such doors shall be tight fitting to the frame and sill. 1207.3 Structure-borne sound. Floor/ceiling assemblies between dwelling units or between a dwelling unit and a public or service area within the structure shall have an impact insulation class (IIC) rating of not less than 50 (45 if field tested) when tested in accordance with ASTM E 492. SECTION 1206 YARDS OR COURTS 1206.1 General. This section shall apply to yards and courts adjacent to exterior openings that provide natural light or ventilation. Such yards and courts shall be on the same property as the building. 1206.2 Yards. Yards shall not be less than 3 feet (914 mm) in width for one- and two-story buildings. For buildings more than two stories in height, the minimum width of the yard shall be increased at the rate of 1 foot (305 mm) for each additional story. For buildings exceeding 14 stories in height, the required width of the yard shall be computed on the basis of 14 stories. 1206.3 Courts. Courts shall not be less than 3 feet (914 mm) in width. Courts having windows opening on opposite sides shall not be less than 6 feet (1829 mm) in width. Courts shall not be less than 10 feet (3048 mm) in length unless bounded on one end by a public way or yard. For buildings more than two stories in height, the court shall be increased 1 foot (305 mm) in width and 2 feet (310 mm) in length for each additional story. For buildings exceeding 14 stories in height, the required dimensions shall be computed on the basis of 14 stories. 1206.3.1 Court access. Access shall be provided to the bottom of courts for cleaning purposes. 1206.3.2 Air intake. Courts more than two stories in height shall be provided with a horizontal air intake at the bottom not less than 10 square feet (0.93 m2) in area and leading to the exterior of the building unless abutting a yard or public way. SECTION 1208 INTERIOR SPACE DIMENSIONS 1208.1 Minimum room widths. Habitable spaces, other than a kitchen, shall not be less than 7 feet (2134 mm) in any plan dimension. Kitchens shall have a clear passageway of not less than 3 feet (914 mm) between counter fronts and appliances or counter fronts and walls. 1208.2 Minimum ceiling heights. Occupiable spaces, habitable spaces and corridors shall have a ceiling height of not less than 7 feet 6 inches (2286 mm). Bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms shall be permitted to have a ceiling height of not less than 7 feet (2134 mm). Exceptions: 1. In one- and two-family dwellings, beams or girders spaced not less than 4 feet (1219 mm) on center and projecting not more than 6 inches (152 mm) below the required ceiling height. 2. If any room in a building has a sloped ceiling, the prescribed ceiling height for the room is required in one-half the area thereof. Any portion of the room measuring less than 5 feet (1524 mm) from the finished floor to the ceiling shall not be included in any computation of the minimum area thereof. 3. Mezzanines constructed in accordance with Section 505.1. 1206.3.3 Court drainage. The bottom of every court shall be properly graded and drained to a public sewer or other approved disposal system complying with the International Plumbing Code. 1208.2.1 Furred ceiling. Any room with a furred ceiling shall be required to have the minimum ceiling height in two-thirds of the area thereof, but in no case shall the height of the furred ceiling be less than 7 feet (2134 mm). SECTION 1207 SOUND TRANSMISSION 1208.3 Room area. Every dwelling unit shall have at least one room that shall have not less than 120 square feet (13.9 m2) of net floor area. Other habitable rooms shall have a net floor area of not less than 70 square feet (6.5 m2). 1207.1 Scope. This section shall apply to common interior walls, partitions and floor/ceiling assemblies between adjacent dwelling units or between dwelling units and adjacent public areas such as halls, corridors, stairs or service areas. 2006 INTERNATIONAL BUILDING CODE® 12_ibc_2006_pg251.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\12_ibc_2006.vp Monday, December 19, 2005 10:56:21 AM Exception: Every kitchen in a one- and two-family dwelling shall have not less than 50 square feet (4.64 m2) of gross floor area. 251 3 Color profile: Generic CMYK printer profile Composite Default screen INTERIOR ENVIRONMENT 1208.4 Efficiency dwelling units. An efficiency living unit shall conform to the requirements of the code except as modified herein: 1. The unit shall have a living room of not less than 220 square feet (20.4 m2) of floor area. An additional 100 square feet (9.3 m2) of floor area shall be provided for each occupant of such unit in excess of two. 1210.4 Waterproof joints. Built-in tubs with showers shall have waterproof joints between the tub and adjacent wall. 1210.5 Toilet rooms. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public. 2. The unit shall be provided with a separate closet. 3. The unit shall be provided with a kitchen sink, cooking appliance and refrigeration facilities, each having a clear working space of not less than 30 inches (762 mm) in front. Light and ventilation conforming to this code shall be provided. 4. The unit shall be provided with a separate bathroom containing a water closet, lavatory and bathtub or shower. SECTION 1209 ACCESS TO UNOCCUPIED SPACES 1209.1 Crawl spaces. Crawl spaces shall be provided with a minimum of one access opening not less than 18 inches by 24 inches (457 mm by 610 mm). 1209.2 Attic spaces. An opening not less than 20 inches by 30 inches (559 mm by 762 mm) shall be provided to any attic area having a clear height of over 30 inches (762 mm). A 30-inch (762 mm) minimum clear headroom in the attic space shall be provided at or above the access opening. 1209.3 Mechanical appliances. Access to mechanical appliances installed in under-floor areas, in attic spaces and on roofs or elevated structures shall be in accordance with the International Mechanical Code. SECTION 1210 SURROUNDING MATERIALS 1210.1 Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches (152 mm). 1210.2 Walls. Walls within 2 feet (610 mm) of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet (1219 mm) above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. 1210.3 Showers. Shower compartments and walls above bathtubs with installed shower heads shall be finished with a smooth, nonabsorbent surface to a height not less than 70 inches (1778 mm) above the drain inlet. 2006 INTERNATIONAL BUILDING CODE® 252 12_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\12_ibc_2006.vp Wednesday, December 07, 2005 10:55:20 AM 4 Color profile: Generic CMYK printer profile Composite Default screen CHAPTER 13 ENERGY EFFICIENCY SECTION 1301 GENERAL 1301.1 Scope. This chapter governs the design and construction of buildings for energy efficiency. 1301.1.1 Criteria. Buildings shall be designed and constructed in accordance with the International Energy Conservation Code. 2006 INTERNATIONAL BUILDING CODE® 13_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\13_ibc_2006.vp Wednesday, December 07, 2005 10:54:31 AM 253 1 Color profile: Generic CMYK printer profile Composite Default screen 2006 INTERNATIONAL BUILDING CODE® 254 13_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\13_ibc_2006.vp Wednesday, December 07, 2005 10:54:31 AM 2 Color profile: Generic CMYK printer profile Composite Default screen CHAPTER 14 EXTERIOR WALLS SECTION 1401 GENERAL 1401.1 Scope. The provisions of this chapter shall establish the minimum requirements for exterior walls; exterior wall coverings; exterior wall openings; exterior windows and doors; architectural trim; balconies and similar projections; and bay and oriel windows. cific assembly including joints, seams, attachments, substrate, framing and other details as appropriate to a particular design. VENEER. A facing attached to a wall for the purpose of providing ornamentation, protection or insulation, but not counted as adding strength to the wall. VINYL SIDING. A shaped material, made principally from rigid polyvinyl chloride (PVC), that is used as an exterior wall covering. SECTION 1402 DEFINITIONS 1402.1 General. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. WATER-RESISTIVE BARRIER. A material behind an exterior wall covering that is intended to resist liquid water that has penetrated behind the exterior covering from futher intruding into the exterior wall assembly. ADHERED MASONRY VENEER. Veneer secured and supported through the adhesion of an approved bonding material applied to an approved backing. SECTION 1403 PERFORMANCE REQUIREMENTS ANCHORED MASONRY VENEER. Veneer secured with approved mechanical fasteners to an approved backing. BACKING. The wall or surface to which the veneer is secured. EXTERIOR WALL. A wall, bearing or nonbearing, that is used as an enclosing wall for a building, other than a fire wall, and that has a slope of 60 degrees (1.05 rad) or greater with the horizontal plane. EXTERIOR WALL COVERING. A material or assembly of materials applied on the exterior side of exterior walls for the purpose of providing a weather-resisting barrier, insulation or for aesthetics, including but not limited to, veneers, siding, exterior insulation and finish systems, architectural trim and embellishments such as cornices, soffits, facias, gutters and leaders. 1403.2 Weather protection. Exterior walls shall provide the building with a weather-resistant exterior wall envelope. The exterior wall envelope shall include flashing, as described in Section 1405.3. The exterior wall envelope shall be designed and constructed in such a manner as to prevent the accumulation of water within the wall assembly by providing a water-resistive barrier behind the exterior veneer, as described in Section 1404.2, and a means for draining water that enters the assembly to the exterior. Protection against condensation in the exterior wall assembly shall be provided in accordance with the International Energy Conservation Code. Exceptions: EXTERIOR WALL ENVELOPE. A system or assembly of exterior wall components, including exterior wall finish materials, that provides protection of the building structural members, including framing and sheathing materials, and conditioned interior space, from the detrimental effects of the exterior environment. FIBER CEMENT SIDING. A manufactured, fiber-reinforcing product made with an inorganic hydraulic or calcium silicate binder formed by chemical reaction and reinforced with organic or inorganic nonasbestos fibers, or both. Additives that enhance manufacturing or product performance are permitted. Fiber cement siding products have either smooth or textured faces and are intended for exterior wall and related applications. METAL COMPOSITE MATERIAL (MCM). A factory-manufactured panel consisting of metal skins bonded to both faces of a plastic core. 1. A weather-resistant exterior wall envelope shall not be required over concrete or masonry walls designed in accordance with Chapters 19 and 21, respectively. 2. Compliance with the requirements for a means of drainage, and the requirements of Sections 1404.2 and 1405.3, shall not be required for an exterior wall envelope that has been demonstrated through testing to resist wind-driven rain, including joints, penetrations and intersections with dissimilar materials, in accordance with ASTM E 331 under the following conditions: 2.1. Exterior wall envelope test assemblies shall include at least one opening, one control joint, one wall/eave interface and one wall sill. All tested openings and penetrations shall be representative of the intended end-use configuration. 2.2. Exterior wall envelope test assemblies shall be at least 4 feet by 8 feet (1219 mm by 2438 mm) in size. METAL COMPOSITE MATERIAL (MCM) SYSTEM. An exterior wall finish system fabricated using MCM in a spe2006 INTERNATIONAL BUILDING CODE® 14_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Wednesday, December 07, 2005 10:54:01 AM 1403.1 General. The provisions of this section shall apply to exterior walls, wall coverings and components thereof. 255 1 Color profile: Generic CMYK printer profile Composite Default screen EXTERIOR WALLS 2.3. Exterior wall envelope assemblies shall be tested at a minimum differential pressure of 6.24 pounds per square foot (psf) (0.297 kN/m2). 2.4. Exterior wall envelope assemblies shall be subjected to a minimum test exposure duration of 2 hours. 1404.4 Masonry. Exterior walls of masonry construction shall be designed and constructed in accordance with this section and Chapter 21. Masonry units, mortar and metal accessories used in anchored and adhered veneer shall meet the physical requirements of Chapter 21. The backing of anchored and adhered veneer shall be of concrete, masonry, steel framing or wood framing. The exterior wall envelope design shall be considered to resist wind-driven rain where the results of testing indicate that water did not penetrate control joints in the exterior wall envelope, joints at the perimeter of openings or intersections of terminations with dissimilar materials. 1404.5 Metal. Exterior walls of formed steel construction, structural steel or lightweight metal alloys shall be designed in accordance with Chapters 22 and 20, respectively. ➡ 1403.3 Structural. Exterior walls, and the associated open- 1404.5.2 Cold-rolled copper. Copper shall conform to the requirements of ASTM B 370. ings, shall be designed and constructed to resist safely the superimposed loads required by Chapter 16. 1404.5.3 Lead-coated copper. Lead-coated copper shall conform to the requirements of ASTM B 101. 1403.4 Fire resistance. Exterior walls shall be fire-resistance rated as required by other sections of this code with opening protection as required by Chapter 7. 1404.6 Concrete. Exterior walls of concrete construction shall be designed and constructed in accordance with Chapter 19. 1403.5 Flood resistance. For buildings in flood hazard areas as established in Section 1612.3, exterior walls extending below the design flood elevation shall be resistant to water damage. Wood shall be pressure-preservative treated in accordance with AWPA U1 for the species, product and end use using a preservative listed in Section 4 of AWPA U1 or decay-resistant heartwood of redwood, black locust or cedar. 1403.6 Flood resistance for high-velocity wave action areas. For buildings in flood hazard areas subject to high-velocity wave action as established in Section 1612.3, electrical, mechanical and plumbing system components shall not be mounted on or penetrate through exterior walls that are designed to break away under flood loads. SECTION 1404 MATERIALS 1404.1 General. Materials used for the construction of exterior walls shall comply with the provisions of this section. Materials not prescribed herein shall be permitted, provided that any such alternative has been approved. 1404.2 Water-resistive barrier. A minimum of one layer of No.15 asphalt felt, complying with ASTM D 226 for Type 1 felt or other approved materials, shall be attached to the studs or sheathing, with flashing as described in Section 1405.3, in such a manner as to provide a continuous water-resistive barrier behind the exterior wall veneer. 1404.3 Wood. Exterior walls of wood construction shall be designed and constructed in accordance with Chapter 23. 1404.3.1 Basic hardboard. Basic hardboard shall conform to the requirements of AHA A135.4. 1404.3.2 Hardboard siding. Hardboard siding shall conform to the requirements of AHA A135.6 and, where used structurally, shall be so identified by the label of an approved agency. 1404.5.1 Aluminum siding. Aluminum siding shall conform to the requirements of AAMA 1402. 1404.7 Glass-unit masonry. Exterior walls of glass-unit masonry shall be designed and constructed in accordance with Chapter 21. 1404.8 Plastics. Plastic panel, apron or spandrel walls as defined in this code shall not be limited in thickness, provided that such plastics and their assemblies conform to the requirements of Chapter 26 and are constructed of approved weather-resistant materials of adequate strength to resist the wind loads for cladding specified in Chapter 16. 1404.9 Vinyl siding. Vinyl siding shall be certified and labeled as conforming to the requirements of ASTM D 3679 by an approved quality control agency. 1404.10 Fiber cement siding. Fiber cement siding shall conform to the requirements of ASTM C 1186 and shall be so identified on labeling listing an approved quality control agency. SECTION 1405 INSTALLATION OF WALL COVERINGS 1405.1 General. Exterior wall coverings shall be designed and constructed in accordance with the applicable provisions of this section. 1405.2 Weather protection. Exterior walls shall provide weather protection for the building. The materials of the minimum nominal thickness specified in Table 1405.2 shall be acceptable as approved weather coverings. 1405.3 Flashing. Flashing shall be installed in such a manner so as to prevent moisture from entering the wall or to redirect it to the exterior. Flashing shall be installed at the perimeters of exterior door and window assemblies, penetrations and terminations of exterior wall assemblies, exterior wall intersections with roofs, chimneys, porches, decks, balconies and similar projections and at built-in gutters and similar locations where moisture could enter the wall. Flashing with projecting flanges shall be installed on both sides and the ends of copings, under sills and continuously above projecting trim. 2006 INTERNATIONAL BUILDING CODE® 256 14_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Wednesday, December 07, 2005 10:54:02 AM 2 Color profile: Generic CMYK printer profile Composite Default screen EXTERIOR WALLS TABLE 1405.2 MINIMUM THICKNESS OF WEATHER COVERINGS COVERING TYPE 1405.3.1 Exterior wall pockets. In exterior walls of buildings or structures, wall pockets or crevices in which moisture can accumulate shall be avoided or protected with caps or drips, or other approved means shall be provided to prevent water damage. MINIMUM THICKNESS (inches) Adhered masonry veneer 0.25 Aluminum siding 0.019 Anchored masonry veneer 2.625 Asbestos-cement boards 0.125 Asbestos shingles 0.156 Cold-rolled copperd 0.0216 nominal Copper shinglesd 0.0162 nominal Exterior plywood (with sheathing) 0.313 Exterior plywood (without sheathing) See Section 2304.6 Fiber cement lap siding 0.25c Fiber cement panel siding 0.25c Fiberboard siding 0.5 Glass-fiber reinforced concrete panels 0.375 Hardboard sidingc 0.25 High-yield copperd 0.0162 nominal Lead-coated copperd 0.0216 nominal Lead-coated high-yield copper 0.0162 nominal Marble slabs 1405.3.2 Masonry. Flashing and weepholes shall be located in the first course of masonry above finished ground level above the foundation wall or slab, and other points of support, including structural floors, shelf angles and lintels where anchored veneers are designed in accordance with Section 1405.5. 1405.4 Wood veneers. Wood veneers on exterior walls of buildings of Type I, II, III and IV construction shall be not less than 1 inch (25 mm) nominal thickness, 0.438-inch (11.1 mm) exterior hardboard siding or 0.375-inch (9.5 mm) exterior-type wood structural panels or particleboard and shall conform to the following: 1. The veneer shall not exceed three stories in height, measured from the grade plane. Where fire-retardant-treated wood is used, the height shall not exceed four stories. 2. T h e v e n e e r i s a t t a c h e d t o o r f u r r e d f r o m a noncombustible backing that is fire-resistance rated as required by other provisions of this code. 3. Where open or spaced wood veneers (without concealed spaces) are used, they shall not project more than 24 inches (610 mm) from the building wall. 1 Particleboard (with sheathing) See Section 2304.6 Particleboard (without sheathing) See Section 2304.6 Precast stone facing 0.625 Steel (approved corrosion resistant) 0.0149 Stone (cast artificial) 1.5 Stone (natural) 2 Structural glass 0.344 1405.5 Anchored masonry veneer. Anchored masonry veneer shall comply with the provisions of Sections 1405.5, 1405.6, 1405.7 and 1405.8 and Sections 6.1 and 6.2 of ACI 530/ASCE 5/TMS 402. 1405.5.1 Tolerances. Anchored masonry veneers in accordance with Chapter 14 are not required to meet the tolerances in Article 3.3 G1 of ACI 530.1/ASCE 6/TMS 602. Stucco or exterior portland cement plaster 1405.5.2 Seismic requirements. Anchored masonry veneer located in Seismic Design Category C, E or F shall conform to the requirements of Section 6.2.2.10 of ACI530/ ASCE5/ TMS 402. Anchored masonry veneer located in Seismic Design Category D shall conform to the requirements for Seismic Design Category E or F. Three-coat work over: Metal plaster base 0.875b Unit masonry 0.625b Cast-in-place or precast concrete 0.625b Two-coat work over: Unit masonry 0.5b Cast-in-place or precast concrete 0.375b Terra cotta (anchored) 1 Terra cotta (adhered) 0.25 Vinyl siding 0.035 Wood shingles 1405.6 Stone veneer. Stone veneer units not exceeding 10 inches (254 mm) in thickness shall be anchored directly to masonry, concrete or to stud construction by one of the following methods: 0.375 a Wood siding (without sheathing) 0.5 For SI: 1 inch = 25.4 mm. a. Wood siding of thicknesses less than 0.5 inch shall be placed over sheathing that conforms to Section 2304.6. b. Exclusive of texture. c. As measured at the bottom of decorative grooves. d. 16 ounces per square foot for cold-rolled copper and lead-coated copper, 12 ounces per square foot for copper shingles, high-yield copper and lead-coated high-yield copper. 2006 INTERNATIONAL BUILDING CODE® 14_ibc_2006_pg257.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Monday, December 19, 2005 10:58:09 AM 1. With concrete or masonry backing, anchor ties shall be not less than 0.1055-inch (2.68 mm) corrosion-resistant wire, or approved equal, formed beyond the base of the backing. The legs of the loops shall be not less than 6 inches (152 mm) in length bent at right angles and laid in the mortar joint, and spaced so that the eyes or loops are 12 inches (305 mm) maximum on center (o.c.) in both directions. There shall be provided not less than a 0.1055-inch (2.68 mm) corrosion-resistant wire tie, or approved equal, threaded through the exposed loops for every 2 square feet (0.2 m2) of stone veneer. This tie shall be a loop having legs not less than 15 inches (381 mm) in length bent so that it will lie in the stone veneer mortar 257 3 Color profile: Generic CMYK printer profile Composite Default screen EXTERIOR WALLS joint. The last 2 inches (51 mm) of each wire leg shall have a right-angle bend. One-inch (25 mm) minimum thickness of cement grout shall be placed between the backing and the stone veneer. backing wall and the space shall be filled solidly with portland cement grout and pea gravel. Immediately prior to setting, the backing wall and the facing shall be drenched with clean water and shall be distinctly damp when the grout is poured. 2. With stud backing, a 2-inch by 2-inch (51 by 51 mm) 0.0625-inch (1.59 mm) corrosion-resistant wire mesh with two layers of water-resistive barrier in accordance with Section 1404.2 shall be applied directly to wood studs spaced a maximum of 16 inches (406 mm) o.c. On studs, the mesh shall be attached with 2-inch-long (51 mm) corrosion-resistant steel wire furring nails at 4 inches (102 mm) o.c. providing a minimum 1.125-inch (29 mm) penetration into each stud and with 8d common nails at 8 inches (203 mm) o.c. into top and bottom plates or with equivalent wire ties. There shall be not less than a 0.1055-inch (2.68 mm) corrosion-resistant wire, or approved equal, looped through the mesh for every 2 square feet (0.2 m2) of stone veneer. This tie shall be a loop having legs not less than 15 inches (381 mm) in length, so bent that it will lie in the stone veneer mortar joint. The last 2 inches (51 mm) of each wire leg shall have a right-angle bend. One-inch (25 mm) minimum thickness of cement grout shall be placed between the backing and the stone veneer. 1405.9 Adhered masonry veneer. Adhered masonry veneer shall comply with the applicable requirements in Section 1405.9.1 and Sections 6.1 and 6.3 of ACI 530/ASCE 5/TMS 402. 1405.9.1 Interior adhered masonry veneers. Interior adhered masonry veneers shall have a maximum weight of 20 psf (0.958 kg/m2) and shall be installed in accordance with Section 1405.9. Where the interior adhered masonry veneer is supported by wood construction, the supporting members shall be designed to limit deflection to 1/600 of the span of the supporting members. 1405.10 Metal veneers. Veneers of metal shall be fabricated from approved corrosion-resistant materials or shall be protected front and back with porcelain enamel, or otherwise be treated to render the metal resistant to corrosion. Such veneers shall not be less than 0.0149-inch (0.378 mm) nominal thickness sheet steel mounted on wood or metal furring strips or approved sheathing on the wood construction. 1405.10.1 Attachment. Exterior metal veneer shall be securely attached to the supporting masonry or framing members with corrosion-resistant fastenings, metal ties or by other approved devices or methods. The spacing of the fastenings or ties shall not exceed 24 inches (610 mm) either vertically or horizontally, but where units exceed 4 square feet (0.4 m2) in area there shall be not less than four attachments per unit. The metal attachments shall have a cross-sectional area not less than provided by W 1.7 wire. Such attachments and their supports shall be capable of resisting a horizontal force in accordance with the wind loads specified in Section 1609, but in no case less than 20 psf (0.958 kg/m2). 1405.7 Slab-type veneer. Slab-type veneer units not exceeding 2 inches (51 mm) in thickness shall be anchored directly to masonry, concrete or stud construction. For veneer units of marble, travertine, granite or other stone units of slab form ties of corrosion-resistant dowels in drilled holes shall be located in the middle third of the edge of the units, spaced a maximum of 24 inches (610 m) apart around the periphery of each unit with not less than four ties per veneer unit. Units shall not exceed 20 square feet (1.9 m2) in area. If the dowels are not tight fitting, the holes shall be drilled not more than 0.063 inch (1.6 mm) larger in diameter than the dowel, with the hole countersunk to a diameter and depth equal to twice the diameter of the dowel in order to provide a tight-fitting key of cement mortar at the dowel locations when the mortar in the joint has set. Veneer ties shall be corrosion-resistant metal capable of resisting, in tension or compression, a force equal to two times the weight of the attached veneer. If made of sheet metal, veneer ties shall be not smaller in area than 0.0336 by 1 inch (0.853 by 25 mm) or, if made of wire, not smaller in diameter than 0.1483-inch (3.76 mm) wire. 1405.8 Terra cotta. Anchored terra cotta or ceramic units not less than 1.625 inches (41 mm) thick shall be anchored directly to masonry, concrete or stud construction. Tied terra cotta or ceramic veneer units shall be not less than 1.625 inches (41 mm) thick with projecting dovetail webs on the back surface spaced approximately 8 inches (203 mm) o.c. The facing shall be tied to the backing wall with corrosion-resistant metal anchors of not less than No. 8 gage wire installed at the top of each piece in horizontal bed joints not less than 12 inches (305 mm) nor more than 18 inches (457 mm) o.c.; these anchors shall be secured to 0.25-inch (6.4 mm) corrosion-resistant pencil rods that pass through the vertical aligned loop anchors in the backing wall. The veneer ties shall have sufficient strength to support the full weight of the veneer in tension. The facing shall be set with not less than a 2-inch (51 mm) space from the 1405.10.2 Weather protection. Metal supports for exterior metal veneer shall be protected by painting, galvanizing or by other equivalent coating or treatment. Wood studs, furring strips or other wood supports for exterior metal veneer shall be approved pressure-treated wood or protected as required in Section 1403.2. Joints and edges exposed to the weather shall be caulked with approved durable waterproofing material or by other approved means to prevent penetration of moisture. 1405.10.3 Backup. Masonry backup shall not be required for metal veneer except as is necessary to meet the fire-resistance requirements of this code. 1405.10.4 Grounding. Grounding of metal veneers on buildings shall comply with the requirements of Chapter 27 of this code or the ICC Electrical Code. 1405.11 Glass veneer. The area of a single section of thin exterior structural glass veneer shall not exceed 10 square feet (0.93 m2) where it is not more than 15 feet (4572 mm) above the level of the sidewalk or grade level directly below, and shall not exceed 6 square feet (0.56 m2) where it is more than 15 feet (4572 mm) above that level. 2006 INTERNATIONAL BUILDING CODE® 258 14_ibc_2006_pg258.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Thursday, January 05, 2006 12:47:24 PM 4 Color profile: Generic CMYK printer profile Composite Default screen EXTERIOR WALLS 1405.11.7 Flashing. Exposed edges of thin exterior structural glass veneer shall be flashed with overlapping corrosion-resistant metal flashing and caulked with a waterproof compound in a manner to effectively prevent the entrance of moisture between the glass veneer and the backing. 1405.11.1 Length and height. The length or height of any section of thin exterior structural glass veneer shall not exceed 48 inches (1219 mm). 1405.11.2 Thickness. The thickness of thin exterior structural glass veneer shall be not less than 0.344 inch (8.7 mm). 1405.11.3 Application. Thin exterior structural glass veneer shall be set only after backing is thoroughly dry and after application of an approved bond coat uniformly over the entire surface of the backing so as to effectively seal the surface. Glass shall be set in place with an approved mastic cement in sufficient quantity so that at least 50 percent of the area of each glass unit is directly bonded to the backing by mastic not less than 0.25 inch (6.4 mm) thick and not more than 0.625 inch (15.9 mm) thick. The bond coat and mastic shall be evaluated for compatibility and shall bond firmly together. 1405.11.4 Installation at sidewalk level. Where glass extends to a sidewalk surface, each section shall rest in an approved metal molding, and be set at least 0.25 inch (6.4 mm) above the highest point of the sidewalk. The space between the molding and the sidewalk shall be thoroughly caulked and made water tight. 1405.11.4.1 Installation above sidewalk level. Where thin exterior structural glass veneer is installed above the level of the top of a bulkhead facing, or at a level more than 36 inches (914 mm) above the sidewalk level, the mastic cement binding shall be supplemented with approved nonferrous metal shelf angles located in the horizontal joints in every course. Such shelf angles shall be not less than 0.0478-inch (1.2 mm) thick and not less than 2 inches (51 mm) long and shall be spaced at approved intervals, with not less than two angles for each glass unit. Shelf angles shall be secured to the wall or backing with expansion bolts, toggle bolts or by other approved methods. 1405.11.5 Joints. Unless otherwise specifically approved by the building official, abutting edges of thin exterior structural glass veneer shall be ground square. Mitered joints shall not be used except where specifically approved for wide angles. Joints shall be uniformly buttered with an approved jointing compound and horizontal joints shall be held to not less than 0.063 inch (1.6 mm) by an approved nonrigid substance or device. Where thin exterior structural glass veneer abuts nonresilient material at sides or top, expansion joints not less than 0.25 inch (6.4 mm) wide shall be provided. 1405.11.6 Mechanical fastenings. Thin exterior structural glass veneer installed above the level of the heads of show windows and veneer installed more than 12 feet (3658 mm) above sidewalk level shall, in addition to the mastic cement and shelf angles, be held in place by the use of fastenings at each vertical or horizontal edge, or at the four corners of each glass unit. Fastenings shall be secured to the wall or backing with expansion bolts, toggle bolts or by other methods. Fastenings shall be so designed as to hold the glass veneer in a vertical plane independent of the mastic cement. Shelf angles providing both support and fastenings shall be permitted. 2006 INTERNATIONAL BUILDING CODE® 14_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Wednesday, December 07, 2005 10:54:02 AM 1405.12 Exterior windows and doors. Windows and doors installed in exterior walls shall conform to the testing and performance requirements of Section 1714.5. 1405.12.1 Installation. Windows and doors shall be installed in accordance with approved manufacturer’s instructions. Fastener size and spacing shall be provided in such instructions and shall be calculated based on maximum loads and spacing used in the tests. 1405.12.2 Window sills. In Occupancy Groups R-2 and R-3, one- and two-family and multiple-family dwellings, where the opening of the sill portion of an operable window is located more than 72 inches (1829 mm) above the finished grade or other surface below, the lowest part of the clear opening of the window shall be a minimum of 24 inches (610 mm) above the finished floor surface of the room in which the window is located. Glazing between the floor and a height of 24 inches (610 mm) shall be fixed or have openings such that a 4-inch (102 mm) diameter sphere cannot pass through. Exception: Openings that are provided with window guards that comply with ASTM F 2006 or F 2090. 1405.13 Vinyl siding. Vinyl siding conforming to the requirements of this section and complying with ASTM D 3679 shall be permitted on exterior walls of buildings of Type V construction located in areas where the basic wind speed specified in Chapter 16 does not exceed 100 miles per hour (45 m/s) and the building height is less than or equal to 40 feet (12 192 mm) in Exposure C. Where construction is located in areas where the basic wind speed exceeds 100 miles per hour (45 m/s), or building heights are in excess of 40 feet (12 192 mm), tests or calculations indicating compliance with Chapter 16 shall be submitted. Vinyl siding shall be secured to the building so as to provide weather protection for the exterior walls of the building. 1405.13.1 Application. The siding shall be applied over sheathing or materials listed in Section 2304.6. Siding shall be applied to conform with the water-resistive barrier requirements in Section 1403. Siding and accessories shall be installed in accordance with approved manufacturer’s instructions. Unless otherwise specified in the approved manufacturer’s instructions, nails used to fasten the siding and accessories shall have a minimum 0.313-inch (7.9 mm) head diameter and 0.125-inch (3.18 mm) shank diameter. The nails shall be corrosion resistant and shall be long enough to penetrate the studs or nailing strip at least 0.75 inch (19 mm). Where the siding is installed horizontally, the fastener spacing shall not exceed 16 inches (406 mm) horizontally and 12 inches (305 mm) vertically. Where the siding is installed vertically, the fastener spacing shall not exceed 12 inches (305 mm) horizontally and 12 inches (305 mm) vertically. 259 5 Color profile: Generic CMYK printer profile Composite Default screen EXTERIOR WALLS 1405.14 Cement plaster. Cement plaster applied to exterior walls shall conform to the requirements specified in Chapter 25. 1406.2.1 Ignition resistance. Combustible exterior wall coverings shall be tested in accordance with NFPA 268. Exceptions: 1405.15 Fiber cement siding. Fiber cement siding complying with Section 1404.10 shall be permitted on exterior walls of Type I, II, III, IV and V construction for wind pressure resistance or wind speed exposures as indicated in the manufacturer’s compliance report and approved installation instructions. Where specified, the siding shall be installed over sheathing or materials listed in Section 2304.6 and shall be installed to conform to the water-resistive barrier requirements in Section 1403. Siding and accessories shall be installed in accordance with approved manufacturer’s instructions. Unless otherwise specified in the approved manufacturer’s instructions, nails used to fasten the siding to wood studs shall be corrosion-resistant round head smooth shank and shall be long enough to penetrate the studs at least 1 inch (25 mm). For metal framing, all-weather screws shall be used and shall penetrate the metal framing at least three full threads. 1 Wood or wood-based products. 2. Other combustible materials covered with an exterior covering other than vinyl sidings listed in Table 1405.2. 3. Aluminum having a minimum thickness of 0.019 inch (0.48 mm). 4. Exterior wall coverings on exterior walls of Type V construction. 1406.2.1.1 Fire separation 5 feet or less. Where installed on exterior walls having a fire separation distance of 5 feet (1524 mm) or less, combustible exterior wall coverings shall not exhibit sustained flaming as defined in NFPA 268. 1406.2.1.2 Fire separation greater than 5 feet. For fire separation distances greater than 5 feet (1524 mm), an assembly shall be permitted that has been exposed to a reduced level of incident radiant heat flux in accordance with the NFPA 268 test method without exhibiting sustained flaming. The minimum fire separation distance required for the assembly shall be determined from Table 1406.2.1.2 based on the maximum tolerable level of incident radiant heat flux that does not cause sustained flaming of the assembly. 1405.16 Fastening. Weather boarding and wall coverings shall be securely fastened with aluminum, copper, zinc, zinc-coated or other approved corrosion-resistant fasteners in accordance with the nailing schedule in Table 2304.9.1 or the approved manufacturer’s installation instructions. Shingles and other weather coverings shall be attached with appropriate standard-shingle nails to furring strips securely nailed to studs, or with approved mechanically bonding nails, except where sheathing is of wood not less than 1-inch (25 mm) nominal thickness or of wood structural panels as specified in Table 2308.9.3(3). TABLE 1406.2.1.2 MINIMUM FIRE SEPARATION FOR COMBUSTIBLE VENEERS 1405.17 Fiber cement siding. 1405.17.1 Panel siding. Panels shall be installed with the long dimension parallel to framing. Vertical joints shall occur over framing members and shall be sealed with caulking or covered with battens. Horizontal joints shall be flashed with Z-flashing and blocked with solid wood framing. 1405.17.2 Horizontal lap siding. Lap siding shall be lapped a minimum of 11/4 inches (32 mm) and shall have the ends sealed with caulking, covered with an H-section joint cover or located over a strip of flashing. Lap siding courses shall be permitted to be installed with the fastener heads exposed or concealed, according to approved manufacturers’ instructions. TOLERABLE LEVEL INCIDENT RADIANT HEAT ENERGY(kW/m2) FIRE SEPARATION DISTANCE (feet) TOLERABLE LEVEL INCIDENT RADIANT HEAT ENERGY(kW/m2) 5 6 7 8 9 10 11 12 13 14 15 12.5 11.8 11.0 10.3 9.6 8.9 8.3 7.7 7.2 6.7 6.3 16 17 18 19 20 21 22 23 24 25 5.9 5.5 5.2 4.9 4.6 4.4 4.1 3.9 3.7 3.5 For SI: 1 foot = 304.8 mm, 1 Btu/H2 ×°F = 0.0057 kW/m2 × K. 1406.2.2 Architectural trim. In buildings of Type I, II, III and IV construction that do not exceed three stories or 40 feet (12 192 mm) in height above grade plane, exterior wall coverings shall be permitted to be constructed of wood where permitted by Section 1405.4 or other equivalent combustible material. Combustible exterior wall coverings, other than fire-retardant-treated wood complying with Section 2303.2 for exterior installation, shall not exceed 10 percent of an exterior wall surface area where the fire separation distance is 5 feet (1524 mm) or less. Architectural trim that exceeds 40 feet (12 192 mm) in height above grade plane shall be constructed of approved SECTION 1406 COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF EXTERIOR WALLS 1406.1 General. Section 1406 shall apply to exterior wall coverings; balconies and similar projections; and bay and oriel windows constructed of combustible materials. 1406.2 Combustible exterior wall coverings. Combustible exterior wall coverings shall comply with this section. Exception: Plastics complying with Chapter 26. 2006 INTERNATIONAL BUILDING CODE® 260 14_ibc_2006_pg260.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Thursday, January 05, 2006 12:49:25 PM FIRE SEPARATION DISTANCE (feet) 6 Color profile: Generic CMYK printer profile Composite Default screen EXTERIOR WALLS noncombustible materials and shall be secured to the wall with metal or other approved noncombustible brackets. oriel windows to provide cladding or weather resistance shall comply with Sections 1407.4 through 1407.13. 1406.2.3 Location. Where combustible exterior wall covering is located along the top of exterior walls, such trim shall be completely backed up by the exterior wall and shall not extend over or above the top of exterior walls. 1407.3 Architectural trim and embellishments. MCM used as architectural trim or embellishments shall comply with Sections 1407.7 through 1407.13. 1406.2.4 Fireblocking. Where the combustible exterior wall covering is furred from the wall and forms a solid surface, the distance between the back of the covering and the wall shall not exceed 1.625 inches (41 mm) and the space thereby created shall be fireblocked in accordance with Section 717. 1407.5 Approval. Results of approved tests or an engineering analysis shall be submitted to the building official to verify compliance with the requirements of Chapter 16 for wind loads. ➡ 1406.3 Balconies and similar projections. Balconies and 1407.6 Weather resistance. MCM systems shall comply with Section 1403 and shall be designed and constructed to resist wind and rain in accordance with this section and the manufacturer’s installation instructions. similar projections of combustible construction other than fire-retardant-treated wood shall be fire-resistance rated in accordance with Table 601 for floor construction or shall be of Type IV construction in accordance with Section 602.4. The aggregate length shall not exceed 50 percent of the building’s perimeter on each floor. 1407.7 Durability. MCM systems shall be constructed of approved materials that maintain the performance characteristics required in Section 1407 for the duration of use. Exceptions: 1. On buildings of Type I and II construction, three stories or less in height, fire-retardant-treated wood shall be permitted for balconies, porches, decks and exterior stairways not used as required exits. 1407.8 Fire-resistance rating. Where MCM systems are used on exterior walls required to have a fire-resistance rating in accordance with Section 704, evidence shall be submitted to the building official that the required fire-resistance rating is maintained. 1407.9 Surface-burning characteristics. Unless otherwise specified, MCM shall have a flame spread index of 75 or less and a smoke-developed index of 450 or less when tested as an assembly in the maximum thickness intended for use in accordance with ASTM E 84. 2. Untreated wood is permitted for pickets and rails or similar guardrail devices that are limited to 42 inches (1067 mm) in height. 3. Balconies and similar projections on buildings of Type III, IV and V construction shall be permitted to be of Type V construction, and shall not be required to have a fire-resistance rating where sprinkler protection is extended to these areas. 1407.10 Type I, II, III and IV construction. Where installed on buildings of Type I, II, III and IV construction, MCM systems shall comply with Sections 1407.10.1 through 1407.10.4, or 1407.11. 4. Where sprinkler protection is extended to the balcony areas, the aggregate length of the balcony on each floor shall not be limited. 1407.10.1 Surface-burning characteristics. MCM shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested as an assembly in the maximum thickness intended for use in accordance with ASTM E 84. 1406.4 Bay windows and oriel windows. Bay and oriel windows shall conform to the type of construction required for the building to which they are attached. Exception: Fire-retardant-treated wood shall be permitted on buildings three stories or less of Type I, II, III and IV construction. SECTION 1407 METAL COMPOSITE MATERIALS (MCM) 1407.1 General. The provisions of this section shall govern the materials, construction and quality of metal composite materials (MCM) for use as exterior wall coverings in addition to other applicable requirements of Chapters 14 and 16. 1407.1.1 Plastic core. The plastic core of the MCM shall not contain foam plastic insulation as defined in Section 2602.1. 1407.2 Exterior wall finish. MCM used as exterior wall finish or as elements of balconies and similar projections and bay and 2006 INTERNATIONAL BUILDING CODE® 14_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Wednesday, December 07, 2005 10:54:03 AM 1407.4 Structural design. MCM systems shall be designed and constructed to resist wind loads as required by Chapter 16 for components and cladding. 1407.10.2 Thermal barriers. MCM shall be separated from the interior of a building by an approved thermal barrier consisting of 0.5-inch (12.7 mm) gypsum wallboard or equivalent thermal barrier material that will limit the average temperature rise of the unexposed surface to not more than 250°F (121°C) after 15 minutes of fire exposure in accordance with the standard time-temperature curve of ASTM E 119. The thermal barrier shall be installed in such a manner that it will remain in place for not less than 15 minutes based on a test conducted in accordance with UL 1715. 1407.10.3 Thermal barrier not required. The thermal barrier specified for MCM in Section 1407.10.2 is not required where: 1. The MCM system is specifically approved based on tests conducted in accordance with UL 1040 or UL 1715. Such testing shall be performed with the MCM in the maximum thickness intended for use. The MCM system shall include seams, joints and other 261 7 Color profile: Generic CMYK printer profile Composite Default screen EXTERIOR WALLS typical details used in the installation and shall be tested in the manner intended for use. 2. The MCM is used as elements of balconies and similar projections, architectural trim or embellishments. 1407.10.4 Full-scale tests. The MCM exterior wall assembly shall be tested in accordance with, and comply with, the acceptance criteria of NFPA 285. Such testing shall be performed on the MCM system with the MCM in the maximum thickness intended for use. 1407.11 Alternate conditions. MCM and MCM systems shall not be required to comply with Sections 1407.10.1 through 1407.10.4 provided such systems comply with Section 1407.11.1 or 1407.11.2. 1407.11.1 Installations up to 40 feet in height. MCM shall not be installed more than 40 feet (12 190 mm) in height above the grade plane where installed in accordance with Sections 1407.11.1.1 and 1407.11.1.2. 1407.11.1.1 Fire separation distance of 5 feet or less. Where the fire separation distance is 5 feet (1524 mm) or less, the area of MCM shall not exceed 10 percent of the exterior wall surface. 1407.11.1.2 Fire separation distance greater than 5 feet. Where the fire separation distance is greater than 5 feet (1524 mm), there shall be no limit on the area of exterior wall surface coverage using MCM. 1407.11.2 Installations up to 50 feet in height. MCM shall not be installed more than 50 feet (15 240 mm) in height above the grade plane where installed in accordance with Sections 1407.11.2.1 and 1407.11.2.2. 1407.11.2.1 Self ignition temperature. MCM shall have a self-ignition temperature of 650°F (343°C) or greater when tested in accordance with ASTM D 1929. 1407.11.2.2 Limitations. Sections of MCM shall not exceed 300 square feet (27.9 m2) in area and shall be separated by a minimum of 4 feet (1219 mm) vertically. 1407.12 Type V construction. MCM shall be permitted to be installed on buildings of Type V construction. 1407.13 Labeling. MCM shall be labeled in accordance with Section 1703.5. 2006 INTERNATIONAL BUILDING CODE® 262 14_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\14_ibc_2006.vp Wednesday, December 07, 2005 10:54:03 AM 8 Color profile: Generic CMYK printer profile Composite Default screen CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES ROOF COVERING. The covering applied to the roof deck for weather resistance, fire classification or appearance. SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and rooftop structures. ROOF COVERING SYSTEM. See “Roof assembly.” ROOF DECK. The flat or sloped surface not including its supporting members or vertical supports. ROOF RECOVER. The process of installing an additional roof covering over a prepared existing roof covering without removing the existing roof covering. SECTION 1502 DEFINITIONS ROOF REPAIR. Reconstruction or renewal of any part of an existing roof for the purposes of its maintenance. 1502.1 General. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. BUILT-UP ROOF COVERING. Two or more layers of felt cemented together and surfaced with a cap sheet, mineral aggregate, smooth coating or similar surfacing material. INTERLAYMENT. A layer of felt or nonbituminous saturated felt not less than 18 inches (457 mm) wide, shingled between each course of a wood-shake roof covering. ROOF REPLACEMENT. The process of removing the existing roof covering, repairing any damaged substrate and installing a new roof covering. ROOF VENTILATION. The natural or mechanical process of supplying conditioned or unconditioned air to, or removing such air from, attics, cathedral ceilings or other enclosed spaces over which a roof assembly is installed. ROOFTOP STRUCTURE. An enclosed structure on or above the roof of any part of a building. MECHANICAL EQUIPMENT SCREEN. A partially enclosed rooftop structure used to aesthetically conceal heating, ventilating and air conditioning (HVAC) electrical or mechanical equipment from view. SCUPPER. An opening in a wall or parapet that allows water to drain from a roof. METAL ROOF PANEL. An interlocking metal sheet having a minimum installed weather exposure of 3 square feet (0.279 m2) per sheet. METAL ROOF SHINGLE. An interlocking metal sheet having an installed weather exposure less than 3 square feet (0.279 m2) per sheet. SINGLE-PLY MEMBRANE. A roofing membrane that is field applied using one layer of membrane material (either homogeneous or composite) rather than multiple layers. UNDERLAYMENT. One or more layers of felt, sheathing paper, nonbituminous saturated felt or other approved material over which a steep-slope roof covering is applied. MODIFIED BITUMEN ROOF COVERING. One or more layers of polymer-modified asphalt sheets. The sheet materials shall be fully adhered or mechanically attached to the substrate or held in place with an approved ballast layer. PENTHOUSE. An enclosed, unoccupied structure above the roof of a building, other than a tank, tower, spire, dome cupola or bulkhead, occupying not more than one-third of the roof area. POSITIVE ROOF DRAINAGE. The drainage condition in which consideration has been made for all loading deflections of the roof deck, and additional slope has been provided to ensure drainage of the roof within 48 hours of precipitation. SECTION 1503 WEATHER PROTECTION 1503.1 General. Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof coverings shall be designed, installed and maintained in accordance with this code and the approved manufacturer’s instructions such that the roof covering shall serve to protect the building or structure. REROOFING. The process of recovering or replacing an existing roof covering. See “Roof recover” and “Roof replacement.” 1503.2 Flashing. Flashing shall be installed in such a manner so as to prevent moisture entering the wall and roof through joints in copings, through moisture-permeable materials and at intersections with parapet walls and other penetrations through the roof plane. ROOF ASSEMBLY. A system designed to provide weather protection and resistance to design loads. The system consists of a roof covering and roof deck or a single component serving as both the roof covering and the roof deck. A roof assembly includes the roof deck, vapor retarder, substrate or thermal barrier, insulation, vapor retarder and roof covering. 1503.2.1 Locations. Flashing shall be installed at wall and roof intersections, at gutters, wherever there is a change in roof slope or direction and around roof openings. Where flashing is of metal, the metal shall be corrosion resistant with a thickness of not less than 0.019 inch (0.483 mm) (No. 26 galvanized sheet). 2006 INTERNATIONAL BUILDING CODE® 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:52:59 AM 263 1 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES TABLE 1504.2.1 ROOF COVERING CLASSIFICATION USING ALTERNATIVE METHOD 1503.3 Coping. Parapet walls shall be properly coped with noncombustible, weatherproof materials of a width no less than the thickness of the parapet wall. [P] 1503.4 Roof drainage. Design and installation of roof drainage systems shall comply with the International Plumbing Code. 1503.4.1 Gutters. Gutters and leaders placed on the outside of buildings, other than Group R-3, private garages and buildings of Type V construction, shall be of noncombustible material or a minimum of Schedule 40 plastic pipe. Class D 120 Class G 150 Class H 1504.3.2 Metal panel roof systems. Metal panel roof systems through fastened or standing seam shall be tested in accordance with UL 580 or ASTM E 1592. 1504.1 Wind resistance of roofs. Roof decks and roof coverings shall be designed for wind loads in accordance with Chapter 16 and Sections 1504.2, 1504.3 and 1504.4. 1504.2.1 Alternative test method. Testing the acceptability of special fastening methods using the methodology in this section is permitted. The wind-induced uplift force on the shingle shall be determined using the method in UL 2390. The resistance of the shingle to the uplift force shall be determined using ASTM D 6381. Shingles passing this test shall be considered suitable for roofs located where the basic wind speed per Figure 1609 is as given in Table 1504.2.1. 90 1504.3.1 Other roof systems. Roof systems with built-up, modified bitumen, fully adhered or mechanically attached single-ply through fastened metal panel roof systems, and other types of membrane roof coverings shall also be tested in accordance with FM 4450, FM 4470, UL 580 or UL 1897. SECTION 1504 PERFORMANCE REQUIREMENTS 1504.2 Wind resistance of clay and concrete tile. Clay and concrete tile roof coverings shall be connected to the roof deck in accordance with Chapter 16. ASTM D 6381 CLASSIFICATION For SI: 1 mile per hour = 0.447m/s. 1503.5 Roof ventilation. Intake and exhaust vents shall be provided in accordance with Section 1203.2 and the manufacturer’s installation instructions. 1504.1.1 Wind resistance of asphalt shingles. Asphalt shingles shall be installed in accordance with Section 1507.2.7. For roofs located where the basic wind speed in accordance with Figure 1609 is 110 mph or greater, asphalt shingles shall be tested in accordance with ASTM D 3161, Class F. As an alternative, load and wind resistance of asphalt shingle roof coverings shall be determined in accordance with Section 1609.5.2. MAXIMUM BASIC WIND SPEED (mph) Exception: Metal roofs constructed of cold-formed steel, where the roof deck acts as the roof covering and provides both weather protection and support for structural loads, shall be permitted to be designed and tested in accordance with the applicable referenced structural design standard in Section 2209.1. 1504.4 Ballasted low-slope roof systems. Ballasted low-slope (roof slope < 2:12) single-ply roof system coverings installed in accordance with Section 1507 shall be designed in accordance with Section 1504.8 and ANSI/SPRI RP-4. 1504.5 Edge securement for low-slope roofs. Low-slope membrane roof system metal edge securement, except gutters, shall be designed and installed for wind loads in accordance with Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1, except the basic wind speed shall be determined from Figure 1609. Classification requires that the resistance of the shingle to wind uplift, measured using the method in ASTM D 6381, exceed the calculated load imposed by wind in the applicable zone as determined using UL 2390. 1504.6 Physical properties. Roof coverings installed on low-slope roofs (roof slope < 2:12) in accordance with Section 1507 shall demonstrate physical integrity over the working life of the roof based upon 2,000 hours of exposure to accelerated weathering tests conducted in accordance with ASTM G 152, ASTM G 155 or ASTM G 154. Those roof coverings that are subject to cyclical flexural response due to wind loads shall not demonstrate any significant loss of tensile strength for unreinforced membranes or breaking strength for reinforced membranes when tested as herein required. Classification by this method applies to buildings less than 60 feet (18 288 mm) high and with Wind Exposures B and C only in an Occupancy Category of I or II. Wrappers of shingle bundles that have been qualified using this alternative method shall be labeled with the tested wind classification and reference UL 2390/ASTM D 6381. 1504.7 Impact resistance. Roof coverings installed on low-slope roofs (roof slope < 2:12) in accordance with Section 1507 shall resist impact damage based on the results of tests conducted in accordance with ASTM D 3746, ASTM D 4272, CGSB 37-GP-52M or the “Resistance to Foot Traffic Test” in Section 5.5 of FM 4470. 1504.3 Wind resistance of nonballasted roofs. Roof coverings installed on roofs in accordance with Section 1507 that are mechanically attached or adhered to the roof deck shall be designed to resist the design wind load pressures for cladding in Chapter 16. 1504.8 Gravel and stone. Gravel or stone shall not be used on the roof of a building located in a hurricane-prone region as defined in Section 1609.2, or on any other building with a mean roof height exceeding that permitted by Table 1504.8 based on the exposure category and basic wind speed at the building site. 2006 INTERNATIONAL BUILDING CODE® 264 15_ibc_2006_pg264.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Thursday, January 05, 2006 12:52:31 PM 2 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES TABLE 1504.8 MAXIMUM ALLOWABLE MEAN ROOF HEIGHT PERMITTED FOR BUILDINGS WITH GRAVEL OR STONE ON THE ROOF IN AREAS OUTSIDE A HURRICANE-PRONE REGION fied as Class A by an approved testing agency. Class A roof assemblies shall be permitted for use in buildings or structures of all types of construction. Exception: Class A roof assemblies include those with coverings of brick, masonry, slate, clay or concrete roof tile, exposed concrete roof deck, ferrous or copper shingles or sheets. MAXIMUM MEAN ROOF HEIGHT (ft)a,c BASIC WIND SPEED FROM FIGURE 1609 (mph)b B C D 85 170 60 30 90 110 35 15 95 75 20 NP 100 55 15 NP 105 40 NP NP 110 30 NP NP 115 20 NP NP 120 15 NP NP Greater than 120 NP NP NP Exposure category 1505.3 Class B roof assemblies. Class B roof assemblies are those that are effective against moderate fire-test exposure. Class B roof assemblies and roof coverings shall be listed and identified as Class B by an approved testing agency. Exception: Class B roof assemblies include those with coverings of metal sheets and shingles. 1505.4 Class C roof assemblies. Class C roof assemblies are those that are effective against light fire-test exposure. Class C roof assemblies and roof coverings shall be listed and identified as Class C by an approved testing agency. For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s. a. Mean roof height in accordance with Section 1609.2. b. For intermediate values of basic wind speed, the height associated with the next higher value of wind speed shall be used, or direct interpolation is permitted. c. NP = gravel and stone not permitted for any roof height. SECTION 1505 FIRE CLASSIFICATION 1505.1 General. Roof assemblies shall be divided into the classes defined below. Class A, B and C roof assemblies and roof coverings required to be listed by this section shall be tested in accordance with ASTM E 108 or UL 790. In addition, fire-retardant-treated wood roof coverings shall be tested in accordance with ASTM D 2898. The minimum roof coverings installed on buildings shall comply with Table 1505.1 based on the type of construction of the building. TABLE 1505.1a,b MINIMUM ROOF COVERING CLASSIFICATION FOR TYPES OF CONSTRUCTION IB IIA IIB IIIA IIIB IV VA VB B B B Cc B Cc B B Cc SECTION 1506 MATERIALS 1 foot = 304.8 mm, 1 square foot = 0.0929 m2. For SI: a. Unless otherwise required in accordance with the International Wildland-Urban Interface Code or due to the location of the building within a fire district in accordance with Appendix D. b. Nonclassified roof coverings shall be permitted on buildings of Group R-3 and Group U occupancies, where there is a minimum fire-separation distance of 6 feet measured from the leading edge of the roof. c. Buildings that are not more than two stories in height and having not more than 6,000 square feet of projected roof area and where there is a minimum 10-foot fire-separation distance from the leading edge of the roof to a lot line on all sides of the building, except for street fronts or public ways, shall be permitted to have roofs of No. 1 cedar or redwood shakes and No. 1 shingles. 1505.2 Class A roof assemblies. Class A roof assemblies are those that are effective against severe fire test exposure. Class A roof assemblies and roof coverings shall be listed and identi2006 INTERNATIONAL BUILDING CODE® 15_ibc_2006_pg_265.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Friday, January 13, 2006 11:10:21 AM 1505.6 Fire-retardant-treated wood shingles and shakes. Fire-retardant-treated wood shakes and shingles shall be treated by impregnation with chemicals by the full-cell vacuum-pressure process, in accordance with AWPA C1. Each bundle shall be marked to identify the manufactured unit and the manufacturer, and shall also be labeled to identify the classification of the material in accordance with the testing required in Section 1505.1, the treating company and the quality control agency. 1505.7 Special purpose roofs. Special purpose wood shingle or wood shake roofing shall conform with the grading and application requirements of Section 1507.8 or 1507.9. In addition, an underlayment of 0.625-inch (15.9 mm) Type X water-resistant gypsum backing board or gypsum sheathing shall be placed under minimum nominal 0.5-inch-thick (12.7 mm) wood structural panel solid sheathing or 1-inch (25 mm) nominal spaced sheathing. Exception: Skylights and sloped glazing that comply with Chapter 24 or Section 2610. IA 1505.5 Nonclassified roofing. Nonclassified roofing is approved material that is not listed as a Class A, B or C roof covering. 1506.1 Scope. The requirements set forth in this section shall apply to the application of roof-covering materials specified herein. Roof coverings shall be applied in accordance with this chapter and the manufacturer’s installation instructions. Installation of roof coverings shall comply with the applicable provisions of Section 1507. 1506.2 Compatibility of materials. Roofs and roof coverings shall be of materials that are compatible with each other and with the building or structure to which the materials are applied. 1506.3 Material specifications and physical characteristics. Roof-covering materials shall conform to the applicable standards listed in this chapter. In the absence of applicable standards or where materials are of questionable suitability, testing 265 3 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES by an approved agency shall be required by the building official to determine the character, quality and limitations of application of the materials. asphalt shingles shall be installed in accordance with the manufacturer’s printed installation instructions for steep-slope roof applications. 1506.4 Product identification. Roof-covering materials shall be delivered in packages bearing the manufacturer’s identifying marks and approved testing agency labels required in accordance with Section 1505. Bulk shipments of materials shall be accompanied with the same information issued in the form of a certificate or on a bill of lading by the manufacturer. 1507.2.8 Underlayment application. For roof slopes from two units vertical in 12 units horizontal (17-percent slope) and up to four units vertical in 12 units horizontal (33-percent slope), underlayment shall be two layers applied in the following manner. Apply a minimum 19-inch-wide (483 mm) strip of underlayment felt parallel with and starting at the eaves, fastened sufficiently to hold in place. Starting at the eave, apply 36-inch-wide (914 mm) sheets of underlayment overlapping successive sheets 19 inches (483 mm), by fastened sufficiently to hold in place. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. For roof slopes of four units vertical in 12 units horizontal (33-percent slope) or greater, underlayment shall be one layer applied in the following manner. Underlayment shall be applied shingle fashion, parallel to and starting from the eave and lapped 2 inches (51 mm), fastened sufficiently to hold in place. Distortions in the underlayment shall not interfere with the ability of the shingles to seal. SECTION 1507 REQUIREMENTS FOR ROOF COVERINGS 1507.1 Scope. Roof coverings shall be applied in accordance with the applicable provisions of this section and the manufacturer’s installation instructions. ➡ 1507.2 Asphalt shingles. The installation of asphalt shingles shall comply with the provisions of this section. 1507.2.1 Deck requirements. Asphalt shingles shall be fastened to solidly sheathed decks. 1507.2.2 Slope. Asphalt shingles shall only be used on roof slopes of two units vertical in 12 units horizontal (17-percent slope) or greater. For roof slopes from two units vertical in 12 units horizontal (17-percent slope) up to four units vertical in 12 units horizontal (33-percent slope), double underlayment application is required in accordance with Section 1507.2.8. 1507.2.8.1 High wind attachment. Underlayment applied in areas subject to high winds (greater than 110 mph in accordance with Figure 1609) shall be applied with corrosion- resistant fasteners in accordance with the manufacturer’s instructions. Fasteners are to be applied along the overlap at a maximum spacing of 36 inches (914 mm) on center. 1507.2.3 Underlayment. Unless otherwise noted, required underlayment shall conform to ASTM D 226, Type I, ASTM D 4869, Type I, or ASTM D 6757. 1507.2.8.2 Ice dam membrane. In areas where there has been a history of ice forming along the eaves causing a backup of water, a membrane that consists of at least two layers of underlayment cemented together or of a self-adhering polymer modified bitumen sheet shall be used in lieu of normal underlayment and extend from the eave’s edge to a point at least 24 inches (610 mm) inside the exterior wall line of the building. 1507.2.4 Self-adhering polymer modified bitumen sheet. Self-adhering polymer modified bitumen sheet shall comply with ASTM D 1970. 1507.2.5 Asphalt shingles. Asphalt shingles shall have self-seal strips or be interlocking and comply with ASTM D 225 or ASTM D 3462. Asphalt shingle packaging shall bear labeling indicating compliance with ASTM D 3161 or a listing by an approved testing agency in accordance with the requirements of Section 1609.5.2. Exception: Detached accessory structures that contain no conditioned floor area. 1507.2.9 Flashings. Flashing for asphalt shingles shall comply with this section. Flashing shall be applied in accordance with this section and the asphalt shingle manufacturer’s printed instructions. 1507.2.6 Fasteners. Fasteners for asphalt shingles shall be galvanized, stainless steel, aluminum or copper roofing nails, minimum 12 gage [0.105 inch (2.67 mm)] shank with a minimum 0.375 inch-diameter (9.5 mm) head, of a length to penetrate through the roofing materials and a minimum of 0.75 inch (19.1 mm) into the roof sheathing. Where the roof sheathing is less than 0.75 inch (19.1 mm) thick, the nails shall penetrate through the sheathing. Fasteners shall comply with ASTM F 1667. 1507.2.9.1 Base and cap flashing. Base and cap flashing shall be installed in accordance with the manufacturer’s instructions. Base flashing shall be of either corrosion-resistant metal of minimum nominal 0.019-inch (0.483 mm) thickness or mineral-surfaced roll roofing weighing a minimum of 77 pounds per 100 square feet (3.76 kg/m2). Cap flashing shall be corrosion-resistant metal of minimum nominal 0.019-inch (0.483 mm) thickness. 1507.2.7 Attachment. Asphalt shingles shall have the minimum number of fasteners required by the manufacturer and Section 1504.1. Asphalt shingles shall be secured to the roof with not less than four fasteners per strip shingle or two fasteners per individual shingle. Where the roof slope exceeds 20 units vertical in 12 units horizontal (166-percent slope), 1507.2.9.2 Valleys. Valley linings shall be installed in accordance with the manufacturer’s instructions before 2006 INTERNATIONAL BUILDING CODE® 266 15_ibc_2006_pg266.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Thursday, January 05, 2006 12:58:12 PM 4 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES applying shingles. Valley linings of the following types shall be permitted: 1507.3.1 Deck requirements. Concrete and clay tile shall be installed only over solid sheathing or spaced structural sheathing boards. 1. For open valleys (valley lining exposed) lined with metal, the valley lining shall be at least 16 inches (406 mm) wide and of any of the corrosion-resistant metals in Table 1507.2.9.2. 1507.3.2 Deck slope. Clay and concrete roof tile shall be installed on roof slopes of 21/2 units vertical in 12 units horizontal (21-percent slope) or greater. For roof slopes from 21/2 units vertical in 12 units horizontal (21-percent slope) to four units vertical in 12 units horizontal (33-percent slope), double underlayment application is required in accordance with Section 1507.3.3. 2. For open valleys, valley lining of two plies of mineral-surfaced roll roofing complying with ASTM D 3909 or ASTM D 6380 shall be permitted. The bottom layer shall be 18 inches (457 mm) and the top layer a minimum of 36 inches (914 mm) wide. 3. For closed valleys (valleys covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D 6380, Class S Type III, Class M Type II or ASTM D 3909 and at least 36 inches (914 mm) wide or types as described in Items 1 and 2 above shall be permitted. Specialty underlayment shall comply with ASTM D 1970. 1507.2.9.3 Drip edge. Provide drip edge at eaves and gables of shingle roofs. Overlap to be a minimum of 2 inches (51 mm). Eave drip edges shall extend 0.25 inch (6.4 mm) below sheathing and extend back on the roof a minimum of 2 inches (51 mm). Drip edge shall be mechanically fastened a maximum of 12 inches (305 mm) o.c. 1507.3.3 Underlayment. Unless otherwise noted, required underlayment shall conform to: ASTM D 226, Type II; ASTM D 2626 or ASTM D 6380, Class M mineral-surfaced roll roofing. 1507.3.3.1 Low-slope roofs. For roof slopes from 21/2 units vertical in 12 units horizontal (21-percent slope), up to four units vertical in 12 units horizontal (33-percent slope), underlayment shall be a minimum of two layers applied as follows: 1. Starting at the eave, a 19-inch (483 mm) strip of underlayment shall be applied parallel with the eave and fastened sufficiently in place. 2. Starting at the eave, 36-inch-wide (914 mm) strips of underlayment felt shall be applied overlapping successive sheets 19 inches (483 mm) and fastened sufficiently in place. 1507.2.9.4 Crickets and saddles. A cricket or saddle shall be installed on the ridge side of any chimney or penetration greater than 30 inches (762 mm) wide as measured perpendicular to the slope. Cricket or saddle coverings shall be sheet metal or of the same material as the roof covering. 1507.3.3.2 High-slope roofs. For roof slopes of four units vertical in 12 units horizontal (33-percent slope) or greater, underlayment shall be a minimum of one layer of underlayment felt applied shingle fashion, parallel to, and starting from the eaves and lapped 2 inches (51 mm), fastened only as necessary to hold in place. 1507.3 Clay and concrete tile. The installation of clay and concrete tile shall comply with the provisions of this section. 1507.3.4 Clay tile. Clay roof tile shall comply with ASTM C 1167. TABLE 1507.2.9.2 VALLEY LINING MATERIAL MATERIAL MINIMUM THICKNESS GAGE WEIGHT Aluminum 0.024 in. — — Cold-rolled copper 0.0216 in. — ASTM B 370, 16 oz. per square ft. — — 16 oz Galvanized steel 0.0179 in. 26 (zinc-coated G90) — High-yield copper 0.0162 in. — ASTM B 370, 12 oz. per square ft. — — 2.5 pounds Lead-coated copper 0.0216 in. — ASTM B 101, 16 oz. per square ft. Lead-coated high-yield copper 0.0162 in. — ASTM B 101, 12 oz. per square ft. Painted terne — — 20 pounds Stainless steel — 28 — 0.027 in. — — Copper Lead Zinc alloy For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg, 1 ounce = 28.35 g. 2006 INTERNATIONAL BUILDING CODE® 15_ibc_2006_pg267.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Monday, December 19, 2005 11:00:43 AM 267 5 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES ➡ 2. The minimum slope for lapped, nonsoldered seam metal roofs with applied lap sealant shall be one-half unit vertical in 12 units horizontal (4-percent slope). Lap sealants shall be applied in accordance with the approved manufacturer’s installation instructions. 1507.3.5 Concrete tile. Concrete roof tile shall comply with ASTM C 1492. 1507.3.6 Fasteners. Tile fasteners shall be corrosion resistant and not less than 11 gage, 5/16-inch (8.0 mm) head, and of sufficient length to penetrate the deck a minimum of 0.75 inch (19.1 mm) or through the thickness of the deck, whichever is less. Attaching wire for clay or concrete tile shall not be smaller than 0.083 inch (2.1 mm). Perimeter fastening areas include three tile courses but not less than 36 inches (914 mm) from either side of hips or ridges and edges of eaves and gable rakes. 3. The minimum slope for standing seam of roof systems shall be one-quarter unit vertical in 12 units horizontal (2-percent slope). 1507.4.3 Material standards. Metal-sheet roof covering systems that incorporate supporting structural members shall be designed in accordance with Chapter 22. Metal-sheet roof coverings installed over structural decking shall comply with Table 1507.4.3.(1). The materials used for metal-sheet roof coverings shall be naturally corrosion resistant or provided with corrosion resistance in accordance with the standards and minimum thicknesses shown in Table 1507.4.3(2). 1507.3.7 Attachment. Clay and concrete roof tiles shall be fastened in accordance with Table 1507.3.7. 1507.3.8 Application. Tile shall be applied according to the manufacturer’s installation instructions, based on the following: 1. Climatic conditions. 1507.4.4 Attachment. Metal roof panels shall be secured to the supports in accordance with the approved manufacturer’s fasteners. In the absence of manufacturer recommendations, the following fasteners shall be used: 2. Roof slope. 3. Underlayment system. 4. Type of tile being installed. 1507.3.9 Flashing. At the juncture of the roof vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer’s installation instructions, and where of metal, shall not be less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch-wide (914 mm) underlayment of either one layer of Type I underlayment running the full length of the valley, or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to other required underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing underlayment shall be solid cemented to the roofing underlayment for slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet shall be installed. 1. Galvanized fasteners shall be used for steel roofs. 2. 300 series stainless-steel fasteners shall be used for copper roofs. 3. Stainless-steel fasteners are acceptable for all types of metal roofs. 1507.5 Metal roof shingles. The installation of metal roof shingles shall comply with the provisions of this section. 1507.5.1 Deck requirements. Metal roof shingles shall be applied to a solid or closely fitted deck, except where the roof covering is specifically designed to be applied to spaced sheathing. 1507.5.2 Deck slope. Metal roof shingles shall not be installed on roof slopes below three units vertical in 12 units horizontal (25-percent slope). 1507.5.3 Underlayment. Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869. In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal underlayment and extend from the eave’s edge to a point at least 24 inches (610 mm) inside the exterior wall line of the building. 1507.4 Metal roof panels. The installation of metal roof panels shall comply with the provisions of this section. Exception: Detached accessory structures that contain no conditioned floor area. 1507.4.1 Deck requirements. Metal roof panel roof coverings shall be applied to a solid or closely fitted deck, except where the roof covering is specifically designed to be applied to spaced supports. 1507.5.4 Material standards. Metal roof shingle roof coverings shall comply with Table 1507.4.3(1). The materials used for metal-roof shingle roof coverings shall be naturally corrosion resistant or provided with corrosion resistance in accordance with the standards and minimum thicknesses specified in the standards listed in Table 1507.4.3(2). 1507.4.2 Deck slope. Minimum slopes for metal roof panels shall comply with the following: 1. The minimum slope for lapped, nonsoldered seam metal roofs without applied lap sealant shall be three units vertical in 12 units horizontal (25-percent slope). 1507.5.5 Attachment. Metal roof shingles shall be secured to the roof in accordance with the approved manufacturer’s installation instructions. 2006 INTERNATIONAL BUILDING CODE® 268 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:53:00 AM 6 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES TABLE 1507.3.7 CLAY AND CONCRETE TILE ATTACHMENTa, b, c GENERAL — CLAY OR CONCRETE ROOF TILE Maximum basic wind speed (mph) Mean roof height (feet) 85 0-60 100 0-40 100 > 40-60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails. The nose of all ridge, hip and rake tiles shall be set in a bead of roofer’s mastic. 110 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. 120 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. 130 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. > 60 The fastening system shall resist the wind forces in Section 1609.5.2. All Roof slope up to 3:12 One fastener per tile. Flat tile without vertical laps, two fasteners per tile. Roof slope 3:12 and over Two fasteners per tile. Only one fastener on slopes of 7:12 and less for tiles with installed weight exceeding 7.5 lbs./sq. ft. having a width no greater than 16 inches. INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGSd, e (Installations on spaced/solid sheathing with battens or spaced sheathing) Maximum basic wind speed (mph) Mean roof height (feet) 85 0-60 100 0-40 100 > 40-60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be set in a bead of roofers’s mastic. 110 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. 120 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. 130 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. All > 60 The fastening system shall resist the wind forces in Section 1609.5.2. Roof slope up to 5:12 Roof slope 5:12 12:12 One fastener per tile every other Fasteners are not required. Tiles row. All perimeter tiles require with installed weight less than 9 one fastener. Tiles with installed lbs./sq. ft. require a minimum of weight less than 9 lbs./sq. ft. require a minimum of one one fastener per tile. fastener per tile. Roof slope 12:12 and over One fastener required for every tile. Tiles with installed weight less than 9 lbs./sq. ft. require a minimum of one fastener per tile. INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS (Installations on solid sheathing without battens) Maximum basic wind speed (mph) Mean roof height (feet) 85 0-60 100 0-40 One fastener per tile. 100 > 40-60 The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be set in a bead of roofer’s mastic. 110 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. 120 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. 130 0-60 The fastening system shall resist the wind forces in Section 1609.5.2. All > 60 The fastening system shall resist the wind forces in Section 1609.5.2. All roof slopes One fastener per tile. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 4.882 k g / m 2 . a. Minimum fastener size. Corrosion-resistant nails not less than No. 11 gage with 5/16-inch head. Fasteners shall be long enough to penetrate into the sheathing 0.75 inch or through the thickness of the sheathing, whichever is less. Attaching wire for clay and concrete tile shall not be smaller than 0.083 inch. b. Snow areas. A minimum of two fasteners per tile are required or battens and one fastener. c. Roof slopes greater than 24:12. The nose of all tiles shall be securely fastened. d. Horizontal battens. Battens shall be not less than 1inch by 2 inch nominal. Provisions shall be made for drainage by a minimum of 1/8-inch riser at each nail or by 4-foot-long battens with at least a 0.5-inch separation between battens. Horizontal battens are required for slopes over 7:12. e. Perimeter fastening areas include three tile courses but not less than 36 inches from either side of hips or ridges and edges of eaves and gable rakes. 2006 INTERNATIONAL BUILDING CODE® 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:53:01 AM 269 7 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES TABLE 1507.4.3(1) METAL ROOF COVERINGS ROOF COVERING TYPE 1507.5.6 Flashing. Roof valley flashing shall be of corrosion-resistant metal of the same material as the roof covering or shall comply with the standards in Table 1507.4.3(1). The valley flashing shall extend at least 8 inches (203 mm) from the centerline each way and shall have a splash diverter rib not less than 0.75 inch (19.1 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing shall have a 36-inch-wide (914 mm) underlayment directly under it consisting of either one layer of underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to underlayment required for metal roof shingles. The metal valley flashing underlayment shall be solidly cemented to the roofing underlayment for roof slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet shall be installed. STANDARD APPLICATION RATE/THICKNESS ASTM B 209, 0.024 inch minimum thickness for roll-formed panels and 0.019 inch minimum thickness for press-formed shingles. Aluminum Aluminum-zinc alloy ASTM A 792 AZ 50 coated steel Cold-rolled copper ASTM B 370 minimum 16 oz/sq. ft. and 12 oz./sq. ft. high yield copper for metal-sheet roof covering systems: 12 oz/sq. ft. for preformed metal shingle systems. Copper 16 oz./sq. ft. for metal-sheet roof-covering systems; 12 oz./sq. ft. for preformed metal shingle systems. Galvanized steel ASTM A 653 G-90 zinc-coateda. Hard lead 2 lbs./sq. ft. Lead-coated copper ASTM B 101 Prepainted steel ASTM A 755 Soft lead 3 lbs./sq. ft. Stainless steel ASTM A 240, 300 Series Alloys Steel ASTM A 924 1507.6 Mineral-surfaced roll roofing. The installation of mineral-surfaced roll roofing shall comply with this section. 1507.6.1 Deck requirements. Mineral-surfaced roll roofing shall be fastened to solidly sheathed roofs. 1507.6.2 Deck slope. Mineral-surfaced roll roofing shall not be applied on roof slopes below one unit vertical in 12 units horizontal (8-percent slope). 1507.6.3 Underlayment. Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869. In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal underlayment and extend from the eave’s edge to a point at least 24 inches (610 mm) inside the exterior wall line of the building. Terne coating of 40 lbs. per double base box, field painted where applicable in Terne and terne-coated stainless accordance with manufacturer’s installation instructions. 0.027 inch minimum thickness; 99.995% electrolytic high grade zinc with alloy additives of copper (0.08% - 0.20%), titanium (0.07% - 0.12%) and aluminum (0.015%). Zinc For SI: 1 ounce per square foot = 0.0026 kg/m2, 1 pound per square foot = 4.882 kg/m2, 1 inch = 25.4 mm, 1 pound = 0.454 kg. a. For Group U buildings, the minimum coating thickness for ASTM A 653 galvanized steel roofing shall be G. Exception: Detached accessory structures that contain no conditioned floor area. 1507.6.4 Material standards. Mineral-surfaced roll roofing shall conform to ASTM D 3909 or ASTM D 6380. 1507.7 Slate shingles. The installation of slate shingles shall comply with the provisions of this section. TABLE 1507.4.3(2) MINIMUM CORROSION RESISTANCE 1507.7.1 Deck requirements. Slate shingles shall be fastened to solidly sheathed roofs. 55% Aluminum-Zinc Alloy Coated ASTM A 792 AZ 50 Steel 5% Aluminum Alloy-coated steel ASTM A875 GF60 Aluminum-coated steel ASTM A463 T2 65 Galvanized Steel ASTM A 653 G-90 Prepainted Steel ASTM A 755a 1507.7.2 Deck slope. Slate shingles shall only be used on slopes of four units vertical in 12 units horizontal (4:12) or greater. 1507.7.3 Underlayment. Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869. In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall extend a. Paint systems in accordance with ASTM A 755 shall be applied over steel products with corrosion resistant coatings complying with ASTM A 792, ASTM A 875, ASTM A 463, or ASTM A 653. 2006 INTERNATIONAL BUILDING CODE® 270 15_ibc_2006_pg270.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Thursday, January 05, 2006 1:00:38 PM 8 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES from the eave’s edge to a point at least 24 inches (610 mm) inside the exterior wall line of the building. 1507.8.4 Material standards. Wood shingles shall be of naturally durable wood and comply with the requirements of Table 1507.8.4. Exception: Detached accessory structures that contain no conditioned floor area. TABLE 1507.8.4 WOOD SHINGLE MATERIAL REQUIREMENTS 1507.7.4 Material standards. Slate shingles shall comply with ASTM C 406. MATERIAL 4:12 < slope < 8:12 4 8:12 < slope < 20:12 3 slope ≥ 20:12 2 CSSB 1507.8.5 Attachment. Fasteners for wood shingles shall be corrosion resistant with a minimum penetration of 0.75 inch (19.1 mm) into the sheathing. For sheathing less than 0.5 inch (12.7 mm) in thickness, the fasteners shall extend through the sheathing. Each shingle shall be attached with a minimum of two fasteners. For SI: 1 inch = 25.4 mm. 1507.7.6 Flashing. Flashing and counterflashing shall be made with sheet metal. Valley flashing shall be a minimum of 15 inches (381 mm) wide. Valley and flashing metal shall be a minimum uncoated thickness of 0.0179-inch (0.455 mm) zinc-coated G90. Chimneys, stucco or brick walls shall have a minimum of two plies of felt for a cap flashing consisting of a 4-inch-wide (102 mm) strip of felt set in plastic cement and extending 1 inch (25 mm) above the first felt and a top coating of plastic cement. The felt shall extend over the base flashing 2 inches (51 mm). 1507.8 Wood shingles. The installation of wood shingles shall comply with the provisions of this section and Table 1507.8. 1507.8.1 Deck requirements. Wood shingles shall be installed on solid or spaced sheathing. Where spaced sheathing is used, sheathing boards shall not be less than 1-inch by 4-inch (25 mm by 102 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. 1507.8.6 Application. Wood shingles shall be laid with a side lap not less than 1.5 inches (38 mm) between joints in adjacent courses, and not be in direct alignment in alternate courses. Spacing between shingles shall be 0.25 to 0.375 inches (6.4 to 9.5 mm). Weather exposure for wood shingles shall not exceed that set in Table 1507.8.6. TABLE 1507.8.6 WOOD SHINGLE WEATHER EXPOSURE AND ROOF SLOPE EXPOSURE (inches) ROOFING MATERIAL LENGTH (inches) Shingles of naturally durable wood GRADE 3:12 pitch to < 4:12 4:12 pitch or steeper 16 No. 1 No. 2 No. 3 3.75 3.5 3 5 4 3.5 18 No. 1 No. 2 No. 3 4.25 4 3.5 5.5 4.5 4 24 No. 1 No. 2 No. 3 5.75 5.5 5 7.5 6.5 5.5 For SI: 1 inch = 25.4 mm. 1507.8.1.1 Solid sheathing required. Solid sheathing is required in areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water. 1507.8.2 Deck slope. Wood shingles shall be installed on slopes of three units vertical in 12 units horizontal (25-percent slope) or greater. 1507.8.3 Underlayment. Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869. In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal underlayment and extend from the eave’s edge to a point at least 24 inches (610 mm) inside the exterior wall line of the building. Exception: Detached accessory structures that contain no conditioned floor area. 2006 INTERNATIONAL BUILDING CODE® 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:53:01 AM 1, 2 or 3 CSSB = Cedar Shake and Shingle Bureau TABLE 1507.7.5 SLATE SHINGLE HEADLAP HEADLAP (inches) GRADING RULES Wood shingles of naturally durable wood 1507.7.5 Application. Minimum headlap for slate shingles shall be in accordance with Table 1507.7.5. Slate shingles shall be secured to the roof with two fasteners per slate. SLOPE APPLICABLE MINIMUM GRADES 1507.8.7 Flashing. At the juncture of the roof and vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer’s installation instructions, and where of metal, shall not be less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch-wide (914 mm) underlayment of either one layer of Type I underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to other required underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing underlayment shall be solidly cemented to the roofing underlayment for slopes under seven units vertical in 12 units horizontal (58-percent 271 9 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES used, sheathing boards shall not be less than 1-inch by 4-inch (25 mm by 102 mm) nominal dimensions and shall be spaced on centers equal to the weather exposure to coincide with the placement of fasteners. Where 1-inch by 4-inch (25 mm by 102 mm) spaced sheathing is installed at 10 inches (254 mm) o.c., additional 1-inch by 4-inch (25 mm by 102 mm) boards shall be installed between the sheathing boards. slope) or self-adhering polymer-modified bitumen sheet shall be installed. 1507.9 Wood shakes. The installation of wood shakes shall comply with the provisions of this section and Table 1507.8. 1507.9.1 Deck requirements. Wood shakes shall only be used on solid or spaced sheathing. Where spaced sheathing is TABLE 1507.8 WOOD SHINGLE AND SHAKE INSTALLATION ROOF ITEM 1. Roof slope WOOD SHINGLES Wood shingles shall be installed on slopes of Wood shakes shall be installed on slopes of four units three units vertical in 12 units horizontal vertical in 12 units horizontal (4:12) or greater. (3:12) or greater. 2. Deck requirement Temperate climate WOOD SHAKES — — Shakes shall be applied to roofs with solid or spaced Shingles shall be applied to roofs with solid sheathing.Where spaced sheathing is used, sheathing or spaced sheathing. Where spaced sheathing boards shall not be less than 1″ × 4″ nominal is used, sheathing boards shall not be less dimensions and shall be spaced on center equal to the than 1″ × 4″ nominal dimensions and shall weather exposure to coincide with the placement of be spaced on center equal to the weather fasteners. When 1″ × 4″ spaced sheathing is installed at exposure to coincide with the placement of 10 inches, boards must be installed between the fasteners. sheathing boards. Solid sheathing required. In areas where the average daily temperature in January is 25°F or less or where there is a possibility of ice forming along the eaves causing a backup of water. Solid sheathing is required. 3. Interlayment Interlayment shall comply with ASTM D 226, Type 1. No requirements. 4. Underlayment — — Temperate climate Underlayment shall comply with ASTM D 226, Type 1. Underlayment shall comply with ASTM D 226, Type 1. In areas where there is a possibility of ice forming along the eaves causing a backup of water. An ice shield that consists of at least two An ice shield that consists of at least two layers of layers of underlayment cemented together or underlayment cemented together or of a self-adhering of a self-adhering polymer-modified bitumen polymer-modified bitumen sheet shall extend from the sheet shall extend from the eave’s edge to a eave’s edge to a point at least 24 inches inside the point at least 24 inches inside the exterior exterior wall line of the building. wall line of the building. 5. Application — — Attachment Fasteners for wood shingles shall be corrosion resistant with a minimum penetration of 0.75 inch into the sheathing. For sheathing less than 0.5 inch thick, the fasteners shall extend through the sheathing. Fasteners for wood shakes shall be corrosion resistant with a minimum penetration of 0.75 inch into the sheathing. For sheathing less than 0.5 inch thick, the fasteners shall extend through the sheathing. No. of fasteners Two per shingle. Two per shake. Exposure Weather exposures shall not exceed those set Weather exposures shall not exceed those set forth in forth in Table 1507.8.6 Table 1507.9.7 Method Shingles shall be laid with a side lap of not Shakes shall be laid with a side lap of not less than 1.5 inches between joints in adjacent courses. Spacing less than 1.5 inches between joints in between shakes shall not be less than 0.375 inch or courses, and no two joints in any three adjacent courses shall be in direct alignment. more than 0.625 inch for shakes and tapersawn shakes of naturally durable wood and shall be 0.25 to 0.375 Spacing between shingles shall be 0.25 to inch for preservative taper sawn shakes. 0.375 inch. Flashing In accordance with Section 1507.8.7. In accordance with Section 1507.9.8. For SI: 1 inch = 25.4 mm, °C = [(°F) - 32]/1.8. 2006 INTERNATIONAL BUILDING CODE® 272 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:53:01 AM 10 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 1507.9.1.1 Solid sheathing required. Solid sheathing is required in areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water. TABLE 1507.9.7 WOOD SHAKE WEATHER EXPOSURE AND ROOF SLOPE ROOFING MATERIAL 1507.9.2 Deck slope. Wood shakes shall only be used on slopes of four units vertical in 12 units horizontal (33-percent slope) or greater. Shakes of naturally durable wood 1507.9.3 Underlayment. Underlayment shall comply with ASTM D 226, Type I or ASTM D 4869. In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice barrier that consists of at least two layers of underlayment cemented together or of a self-adhering polymer-modified bitumen sheet shall be used in lieu of normal underlayment and extend from the eave’s edge to a point at least 24 inches (610 mm) inside the exterior wall line of the building. Preservative-treated taper sawn shakes of Southern yellow pine Exception: Detached accessory structures that contain no conditioned floor area. 1507.9.5 Material standards. Wood shakes shall comply with the requirements of Table 1507.9.5. TABLE 1507.9.5 WOOD SHAKE MATERIAL REQUIREMENTS MATERIAL APPLICABL E GRADING RULES Wood shakes of naturally durable wood 1 CSSB Taper sawn shakes of naturally durable wood 1 or 2 CSSB Preservative-treated shakes and shingles of naturally durable wood 1 CSSB Fire-retardant-treated shakes and shingles of naturally durable wood 1 CSSB 1 or 2 TFS Preservative-treated taper sawn shakes of Southern pine treated in accordance with AWPA U1 (Commodity Specification A, Use Category 3B and Section 5.6) CSSB = Cedar Shake and Shingle Bureau. TFS = Forest Products Laboratory of the Texas Forest Services. 1507.9.6 Attachment. Fasteners for wood shakes shall be corrosion resistant with a minimum penetration of 0.75 inch (19.1 mm) into the sheathing. For sheathing less than 0.5 inch (12.7 mm) in thickness, the fasteners shall extend through the sheathing. Each shake shall be attached with a minimum of two fasteners. 1507.9.7 Application. Wood shakes shall be laid with a side lap not less than 1.5 inches (38 mm) between joints in adjacent courses. Spacing between shakes in the same course shall be 0.375 to 0.625 inches (9.5 to 15.9 mm) for shakes and taper sawn shakes of naturally durable wood and shall be 0.25 to 0.375 inch (6.4 to 9.5 mm) for preservative taper sawn shakes. Weather exposure for wood shakes shall not exceed those set in Table 1507.9.7. 2006 INTERNATIONAL BUILDING CODE® 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:53:02 AM GRADE 18 24 No. 1 No. 1 7.5 10a 18 24 No. 1 No. 1 7.5 10 18 24 No. 2 No. 2 5.5 7.5 18 24 No. 1 No. 1 7.5 10 18 24 No. 2 No. 2 5.5 7.5 For SI: 1 inch = 25.4 mm. a. For 24-inch by 0.375-inch handsplit shakes, the maximum exposure is 7.5 inches. 1507.9.8 Flashing. At the juncture of the roof and vertical surfaces, flashing and counterflashing shall be provided in accordance with the manufacturer’s installation instructions, and where of metal, shall not be less than 0.019-inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal. The valley flashing shall extend at least 11 inches (279 mm) from the centerline each way and have a splash diverter rib not less than 1 inch (25 mm) high at the flow line formed as part of the flashing. Sections of flashing shall have an end lap of not less than 4 inches (102 mm). For roof slopes of three units vertical in 12 units horizontal (25-percent slope) and over, the valley flashing shall have a 36-inch-wide (914 mm) underlayment of either one layer of Type I underlayment running the full length of the valley or a self-adhering polymer-modified bitumen sheet complying with ASTM D 1970, in addition to other required underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less or where there is a possibility of ice forming along the eaves causing a backup of water, the metal valley flashing underlayment shall be solidly cemented to the roofing underlayment for slopes under seven units vertical in 12 units horizontal (58-percent slope) or self-adhering polymer-modified bitumen sheet shall be installed. 1507.9.4 Interlayment. Interlayment shall comply with ASTM D 226, Type I. MINIMUM GRADES Taper sawn shakes of naturally durable wood LENGTH (inches) EXPOSURE (inches) 4:12 PITCH OR STEEPER 1507.10 Built-up roofs. The installation of built-up roofs shall comply with the provisions of this section. 1507.10.1 Slope. Built-up roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage, except for coal-tar built-up roofs that shall have a design slope of a minimum one-eighth unit vertical in 12 units horizontal (1-percent slope). 1507.10.2 Material standards. Built-up roof covering materials shall comply with the standards in Table 1507.10.2. 1507.11 Modified bitumen roofing. The installation of modified bitumen roofing shall comply with the provisions of this section. 273 11 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES TABLE 1507.10.2 BUILT-UP ROOFING MATERIAL STANDARDS MATERIAL STANDARD STANDARD Acrylic coatings used in roofing ASTM D 6083 Aggregate surfacing ASTM D 1863 Asphalt adhesive used in roofing ASTM D 3747 Asphalt cements used in roofing ASTM D 3019; D 2822; D 4586 Asphalt-coated glass fiber base sheet ASTM D 4601 Asphalt coatings used in roofing ASTM D1227; D 2823; D 4479 Asphalt glass felt ASTM D 2178 Asphalt primer used in roofing ASTM D 41 1507.13 Thermoplastic single-ply roofing. The installation of thermoplastic single-ply roofing shall comply with the provisions of this section. 1507.13.1 Slope. Thermoplastic single-ply membrane roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope). 1507.13.2 Material standards. Thermoplastic single-ply roof coverings shall comply with ASTM D 4434, ASTM D 6754, ASTM D 6878 or CGSB CAN/CGSB 37-54. 1507.14 Sprayed polyurethane foam roofing. The installation of sprayed polyurethane foam roofing shall comply with the provisions of this section. 1507.14.1 Slope. Sprayed polyurethane foam roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage. Asphalt-saturated and asphalt-coated ASTM D 2626 organic felt base sheet Asphalt-saturated organic felt (perforated) ASTM D 226 Asphalt used in roofing ASTM D 312 Coal-tar cements used in roofing ASTM D 4022; D 5643 Coal-tar saturated organic felt ASTM D 227 Coal-tar pitch used in roofing ASTM D 450; Type I or II Coal-tar primer used in roofing, dampproofing and waterproofing ASTM D 43 Glass mat, coal tar ASTM D 4990 Glass mat, venting type ASTM D 4897 1507.14.2 Material standards. Spray-applied polyurethane foam insulation shall comply with ASTM C 1029. 1507.14.3 Application. Foamed-in-place roof insulation shall be installed in accordance with the manufacturer’s instructions. A liquid-applied protective coating that complies with Section 1507.15 shall be applied no less than 2 hours nor more than 72 hours following the application of the foam. 1507.14.4 Foam plastics. Foam plastic materials and installation shall comply with Chapter 26. 1507.15 Liquid-applied coatings. The installation of liquid-applied coatings shall comply with the provisions of this section. 1507.15.1 Slope. Liquid-applied roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope). Mineral-surfaced inorganic cap sheet ASTM D 3909 Thermoplastic fabrics used in roofing ASTM D 5665, D 5726 1507.15.2 Material standards. Liquid-applied roof coatings shall comply with ASTM C 836, ASTM C 957, ASTM D 1227 or ASTM D 3468, ASTM D 6083 or ASTM D 6694. 1507.11.1 Slope. Modified bitumen membrane roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage. 1507.11.2 Material standards. Modified bitumen roof coverings shall comply with CGSB 37-GP-56M, ASTM D 6162, ASTM D 6163, ASTM D 6164, ASTM D 6222, ASTM D 6223 or ASTM D 6298. 1507.12 Thermoset single-ply roofing. The installation of thermoset single-ply roofing shall comply with the provisions of this section. SECTION 1508 ROOF INSULATION 1508.1 General. The use of above-deck thermal insulation shall be permitted provided such insulation is covered with an approved roof covering and passes the tests of FM 4450 or UL 1256 when tested as an assembly. Exceptions: 1. Foam plastic roof insulation shall conform to the material and installation requirements of Chapter 26. 1507.12.1 Slope. Thermoset single-ply membrane roofs shall have a design slope of a minimum of one-fourth unit vertical in 12 units horizontal (2-percent slope) for drainage. 2. Where a concrete roof deck is used and the above-deck thermal insulation is covered with an approved roof covering. 1508.1.1 Cellulosic fiberboard. Cellulosic fiberboard roof insulation shall conform to the material and installation requirements of Chapter 23. 1507.12.2 Material standards. Thermoset single-ply roof coverings shall comply with ASTM D 4637, ASTM D 5019 or CGSB 37-GP-52M. 2006 INTERNATIONAL BUILDING CODE® 274 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:53:02 AM 12 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES fire separation distance of 20 feet (6096 mm) or greater from a common property line shall be of Type IV or noncombustible construction. Roofs shall be constructed of materials and fire-resistance rated as required in Table 601. Interior framing and walls shall be Type IV or noncombustible construction. 1508.2 Material standards. Above-deck thermal insulation board shall comply with the standards in Table 1508.2. TABLE 1508.2 MATERIAL STANDARDS FOR ROOF INSULATION Cellular glass board ASTM C 552 Composite boards ASTM C 1289, Type III, IV, V or VI Expanded polystyrene ASTM C 578 3. Unprotected noncombustible enclosures housing only mechanical equipment and located with a minimum fire separation distance of 20 feet (6096 mm) shall be permitted. Extruded polystyrene board ASTM C 578 Perlite board ASTM C 728 Polyisocyanurate board ASTM C 1289, Type I or Type II Wood fiberboard ASTM C 208 4. On one-story buildings, combustible unroofed mechanical equipment screens, fences or similar enclosures are permitted where located with a fire separation distance of at least 20 feet (6096 mm) from adjacent property lines and where not exceeding 4 feet (1219 mm) in height above the roof surface. SECTION 1509 ROOFTOP STRUCTURES 5. Dormers shall be of the same type of construction as the roof on which they are placed, or of the exterior walls of the building. 1509.1 General. The provisions of this section shall govern the construction of rooftop structures. 1509.2 Penthouses. A penthouse or other projection above the roof in structures of other than Type I construction shall not exceed 28 feet (8534 mm) above the roof where used as an enclosure for tanks or for elevators that run to the roof and in all other cases shall not extend more than 18 feet (5486 mm) above the roof. The aggregate area of penthouses and other rooftop structures shall not exceed one-third the area of the supporting roof. A penthouse, bulkhead or any other similar projection above the roof shall not be used for purposes other than shelter of mechanical equipment or shelter of vertical shaft openings in the roof. Provisions such as louvers, louver blades or flashing shall be made to protect the mechanical equipment and the building interior from the elements. Penthouses or bulkheads used for purposes other than permitted by this section shall conform to the requirements of this code for an additional story. The restrictions of this section shall not prohibit the placing of wood flagpoles or similar structures on the roof of any building. 1509.2.1 Type of construction. Penthouses shall be constructed with walls, floors and roof as required for the building. Exceptions: 1. On buildings of Type I and II construction, the exterior walls and roofs of penthouses with a fire separation distance of more than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be of at least 1-hour fire-resistance-rated noncombustible construction. Walls and roofs with a fire separation distance of 20 feet (6096 mm) or greater shall be of noncombustible construction. Interior framing and walls shall be of noncombustible construction. 2. On buildings of Type III, IV and V construction, the exterior walls of penthouses with a fire separation distance of more than 5 feet (1524 mm) and less than 20 feet (6096 mm) shall be at least 1-hour fire-resistance-rated construction. Walls with a 2006 INTERNATIONAL BUILDING CODE® 15_ibc_2006_pg275.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Thursday, January 05, 2006 1:01:28 PM 1509.3 Tanks. Tanks having a capacity of more than 500 gallons (2 m3) placed in or on a building shall be supported on masonry, reinforced concrete, steel or Type IV construction provided that, where such supports are located in the building above the lowest story, the support shall be fire-resistance rated as required for Type IA construction. 1509.3.1 Valve. Such tanks shall have in the bottom or on the side near the bottom, a pipe or outlet, fitted with a suitable quick opening valve for discharging the contents in an emergency through an adequate drain. 1509.3.2 Location. Such tanks shall not be placed over or near a line of stairs or an elevator shaft, unless there is a solid roof or floor underneath the tank. 1509.3.3 Tank cover. Unenclosed roof tanks shall have covers sloping toward the outer edges. 1509.4 Cooling towers. Cooling towers in excess of 250 square feet (23.2 m2) in base area or in excess of 15 feet (4572 mm) high where located on building roofs more than 50 feet (15 240 mm) high shall be of noncombustible construction. Cooling towers shall not exceed one-third of the supporting roof area. Exception: Drip boards and the enclosing construction of wood not less than 1 inch (25 mm) nominal thickness, provided the wood is covered on the exterior of the tower with noncombustible material. 1509.5 Towers, spires, domes and cupolas. Any tower, spire, dome or cupola shall be of a type of construction not less in fire-resistance rating than required for the building to which it is attached, except that any such tower, spire, dome or cupola that exceeds 85 feet (25 908 mm) in height above grade plane, exceeds 200 square feet (18.6 m2) in horizontal area or is used for any purpose other than a belfry or an architectural embellishment shall be constructed of and supported on Type I or II construction. 275 13 Color profile: Generic CMYK printer profile Composite Default screen ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 1509.5.1 Noncombustible construction required. Any tower, spire, dome or cupola that exceeds 60 feet (18 288) in height above the highest point at which it comes in contact with the roof, or that exceeds 200 square feet (18.6 m2) in area at any horizontal section, or which is intended to be used for any purpose other than a belfry or architectural embellishment, shall be entirely constructed of and supported by noncombustible materials. Such structures shall be separated from the building below by construction having a fire-resistance rating of not less than 1.5 hours with openings protected with a minimum 1.5-hour fire-protection rating. Structures, except aerial supports 12 feet (3658 mm) high or less, flagpoles, water tanks and cooling towers, placed above the roof of any building more than 50 feet (15 240 mm) in height, shall be of noncombustible material and shall be supported by construction of noncombustible material. 1509.5.2 Towers and spires. Towers and spires where enclosed shall have exterior walls as required for the building to which they are attached. The roof covering of spires shall be of a class of roof covering as required for the main roof of the rest of the structure. SECTION 1510 REROOFING 2. Metal panel, metal shingle and concrete and clay tile roof coverings shall be permitted to be installed over existing wood shake roofs when applied in accordance with Section 1510.4. 3. The application of a new protective coating over an existing spray polyurethane foam roofing system shall be permitted without tear-off of existing roof coverings. 1510.4 Roof recovering. Where the application of a new roof covering over wood shingle or shake roofs creates a combustible concealed space, the entire existing surface shall be covered with gypsum board, mineral fiber, glass fiber or other approved materials securely fastened in place. 1510.5 Reinstallation of materials. Existing slate, clay or cement tile shall be permitted for reinstallation, except that damaged, cracked or broken slate or tile shall not be reinstalled. Existing vent flashing, metal edgings, drain outlets, collars and metal counterflashings shall not be reinstalled where rusted, damaged or deteriorated. Aggregate surfacing materials shall not be reinstalled. 1510.6 Flashings. Flashings shall be reconstructed in accordance with approved manufacturer’s installation instructions. Metal flashing to which bituminous materials are to be adhered shall be prim ed prior to installation. 1510.1 General. Materials and methods of application used for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15. Exception: Reroofing shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal (2-percent slope) in Section 1507 for roofs that provide positive roof drainage. 1510.2 Structural and construction loads. Structural roof components shall be capable of supporting the roof-covering system and the material and equipment loads that will be encountered during installation of the system. 1510.3 Recovering versus replacement. New roof coverings shall not be installed without first removing all existing layers of roof coverings where any of the following conditions occur: 1. Where the existing roof or roof covering is water soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for additional roofing. 2. Where the existing roof covering is wood shake, slate, clay, cement or asbestos-cement tile. 3. Where the existing roof has two or more applications of any type of roof covering. Exceptions: 1. Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building’s structural system and that do not rely on existing roofs and roof coverings for support, shall not require the removal of existing roof coverings. 2006 INTERNATIONAL BUILDING CODE® 276 15_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\15_ibc_2006.vp Wednesday, December 07, 2005 10:53:02 AM 14 Color profile: Generic CMYK printer profile Composite Default screen CHAPTER 16 STRUCTURAL DESIGN ESSENTIAL FACILITIES. Buildings and other structures that are intended to remain operational in the event of extreme environmental loading from flood, wind, snow or earthquakes. 1602.1 Definitions. The following words and terms shall, for the purposes of this chapter, have the meanings shown herein. ALLOWABLE STRESS DESIGN. A method of proportioning structural members, such that elastically computed stresses produced in the members by nominal loads do not exceed specified allowable stresses (also called “working stress design”). FACTORED LOAD. The product of a nominal load and a load factor. BALCONY, EXTERIOR. An exterior floor projecting from and supported by a structure without additional independent supports. GUARD. See Section 1002.1. ➡ DEAD LOADS. The weight of materials of construction incorporated into the building, including but not limited to walls, floors, roofs, ceilings, stairways, built-in partitions, finishes, cladding and other similarly incorporated architectural and structural items, and the weight of fixed service equipment, such as cranes, plumbing stacks and risers, electrical feeders, heating, ventilating and air-conditioning systems and fire sprinkler systems. DECK. An exterior floor supported on at least two opposing sides by an adjacent structure, and/or posts, piers or other independent supports. IMPACT LOAD. The load resulting from moving machinery, elevators, craneways, vehicles and other similar forces and kinetic loads, pressure and possible surcharge from fixed or moving loads. LIMIT STATE. A condition beyond which a structure or member becomes unfit for service and is judged to be no longer useful for its intended function (serviceability limit state) or to be unsafe (strength limit state). LIVE LOADS. Those loads produced by the use and occupancy of the building or other structure and do not include construction or environmental loads such as wind load, snow load, rain load, earthquake load, flood load or dead load. ➡ DESIGN STRENGTH. The product of the nominal strength and a resistance factor (or strength reduction factor). DIAPHRAGM. A horizontal or sloped system acting to transmit lateral forces to the vertical-resisting elements. When the term “diaphragm” is used, it shall include horizontal bracing systems. Diaphragm, blocked. In light-frame construction, a diaphragm in which all sheathing edges not occurring on a framing member are supported on and fastened to blocking. Diaphragm boundary. In light-frame construction, a location where shear is transferred into or out of the diaphragm sheathing. Transfer is either to a boundary element or to another force-resisting element. LIVE LOADS (ROOF). Those loads produced (1) during maintenance by workers, equipment and materials; and (2) during the life of the structure by movable objects such as planters and by people. LOAD AND RESISTANCE FACTOR DESIGN (LRFD). A method of proportioning structural members and their connections using load and resistance factors such that no applicable limit state is reached when the structure is subjected to appropriate load combinations. The term “LRFD” is used in the design of steel and wood structures. LOAD EFFECTS. Forces and deformations produced in structural members by the applied loads. Diaphragm chord. A diaphragm boundary element perpendicular to the applied load that is assumed to take axial stresses due to the diaphragm moment. Diaphragm flexible. A diaphragm is flexible for the purpose of distribution of story shear and torsional moment where so indicated in Section 12.3.1 of ASCE 7, as modified in Section 1613.6.1. LOAD FACTOR. A factor that accounts for deviations of the actual load from the nominal load, for uncertainties in the analysis that transforms the load into a load effect, and for the probability that more than one extreme load will occur simultaneously. LOADS. Forces or other actions that result from the weight of building materials, occupants and their possessions, environ- 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:44 AM FABRIC PARTITIONS. A partition consisting of a finished surface made of fabric, without a continuous rigid backing, that is directly attached to a framing system in which the vertical framing members are spaced greater than 4 feet (1219 mm) on center. 277 1 ➡ SECTION 1602 DEFINITIONS AND NOTATIONS DURATION OF LOAD. The period of continuous application of a given load, or the aggregate of periods of intermittent applications of the same load. ➡ 1601.1 Scope. The provisions of this chapter shall govern the structural design of buildings, structures and portions thereof regulated by this code. Diaphragm, rigid. A diaphragm is rigid for the purpose of distribution of story shear and torsional moment when the lateral deformation of the diaphragm is less than or equal to two times the average story drift. ➡ SECTION 1601 GENERAL Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN NOMINAL LOADS. The magnitudes of the loads specified in this chapter (dead, live, soil, wind, snow, rain, flood and earthquake). L = Live load, except roof live load, including any permitted live load reduction. Lr = Roof live load including any permitted live load reduction. R = S = Rain load. Snow load. T = Self-straining force arising from contraction or expansion resulting from temperature change, shrinkage, moisture change, creep in component materials, movement due to differential settlement or combinations thereof. W = Load due to wind pressure. OCCUPANCY CATEGORY. A category used to determine structural requirements based on occupancy. OTHER STRUCTURES. Structures, other than buildings, for which loads are specified in this chapter. ➡ PANEL (PART OF A STRUCTURE). The section of a floor, wall or roof comprised between the supporting frame of two adjacent rows of columns and girders or column bands of floor or roof construction. RESISTANCE FACTOR. A factor that accounts for deviations of the actual strength from the nominal strength and the manner and consequences of failure (also called “strength reduction factor”). ➡ STRENGTH, NOMINAL. The capacity of a structure or member to resist the effects of loads, as determined by computations using specified material strengths and dimensions and equations derived from accepted principles of structural mechanics or by field tests or laboratory tests of scaled models, allowing for modeling effects and differences between laboratory and field conditions. SECTION 1603 CONSTRUCTION DOCUMENTS 1603.1 General. Construction documents shall show the size, section and relative locations of structural members with floor levels, column centers and offsets dimensioned. The design loads and other information pertinent to the structural design required by Sections 1603.1.1 through 1603.1.8 shall be indicated on the construction documents. Exception: Construction documents for buildings constructed in accordance with the conventional light-frame construction provisions of Section 2308 shall indicate the following structural design information: 1. Floor and roof live loads. STRENGTH, REQUIRED. Strength of a member, cross section or connection required to resist factored loads or related internal moments and forces in such combinations as stipulated by these provisions. 2. Ground snow load, Pg. 3. Basic wind speed (3-second gust), miles per hour (mph) (km/hr) and wind exposure. 4. Seismic design category and site class. STRENGTH DESIGN. A method of proportioning structural members such that the computed forces produced in the members by factored loads do not exceed the member design strength [also called “load and resistance factor design” (LRFD)]. The term “strength design” is used in the design of concrete and masonry structural elements. 5. Flood design data, if located in flood hazard areas established in Section 1612.3. 1603.1.1 Floor live load. The uniformly distributed, concentrated and impact floor live load used in the design shall be indicated for floor areas. Use of live load reduction in accordance with Section 1607.9 shall be indicated for each type of live load used in the design. VEHICLE BARRIER SYSTEM. A system of building components near open sides of a garage floor or ramp or building walls that act as restraints for vehicles. ➡ NOTATIONS. 1603.1.2 Roof live load. The roof live load used in the design shall be indicated for roof areas (Section 1607.11). D = E = Dead load. Combined effect of horizontal and vertical earthquake induced forces as defined in Section 12.4.2 of ASCE 7. Em = Maximum seismic load effect of horizontal and vertical seismic forces as set forth in Section 12.4.3 of ASCE 7. Load due to fluids with well-defined pressures and maximum heights. 1603.1.3 Roof snow load. The ground snow load, Pg, shall be indicated. In areas where the ground snow load, Pg, exceeds 10 pounds per square foot (psf) (0.479 kN/m2), the following additional information shall also be provided, regardless of whether snow loads govern the design of the roof: F = Fa = H = 1. Flat-roof snow load, Pf. 2. Snow exposure factor, Ce. 3. Snow load importance factor, I. 4. Thermal factor, Ct. Flood load. Load due to lateral earth pressures, ground water pressure or pressure of bulk materials. 1603.1.4 Wind design data. The following information related to wind loads shall be shown, regardless of whether 2006 INTERNATIONAL BUILDING CODE® 278 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:44 AM 2 ➡ mental effects, differential movement and restrained dimensional changes. Permanent loads are those loads in which variations over time are rare or of small magnitude, such as dead loads. All other loads are variable loads (see also “Nominal loads”). Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN wind loads govern the design of the lateral-force-resisting system of the building: 1603.1.8 Systems and components requiring special inspections for seismic resistance. Construction documents or specifications shall be prepared for those systems and components requiring special inspection for seismic resistance as specified in Section 1707.1 by the registered design professional responsible for their design and shall be submitted for approval in accordance with Section 106.1. Reference to seismic standards in lieu of detailed drawings is acceptable. 1. Basic wind speed (3-second gust), miles per hour (km/hr). 2. Wind importance factor, I, and occupancy category. 3. Wind exposure, if more than one wind exposure is utilized, the wind exposure and applicable wind direction shall be indicated. 1603.2 Restrictions on loading. It shall be unlawful to place, or cause or permit to be placed, on any floor or roof of a building, structure or portion thereof, a load greater than is permitted by these requirements. 4. The applicable internal pressure coefficient. 5. Components and cladding. The design wind pressures in terms of psf (kN/m2) to be used for the design of exterior component and cladding materials not specifically designed by the registered design professional. 1603.3 Live loads posted. Where the live loads for which each floor or portion thereof of a commercial or industrial building is or has been designed to exceed 50 psf (2.40 kN/m2), such design live loads shall be conspicuously posted by the owner in that part of each story in which they apply, using durable signs. It shall be unlawful to remove or deface such notices. 1603.1.5 Earthquake design data. The following information related to seismic loads shall be shown, regardless of whether seismic loads govern the design of the lateral-force-resisting system of the building: 1603.4 Occupancy permits for changed loads. Occupancy permits for buildings hereafter erected shall not be issued until the floor load signs, required by Section 1603.3, have been installed. 1. Seismic importance factor, I, and occupancy category. 2. Mapped spectral response accelerations, SS and S1. 3. Site class. 4. Spectral response coefficients, SDS and SD1. SECTION 1604 GENERAL DESIGN REQUIREMENTS 5. Seismic design category. 6. Basic seismic-force-resisting system(s). 1604.1 General. Building, structures and parts thereof shall be designed and constructed in accordance with strength design, load and resistance factor design, allowable stress design, empirical design or conventional construction methods, as permitted by the applicable material chapters. 7. Design base shear. 8. Seismic response coefficient(s), CS. 9. Response modification factor(s), R. 10. Analysis procedure used. 1603.1.6 Flood design data. For buildings located in whole or in part in flood hazard areas as established in Section 1612.3, the documentation pertaining to design, if required in Section 1612.5, shall be included and the following information, referenced to the datum on the community’s Flood Insurance Rate Map (FIRM), shall be shown, regardless of whether flood loads govern the design of the building: 1604.2 Strength. Buildings and other structures, and parts thereof, shall be designed and constructed to support safely the factored loads in load combinations defined in this code without exceeding the appropriate strength limit states for the materials of construction. Alternatively, buildings and other structures, and parts thereof, shall be designed and constructed to support safely the nominal loads in load combinations defined in this code without exceeding the appropriate specified allowable stresses for the materials of construction. 1. In flood hazard areas not subject to high-velocity wave action, the elevation of the proposed lowest floor, including the basement. Loads and forces for occupancies or uses not covered in this chapter shall be subject to the approval of the building official. 2. In flood hazard areas not subject to high-velocity wave action, the elevation to which any nonresidential building will be dry floodproofed. 1604.3 Serviceability. Structural systems and members thereof shall be designed to have adequate stiffness to limit deflections and lateral drift. See Section 12.12.1 of ASCE 7 for drift limits applicable to earthquake loading. 3. In flood hazard areas subject to high-velocity wave action, the proposed elevation of the bottom of the lowest horizontal structural member of the lowest floor, including the basement. 1603.1.7 Special loads. Special loads that are applicable to the design of the building, structure or portions thereof shall be indicated along with the specified section of this code that addresses the special loading condition. 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:44 AM 1604.3.1 Deflections. The deflections of structural members shall not exceed the more restrictive of the limitations of Sections 1604.3.2 through 1604.3.5 or that permitted by Table 1604.3. 1604.3.2 Reinforced concrete. The deflection of reinforced concrete structural members shall not exceed that permitted by ACI 318. 279 3 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN TABLE 1604.3 DEFLECTION LIMITSa, b, c, h, i L S or W f D + Ld,g Roof members:e Supporting plaster ceiling Supporting nonplaster ceiling Not supporting ceiling l/360 l/240 l/180 l/360 l/240 l/180 l/240 l/180 l/120 Floor members l/360 — l/240 — — l/240 l/120 — — Farm buildings — — l/180 Greenhouses — — l/120 CONSTRUCTION Exterior walls and interior partitions: With brittle finishes With flexible finishes For SI: 1 foot = 304.8 mm. a. For structural roofing and siding made of formed metal sheets, the total load deflection shall not exceed l/60. For secondary roof structural members supporting formed metal roofing, the live load deflection shall not exceed l/150. For secondary wall members supporting formed metal siding, the design wind load deflection shall not exceed l/90. For roofs, this exception only applies when the metal sheets have no roof covering. b. Interior partitions not exceeding 6 feet in height and flexible, folding and portable partitions are not governed by the provisions of this section. The deflection criterion for interior partitions is based on the horizontal load defined in Section 1607.13. c. See Section 2403 for glass supports. d. For wood structural members having a moisture content of less than 16 percent at time of installation and used under dry conditions, the deflection resulting from L + 0.5D is permitted to be substituted for the deflection resulting from L + D. e. The above deflections do not ensure against ponding. Roofs that do not have sufficient slope or camber to assure adequate drainage shall be investigated for ponding. See Section 1611 for rain and ponding requirements and Section 1503.4 for roof drainage requirements. f. The wind load is permitted to be taken as 0.7 times the “component and cladding” loads for the purpose of determining deflection limits herein. g. For steel structural members, the dead load shall be taken as zero. h. For aluminum structural members or aluminum panels used in skylights and sloped glazing framing, roofs or walls of sunroom additions or patio covers, not supporting edge of glass or aluminum sandwich panels, the total load deflection shall not exceed l/60. For aluminum sandwich panels used in roofs or walls of sunroom additions or patio covers, the total load deflection shall not exceed l/120. i. For cantilever members, l shall be taken as twice the length of the cantilever. 1604.3.3 Steel. The deflection of steel structural members shall not exceed that permitted by AISC 360, AISI-NAS, AISI-General, AISI-Truss, ASCE 3, ASCE 8, SJI JG-1.1, SJI K-1.1 or SJI LH/DLH-1.1, as applicable. 1604.3.4 Masonry. The deflection of masonry structural members shall not exceed that permitted by ACI 530/ASCE 5/TMS 402. 1604.3.5 Aluminum. The deflection of aluminum structural members shall not exceed that permitted by AA ADM1. 1604.3.6 Limits. Deflection of structural members over span, l, shall not exceed that permitted by Table 1604.3. 1604.4 Analysis. Load effects on structural members and their connections shall be determined by methods of structural analysis that take into account equilibrium, general stability, geometric compatibility and both short- and long-term material properties. Members that tend to accumulate residual deformations under repeated service loads shall have included in their analysis the added eccentricities expected to occur during their service life. Any system or method of construction to be used shall be based on a rational analysis in accordance with well-established principles of mechanics. Such analysis shall result in a system that provides a complete load path capable of transferring loads from their point of origin to the load-resisting elements. The total lateral force shall be distributed to the various vertical elements of the lateral-force-resisting system in proportion to their rigidities, considering the rigidity of the horizontal bracing system or diaphragm. Rigid elements assumed not to be a part of the lateral-force-resisting system are permitted to be incorporated into buildings provided their effect on the action of the system is considered and provided for in the design. Except where diaphragms are flexible, or are permitted to be analyzed as flexible, provisions shall be made for the increased forces induced on resisting elements of the structural system resulting from torsion due to eccentricity between the center of application of the lateral forces and the center of rigidity of the lateral-force-resisting system. Every structure shall be designed to resist the overturning effects caused by the lateral forces specified in this chapter. See Section 1609 for wind loads, Section 1610 for lateral soil loads and Section 1613 for earthquake loads. 1604.5 Occupancy category. Buildings shall be assigned an occupancy category in accordance with Table 1604.5. 1604.5.1 Multiple occupancies. Where a structure is occupied by two or more occupancies not included in the same occupancy category, the structure shall be assigned the classification of the highest occupancy category corresponding to the various occupancies. Where structures have two or more portions that are structurally separated, each portion shall be separately classified. Where a separated portion of a structure provides required access to, required egress from or shares life safety components with another portion having a higher occupancy category, both portions shall be assigned to the higher occupancy category. 1604.6 In-situ load tests. The building official is authorized to require an engineering analysis or a load test, or both, of any construction whenever there is reason to question the safety of the construction for the intended occupancy. Engineering analysis and load tests shall be conducted in accordance with Section 1713. 1604.7 Preconstruction load tests. Materials and methods of construction that are not capable of being designed by approved engineering analysis or that do not comply with the applicable material design standards listed in Chapter 35, or alternative test procedures in accordance with Section 1711, shall be load tested in accordance with Section 1714. 2006 INTERNATIONAL BUILDING CODE® 280 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:45 AM 4 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN TABLE 1604.5 OCCUPANCY CATEGORY OF BUILDINGS AND OTHER STRUCTURES OCCUPANCY CATEGORY NATURE OF OCCUPANCY I Buildings and other structures that represent a low hazard to human life in the event of failure, including but not limited to: Agricultural facilities. Certain temporary facilities. Minor storage facilities. II Buildings and other structures except those listed in Occupancy Categories I, III and IV III Buildings and other structures that represent a substantial hazard to human life in the event of failure, including but not limited to: Covered structures whose primary occupancy is public assembly with an occupant load greater than 300. Buildings and other structures with elementary school, secondary school or day care facilities with an occupant load greater than 250. Buildings and other structures with an occupant load greater than 500 for colleges or adult education facilities. Health care facilities with an occupant load of 50 or more resident patients, but not having surgery or emergency treatment facilities. Jails and detention facilities. Any other occupancy with an occupant load greater than 5,000. Power-generating stations, water treatment for potable water, waste water treatment facilities and other public utility facilities not included in Occupancy Category IV. Buildings and other structures not included in Occupancy Category IV containing sufficient quantities of toxic or explosive substances to be dangerous to the public if released. Buildings and other structures designated as essential facilities, including but not limited to: Hospitals and other health care facilities having surgery or emergency treatment facilities. Fire, rescue and police stations and emergency vehicle garages. Designated earthquake, hurricane or other emergency shelters. Designated emergency preparedness, communication, and operation centers and other facilities required for emergency response. Power-generating stations and other public utility facilities required as emergency backup facilities for Occupancy Category IV structures. Structures containing highly toxic materials as defined by Section 307 where the quantity of the material exceeds the maximum allowable quantities of Table 307.1.(2). Aviation control towers, air traffic control centers and emergency aircraft hangars. Buildings and other structures having critical national defense functions. Water treatment facilities required to maintain water pressure for fire suppression. IV 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:45 AM 281 5 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN 1605.2.1 Basic load combinations. Where strength design or load and resistance factor design is used, structures and portions thereof shall resist the most critical effects from the following combinations of factored loads: 1604.8 Anchorage. 1604.8.1 General. Anchorage of the roof to walls and columns, and of walls and columns to foundations, shall be provided to resist the uplift and sliding forces that result from the application of the prescribed loads. 1604.8.2 Concrete and masonry walls. Concrete and masonry walls shall be anchored to floors, roofs and other structural elements that provide lateral support for the wall. Such anchorage shall provide a positive direct connection capable of resisting the horizontal forces specified in this chapter but not less than a minimum strength design horizontal force of 280 plf (4.10 kN/m) of wall, substituted for “E” in the load combinations of Section 1605.2 or 1605.3. Walls shall be designed to resist bending between anchors where the anchor spacing exceeds 4 feet (1219 mm). Required anchors in masonry walls of hollow units or cavity walls shall be embedded in a reinforced grouted structural element of the wall. See Sections 1609 for wind design requirements and see Section 1613 for earthquake design requirements. 1604.8.3 Decks. Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and designed for both vertical and lateral loads as applicable. Such attachment shall not be accomplished by the use of toenails or nails subject to withdrawal. Where positive connection to the primary building structure cannot be verified during inspection, decks shall be self-supporting. For decks with cantilevered framing members, connections to exterior walls or other framing members shall be designed and constructed to resist uplift resulting from the full live load specified in Table 1607.1 acting on the cantilevered portion of the deck. (Equation 16-1) 1.2(D + F + T) + 1.6(L + H) + 0.5 (Lr or S or R) (Equation 16-2) 1.2D + 1.6(Lr or S or R) + (f1L or 0.8W) (Equation 16-3) 1.2D + 1.6W + f1L + 0.5(Lr or S or R) (Equation 16-4) 1.2D + 1.0E + f1L + f2S (Equation 16-5) 0.9D + 1.6W + 1.6H (Equation 16-6) 0.9D + 1.0E + 1.6H (Equation 16-7) f1 = 1 for floors in places of public assembly, for live loads in excess of 100 pounds per square foot (4.79 kN/m2), and for parking garage live load, and = 0.5 for other live loads. f2 = 0.7 for roof configurations (such as saw tooth) that do not shed snow off the structure, and = 0.2 for other roof configurations. Exception: Where other factored load combinations are specifically required by the provisions of this code, such combinations shall take precedence. 1605.2.2 Other loads. Where Fa is to be considered in the design, the load combinations of Section 2.3.3 of ASCE 7 shall be used. 1605.3 Load combinations using allowable stress design. 1604.9 Counteracting structural actions. Structural members, systems, components and cladding shall be designed to resist forces due to earthquake and wind, with consideration of overturning, sliding, and uplift. Continuous load paths shall be provided for transmitting these forces to the foundation. Where sliding is used to isolate the elements, the effects of friction between sliding elements shall be included as a force. 1605.3.1 Basic load combinations. Where allowable stress design (working stress design), as permitted by this code, is used, structures and portions thereof shall resist the most critical effects resulting from the following combinations of loads: 1604.10 Wind and seismic detailing. Lateral-force-resisting systems shall meet seismic detailing requirements and limitations prescribed in this code and ASCE 7, excluding Chapter 14 and Appendix 11A, even when wind code prescribed load effects are greater than seismic load effects. SECTION 1605 LOAD COMBINATIONS 1605.1 General. Buildings and other structures and portions thereof shall be designed to resist the load combinations specified in Section 1605.2 or 1605.3 and Chapters 18 through 23, and the special seismic load combinations of Section 1605.4 where required by Section 12.3.3.3 or 12.10.2.1 of ASCE 7. Applicable loads shall be considered, including both earthquake and wind, in accordance with the specified load combinations. Each load combination shall also be investigated with one or more of the variable loads set to zero. D+F (Equation 16-8) D+H+F+L+T (Equation 16-9) D + H + F + (Lr or S or R) (Equation 16-10) D + H + F + 0.75(L + T) + 0.75 (Lr or S or R) (Equation 16-11) D + H + F + (W or 0.7E) (Equation 16-12) D + H + F + 0.75(W or 0.7E) + 0.75L + 0.75 (Lr or S or R) (Equation 16-13) 0.6D + W + H (Equation 16-14) 0.6D + 0.7E + H (Equation 16-15) Exceptions: 1. Crane hook loads need not be combined with roof live load or with more than three-fourths of the snow load or one-half of the wind load. 2. Flat roof snow loads of 30 psf (1.44 kN/m2) or less need not be combined with seismic loads. Where 1605.2 Load combinations using strength design or load and resistance factor design. 2006 INTERNATIONAL BUILDING CODE® 282 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:45 AM 1.4 (D + F) 6 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN flat roof snow loads exceed 30 psf (1.44 kN/m2), 20 percent shall be combined with seismic loads. elements and components shall be designed to resist the forces calculated using Equation 16-22 when the effects of the seismic ground motion are additive to gravity forces and those calculated using Equation 16-23 when the effects of the seismic ground motion counteract gravity forces. 1605.3.1.1 Stress increases. Increases in allowable stresses specified in the appropriate material chapter or the referenced standards shall not be used with the load combinations of Section 1605.3.1, except that a duration of load increase shall be permitted in accordance with Chapter 23. 1605.3.1.2 Other loads. Where Fa is to be considered in design, the load combinations of Section 2.4.2 of ASCE 7 shall be used. (Equation 16-16) D + L + (ωW) (Equation 16-17) D + L + ωW + S/2 (Equation 16-18) D + L + S + ωW/2 (Equation 16-19) D + L + S + E/1.4 (Equation 16-20) 0.9D + E/1.4 (Equation 16-21) 0.9D + Em (Equation 16-23) Em = The maximum effect of horizontal and vertical forces as set forth in Section 12.4.3 of ASCE 7. f1 = 1 for floors in places of public assembly, for live loads in excess of 100 psf (4.79 kN/m2) and for parking garage live load, or = 0.5 for other live loads. 1605.5 Heliports and helistops. Heliport and helistop landing areas shall be designed for the following loads, combined in accordance with Section 1605: 1. Dead load, D, plus the gross weight of the helicopter, Dh, plus snow load, S. 2. Dead load, D, plus two single concentrated impact loads, L, approximately 8 feet (2438 mm) apart applied anywhere on the landing area (representing the helicopter’s two main landing gear, whether skid type or wheeled type), having a magnitude of 0.75 times the gross weight of the helicopter. Both loads acting together total one-and one half times the gross weight of the helicopter. 3. Dead load, D, plus a uniform live load, L, of 100 psf (4.79 kN/m2). Exception: Landing areas designed for helicopters with gross weights not exceeding 3,000 pounds (13.34 kN) in accordance with Items 1 and 2 shall be permitted to be designed using a 40 psf (1.92 kN/m2) uniform live load in Item 3, provided the landing area is identified with a 3,000 pound (13.34 kN) weight limitation. This 40 psf (1.92 kN/m2) uniform live load shall not be reduced. The landing area weight limitation shall be indicated by the numeral “3” (kips) located in the bottom right corner of the landing area as viewed from the primary approach path. The landing area weight limitation shall be a minimum of 5 feet (1524 mm) in height. Exceptions: 1. Crane hook loads need not be combined with roof live loads or with more than three-fourths of the snow load or one-half of the wind load. 2. Flat roof snow loads of 30 psf (1.44 kN/m2) or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 psf (1.44 kN/m2), 20 percent shall be combined with seismic loads. SECTION 1606 DEAD LOADS 1606.1 General. Dead loads are those loads defined in Section 1602.1. Dead loads shall be considered permanent loads. 1605.3.2.1 Other loads. Where F, H or T are to be considered in the design, each applicable load shall be added to the combinations specified in Section 1605.3.2. 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. 1605.4 Special seismic load combinations. For both allowable stress design and strength design methods where specifically required by Section 1605.1 or by Chapters 18 through 23, 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:45 AM (Equation 16-22) where: 1605.3.2 Alternative basic load combinations. In lieu of the basic load combinations specified in Section 1605.3.1, structures and portions thereof shall be permitted to be designed for the most critical effects resulting from the following combinations. When using these alternative basic load combinations that include wind or seismic loads, allowable stresses are permitted to be increased or load combinations reduced where permitted by the material chapter of this code or the referenced standards. For load combinations that include the counteracting effects of dead and wind loads, only two-thirds of the minimum dead load likely to be in place during a design wind event shall be used. Where wind loads are calculated in accordance with Chapter 6 of ASCE 7, the coefficient ω in the following equations shall be taken as 1.3. For other wind loads, ω shall be taken as 1. When using these alternative load combinations to evaluate sliding, overturning and soil bearing at the soil-structure interface, the reduction of foundation overturning from Section 12.13.4 in ASCE 7 shall not be used. When using these alternative basic load combinations for proportioning foundations for loadings, which include seismic loads, the vertical seismic load effect, Ev, in Equation 12.4-4 of ASCE 7 is permitted to be taken equal to zero. D + L + (Lr or S or R) 1.2D + f1L + Em 283 7 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN SECTION 1607 LIVE LOADS vidual lanes so as to produce the maximum stress in each structural member. Single spans shall be designed for the uniform load in Table 1607.6 and one simultaneous concentrated load positioned to produce the maximum effect. Multiple spans shall be designed for the uniform load in Table 1607.6 on the spans and two simultaneous concentrated loads in two spans positioned to produce the maximum negative moment effect. Multiple span design loads, for other effects, shall be the same as for single spans. 1607.1 General. Live loads are those loads defined in Section 1602.1. 1607.2 Loads not specified. For occupancies or uses not designated in Table 1607.1, the live load shall be determined in accordance with a method approved by the building official. 1607.3 Uniform live loads. The live loads used in the design of buildings and other structures shall be the maximum loads expected by the intended use or occupancy but shall in no case be less than the minimum uniformly distributed unit loads required by Table 1607.1. 1607.7 Loads on handrails, guards, grab bars and vehicle barriers. Handrails, guards, grab bars as designed in ICC A117.1 and vehicle barriers shall be designed and constructed to the structural loading conditions set forth in this section. 1607.4 Concentrated loads. Floors and other similar surfaces shall be designed to support the uniformly distributed live loads prescribed in Section 1607.3 or the concentrated load, in pounds (kilonewtons), given in Table 1607.1, whichever produces the greater load effects. Unless otherwise specified, the indicated concentration shall be assumed to be uniformly distributed over an area 2.5 feet by 2.5 feet [6.25 square feet (0.58 m2)] and shall be located so as to produce the maximum load effects in the structural members. 1607.7.1 Handrails and guards. Handrail assemblies and guards shall be designed to resist a load of 50 plf (0.73 kN/m) applied in any direction at the top and to transfer this load through the supports to the structure. Glass handrail assemblies and guards shall also comply with Section 2407. Exceptions: 1. For one- and two-family dwellings, only the single concentrated load required by Section 1607.7.1.1 shall be applied. 1607.5 Partition loads. In office buildings and in other buildings where partition locations are subject to change, provisions for partition weight shall be made, whether or not partitions are shown on the construction documents, unless the specified live load exceeds 80 psf (3.83 kN/m2). The partition load shall not be less than a uniformly distributed live load of 15 psf (0.74 kN/m2). 2. In Group I-3, F, H and S occupancies, for areas that are not accessible to the general public and that have an occupant load less than 50, the minimum load shall be 20 pounds per foot (0.29 kN/m). 1607.7.1.1 Concentrated load. Handrail assemblies and guards shall be able to resist a single concentrated load of 200 pounds (0.89 kN), applied in any direction at any point along the top, and have attachment devices and supporting structure to transfer this loading to appropriate structural elements of the building. This load need not be assumed to act concurrently with the loads specified in the preceding paragraph. 1607.6 Truck and bus garages. Minimum live loads for garages having trucks or buses shall be as specified in Table 1607.6, but shall not be less than 50 psf (2.40 kN/m2), unless other loads are specifically justified and approved by the building official. Actual loads shall be used where they are greater than the loads specified in the table. TABLE 1607.6 UNIFORM AND CONCENTRATED LOADS UNIFORM LOAD (pounds/linear foot of lane) For moment design For shear design H20-44 and HS20-44 640 18,000 26,000 H15-44 and HS15-44 480 13,500 19,500 LOADING CLASSa 1607.7.1.2 Components. Intermediate rails (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds (0.22 kN) on an area equal to 1 square foot (0.093m2), including openings and space between rails. Reactions due to this loading are not required to be superimposed with those of Section 1607.7.1 or 1607.7.1.1. CONCENTRATED LOAD (pounds)b For SI: 1 pound per linear foot = 0.01459 kN/m, 1 pound = 0.004448 kN, 1 ton = 8.90 kN. a. An H loading class designates a two-axle truck with a semitrailer. An HS loading class designates a tractor truck with a semitrailer. The numbers following the letter classification indicate the gross weight in tons of the standard truck and the year the loadings were instituted. b. See Section 1607.6.1 for the loading of multiple spans. 1607.7.1.3 Stress increase. Where handrails and guards are designed in accordance with the provisions for allowable stress design (working stress design) exclusively for the loads specified in Section 1607.7.1, the allowable stress for the members and their attachments are permitted to be increased by one-third. 1607.6.1 Truck and bus garage live load application. The concentrated load and uniform load shall be uniformly distributed over a 10-foot (3048 mm) width on a line normal to the centerline of the lane placed within a 12-foot-wide (3658 mm) lane. The loads shall be placed within their indi- 1607.7.2 Grab bars, shower seats and dressing room bench seats. Grab bars, shower seats and dressing room bench seat systems shall be designed to resist a single concentrated load of 250 pounds (1.11 kN) applied in any direction at any point. 2006 INTERNATIONAL BUILDING CODE® 284 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:46 AM 8 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN TABLE 1607.1 MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS AND MINIMUM CONCENTRATED LIVE LOADSg OCCUPANCY OR USE UNIFORM (psf) CONCENTRATED (lbs.) 23. Libraries Corridors above first floor Reading rooms Stack rooms 80 60 150b 1,000 1,000 1,000 24. Manufacturing Heavy Light 250 125 3,000 2,000 25. Marquees 75 — 80 2,000 UNIFORM CONCENTRATED (psf) (lbs.) 1. Apartments (see residential) — — 2. Access floor systems Office use Computer use 50 100 2,000 2,000 3. Armories and drill rooms 150 — 4. Assembly areas and theaters Fixed seats (fastened to floor) Follow spot, projections and control rooms Lobbies Movable seats Stages and platforms OCCUPANCY OR USE 60 50 100 100 125 — 5. Balconies On one- and two-family residences only, and not exceeding 100 sq ft 100 60 6. Bowling alleys 75 — 7. Catwalks 40 300 8. Dance halls and ballrooms 100 — — occupancy servedh — 10. Dining rooms and restaurants 100 — 11. Dwellings (see residential) — — 12. Cornices 60 — 13. Corridors, except as otherwise indicated 100 — 14. Elevator machine room grating 2 (on area of 4 in ) — 300 15. Finish light floor plate construction 2 (on area of 1 in ) — — 200 16. Fire escapes On single-family dwellings only 100 40 — 17. Garages (passenger vehicles only) Trucks and buses 40 Note a See Section 1607.6 18. Grandstands (see stadium and arena bleachers) — — 19. Gymnasiums, main floors and balconies 100 — 20. Handrails, guards and grab bars See Section 1607.7 21. Hospitals Corridors above first floor Operating rooms, laboratories Patient rooms 80 60 40 1,000 1,000 1,000 22. Hotels (see residential) — — — — 100 50 2,000 2,000 27. Penal institutions Cell blocks Corridors 40 100 — 28. Residential One- and two-family dwellings i Uninhabitable attics without storage Uninhabitable attics with limited i, j, k storage Habitable attics and sleeping areas All other areas except balconies and decks Hotels and multiple-family dwellings Private rooms and corridors serving them Public rooms and corridors serving them Same as 9. Decks 26. Office buildings Corridors above first floor File and computer rooms shall be designed for heavier loads based on anticipated occupancy Lobbies and first-floor corridors Offices 29. Reviewing stands, grandstands and bleachers 10 20 30 40 — 40 100 Note c 30. Roofs All roof surfaces subject to maintenance workers Awnings and canopies Fabric construction supported by a 5 lightweight rigid skeleton structure nonreduceable All other construction 20 Ordinary flat, pitched, and curved roofs 20 Primary roof members, exposed to a work floor Single panel point of lower chord of roof trusses or any point along primary structural members supporting roofs: Over manufacturing, storage warehouses, and repair garages All other occupancies Roofs used for other special purposes Note 1 Roofs used for promenade purposes 60 Roofs used for roof gardens or 100 assembly purposes 300 2,000 300 Note 1 (continued) 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006_pg285.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Thursday, January 05, 2006 1:04:31 PM 285 9 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN TABLE 1607.1—continued MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS AND MINIMUM CONCENTRATED LIVE LOADSg OCCUPANCY OR USE 31. Schools Classrooms Corridors above first floor First-floor corridors UNIFORM CONCENTRATED (psf) (lbs.) 40 80 100 1,000 1,000 1,000 32. Scuttles, skylight ribs and accessible ceilings — 200 33. Sidewalks, vehicular driveways and yards, subject to trucking 250d 8,000e 34. Skating rinks 100 — 35. Stadiums and arenas Bleachers Fixed seats (fastened to floor) 100c 60c — 36. Stairs and exits One- and two-family dwellings All other 40 100 Note f 37. Storage warehouses (shall be designed for heavier loads if required for anticipated storage) Heavy Light 250 125 38. Stores Retail First floor Upper floors Wholesale, all floors 100 75 125 39. Vehicle barriers See Section 1607.7.3 40. Walkways and elevated platforms (other than exitways) 60 41. Yards and terraces, pedestrians 100 g. Where snow loads occur that are in excess of the design conditions, the structure shall be designed to support the loads due to the increased loads caused by drift buildup or a greater snow design determined by the building official (see Section 1608). For special-purpose roofs, see Section 1607.11.2.2. h. See Section 1604.8.3 for decks attached to exterior walls. i. Attics without storage are those where the maximum clear height between the joist and rafter is less than 42 inches, or where there are not two or more adjacent trusses with the same web configuration capable of containing a rectangle 42 inches high by 2 feet wide, or greater, located within the plane of the truss. For attics without storage, this live load need not be assumed to act concurrently with any other live load requirements. j. For attics with limited storage and constructed with trusses, this live load need only be applied to those portions of the bottom chord where there are two or more adjacent trusses with the same web configuration capable of containing a rectangle 42 inches high by 2 feet wide or greater, located within the plane of the truss. The rectangle shall fit between the top of the bottom chord and the bottom of any other truss member, provided that each of the following criteria is met: i. The attic area is accessible by a pull-down stairway or framed opening in accordance with Section 1209.2, and ii. The truss shall have a bottom chord pitch less than 2:12. iii.Bottom chords of trusses shall be designed for the greater of actual imposed dead load or 10 psf, uniformly distributed over the entire span. k. Attic spaces served by a fixed stair shall be designed to support the minimum live load specified for habitable attics and sleeping rooms. l. Roofs used for other special purposes shall be designed for appropriate loads as approved by the building official. 1607.7.3 Vehicle barriers. Vehicle barrier systems for passenger cars shall be designed to resist a single load of 6,000 pounds (26.70 kN) applied horizontally in any direction to the barrier system and shall have anchorage or attachment capable of transmitting this load to the structure. For design of the system, the load shall be assumed to act at a minimum height of 1 foot, 6 inches (457 mm) above the floor or ramp surface on an area not to exceed 1 square foot (305 mm2), and is not required to be assumed to act concurrently with any handraolil or guard loadings specified in the preceding paragraphs of Section 1607.7.1. Garages accommodating trucks and buses shall be designed in accordance with an approved method that contains provision for traffic railings. 1,000 1,000 1,000 — — 2 For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm , 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kN/m2, 1 pound = 0.004448 kN, 1 pound per cubic foot = 16 kg/m3 a. Floors in garages or portions of buildings used for the storage of motor vehicles shall be designed for the uniformly distributed live loads of Table 1607.1 or the following concentrated loads: (1) for garages restricted to vehicles accommodating not more than nine passengers, 3,000 pounds acting on an area of 4.5 inches by 4.5 inches; (2) for mechanical parking structures without slab or deck which are used for storing passenger vehicles only, 2,250 pounds per wheel. b. The loading applies to stack room floors that support nonmobile, double-faced library bookstacks, subject to the following limitations: 1. The nominal bookstack unit height shall not exceed 90 inches; 2. The nominal shelf depth shall not exceed 12 inches for each face; and 3. Parallel rows of double-faced bookstacks shall be separated by aisles not less than 36 inches wide. c. Design in accordance with the ICC Standard on Bleachers, Folding and Telescopic Seating and Grandstands. d. Other uniform loads in accordance with an approved method which contains provisions for truck loadings shall also be considered where appropriate. e. The concentrated wheel load shall be applied on an area of 20 square inches. f. Minimum concentrated load on stair treads (on area of 4 square inches) is 300 pounds. 1607.8 Impact loads. The live loads specified in Section 1607.3 include allowance for impact conditions. Provisions shall be made in the structural design for uses and loads that involve unusual vibration and impact forces. 1607.8.1 Elevators. Elevator loads shall be increased by 100 percent for impact and the structural supports shall be designed within the limits of deflection prescribed by ASME A17.1. 1607.8.2 Machinery. For the purpose of design, the weight of machinery and moving loads shall be increased as follows to allow for impact: (1) elevator machinery, 100 percent; (2) light machinery, shaft- or motor-driven, 20 percent; (3) reciprocating machinery or power-driven units, 50 percent; (4) hangers for floors or balconies, 33 percent. Percentages shall be increased where specified by the manufacturer. 1607.9 Reduction in live loads. Except for roof uniform live loads, all other minimum uniformly distributed live loads, Lo, in Table 1607.1 are permitted to be reduced in accordance with Section 1607.9.1 or 1607.9.2. 2006 INTERNATIONAL BUILDING CODE® 286 16_ibc_2006_pg285-287.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Monday, December 19, 2005 11:21:37 AM 10 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN 1607.9.1 General. Subject to the limitations of Sections 1607.9.1.1 through 1607.9.1.4, members for which a value of KLLAT is 400 square feet (37.16 m2) or more are permitted to be designed for a reduced live load in accordance with the following equation: ⎛ 15 ⎞ ⎟ L = L o ⎜⎜ 0.25 + ⎟ K LL AT ⎠ ⎝ 1607.9.1.3 Special occupancies. Live loads of 100 psf (4.79 kN/m2) or less shall not be reduced in public assembly occupancies. (Equation 16-24) ⎛ 4.57 ⎞ ⎟ For SI: L = L o ⎜⎜ 0.25 + ⎟ K LL AT ⎠ ⎝ 1607.9.1.4 Special structural elements. Live loads shall not be reduced for one-way slabs except as permitted in Section 1607.9.1.1. Live loads of 100 psf (4.79 kN/m2) or less shall not be reduced for roof members except as specified in Section 1607.11.2. where: L = Reduced design live load per square foot (meter) of area supported by the member. Lo = Unreduced design live load per square foot (meter) of area supported by the member (see Table 1607.1). KLL = Live load element factor (see Table 1607.9.1). AT = Tributary area, in square feet (square meters). L shall not be less than 0.50Lo for members supporting one floor and L shall not be less than 0.40Lo for members supporting two or more floors. TABLE 1607.9.1 LIVE LOAD ELEMENT FACTOR, KLL ELEMENT KLL Interior columns Exterior columns without cantilever slabs 4 4 Edge columns with cantilever slabs 3 Corner columns with cantilever slabs Edge beams without cantilever slabs Interior beams 2 2 2 All other members not identified above including: Edge beams with cantilever slabs Cantilever beams Two-way slabs Members without provisions for continuous shear transfer normal to their span 1 1607.9.1.2 Passenger vehicle garages. The live loads shall not be reduced in passenger vehicle garages except the live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent, but the live load shall not be less than L as calculated in Section 1607.9.1. 1607.9.2 Alternate floor live load reduction. As an alternative to Section 1607.9.1, floor live loads are permitted to be reduced in accordance with the following provisions. Such reductions shall apply to slab systems, beams, girders, columns, piers, walls and foundations. 1. A reduction shall not be permitted in Group A occupancies. 2. A reduction shall not be permitted where the live load exceeds 100 psf (4.79 kN/m2) except that the design live load for members supporting two or more floors is permitted to be reduced by 20 percent. 3. A reduction shall not be permitted in passenger vehicle parking garages except that the live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent. 4. For live loads not exceeding 100 psf (4.79 kN/m2), the design live load for any structural member supporting 150 square feet (13.94 m2) or more is permitted to be reduced in accordance with the following equation: R = 0.08 (A -150) (Equation 16-25) For SI: R = 0.861 (A -13.94) Such reduction shall not exceed the smallest of: 1. 40 percent for horizontal members; 1607.9.1.1 Heavy live loads. Live loads that exceed 100 psf (4.79 kN/m2) shall not be reduced. 2. 60 percent for vertical members; or 3. R as determined by the following equation. Exceptions: 1. The live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent, but the live load shall not be less than L as calculated in Section 1607.9.1. 2. For uses other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and that such reductions are warranted. R = 23.1 (1 + D/Lo) (Equation 16-26) where: A = Area of floor supported by the member, square feet (m2). D = Dead load per square foot (m2) of area supported. Lo = Unreduced live load per square foot (m2) of area supported. R = Reduction in percent. ➡ 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006_pg287.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Thursday, January 05, 2006 1:05:19 PM 287 11 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN R1 = 0.6 for At > 600 square feet (55.74 m2) 1607.10 Distribution of floor loads. Where uniform floor live loads are involved in the design of structural members arranged so as to create continuity, the minimum applied loads shall be the full dead loads on all spans in combination with the floor live loads on spans selected to produce the greatest effect at each location under consideration. It shall be permitted to reduce floor live loads in accordance with Section 1607.9. where: At = Tributary area (span length multiplied by effective width) in square feet (m2) supported by any structural member, and 1607.11 Roof loads. The structural supports of roofs and marquees shall be designed to resist wind and, where applicable, snow and earthquake loads, in addition to the dead load of construction and the appropriate live loads as prescribed in this section, or as set forth in Table 1607.1. The live loads acting on a sloping surface shall be assumed to act vertically on the horizontal projection of that surface. (Equation 16-27) (Equation 16-31) R2 = 1.2 – 0.05 F for 4 < F < 12 (Equation 16-32) R2 = 0.6 for F > 12 (Equation 16-33) F = For a sloped roof, the number of inches of rise per foot (for SI: F = 0.12 × slope, with slope expressed as a percentage), or for an arch or dome, the rise-to-span ratio multiplied by 32. 1607.11.2.2 Special-purpose roofs. Roofs used for promenade purposes, roof gardens, assembly purposes or other special purposes shall be designed for a minimum live load as required in Table 1607.1. Such roof live loads are permitted to be reduced in accordance with 1607.9. 1607.11.2.3 Landscaped roofs. Where roofs are to be landscaped, the uniform design live load in the landscaped area shall be 20 psf (0.958 kN/m2). The weight of the landscaping materials shall be considered as dead load and shall be computed on the basis of saturation of the soil. 1607.11.2 Reduction in roof live loads. The minimum uniformly distributed roof live loads, Lo, in Table 1607.1 are permitted to be reduced according to the following provisions. Lr = Lo R1R2 R2 = 1 for F ≤ 4 where: 1607.11.1 Distribution of roof loads. Where uniform roof live loads are reduced to less than 20 psf (0.96 kN/m2) in accordance with Section 1607.11.2.1 and are involved in the design of structural members arranged so as to create continuity, the minimum applied loads shall be the full dead loads on all spans in combination with the roof live loads on adjacent spans or on alternate spans, whichever produces the greatest effect. See Section 1607.11.2 for minimum roof live loads and Section 7.5 of ASCE 7 for partial snow loading. 1607.11.2.1 Flat, pitched and curved roofs. Ordinary flat, pitched and curved roofs are permitted to be designed for a reduced roof live load as specified in the following equation or other controlling combinations of loads in Section 1605, whichever produces the greater load. In structures where special scaffolding is used as a work surface for workers and materials during maintenance and repair operations, a lower roof load than specified in the following equation shall not be used unless approved by the building official. Greenhouses shall be designed for a minimum roof live load of 12 psf (0.58 kN/m2). (Equation 16-30) 1607.11.2.4 Awnings and canopies. Awnings and canopies shall be designed for uniform live loads as required in Table 1607.1 as well as for snow loads and wind loads as specified in Sections 1608 and 1609. 1607.12 Crane loads. The crane live load shall be the rated capacity of the crane. Design loads for the runway beams, including connections and support brackets, of moving bridge cranes and monorail cranes shall include the maximum wheel loads of the crane and the vertical impact, lateral and longitudinal forces induced by the moving crane. 1607.12.1 Maximum wheel load. The maximum wheel loads shall be the wheel loads produced by the weight of the bridge, as applicable, plus the sum of the rated capacity and the weight of the trolley with the trolley positioned on its runway at the location where the resulting load effect is maximum. where: 12 ≤ Lr ≤ 20 For SI: Lr = Lo R1R2 where: 0.58 ≤ Lr ≤ 0.96 Lr = Reduced live load per square foot (m2) of horizontal projection in pounds per square foot (kN/m2). 1607.12.2 Vertical impact force. The maximum wheel loads of the crane shall be increased by the percentages shown below to determine the induced vertical impact or vibration force: The reduction factors R1 and R2 shall be determined as follows: R1 = 1 for At ≤ 200 square feet (18.58 m2) (Equation 16-28) R1 = 1.2 – 0.001At for 200 square feet < At < 600 square feet (Equation 16-29) Pendant-operated bridge cranes (powered) · 10 percent For SI: 1.2 – 0.011At for 18.58 square meters < At < 55.74 square meters Bridge cranes or monorail cranes with hand-geared bridge, trolley and hoist · · · · · 0 percent Monorail cranes (powered) · · · · · · · · · 25 percent Cab-operated or remotely operated bridge cranes (powered) · · · · · · · · · · · 25 percent 2006 INTERNATIONAL BUILDING CODE® 288 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:47 AM 12 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN 1607.12.3 Lateral force. The lateral force on crane runway beams with electrically powered trolleys shall be calculated as 20 percent of the sum of the rated capacity of the crane and the weight of the hoist and trolley. The lateral force shall be assumed to act horizontally at the traction surface of a runway beam, in either direction perpendicular to the beam, and shall be distributed according to the lateral stiffness of the runway beam and supporting structure. 2. A concentrated load of 40 pounds (0.176 kN) applied to an 8-inch diameter (203 mm) area [50.3 square inches (32 452 mm2)] of the fabric face at a height of 54 inches (1372 mm) above the floor. 1607.12.4 Longitudinal force. The longitudinal force on crane runway beams, except for bridge cranes with hand-geared bridges, shall be calculated as 10 percent of the maximum wheel loads of the crane. The longitudinal force shall be assumed to act horizontally at the traction surface of a runway beam, in either direction parallel to the beam. 1608.1 General. Design snow loads shall be determined in accordance with Chapter 7 of ASCE 7, but the design roof load shall not be less than that determined by Section 1607. Exception: Fabric partitions complying with Section 1607.13.1 shall not be required to resist the minimum horizontal load of 5 psf (0.24 kN/m2). 1607.13.1 Fabric partitions. Fabric partitions that exceed 6 feet (1829 mm) in height, including their finish materials, shall have adequate strength to resist the following load conditions: 1. A horizontal distributed load of 5 psf (0.24 kN/m2) applied to the partition framing. The total area used to determine the distributed load shall be the area of the fabric face between the framing members to which the fabric is attached. The total distributed load shall be uniformly applied to such framing members in proportion to the length of each member. 1608.2 Ground snow loads. The ground snow loads to be used in determining the design snow loads for roofs shall be determined in accordance with ASCE 7 or Figure 1608.2 for the contiguous United States and Table 1608.2 for Alaska. Site-specific case studies shall be made in areas designated “CS” in Figure 1608.2. Ground snow loads for sites at elevations above the limits indicated in Figure 1608.2 and for all sites within the CS areas shall be approved. Ground snow load determination for such sites shall be based on an extreme value statistical analysis of data available in the vicinity of the site using a value with a 2-percent annual probability of being exceeded (50-year mean recurrence interval). Snow loads are zero for Hawaii, except in mountainous regions as approved by the building official. ➡ 1607.13 Interior walls and partitions. Interior walls and partitions that exceed 6 feet (1829 mm) in height, including their finish materials, shall have adequate strength to resist the loads to which they are subjected but not less than a horizontal load of 5 psf (0.240 kN/m2). SECTION 1608 SNOW LOADS SECTION 1609 WIND LOADS 1609.1 Applications. Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads prescribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures. TABLE 1608.2 GROUND SNOW LOADS, pg , FOR ALASKAN LOCATIONS LOCATION POUNDS PER SQUARE FOOT LOCATION POUNDS PER SQUARE FOOT LOCATION POUNDS PER SQUARE FOOT Adak 30 Galena 60 Petersburg 150 Anchorage 50 Gulkana 70 St. Paul Islands 40 Angoon 70 Homer 40 Seward 50 Barrow 25 Juneau 60 Shemya 25 Barter Island 35 Kenai 70 Sitka 50 Bethel 40 Kodiak 30 Talkeetna 120 Big Delta 50 Kotzebue 60 Unalakleet 50 Cold Bay 25 McGrath 70 Valdez 160 Cordova 100 Nenana 80 Whittier 300 Fairbanks 60 Nome 70 Wrangell 60 Fort Yukon 60 Palmer 50 Yakutat 150 2 For SI: 1 pound per square foot = 0.0479 kN/m . 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:47 AM 289 13 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1608.2 GROUND SNOW LOADS, pg, FOR THE UNITED STATES (psf) 2006 INTERNATIONAL BUILDING CODE® 290 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:48 AM 14 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1608.2–continued GROUND SNOW LOADS, pg, FOR THE UNITED STATES (psf) 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:48 AM 291 15 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN nents and cladding loads determined in accordance with the provisions of ASCE 7. Attachment in accordance with Table 1609.1.2 is permitted for buildings with a mean roof height of 33 feet (10 058 mm) or less where wind speeds do not exceed 130 mph (57.2 m/s). 1609.1.1 Determination of wind loads. Wind loads on every building or structure shall be determined in accordance with Chapter 6 of ASCE 7. The type of opening protection required, the basic wind speed and the exposure category for a site is permitted to be determined in accordance with Section 1609 or ASCE 7. Wind shall be assumed to come from any horizontal direction and wind pressures shall be assumed to act normal to the surface considered. 2. Glazing in Occupancy Category I buildings as defined in Section 1604.5, including greenhouses that are occupied for growing plants on a production or research basis, without public access shall be permitted to be unprotected. 1. Subject to the limitations of Section 1609.1.1.1, the provisions of SBCCI SSTD 10 shall be permitted for applicable Group R-2 and R-3 buildings. 3. Glazing in Occupancy Category II, III or IV buildings located over 60 feet (18 288 mm) above the ground and over 30 feet (9144 mm) above aggregate surface roofs located within 1,500 feet (458 m) of the building shall be permitted to be unprotected. 2. Subject to the limitations of Section 1609.1.1.1, residential structures using the provisions of the AF&PA WFCM. 3. Designs using NAAMM FP 1001. 4. Designs using TIA/EIA-222 for antenna-supporting structures and antennas. 1609.1.2.1 Louvers. Louvers protecting intake and exhaust ventilation ducts not assumed to be open that are located within 30 feet (9144 mm) of grade shall meet requirements of an approved impact-resisting standard or the Large Missile Test of ASTM E 1996. 1609.1.1.1 Applicability. The provisions of SSTD 10 are applicable only to buildings located within Exposure B or C as defined in Section 1609.4. The provisions of SBCCI SSTD 10 and the AF&PA WFCM shall not apply to buildings sited on the upper half of an isolated hill, ridge or escarpment meeting the following conditions: TABLE 1609.1.2 WIND-BORNE DEBRIS PROTECTION FASTENING SCHEDULE FOR WOOD STRUCTURAL PANELSa,b,c,d 1. The hill, ridge or escarpment is 60 feet (18 288 mm) or higher if located in Exposure B or 30 feet (9144 mm) or higher if located in Exposure C; 1609.1.2 Protection of openings. In wind-borne debris regions, glazing in buildings shall be impact-resistant or protected with an impact-resistant covering meeting the requirements of an approved impact-resisting standard or ASTM E 1996 and ASTM E 1886 referenced therein as follows: 1. Glazed openings located within 30 feet (9144 mm) of grade shall meet the requirements of the Large Missile Test of ASTM E 1996. 2. Glazed openings located more than 30 feet (9144 mm) above grade shall meet the provisions of the Small Missile Test of ASTM E 1996. Panel 6 feet 6 feet Span Panel 8 feet 16 12 9 No. 8 screws 16 16 12 For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.4 N, 1 mile per hour = 0.44 m/s. a. This table is based on a maximum wind speed (3-second gust) of 130 mph and mean roof height of 33 feet or less. b. Fasteners shall be installed at opposing ends of the wood structural panel. Fasteners shall be located a minimum of 1 inch from the edge of the panel. c. Fasteners shall be long enough to penetrate through the exterior wall covering a minimum of 1.75 inches into wood wall framing; a minimum of 1.25 inches into concrete block or concrete; or into steel framing by at least three threads. Fasteners shall be located a minimum of 2.5 inches from the edge of concrete block or concrete. d. Where screws are attached to masonry or masonry/stucco, they shall be attached utilizing vibration-resistant anchors having a minimum withdrawal capacity of 490 pounds. 1609.2 Definitions. The following words and terms shall, for the purposes of Section 1609, have the meanings shown herein. HURRICANE-PRONE REGIONS. Areas vulnerable to hurricanes defined as: 1. The U. S. Atlantic Ocean and Gulf of Mexico coasts where the basic wind speed is greater than 90 mph (40 m/s) and 2. Hawaii, Puerto Rico, Guam, Virgin Islands and American Samoa. WIND-BORNE DEBRIS REGION. Portions of hurricane-prone regions that are within 1 mile (1.61 km) of the coastal mean high water line where the basic wind speed is 110 mph (48 m/s) or greater; or portions of hurricane-prone regions 2006 INTERNATIONAL BUILDING CODE® 292 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:48 AM 4 feet Span No. 6 screws Exceptions: 1. Wood structural panels with a minimum thickness of 7/16 inch (11.1 mm) and maximum panel span of 8 feet (2438 mm) shall be permitted for opening protection in one- and two-story buildings. Panels shall be precut so that they shall be attached to the framing surrounding the opening containing the product with the glazed opening. Panels shall be secured with the attachment hardware provided. Attachments shall be designed to resist the compo- Panel Span 4 feet 16 ➡ ➡ 3. The hill, ridge or escarpment is unobstructed upwind by other such topographic features for a distance from the high point of 50 times the height of the hill or 1 mile (1.61 km), whichever is greater. FASTENER SPACING (inches) FASTENER TYPE ➡ 2. The maximum average slope of the hill exceeds 10 percent; and ➡ Exceptions: ➡ Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN where the basic wind speed is 120 mph (53 m/s) or greater; or Hawaii. 1609.4.2 Surface roughness categories. A ground surface roughness within each 45-degree (0.79 rad) sector shall be determined for a distance upwind of the site as defined in Section 1609.4.3 from the categories defined below, for the purpose of assigning an exposure category as defined in Section 1609.4.3. ➡ 1609.3 Basic wind speed. The basic wind speed, in mph, for the determination of the wind loads shall be determined by Figure 1609. Basic wind speed for the special wind regions indicated, near mountainous terrain and near gorges shall be in accordance with local jurisdiction requirements. Basic wind speeds determined by the local jurisdiction shall be in accordance with Section 6.5.4 of ASCE 7. Surface Roughness B. Urban and suburban areas, wooded areas or other terrain with numerous closely spaced obstructions having the size of single-family dwellings or larger. In nonhurricane-prone regions, when the basic wind speed is estimated from regional climatic data, the basic wind speed shall be not less than the wind speed associated with an annual probability of 0.02 (50-year mean recurrence interval), and the estimate shall be adjusted for equivalence to a 3-second gust wind speed at 33 feet (10 m) above ground in Exposure Category C. The data analysis shall be performed in accordance with Section 6.5.4.2 of ASCE 7. Surface Roughness C. Open terrain with scattered obstructions having heights generally less than 30 feet (9144 mm). This category includes flat open country, grasslands, and all water surfaces in hurricane-prone regions. 1609.3.1 Wind speed conversion. When required, the 3-second gust basic wind speeds of Figure 1609 shall be converted to fastest-mile wind speeds, Vfm, using Table 1609.3.1 or Equation 16-34. (V3 S − 10. 5) 1.05 1609.4.3 Exposure categories. An exposure category shall be determined in accordance with the following: Exposure B. Exposure B shall apply where the ground surface roughness condition, as defined by Surface Roughness B, prevails in the upwind direction for a distance of at least 2,600 feet (792 m) or 20 times the height of the building, whichever is greater. (Equation 16-34) where: V3S = 3-second gust basic wind speed from Figure 1609. Exception: For buildings whose mean roof height is less than or equal to 30 feet (9144 mm), the upwind distance is permitted to be reduced to 1,500 feet (457 m). 1609.4 Exposure category. For each wind direction considered, an exposure category that adequately reflects the characteristics of ground surface irregularities shall be determined for the site at which the building or structure is to be constructed. Account shall be taken of variations in ground surface roughness that arise from natural topography and vegetation as well as from constructed features. 1609.4.1 Wind directions and sectors. For each selected wind direction at which the wind loads are to be evaluated, the exposure of the building or structure shall be determined for the two upwind sectors extending 45 degrees (0.79 rad) either side of the selected wind direction. The exposures in these two sectors shall be determined in accordance with Sections 1609.4.2 and 1609.4.3 and the exposure resulting in the highest wind loads shall be used to represent winds from that direction. Exposure C. Exposure C shall apply for all cases where Exposures B or D do not apply. Exposure D. Exposure D shall apply where the ground surface roughness, as defined by Surface Roughness D, prevails in the upwind direction for a distance of at least 5,000 feet (1524 m) or 20 times the height of the building, whichever is greater. Exposure D shall extend inland from the shoreline for a distance of 600 feet (183 m) or 20 times the height of the building, whichever is greater. 1609.5 Roof systems. 1609.5.1 Roof deck. The roof deck shall be designed to withstand the wind pressures determined in accordance with ASCE 7. TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEEDSa,b,c V3S 85 90 100 105 110 120 125 130 140 145 150 160 170 Vfm 71 76 85 90 95 104 109 114 123 128 133 142 152 For SI: 1 mile per hour = 0.44 m/s. a. Linear interpolation is permitted. b. V3S is the 3-second gust wind speed (mph). c. Vfm is the fastest mile wind speed (mph). 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006_update.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Thursday, December 08, 2005 8:28:43 AM 293 17 ➡ Vfm = Surface Roughness D. Flat, unobstructed areas and water surfaces outside hurricane-prone regions. This category includes smooth mud flats, salt flats and unbroken ice. Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1609 BASIC WIND SPEED (3-SECOND GUST) 2006 INTERNATIONAL BUILDING CODE® 294 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:53 AM 18 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1609—continued BASIC WIND SPEED (3-SECOND GUST) 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:56 AM 295 19 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1609–continued BASIC WIND SPEED (3-SECOND GUST) WESTERN GULF OF MEXICO HURRICANE COASTLINE 2006 INTERNATIONAL BUILDING CODE® 296 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:49:59 AM 20 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1609–continued BASIC WIND SPEED (3-SECOND GUST) EASTERN GULF OF MEXICO AND SOUTHEASTERN U.S. HURRICANE COASTLINE 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:02 AM 297 21 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1609–continued BASIC WIND SPEED (3-SECOND GUST) MID AND NORTHERN ATLANTIC HURRICANE COASTLINE 2006 INTERNATIONAL BUILDING CODE® 298 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:05 AM 22 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN Concrete and clay roof tiles complying with the following limitations shall be designed to withstand the aerodynamic uplift moment as determined by this section. 1609.5.2 Roof coverings. Roof coverings shall comply with Section 1609.5.1. Exception: Rigid tile roof coverings that are air permeable and installed over a roof deck complying with Section 1609.5.1 are permitted to be designed in accordance with Section 1609.5.3. 1. The roof tiles shall be either loose laid on battens, mechanically fastened, mortar set or adhesive set. 2. The roof tiles shall be installed on solid sheathing which has been designed as components and cladding. Asphalt shingles installed over a roof deck complying with Section 1609.5.1 shall be tested to determine the resistance of the sealant to uplift forces using ASTM D 6381. 3. An underlayment shall be installed in accordance with Chapter 15. Asphalt shingles installed over a roof deck complying with Section 1609.5.1 are permitted to be designed using UL 2390 to determine appropriate uplift and force coefficients applied to the shingle. 4. The tile shall be single lapped interlocking with a minimum head lap of not less than 2 inches (51 mm). 1609.5.3 Rigid tile. Wind loads on rigid tile roof coverings shall be determined in accordance with the following equation: 5. The length of the tile shall be between 1.0 and 1.75 feet (305 mm and 533 mm). Ma = qhCLbLLa[1.0 – GCp] 6. The exposed width of the tile shall be between 0.67 and 1.25 feet (204 mm and 381 mm). For SI: Ma = [ q h C L bLL a 1.0 − GC p (Equation 16-35) ] 7. The maximum thickness of the tail of the tile shall not exceed 1.3 inches (33 mm). 1, 000 8. Roof tiles using mortar set or adhesive set systems shall have at least two-thirds of the tile’s area free of mortar or adhesive contact. where: b CL = Exposed width, feet (mm) of the roof tile. = Lift coefficient. The lift coefficient for concrete and clay tile shall be 0.2 or shall be determined by test in accordance with Section 1715.2. SECTION 1610 SOIL LATERAL LOADS GCp = Roof pressure coefficient for each applicable roof zone determined from Chapter 6 of ASCE 7. Roof coefficients shall not be adjusted for internal pressure. L = Length, feet (mm) of the roof tile. La = Moment arm, feet (mm) from the axis of rotation to the point of uplift on the roof tile. The point of uplift shall be taken at 0.76L from the head of the tile and the middle of the exposed width. For roof tiles with nails or screws (with or without a tail clip), the axis of rotation shall be taken as the head of the tile for direct deck application or as the top edge of the batten for battened applications. For roof tiles fastened only by a nail or screw along the side of the tile, the axis of rotation shall be determined by testing. For roof tiles installed with battens and fastened only by a clip near the tail of the tile, the moment arm shall be determined about the top edge of the batten with consideration given for the point of rotation of the tiles based on straight bond or broken bond and the tile profile. Ma = Aerodynamic uplift moment, feet-pounds (N-mm) acting to raise the tail of the tile. qh = Wind velocity pressure, psf (kN/m2) determined from Section 6.5.10 of ASCE 7. 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:06 AM 1610.1 General. Basement, foundation and retaining walls shall be designed to resist lateral soil loads. Soil loads specified in Table 1610.1 shall be used as the minimum design lateral soil loads unless specified otherwise in a soil investigation report approved by the building official. Basement walls and other walls in which horizontal movement is restricted at the top shall be designed for at-rest pressure. Retaining walls free to move and rotate at the top are permitted to be designed for active pressure. Design lateral pressure from surcharge loads shall be added to the lateral earth pressure load. Design lateral pressure shall be increased if soils with expansion potential are present at the site. Exception: Basement walls extending not more than 8 feet (2438 mm) below grade and supporting flexible floor systems shall be permitted to be designed for active pressure. SECTION 1611 RAIN LOADS 1611.1 Design rain loads. Each portion of a roof shall be designed to sustain the load of rainwater that will accumulate on it if the primary drainage system for that portion is blocked plus the uniform load caused by water that rises above the inlet of the secondary drainage system at its design flow. R = 5.2 (ds + dh) (Equation 16-36) 299 23 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN For SI: R = 0.0098 (ds + dh) where: dh = Additional depth of water on the undeflected roof above the inlet of secondary drainage system at its design flow (i.e., the hydraulic head), in inches (mm). ds = Depth of water on the undeflected roof up to the inlet of secondary drainage system when the primary drainage system is blocked (i.e., the static head), in inches (mm). R = Rain load on the undeflected roof, in psf (kN/m2). When the phrase “undeflected roof” is used, deflections from loads (including dead loads) shall not be considered when determining the amount of rain on the roof. 1611.2 Ponding instability. For roofs with a slope less than 1/4 inch per foot [1.19 degrees (0.0208 rad)], the design calculations shall include verification of adequate stiffness to preclude progressive deflection in accordance with Section 8.4 of ASCE 7. 1611.3 Controlled drainage. Roofs equipped with hardware to control the rate of drainage shall be equipped with a secondary drainage system at a higher elevation that limits accumulation of water on the roof above that elevation. Such roofs shall be designed to sustain the load of rainwater that will accumulate on them to the elevation of the secondary drainage system plus the uniform load caused by water that rises above the inlet of the secondary drainage system at its design flow determined from Section 1611.1. Such roofs shall also be checked for ponding instability in accordance with Section 1611.2. SECTION 1612 FLOOD LOADS 1612.1 General. Within flood hazard areas as established in Section 1612.3, all new construction of buildings, structures and portions of buildings and structures, including substantial improvement and restoration of substantial damage to buildings and structures, shall be designed and constructed to resist the effects of flood hazards and flood loads. For buildings that are located in more than one flood hazard area, the provisions associated with the most restrictive flood hazard area shall apply. 1612.2 Definitions. The following words and terms shall, for the purposes of this section, have the meanings shown herein. BASE FLOOD. The flood having a 1-percent chance of being equaled or exceeded in any given year. TABLE 1610.1 SOIL LATERAL LOAD DESIGN LATERAL SOIL LOADa (pound per square foot per foot of depth) UNIFIED SOIL CLASSIFICATION Active pressure At-rest pressure Well-graded, clean gravels; gravel-sand mixes GW 30 60 Poorly graded clean gravels; gravel-sand mixes GP 30 60 Silty gravels, poorly graded gravel-sand mixes GM 40 60 Clayey gravels, poorly graded gravel-and-clay mixes GC 45 60 Well-graded, clean sands; gravelly sand mixes SW 30 60 Poorly graded clean sands; sand-gravel mixes SP 30 60 Silty sands, poorly graded sand-silt mixes SM 45 60 SM-SC 45 100 Clayey sands, poorly graded sand-clay mixes SC 60 100 Inorganic silts and clayey silts ML 45 100 Mixture of inorganic silt and clay ML-CL 60 100 Inorganic clays of low to medium plasticity CL 60 100 Organic silts and silt clays, low plasticity OL Note b Note b Inorganic clayey silts, elastic silts MH Note b Note b Inorganic clays of high plasticity CH Note b Note b Organic clays and silty clays OH Note b Note b DESCRIPTION OF BACKFILL MATERIALc Sand-silt clay mix with plastic fines For SI: 1 pound per square foot per foot of depth = 0.157 kPa/m, 1 foot = 304.8 mm. a. Design lateral soil loads are given for moist conditions for the specified soils at their optimum densities. Actual field conditions shall govern. Submerged or saturated soil pressures shall include the weight of the buoyant soil plus the hydrostatic loads. b. Unsuitable as backfill material. c. The definition and classification of soil materials shall be in accordance with ASTM D 2487. 2006 INTERNATIONAL BUILDING CODE® 300 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:06 AM 24 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN BASE FLOOD ELEVATION. The elevation of the base flood, including wave height, relative to the National Geodetic Vertical Datum (NGVD), North American Vertical Datum (NAVD) or other datum specified on the Flood Insurance Rate Map (FIRM). FLOOD INSURANCE RATE MAP (FIRM). An official map of a community on which the Federal Emergency Management Agency (FEMA) has delineated both the special flood hazard areas and the risk premium zones applicable to the community. BASEMENT. The portion of a building having its floor subgrade (below ground level) on all sides. FLOOD INSURANCE STUDY. The official report provided by the Federal Emergency Management Agency containing the Flood Insurance Rate Map (FIRM), the Flood Boundary and Floodway Map (FBFM), the water surface elevation of the base flood and supporting technical data. DESIGN FLOOD. The flood associated with the greater of the following two areas: 1. Area with a flood plain subject to a 1-percent or greater chance of flooding in any year; or FLOODWAY. The channel of the river, creek or other watercourse and the adjacent land areas that must be reserved in order to discharge the base flood without cumulatively increasing the water surface elevation more than a designated height. 2. Area designated as a flood hazard area on a community’s flood hazard map, or otherwise legally designated. DESIGN FLOOD ELEVATION. The elevation of the “design flood,” including wave height, relative to the datum specified on the community’s legally designated flood hazard map. In areas designated as Zone AO, the design flood elevation shall be the elevation of the highest existing grade of the building’s perimeter plus the depth number (in feet) specified on the flood hazard map. In areas designated as Zone AO where a depth number is not specified on the map, the depth number shall be taken as being equal to 2 feet (610 mm). DRY FLOODPROOFING. A combination of design modifications that results in a building or structure, including the attendant utility and sanitary facilities, being water tight with walls substantially impermeable to the passage of water and with structural components having the capacity to resist loads as identified in ASCE 7. EXISTING CONSTRUCTION. Any buildings and structures for which the “start of construction” commenced before the effective date of the community’s first flood plain management code, ordinance or standard. “Existing construction” is also referred to as “existing structures.” EXISTING STRUCTURE. See “Existing construction.” FLOOD or FLOODING. A general and temporary condition of partial or complete inundation of normally dry land from: 1. The overflow of inland or tidal waters. 2. The unusual and rapid accumulation or runoff of surface waters from any source. FLOOD DAMAGE-RESISTANT MATERIALS. Any construction material capable of withstanding direct and prolonged contact with floodwaters without sustaining any damage that requires more than cosmetic repair. SPECIAL FLOOD HAZARD AREA. The land area subject to flood hazards and shown on a Flood Insurance Rate Map or other flood hazard map as Zone A, AE, A1-30, A99, AR, AO, AH, V, VO, VE or V1-30. START OF CONSTRUCTION. The date of permit issuance for new construction and substantial improvements to existing structures, provided the actual start of construction, repair, reconstruction, rehabilitation, addition, placement or other improvement is within 180 days after the date of issuance. The actual start of construction means the first placement of permanent construction of a building (including a manufactured home) on a site, such as the pouring of a slab or footings, installation of pilings or construction of columns. Permanent construction does not include land preparation (such as clearing, excavation, grading or filling), the installation of streets or walkways, excavation for a basement, footings, piers or foundations, the erection of temporary forms or the installation of accessory buildings such as garages or sheds not occupied as dwelling units or not part of the main building. For a substantial improvement, the actual “start of construction” means the first alteration of any wall, ceiling, floor or other structural part of a building, whether or not that alteration affects the external dimensions of the building. SUBSTANTIAL DAMAGE. Damage of any origin sustained by a structure whereby the cost of restoring the structure to its before-damaged condition would equal or exceed 50 percent of the market value of the structure before the damage occurred. FLOOD HAZARD AREA. The greater of the following two areas: 1. The area within a flood plain subject to a 1-percent or greater chance of flooding in any year. 2. The area designated as a flood hazard area on a community’s flood hazard map, or otherwise legally designated. FLOOD HAZARD AREA SUBJECT TO HIGH VELOCITY WAVE ACTION. Area within the flood hazard area that is subject to high velocity wave action, and shown on a Flood Insurance Rate Map (FIRM) or other flood hazard map as Zone V, VO, VE or V1-30. 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:06 AM LOWEST FLOOR. The floor of the lowest enclosed area, including basement, but excluding any unfinished or flood-resistant enclosure, usable solely for vehicle parking, building access or limited storage provided that such enclosure is not built so as to render the structure in violation of this section. SUBSTANTIAL IMPROVEMENT. Any repair, reconstruction, rehabilitation, addition or improvement of a building or structure, the cost of which equals or exceeds 50 percent of the market value of the structure before the improvement or repair is started. If the structure has sustained substantial damage, any repairs are considered substantial improvement regardless of the actual repair work performed. The term does not, however, include either: 1. Any project for improvement of a building required to correct existing health, sanitary or safety code violations 301 25 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN identified by the building official and that are the minimum necessary to assure safe living conditions. 2.3. For breakaway walls designed to resist a nominal load of less than 10 psf (0.48 kN/m2) or more than 20 psf (0.96 kN/m2), construction documents shall include a statement that the breakaway wall is designed in accordance with ASCE 24. 1612.3 Establishment of flood hazard areas. To establish flood hazard areas, the governing body shall adopt a flood hazard map and supporting data. The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency in an engineering report entitled “The Flood Insurance Study for [INSERT NAME OF JURISDICTION],” dated [INSERT DATE OF ISSUANCE], as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto. The adopted flood hazard map and supporting data are hereby adopted by reference and declared to be part of this section. SECTION 1613 EARTHQUAKE LOADS 1613.1 Scope. Every structure, and portion thereof, including nonstructural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7, excluding Chapter 14 and Appendix 11A. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7. Exceptions: 1612.4 Design and construction. The design and construction of buildings and structures located in flood hazard areas, including flood hazard areas subject to high velocity wave action, shall be in accordance with ASCE 24. 1. Detached one- and two-family dwellings, assigned to Seismic Design Category A, B or C, or located where the mapped short-period spectral response acceleration, SS, is less than 0.4 g. 1612.5 Flood hazard documentation. The following documentation shall be prepared and sealed by a registered design professional and submitted to the building official: 2. The seismic-force-resisting system of wood-frame buildings that conform to the provisions of Section 2308 are not required to be analyzed as specified in this section. 1. For construction in flood hazard areas not subject to high-velocity wave action: 3. Agricultural storage structures intended only for incidental human occupancy. 1.1. The elevation of the lowest floor, including the basement, as required by the lowest floor elevation inspection in Section 109.3.3. 1.2. For fully enclosed areas below the design flood elevation where provisions to allow for the automatic entry and exit of floodwaters do not meet the minimum requirements in Section 2.6.2.1 of ASCE 24, construction documents shall include a statement that the design will provide for equalization of hydrostatic flood forces in accordance with Section 2.6.2.2 of ASCE 24. 1.3. For dry floodproofed nonresidential buildings, construction documents shall include a statement that the dry floodproofing is designed in accordance with ASCE 24. 4. Structures that require special consideration of their response characteristics and environment that are not addressed by this code or ASCE 7 and for which other regulations provide seismic criteria, such as vehicular bridges, electrical transmission towers, hydraulic structures, buried utility lines and their appurtenances and nuclear reactors. 1613.2 Definitions. The following words and terms shall, for the purposes of this section, have the meanings shown herein. DESIGN EARTHQUAKE GROUND MOTION. The earthquake ground motion that buildings and structures are specifically proportioned to resist in Section 1613. 2. For construction in flood hazard areas subject to high-velocity wave action: MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION. The most severe earthquake effects considered by this code. 2.1. The elevation of the bottom of the lowest horizontal structural member as required by the lowest floor elevation inspection in Section 109.3.3. MECHANICAL SYSTEMS. For the purposes of determining seismic loads in ASCE 7, mechanical systems shall include plumbing systems as specified therein. 2.2. Construction documents shall include a statement that the building is designed in accordance with ASCE 24, including that the pile or column foundation and building or structure to be attached thereto is designed to be anchored to resist flotation, collapse and lateral movement due to the effects of wind and flood loads acting simultaneously on all building components, and other load requirements of Chapter 16. ORTHOGONAL. To be in two horizontal directions, at 90 degrees (1.57 rad) to each other. SEISMIC DESIGN CATEGORY. A classification assigned to a structure based on its occupancy category and the severity of the design earthquake ground motion at the site. SEISMIC-FORCE-RESISTING SYSTEM. That part of the structural system that has been considered in the design to provide the required resistance to the prescribed seismic forces. 2006 INTERNATIONAL BUILDING CODE® 302 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:07 AM 26 ➡ 2. Any alteration of a historic structure provided that the alteration will not preclude the structure’s continued designation as a historic structure. Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN D, E or F in accordance with Table 1613.5.2. When the soil properties are not known in sufficient detail to determine the site class, Site Class D shall be used unless the building official or geotechnical data determines that Site Class E or F soil is likely to be present at the site. SITE CLASS. A classification assigned to a site based on the types of soils present and their engineering properties as defined in Section 1613.5.2. SITE COEFFICIENTS. The values of Fa and Fv indicated in Tables 1613.5.3(1) and 1613.5.3(2), respectively. 1613.5.3 Site coefficients and adjusted maximum considered earthquake spectral response acceleration parameters. The maximum considered earthquake spectral response acceleration for short periods, SMS, and at 1-second period, SM1, adjusted for site class effects shall be determined by Equations 16-37 and 16-38, respectively: 1613.3 Existing buildings. Additions, alterations, modification, or change of occupancy of existing buildings shall be in accordance with Sections 3403.2.3 and 3406.4. 1613.4 Special inspections. Where required by Section 1705.3, the statement of special inspections shall include the special inspections required by Section 1705.3.1. 1613.5 Seismic ground motion values. Seismic ground motion values shall be determined in accordance with this section. SMS = FaSs (Equation 16-37) SM1 = Fv S1 (Equation 16-38) 1613.5.1 Mapped acceleration parameters. The parameters Ss and S1 shall be determined from the 0.2 and 1-second spectral response accelerations shown on Figures 1613.5(1) through 1613.5(14). Where S1 is less than or equal to 0.04 and Ss is less than or equal to 0.15, the structure is permitted to be assigned to Seismic Design Category A. where: 1613.5.2 Site class definitions. Based on the site soil properties, the site shall be classified as either Site Class A, B, C, S1 = The mapped spectral accelerations for a 1-second period as determined in Section 1613.5.1. Fa = Site coefficient defined in Table 1613.5.3(1). Fv = Site coefficient defined in Table 1613.5.3(2). SS = The mapped spectral accelerations for short periods as determined in Section 1613.5.1. TABLE 1613.5.2 SITE CLASS DEFINITIONS AVERAGE PROPERTIES IN TOP 100 feet, SEE SECTION 1613.5.5 SITE CLASS SOIL PROFILE NAME Soil shear wave velocity, v S , (ft/s) A Hard rock v s > 5,000 N/A N/A B Rock 2,500 < v s ≤ 5,000 N/A N/A C Very dense soil and soft rock 1,200 < v s ≤ 2,500 N > 50 s u ≥ 2,000 D Stiff soil profile 600 ≤ v s ≤ 1,200 15 ≤ N ≤ 50 1,000 ≤ s u ≤ 2,000 E Soft soil profile v s < 600 N < 15 s u < 1,000 Standard penetration resistance, N Soil undrained shear strength, s u , (psf) Any profile with more than 10 feet of soil having the following characteristics: 1. Plasticity index PI > 20, E — 2. Moisture content w ≥ 40%, and 3. Undrained shear strength s u < 500 psf F — Any profile containing soils having one or more of the following characteristics: 1. Soils vulnerable to potential failure or collapse under seismic loading such as liquefiable soils, quick and highly sensitive clays, collapsible weakly cemented soils. 2. Peats and/or highly organic clays (H > 10 feet of peat and/or highly organic clay where H = thickness of soil) 3. Very high plasticity clays (H >25 feet with plasticity index PI >75) 4. Very thick soft/medium stiff clays (H >120 feet) For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa. N/A = Not applicable 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:07 AM 303 27 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN TABLE 1613.5.3(1) VALUES OF SITE COEFFICIENT Fa a SITE CLASS MAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD Ss 0.25 Ss = 0.50 Ss = 0.75 Ss = 1.00 Ss 1.25 A 0.8 0.8 0.8 0.8 0.8 B 1.0 1.0 1.0 1.0 1.0 C 1.2 1.2 1.1 1.0 1.0 D 1.6 1.4 1.2 1.1 1.0 E 2.5 1.7 1.2 0.9 0.9 F Note b Note b Note b Note b Note b a. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at short period, Ss. b. Values shall be determined in accordance with Section 11.4.7 of ASCE 7. TABLE 1613.5.3(2) VALUES OF SITE COEFFICIENT FV a SITE CLASS MAPPED SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD S1 0.1 S1 = 0.2 S1 = 0.3 S1 = 0.4 S1 0.5 A 0.8 0.8 0.8 0.8 0.8 B 1.0 1.0 1.0 1.0 1.0 C 1.7 1.6 1.5 1.4 1.3 D 2.4 2.0 1.8 1.6 1.5 E 3.5 3.2 2.8 2.4 2.4 F Note b Note b Note b Note b Note b a. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at 1-second period, S1. b. Values shall be determined in accordance with Section 11.4.7 of ASCE 7. 1613.5.4 Design spectral response acceleration parameters. Five-percent damped design spectral response acceleration at short periods, SDS, and at 1-second period, SD1, shall be determined from Equations 16-39 and 16-40, respectively: 2 SDS = SMS 3 (Equation 16-39) 2 SD1 = SM1 3 (Equation 16-40) 1613.5.5 Site classification for seismic design. Site classification for Site Class C, D or E shall be determined from Table 1613.5.5. The notations presented below apply to the upper 100 feet (30 480 mm) of the site profile. Profiles containing distinctly different soil and/or rock layers shall be subdivided into those layers designated by a number that ranges from 1 to n at the bottom where there is a total of n distinct layers in the upper 100 feet (30 480 mm). The symbol i then refers to any one of the layers between 1 and n. where: vsi = The shear wave velocity in feet per second (m/s). di = The thickness of any layer between 0 and 100 feet (30 480 mm). where: where: ➡ SMS = The maximum considered earthquake spectral response accelerations for short period as determined in Section 1613.5.3. SM1 = The maximum considered earthquake spectral response accelerations for 1-second period as determined in Section 1613.5.3. n vs = n di ∑ i =1 v si (Equation 16-41) 2006 INTERNATIONAL BUILDING CODE® 304 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:08 AM di ∑ i =1 28 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN n k = The number of cohesive soil layers in the top 100 feet (30 480 mm). di = 100 feet (30 480 mm) ∑ i =1 Ni is the Standard Penetration Resistance (ASTM D 1586) not to exceed 100 blows/foot (305 mm) as directly measured in the field without corrections. When refusal is met for a rock layer, Ni shall be taken as 100 blows/foot (305 mm). n N= di ∑ i =1 (Equation 16-42) di ∑=1 N i i where Ni and di in Equation 16-42 are for cohesionless soil, cohesive soil and rock layers. (Equation 16-43) The hard rock category, Site Class A, shall be supported by shear wave velocity measurements either on site or on profiles of the same rock type in the same formation with an equal or greater degree of weathering and fracturing. Where hard rock conditions are known to be continuous to a depth of 100 feet (30 480 mm), surficial shear wave velocity measurements are permitted to be extrapolated to assess vs. m di = ds ∑ i =1 Use di and Ni for cohesionless soil layers only in Equation 16-43. ds = The total thickness of cohesionless soil layers in the top 100 feet (30 480 mm). m = The number of cohesionless soil layers in the top 100 feet (30 480 mm). sui = The undrained shear strength in psf (kPa), not to exceed 5,000 psf (240 kPa), ASTM D 2166 or D 2850. dc d ∑=1 s i i ui where: su = Where a site does not qualify under the criteria for Site Class F and there is a total thickness of soft clay greater than 10 feet (3048 mm) where a soft clay layer is defined by: su < 500 psf (24 kPa), w ≥ 40 percent, and PI > 20, it shall be classified as Site Class E. The shear wave velocity for rock, Site Class B, shall be either measured on site or estimated by a geotechnical engineer or engineering geologist/seismologist for competent rock with moderate fracturing and weathering. Softer and more highly fractured and weathered rock shall either be measured on site for shear wave velocity or classified as Site Class C. n d N ch = m s d ∑=1 N i i i where: PI = The plasticity index, ASTM D 4318. w = The moisture content in percent, ASTM D 2216. The rock categories, Site Classes A and B, shall not be used if there is more than 10 feet (3048 mm) of soil between the rock surface and the bottom of the spread footing or mat foundation. 1613.5.5.1 Steps for classifying a site. 1. Check for the four categories of Site Class F requiring site-specific evaluation. If the site corresponds to any of these categories, classify the site as Site Class F and conduct a site-specific evaluation. (Equation 16-44) k 2. Check for the existence of a total thickness of soft clay > 10 feet (3048 mm) where a soft clay layer is defined by: su < 500 psf (24 kPa), w ≥ 40 percent and PI > 20. If these criteria are satisfied, classify the site as Site Class E. k di = dc ∑ i =1 3. Categorize the site using one of the following three methods with v s , N, and s u and computed in all cases as specified. dc = The total thickness of cohesive soil layers in the top 100 feet (30 480 mm). TABLE 1613.5.5 SITE CLASSIFICATIONa SITE CLASS vs N or N ch su E < 600 ft/s < 15 < 1,000 psf D 600 to 1,200 ft/s 15 to 50 1,000 to 2,000 psf C 1,200 to 2,500 ft/s > 50 > 2,000 For SI: 1 foot per second = 304.8 mm per second, 1 pound per square foot = 0.0479kN/m2. a. If the su method is used and the N ch and su criteria differ, select the category with the softer soils (for example, use Site Class E instead of D). 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:08 AM 305 29 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN 3.1. v s for the top 100 feet (30 480 mm) (v s method). 1613.5.6.1 Alternative seismic design category determination. Where S1 is less than 0.75, the seismic design category is permitted to be determined from Table 1613.5.6(1) alone when all of the following apply: 3.2. N ch for the top 100 feet (30 480 mm) (N method). 1. In each of the two orthogonal directions, the approximate fundamental period of the structure, Ta, in each of the two orthogonal directions determined in accordance with Section 12.8.2.1 of ASCE 7, is less than 0.8 Ts determined in accordance with Section 11.4.5 of ASCE 7. 1613.5.6 Determination of seismic design category. Occupancy Category I, II or III structures located where the mapped spectral response acceleration parameter at 1-second period, Sl, is greater than or equal to 0.75 shall be assigned to Seismic Design Category E. Occupancy Category IV structures located where the mapped spectral response acceleration parameter at 1-second period, S1, is greater than or equal to 0.75 shall be assigned to Seismic Design Category F. All other structures shall be assigned to a seismic design category based on their occupancy category and the design spectral response acceleration coefficients, SDS and SD1, determined in accordance with Section 1613.5.4 or the site-specific procedures of ASCE 7. Each building and structure shall be assigned to the more severe seismic design category in accordance with Table 1613.5.6(1) or 1613.5.6(2), irrespective of the fundamental period of vibration of the structure, T. 2. In each of the two orthogonal directions, the fundamental period of the structure used to calculate the story drift is less than Ts. TABLE 1613.5.6(1) SEISMIC DESIGN CATEGORY BASED ON SHORT-PERIOD RESPONSE ACCELERATIONS 3. Equation 12.8-2 of ASCE 7 is used to determine the seismic response coefficient, Cs. 4. The diaphragms are rigid as defined in Section 12.3.1 in ASCE 7 or for diaphragms that are flexible, the distance between vertical elements of the seismic-force-resisting system does not exceed 40 feet (12 192 mm). 1613.5.6.2 Simplified design procedure. Where the alternate simplified design procedure of ASCE 7 is used, the seismic design category shall be determined in accordance with ASCE 7. 1613.6 Alternatives to ASCE 7. The provisions of Section 1613.6 shall be permitted as alternatives to the relevant provisions of ASCE 7. 1613.6.1 Assumption of flexible diaphragm. Add the following text at the end of Section 12.3.1.1 of ASCE 7: OCCUPANCY CATEGORY VALUE OF SDS I or II III IV SDS < 0.167g A A A 0.167g ≤ SDS < 0.33g B B C 0.33g ≤ SDS < 0.50g C C D 0.50g ≤ SDS D D D ➡ Diaphragms constructed of wood structural panels or untopped steel decking shall also be permitted to be idealized as flexible, provided all of the following conditions are met: 1. Toppings of concrete or similar materials are not placed over wood structural panel diaphragms except for nonstructural toppings no greater than 11/2 inches (38 mm) thick. TABLE 1613.5.6(2) SEISMIC DESIGN CATEGORY BASED ON 1-SECOND PERIOD RESPONSE ACCELERATION 2. Each line of vertical elements of the lateral-force-resisting system complies with the allowable story drift of Table 12.12-1. OCCUPANCY CATEGORY VALUE OF SD1 I or II III IV SD1 < 0.067g A A A 0.067g ≤ SD1 < 0.133g B B C 0.133g ≤ SD1 < 0.20g C C D 0.20g ≤ SD1 D D D 3. Vertical elements of the lateral-force-resisting system are light-framed walls sheathed with wood structural panels rated for shear resistance or steel sheets. 4. Portions of wood structural panel diaphragms that cantilever beyond the vertical elements of the lateral-force-resisting system are designed in accordance with Section 2305.2.5 of the International Building Code. ➡ 2006 INTERNATIONAL BUILDING CODE® 306 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:08 AM 30 ➡ ➡ 3.3. N for cohesionless soil layers (PI < 20) in the top 100 feet (30 480 mm) and average, s u for cohesive soil layers (PI > 20) in the top 100 feet (30 480 mm) ( s u method). Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN 1613.6.2 Additional seismic-force-resisting systems for seismically isolated structures. Add the following exception to the end of Section 17.5.4.2 of ASCE 7: Exception: For isolated structures designed in accordance with this standard, the Structural System Limitations and the Building Height Limitations in Table 12.2-1 for ordinary steel concentrically braced frames (OCBFs) as defined in Chapter 11 and ordinary moment frames (OMFs) as defined in Chapter 11 are permitted to be taken as 160 feet (48 768 mm) for structures assigned to Seismic Design Category D, E or F, provided that the following conditions are satisfied: 1. The value of RI as defined in Chapter 17 is taken as 1. 2. For OMFs and OCBFs, design is in accordance with AISC 341. 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:09 AM 307 31 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1613.5(1) MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF 0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 2006 INTERNATIONAL BUILDING CODE® 308 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:18 AM 32 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1613.5(1)—continued MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF 0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:23 AM 309 33 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1613.5(2) MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 2006 INTERNATIONAL BUILDING CODE® 310 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:31 AM 34 Color profile: Generic CMYK printer profile Composite Default screen STRUCTURAL DESIGN FIGURE 1613.5(2)—continued MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 2006 INTERNATIONAL BUILDING CODE® 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:36 AM 311 35 Color profile: Generic CMYK printer profile Composite Default screen FIGURE 1613.5(3) MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF 0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B STRUCTURAL DESIGN 2006 INTERNATIONAL BUILDING CODE® 312 16_ibc_2006.prn M:\data\CODES\2006 I-Codes\Building\Final VP_Chgo\16_ibc_2006.vp Wednesday, December 07, 2005 10:50:39 AM 36
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )