VLS-VLH control 4 Compressors ELECTRONIC SERVICE MANUAL VLS/VLH 09/05 VLS-VLH CHILLER - 4 COMPRESSORS 1 GENERAL INFORMATION 2.1 1.1 INTRODUCTION 2.1.1 GENERAL INFORMATION This document contains the information and the operating instructions for VLS-VLH 4 compressors & electronic control. This information is for the after-sales service and the production operators, for the end-of-line testing. 1.2 The figure shows the terminal with the front door open. It is provided with a LCD 4 lines x 20 columns, keyboard and microprocessor-controlled LED's, so as to allow the programming of the control parameters (setpoint, differential bands, alarm thresholds) and the main operations to be carried out by the user. MAIN CHARACTERISTICS – Microprocessor control – User-friendly keyboard – Proportional and integral control of the return water temperature (RWT) – Hysteresis control of the leaving water temperature (LWT) – Access code to enter the Manufacturer's Level – Access code to enter the Assistance Level – Alarm buzzer and LED – backlighted LCD – Closed-loop condensing pressure control – Pump-Down logic (start-stop) – Rotation of the compressor operation – Oil return function – Night mode (or Low Noise) control – Counting of the pump/compressors' hours of operation – Display of discharge pressure values – History of stored alarms (option) – Programming of different setpoints with 4 ranges of time/setpoint. The following accessories can be also connected: – Real Time Clock Memory Card: alarm history and programming of different setpoints with ranges of time – Serial Communication RS485 Card; to connect the Chiller Control to a BMS network – Remote Display Terminal – Wire Remote Control – Phase monitor kit 2 KEYBOARD & DISPLAY TERMINAL 2.1.2 TERMINAL & KEY BOARD DESCRIPTION The terminal makes it possible to carry out the following operations: – the initial configuration of the machine – the change of all the main operating parameters – the display of the detected alarms and their acoustic signalling by a “buzzer” – the display of all the measured quantities The terminal and the card are connected by a 6-way phone cable. The connection of the terminal to the basic card is not essential for the normal operation of the controller. CONTROL OF VLS-VLH WITH 4 COMPRESSORS THE CHILLER CONTROL SYSTEM The VLS-VLH machines with 4 scroll compressors are provided with a microprocessor card which is fully programmed by default for the control of a chiller of cold only type with 2 circuits, 2 compressors per circuit, a high-pressure transducer per circuit. The control system consists of: 2 VLS/VLH 09/05 Access to the “display mask” of the machine status. 4. Arrow down key: allows you to set the control parameters' values and to move from one mask to another (not backlighted). 5. Enter key: used to move the cursor inside the masks and to save the values of the set parameters. This key is always backlighted (yellow light) to indicate the presence of the power supply. Access to the “maintenance level mask”. Access to the “printing mask” (not available). 2.2 DISPLAY Access to the “display mask” of the status of digital/analog inputs and outputs. Access to the “clock“ mask” (if the clock card is available). Access to the display/control “setpoint masks”. Access to the “Service Level” masks. The display is an LCD 4 lines x 20 columns. The quantities and the information about the operation of the unit are alternated in the form of subsequent screens, named "masks". Press these keys at the same time to enter the "manufactur-er Level masks “of the machine. You can move inside the masks with the terminal keys, as described below. +--------------------+ x Line0 Home Line1 Line2 Line3 +--------------------+ Displays the information on the software version. The LED's next to each key light up when the relative function is enabled. 2.3 KEYBOARD 2.3.1 ARROWS KEYS - UP/DOWN/ENTER 1. On/off key: allows you to turn the unit on/off. The green LED which lights up the key indicate the status of the unit. If the cursor is in the top left-hand corner (Home), press the UP/DOWN keys to access the subsequent masks associated to the selected branch. If a mask includes some value setting fields and you press the ENTER key, the cursor will reach these fields. 2. Alarm key: used to display the alarms, to reset them in manual mode and to silence the buzzer. If the key lights up (in red), at least an alarm has been identified. Press it one to silence the buzzer and to display the mask of the activated alarm. Press it again to reset the alarm signal. Once you have reached the quantity setting field, you can modify any value (within the expected limits) by pressing the UP/DOWN keys. After you have selected the desired value, press the ENTER key again to store it. 3. Arrow up key: allows you to set the control parameters' values and to move from one mask to another (not backlighted). 3 VLS/VLH 09/05 2.3.2 ALARMS Code Alarm description Comp Status Ventil. Status Pump Status Aut/Man Reset Delay AL01 AL02 AL03 AL04 AL05 AL06 AL07 AL08 AL11 AL12 AL13 AL14 AL15 AL21 AL22 AL23 AL24 AL25 AL26 AL27 Off Off Sys 1 Off Sys 2 Off Off Sys 1 Off Sys 2 Off Sys 1 Off Sys 2 Off Comp. 1 Off Comp. 2 Off Comp. 3 Off Comp. 4 Off Off Off Off Run Run Run Run Off Off Off Off Run Run Run Run Run Run Run Run Off Off Off Off Max Run Run Max Off Run Run Off Run Run Run Run Run Run Run Run Run Run Run Run Run Run Run Run Man Man Man Man Man Man Man Man Man Man Man Man Man Auto Auto Auto Auto Auto Auto Auto 30 sec No No Parameter Parameter Parameter No No No No No No No 10 sec 10 sec 10 sec 10 sec 10 sec 10 sec 10 sec Run Max Run Auto 10 sec AL31 AL32 AL33 AL34 AL35 AL55 Efficiency alarm CPS Sys 1 Antifreeze alarm Sys 2 Antifreeze alarm Flow meter alarm Sys 1 Low pressure Sys 2 Low pressure Sys 1 High pressure Sys 2 High pressure Thermal switch, compressor 1 Thermal switch, compressor 2 Thermal switch, compressor 3 Thermal switch, compressor 4 Thermal switch, fans Failure of sensor B1 Tin Failure of sensor B2 Tout1 Failure of sensor B3 Tout2 Failure of sensor B4 Tair Failure of sensor B5 Tcoil1 Failure of sensor B6 Tcoil2 Failure of sensor B7 Sys 1 HP pressure transducer Failure of sensor B8 Sys 2 HP pressure transducer Maintenance of compressor 1 Maintenance of compressor 2 Maintenance of compressor 3 Maintenance of compressor 4 Pump maintenance alarm Failure of clock card Run Run Run Run Off Run Run Run Run Run Off Run Run Run Run Run Off Run Man Man Man Man Man Man AL56 Thermal switch, compressor 1 Off Comp. 1 Run Run Man AL57 Thermal switch, compressor 2 Off Comp. 2 Run Run Man AL58 Thermal switch, compressor 3 Off Comp. 3 Run Run Man AL59 Thermal switch, compressor 4 Off Comp. 4 Run Run Man AL60 AL61 AL62 AL63 Sys 1 Low pressure Sys 2 Low pressure Thermal switch, fans Sys 1-2 Antifreeze alarm Off Sys 1 Off Sys 2 Off Off Sys 1-2 Run Run Off Off Run Run Run Run Man Man Man Man No No No No No No 1 time auto VLS 3 time auto VLH 1 time auto VLS 3 time auto VLH 1 time auto VLS 3 time auto VLH 1 time auto VLS 3 time auto VLH 3 time auto 3 time auto 1 time auto 1 time auto AL28 4 VLS/VLH 09/05 Notes defrost every 40’ defrost every 40’ 2.3.3 MENU KEY Press the “menu” key to display the main mask: RWT................................. °C SYS 1 comp off SYS 2 comp off Unit off 2.3.4 MAINTENANCE LEVEL KEY Press the “Maintenance” key to access the following masks : Parameter Type Min. Value Max. Value Default 3 0 N° 0000 AL 000 h 00:00 00/00/00 Setpoint 00,0 °C Water temp. 00,0 ° C Pump 000000 h SYS 1 – comp. 1 . 000000 h SYS 1 – comp. 2 . 000000 h SYS 1 – comp. 3 . 000000 h SYS 1 – comp. 4 . 000000 h Insert the password 0000 1234 Offset probe T in °C -3 T out °C -3 3 0 T air °C -3 3 0 T coil 1 °C -3 3 0 T coil 2 °C -3 3 0 DP 1 bar -3 3 0 DP 2 bar -3 3 0 N(Hours x1000) 0 100 10 Pump flag N=NO Y=YES N Compressors flag N=NO Y=YES N Maintenance Alarm thershold Reset hours Disabile compressors C1: N 2.3.5 PRINTING KEY C2 : N C3 : N C4 : N (Not used) 5 VLS/VLH 09/05 2.3.6 I/O (INPUT/OUTPUT) KEY Press the I/O key to access the display masks of the val-ues of all sensors mounted on the machine: Acronym Description Tin Entering water temperature Tmixed Leaving water temperature Tair Room air temperature Tcoil1 Coil 1 sensor defrost control Tcoil 2t Coil 2 sensor defrost control DP-1 Sys 1: discharge pressure transducer DP-2 Sys 2: discharge pressure transducer IN Status of the Chiller Control's digital inputs OUT Status of the Chiller Control's digital i outputs Chiller control Code ……….. Rel. ………. 2.3.7 CLOCK KEY Press the “clock “ key you can access the following masks: User parameters Control mode Min. Value Max. Value 00:00 24:00 Default Clock Hour Day Monday Sunday Date 01.01.05 12.12.05 Daily Time zone with variation of the setpoint N=NO Y=YES If Daily zone Y you can to enter in the follow mask Setp1= 00.0 - 00:00h Setp2= 00.0 - 00:00h Setp3= 00.0 - 00:00h Setp4= 00.0 - 23:59h 6 VLS/VLH 09/05 N 2.3.8 USER LEVEL - SETPOINT KEY are listed below, together with the limit values and the default values (standard shop set-up). Press the Set key to enter the Setpoint level, which can be accessed by the user. The parameters that can be set User parameters Control mode Min. Value Max. Value Default Sys #1 ON/OFF – OFF ON OFF Sys #2 ON/OFF – OFF ON OFF Cooling Setpoint Return mCS+2 20 10 Outlet mCS 20 8 Heating Setpoint Return 20 MHS-5 40 Outlet 20 MHS 40 Glycole Setpoint Return –15 20 10 Outlet –15 20 8 Proportional Band Return 1 10 5 Neutral Band Outlet 1 6 2 Language selection — ITA ENG GER SPA FRA ITA At this level you can select the language of opera-tion (English or Italian). French, German and Spanish are available with other eproms. Where mCS = min. cold limit for the setpoint (see Service level) Where MHS = max. heat limit for the setpoint (see Service level) When the machine is turned on, every single circuit is activated through the SYSTEM # ON/OFF parameters (SET key). 2.3.9 SERVICE LEVEL KEY Press the “Prog” key (correct password 1234) to access the Service Level: Parameters Type Min. Value Max. Value Default Min. time stop compressor Sec 10 600 90 Min.running time compressor Sec 10 180 90 Time betw. On same compr. Sec 10 999 450 Loading time Between comp. Sec 10 999 20 LWT Unloading time compressor Sec 10 999 20 ChillerNet Flag N=NO Y=YES N Water temperature control mode Flag RWT - P RWT P+I LWT RWT P RWT P+I Sec 0 999 600 °C -20 +20 4,5 R134A unit LWT Stop Comp Cooling Heating Heat set. comp. °C +20 +60 55 Flag N=NO Y=YES N Set point °C -999,9 999,9 005.0 Diff. °C -999,9 999,9 10.0 Max. °C -999,9 999,9 005.0 7 VLS/VLH 09/05 Parameters Type Min. Value Max. Value Default Cool set.comp. Flag N=NO Y=YES N Set point °C -999,9 999,9 24.0 Diff. °C -999,9 999,9 10.0 Max. °C -999,9 999,9 -002.0 Auto restart Flag N=NO Y=YES N Glycole Flag N=NO Y=YES N Enable rotation Flag N=NO Y=YES YES Clock 32 Kbyte Flag N=NO Y=YES N Remote logic Flag N=NO Y=YES N Stand-by hour 1 24 12h Delay stop Sec 0 60 20 running Sec 0 99 1 Start-up Sec 0 99 10 Sec 0 99 40 Limit °C -15 10 4 Diff. °C 0 99 2 Setpoint °C -15 10 5 Diff. °C 0 99 2 Condensation type control (note 2) Flag STEP FSC STD: STEP LAK: FSC Delay start fans Sec -10 10 0 °C -20 0 -10 Setpoint (with odd fans) °C -20 0 -20 Diff. °C 0 99 45 HP1 bar 16 28 21 R134A unit Pump management Flowswitch/Interbloc delay time alarm Low pressure Delay time Antifreeze Antifreeze heater LS (low speed) only if STEP Setpoint (with peer fans) LS (low speed) only if STEP LP1 14 bar 10 16 13 7 DPSET (only if FSC) bar 10 24 15 10 MINDP (only if FSC) bar 1 25 10,5 6 MIN Speed (only if FSC) Vdc 0 10 0 MAX Speed (only if FSC) Vdc 0 10 10 MDP bar 18 28 24 15 High bar 18 28 26 18 Condensation Fan step heating with odd fans Low °C 0 99 15 with peer fans Low °C 0 99 20 High °C 0 99 30 8 VLS/VLH 09/05 Parameters Type Min. Value Max. Value R134A unit Default Defrost mangement Start °C -20 20 0 Stop °C -20 20 8 Start time Min 0 99 40 Max time Min 1 10 5 Off tandem Sec N=NO Y=YES N Enable Flag N=NO Y=YES Y (VLS) N (VLH) Max time Pump down Sec 5 90 10 Min.cooling setpoint (mCS) °C 5 12 6 Max. heating setpoint (MHS) °C 30 55 45 Efficiency value bar 0.0 3.0 0 Flag N=NO Y=YES N enabled Flag N=NO Y=YES N enabled Flag N=NO Y=YES N Night mode “Only with Clock option” Flag N=NO Y=YES N DPOFFSET bar 0 8 2 Serial Card On/off remote Cool/heat remote TMAX °C -20 50 30 DELTA-V Volt 0.0 5.0 5 T MIN °C -20 30 -2 DELTA V Volt 0 5 5 Set point °C - 20 °C 99,9 - 20°C Diff. °C 0 99,9 0,5 Min.T air °C - 20 °C 99,9 00.0 Min.twin air temp. Set point Press key ENTER for reset history Press the ENTER key to erase the alarm history memory Press the key ENTER for default values Press the ENTER key to go back default value Warning: Carry out this operation whenever the eprom is changed Insert the new service password 1234 Note 2: Set this parameter to FSC only if the speed controller is available, otherwise set it to STEP. 9 VLS/VLH 09/05 2.3.10 MANUFACTURER LEVEL KEY Press the “menu” + “prog” keys at the same time, under a valid access code (4939), to enter the Manufacturer Level. The parameters are available only in Italian. User parameters Type Min. Value Max. Value Default Enter password Manifactured Exact password 0000 0 9999 4939 Flag Chiller Heat pump VLS: Chiller VLH: Heat pump N° 1 2 2 - BTB - TWO CIR - DUAL Unit Number of compressor per circuit LWT sensor Log Enable sensor B1:Y B2:Y B4:Y B5:N B7: Y B8:Y B3:N B6:N (See note) Liquid solenoid valve ( Note ) Flag B5 = N For chiller B6 = N For chiller N=NO DUAL B5 = Y For heat pump B6 = Y For heat pump Y=YES Y Cycle rev. valve Flag NA NC NA Analog inputs Range 0-1 V 4-20 mA 0-1 V Start -30° C End 90°C 0 bar 30 bar Start 0 bar End 30 bar Tcoil os Lp Analog inputs Range High pressure DP ……………. Hour autoreset numbers LP 1 alarm N° 0 99 3 LP 2 alarm N° 0 99 3 Term.comp 1 N° 0 99 1 VLS / 3 VLH Term.comp 2 N° 0 99 1 VLS / 3 VLH Term.comp 3 N° 0 99 1 VLS / 3 VLH Term.comp 4 N° 0 99 1 VLS / 3 VLH Term.fan N° 0 99 1 Antifreezing N° 0 99 1 Push the ENTER key to initialize the unit Warning Carry out this operation whenever the eprom is changed Set the new manufacturer’s password……. 0000 10 VLS/VLH 09/05 3 THERMOSTAT CONFIGURATION (VLH only) charges also the other compressor of the tandem and resets at 115°C. One thermostat is mounted for each tandem of compressors. The thermostat is used to control the tandem scroll discharge temperature. Above 125 °C it discharges a compressor and resets at 105 °C. Above 135 °C it dis- Note: configure the dP parameter in oF before all the other parameters. Parameter Description Range Default Unit SET 1 SET-POINT LS-HS 120 °C SET 2 SET-POINT LS-HS 125 °C d1 DIFFERENTIAL -99 / 240 -20 °C d2 DIFFERENTIAL -99 / 240 -20 °C LS1 MINIMUM SET -70 / 999 0 °C LS2 MINIMUM SET -70 / 999 0 °C HS1 MAXIMUM SET -70 / 999 150 °C HS2 MAXIMUM SET -70 / 999 150 °C od RELAY DELAY 0 / 500 0 seconds CAL OFFSET SENSOR -99 / 999 0 °C Ft OPERATING MODE on / nr on Flag OCO SET-POINT TYPE di / in in Flag HC1 OPERATING MODE C/H H Flag HC2 OPERATING MODE C/H H Flag rP1 RELAY STATUS: ALARM ro / rc ro Flag rP2 RELAY STATUS: ALARM ro / rc ro Flag LF1 LED STATUS di / in di Flag LF2 LED STATUS di / in di Flag dP DECIMAL POINT oF / on oF Flag hdd RESOLUTION n/y n Flag tAb CONFIGURATION / / / 11 VLS/VLH 09/05 4 EPROM CHANGE pCo 4.1 NEW EPROM HAS NO EFFECT YET Enter in factory level (press simultaneusly Menu + Prog and enter password 4939) 1. Check if address board is already fitted on pCO board, if not add it (look at “clock” labelled socket on pCO) and set only dip1 to ON scroll masks until you find: 2. Check if terminal display is addressed with (dip1,2,3,4 = ON). Premere tasto ENTER per inizializzare l'unità 3. Replace the eprom with new one 4. Power on the control pressing in the same time both arrow keys and enter until Press enter to initialize the pCO control to new eprom: in the end of initializing: Terminal Adr: 15 I/O Board Adr: - Premere tasto ENTER per inizializzare l'unità Use ARROWS and ENTER to set I/O Board Adr a 1: OPERAZIONE ESEGUITA! Terminal Adr: 15 I/O Board Adr: 1 Now you have to off the pCO and on it again. Now pCO is programmed with standard default parameters value as cooling only unit. Press ENTER: Terminal Config Press ENTER to continue Enter – P:01 Adr Trm1 15 Trm2 None Trm3 None Priv/Shared Pr --- Ok?-- Press ENTER and set the following mask accordingly: P:01 Adr Trm1 15 Trm2 None Trm3 None Priv/Shared Pr --- Ok? Yes Press ENTER to confirm now the pCo is configurate. 12 VLS/VLH 09/05 5 COMPRESSORS LEAVING LIQUID CONTROL (COOLING MODE) If the LWT falls below the SetPoint High Limit and greater than the SetPoint Low Limit, temp is in the Neutral Band. No actions is occurring. No load and no unloading. If Leaving Control mode is selected, the leaving mixed water temperature LWT will be controlled between the setpoint and the setpoint + Neutral Band. The SetPoint High Limit is the Setpoint plus the Neutral Band. The SetPoint Low Limit is the Setpoint. If the LWT falls below the SetPoint one compressor is switched off. Until the LWT is below the Setpoint, compressors are unloaded according to the Unload time parameter value. If the mixed leaving water temperature LWT is above the SetPoint High Limit, the compressors will be energized one by one separated by the Time between Start and Start different compressors 6 COMPRESSORS LEAVING LIQUID CONTROL (HEATING MODE) If the LWT is between the SetPoint Low Limit and the SetPoint High Limit, temp is in the Neutral Band. No actions is occurring. No load and no unloading. If leaving Control mode is selected, the leaving mixed water temperature LWT will be controlled between the setpoint and the setpoint - Neutral Band. The SetPoint High Limit is the Setpoint. The SetPoint Low Limit is the Setpoint – Neutral Band. If the LWT is above the SetPoint High Limit one compressor is switched off. Until the LWT is above the Setpoint High Limit, compressors are unloaded according to the Unload time parameter value. If the mixed leaving water temperature LWT is below the SetPoint Low Limit, the compressors will be energized one by one separated by the Time between Start and Start different compressors. 13 VLS/VLH 09/05 7 COMPRESSORS RETURN LIQUID CONTROL (COOLING MODE) If the RWT is above the Sepoint, control starts to load each stages. The higher is the RWT, the more compressors will be loaded, according to the compressor activity logic, timer and rules described. If Return Control Mode is selected, the return water temperature RWT is controlled between the Setpoint and the Setpoint + Proportional Band. We call this zone: the Loading Zone. All stages, 2 or 4 compressors, are placed in the proportional band, dividing it in the number of the compressors. Example: regulation diagram for machines with max. 4 compressors: All the unit compressors will be proportionally positioned in the band called Loading Zone. 8 COMPRESSORS RETURN LIQUID CONTROL (HEATING MODE) The difference is that the loading zone is between Set Point – Proportional Band and Set Point. The compressors are loaded in the same proportional way used in Return Control in Cooling. 14 VLS/VLH 09/05 9 CONDENSER FAN CONTROL (IN COOLING MODE WITH FAN SPEED CONTROL) As soon as the first compressor starts, the fan relay will turn on, and it will stay on until the all compressors turn off. For the first 10 seconds the fans will begin at an output level proportional to the ambient temperature. The hotter it is out, the faster the fans will start. Below is a chart showing the correlation. Parameter used: Minimum Fan Speed, Max Fan Speed, Discharge Pressure Set (DPSET), Max Discharge Pressure, MINDP, Condensation type Control (STEP or FSC). Control uses one digital output to power on one fans relay and an analogue output 0-10Vdc to drive a Fan Speed Controller (FSC). The fans try to maintain a constant condenser pressure equal to the programmed set point by varying fan speed. Table 1 – Startup Fan Values is running at lower capacity as long as neither pressure exceeds the maximum discharge pressure. There is one high pressure transducer each system. If only one compressor is running, the fans control to its discharge pressure. If two compressors are running, the fans control the pressure of the 1st system started, or the one which is running at 100% capacity if the other one Once on, the fan speed is recalculated every second according to the below basic rules: If DPSET-1 < DP < DPSET+1 then no change in AO If (DPSET+1 < DP < DPSET+2) AND (DP IS NOT DECREASING) then AO = AO + 1 % If (DP > DPSET + 2) AND (DP IS NOT DECREASING) then AO = AO + 5 % If (DPSET-2 < DP < DPSET-1) AND (DP IS NOT INCREASING) then AO = AO -1% If (DPSET-2 < DP < 10.5) AND (DP IS NOT INCREASING) then AO = AO -2% If (DP < MINDP) then AO = AO - 2 % To check if DP is increasing or decreasing, value DDP = ± 0.2 bar/sec is used. 15 VLS/VLH 09/05 10 CONDENSER FAN CONTROL (COOLING MODE) IN STEP The fan step control is managed by the parameters LP1-HP1-LS-Diff The fans start under sensor air (B4)control OAT During the fans running : If DP>HP1 one step is load independent by OAT value If DP<LP1 unloaded the step DP is the leader between the two transducer LS - Default = Peer fans -10°C Odd fans -20°C DIFF - Default = Peer/Odd 45°C HP1 - Default = 21 bar (R410C) 14 bar (R134A) LP1 - Default = 13 bar (R410C) 7 bar (R134A) 16 VLS/VLH 09/05 11 CONDENSER FAN CONTROL IN HEATING WITH FSC Two parameters used: Low Air Temp Heating and High Air Temp Heating. pressure. At unit startup, the fans will run for 3 seconds at max speed before the compressor starts. If the Tair probe is installed, fan control in heat pump mode is always based on ambient temperature and not After startup, the fans will run according to the following rule: If Tair < Low Air Temp Heating then AO = Max Fan Speed If Low Air Temp Cooling < Tair < High Air Temp Cooling then AO from Max to Min with linear progression If Tair > High Air Temp Heating then AO = Min Fan Speed If Air Temp Probe (B4) isn’t installed, the Analogue Output is forced to the 10Vdc value. The Fan relay is energized whenever at least one compressor is running. If High pressure transducer are installed, during the defrost cycle, the fans will turn on at 20Bar and run at 50%. AO = 5Vdc. The fans will stay on until the higher discharge pressure drops to 15 Bar, and then they will turn off. 17 VLS/VLH 09/05 12 CONDENSER FAN CONTROL (HEATING MODE) IN STEP LOW – Default = Odd fans 15°C Peer fans 20°C HIGH – Default = Peer/Odd fans 30°C 18 VLS/VLH 09/05 13 NIGHT MANAGEMENT (or LOW NOISE OPTION) with the CLOCK key, if enabled: PM = night mode start AM = night mode end MAX FAN SPEED IN COOLING IN NIGHT MODE: The parameter is defined at the Service level: “Night Mode”. If set to SI, the DPSET is modified as follows: DPSET night=DPSET+DPOFFSET from PM hours to AM hours Where:DPOFFSET = parameter in bars at Service Level. It is the correction of the pressure target of the condensation control with speed controller. PM and AM = parameters that can be set with a mask MaxFanSpeed is no longer a fixed parameter, but is a function of B4, air temperature The analogue output value AO, is always between the Min Fan Speed and the Max Fan Speed. Whenever one of the two high pressure measures by the transducer 14 reaches the MDP Value, soon the fan must run at max speed, until that high pressure value falls again to the 90% of the Max High Pressure Value. COMPRESSORS CAPACITY CONTROL ning), the high pressure value reaches the setted Disch Pressure Limit default value 26 bar, the last sys compressor loaded is soon unloaded. Parameters used: Disch Pressure Limit, (HI) Max Disch Pressure.(MDP) If high pressure transducer are installed and if the unit is a 4 compressors unit, the compressors capacity control is active. Second compressor of the system will be allowed to run only when Sys High Pressure value falls below the Max Discharge Pressure default value 24 bar. If, at any time while the sys is full loaded (2 comps run- 19 VLS/VLH 09/05 15 OIL RECOVERY FUNCTION If one of the tandem (System1-2) running at 50% (only one compressor running) more than 40’ the control will force the tandem at 100% for 5 minuts. 16 PUMP CONTROL When the unit is in Off, always pump runs for 5 mins every “Pump Stand-by Interval” value, setted in Service Level. Default must be 12 hours. Parameters used in Pump management mask: Remote logic, Stand-by, Delay Stop. Pump always starts 30 seconds before the first compressor is loaded and stops always a parameter Pump Delay Time value in seconds after the unit is stopped locally or by remote start/stop digital input. If the pump is not controlled by the electronic control put the stand by value at 00. If the unit is in stand-by, the pump must anyway be started if the Antifreeze heater is powered or the unit is in Antifreeze alarm. If the parameter “Pump Remote Logic” is in YES, if the unit is stopped by the remote Start/Stop digital input, the pump continues to run. It only stops if the unit is locally stopped by panel. 17 PUMP-DOWN LOGIC – LIQUID LINE SOLENOID VALVE CONTROL Each system is equipped with one liquid line solenoid valve, to feature a pumping down. Pump Down during start-up of the first compressor of each system and during stop of the last compressor of each system. Pump-down finishes by low pressure, when Low Pressure Switch opens and/or by maximum time reached. See the mask and graphs below for further information. Parameters used: Pump-Down Max Time, Pump-Down Enable, Liquid Line Solenoid Valve Enable. All the following logic is valid only if Liquid Line Valve are selected as present in Factory Level, and if Pump-Down is enable in Service Level. 18 DEFROST CYCLE (HEAT PUMPS ONLY) Defrosting of a circuit with time/temperature control: 20 VLS/VLH 09/05 It is a Simultaneous Global Defrost. Parameters used: Defrost start Temp; Defrost stop temp, defrost Delay time, defrost Max time, Reversing Off Time. It is possible to set compressor switch off time (Reversing Off parameter) when system enter and exit from defrost mode. Compressors are not switched off if time is set to 0 seconds. Moreover cycle reversion during normal operation (changing from summer to winter mode or back) always follow compressors switch off. During defrost cycle, if the discharge pressure in one of the two systems, reaches an high dangerous value, fans must run at max speed. So, if discharge pressure transducer are attached, if one of the two high pressure values reaches the Max Discharge Pressure value (see MDP) the fans contactor is energized and the analogue output is forced to 5Vdc. Defrost cycle stops when both the Tcoil values rises up to the Defrost Stop Temp value, anyway if the Defrost Max Time has elapsed. If one of the two Tcoil probes temperature values fall below the Defrost start Temp, a timer starts. The timer is increased while the Tcoil value is under the Defrost start Temp. When the timer (t1 + t2 + t3 + …) reaches the defrost start time value, the defrost cycle starts for both system. When defrost cycle is ended, the reverse valve is unpowered and fans are powered again, according to fans rule logic. During defrost cycle, fans are stopped, all compressors run (if one or more are in off, they must be powered), reverse valve is powered. 19 VLS-VLH TROUBLE SHOOTING The following table details possible unit faults, their probable cause and suggested remedies, for any other problems not immediately recognisable and/or technical assistance, call an authorised Technical Service Center. Faulty Probable cause Remedy AL01 Efficiency alarm CPS Gas circuit empty Wrong compressors rotation To charge the circuit To check the electrical connection AL02 Sys 1 Antifreezing Low water flow Wrong pump Water filter dirty Dirty exchanger High circuit pressure drop To check the pump To check the pump size To clean the filter To clean the exchanger To check the plant pressure drop AL03 Sys 2 Antifreezing Low water flow Wrong pump Water filter dirty Dirty exchanger High circuit pressure drop To check the pump To check the pump size To clean the filter To clean the exchanger To check the plant pressure drop AL04 Flow meter Water pump stop Water pump blocked Pump thermal contact open Flow switch blocked To check the pump To release the pump To reset the thermal contact and to check the scale To release the flow switch AL05 Sys 1 Low pressure Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open Solenoid valve not open To replace the espansion valve To charge the circuit To find and repair the leak To check the plant thermal load To check the electrical connection To check Pump Down setting AL06 Sys 2 Low pressure Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open Solenoid valve not open To replace the espansion valve To charge the circuit To find and repair the leak To check the plant thermal load To check the electrical connection To check Pump Down setting 21 VLS/VLH 09/05 Faulty Probable cause Remedy AL07 Sys 1 High pressure COOL Fan stop Low ventilation Fan thermal contact open High gas charge Coil dirty Coil obstruct Faulty high pressure transducer To check the fan To check the fan speed To reset the contact To check the gas charge To clean the coil To check the installation position To replace the transducer HEAT Low water flow Wrong pump Dirty filter Dirty exchanger High circuit pressure drop To check the pump To check the pump size To clean the filter To clean the exchanger To check the plant pressure drop COOL Fan stop Low ventilation Fan thermal contact open High gas charge Coil dirty Coil obstruct Faulty high pressure transducer To check the fan To check the fan speed To reset the contact To check the gas charge To clean the coil To check the installation position To replace the transducer HEAT Low water flow Wrong pump Dirty filter Dirty exchanger High circuit pressure drop To check the pump To check the pump size To clean the filter To clean the exchanger To check the plant pressure drop AL11 Thermal switch compressor 1 Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL12 Thermal switch compressor 2 Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL13 Thermal switch compressor 3 Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL14 Thermal switch compressor 4 Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL08 Sys 2 High pressure 22 VLS/VLH 09/05 Faulty Probable cause Remedy AL15 Thermal switch fans Fan stop Fan thermal contact open Fan blocked Wrong electrical cable connection & phase missing To check the motor To reset the thermal contact and to check the scale To release the fan To check the electrical connection, to tighten the terminal block screws AL21 Failure sensor B1 Entering water temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To replace the sensor To replace cable To check the electrical connection To check the insulation AL22 Failure sensor B2 Outlet water temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To replace the sensor To replace cable To check the electrical connection To check the insulation AL23 Failure sensor B3 Outlet water temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To replace the sensor To replace cable To check the electrical connection To check the insulation AL24 Failure sensor B4 Outdoor air temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To replace the sensor To replace cable To check the electrical connection To check the insulation AL25 Failure sensor B5 Coil 1 temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To replace the sensor To replace cable To check the electrical connection To check the insulation AL26 Failure sensor B6 Coil 2 temperature Faulty sensor Cut cable Sensor not connected Water inside the sensor To replace the sensor To replace cable To check the electrical connection To check the insulation AL27 Failure sensor B7 Transducer High pressure Circuit 1 High pressure transducer damaged Cut cable Water inside the transducer Connector loose To replace the transducer To check the cable To check the insulation To tighten the connector screws AL28 Failure sensor B8 Transducer High pressure Circuit 2 High pressure transducer damaged Cut cable Water inside the transducer Connector loose To replace the transducer To check the cable To check the insulation To tighten the connector screws AL31 Compressore 1 Mantenance Exceeded hours of operation compressor 1 To do mantenance AL32 Compressore 2 Mantenance Exceeded hours of operation compressor 2 To do mantenance AL33 Compressore 3 Mantenance Exceeded hours of operation compressor 3 To do mantenance 23 VLS/VLH 09/05 Faulty Probable cause Remedy AL34 Compressore 4 Mantenance Exceeded hours of operation compressor 4 To do mantenance AL35 Pump Mantenance Exceeded hours of operation pump To do mantenance AL55 Clock damage Failure of clock card Clock faulty Clock cardout of support To replace the clock To insert the clock card in the support AL56 Thermal switch compressor 1 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL57 Thermal switch compressor 2 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL58 Thermal switch compressor 3 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL59 Thermal switch compressor 4 Only with “AUTO RESET” Motor compressor faulty Compressor thermal contact open Wrong charge Wrong electrical cable connection & phase missing To check the compressor motor To reset the thermal contact To check the gas charge To check the electrical connection, to tighten the terminal block screws AL60 Sys 1 Low pressure Only with “AUTO RESET” Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open Solenoid valve not open To replace the espansion valve To charge the circuit To find and repair the leak To check the plant thermal load To check the electrical connection To check Pump Down setting AL61 Sys 2 Low pressure Only with “AUTO RESET” Espansion valve broken Gas circuit empty Gas leak High temperature water inlet Solenoid valve not open Solenoid valve not open To replace the espansion valve To charge the circuit To find and repair the leak To check the plant thermal load To check the electrical connection To check Pump Down setting AL62 Thermal switch fans Only with “AUTO RESET” Fan stop Fan thermal contact open Fan blocked Wrong electrical cable connection & phase missing To check the motor To reset the thermal contact and to check the scale To release the fan To check the electrical connection, to tighten the terminal block screws AL63 Sys 1-2 Antifreezing Only with “AUTO RESET” Low water flow Wrong pump Water filter dirty Dirty exchanger High circuit pressure drop To check the pump To check the pump size To clean the filter To clean the exchanger To check the plant pressure drop 24 VLS/VLH 09/05 20 LIST OF ITELCO-CLIMA APPLICATION SUPERVISOR VARIABLES FOR PCO APPLICATION CHILLER/HEATPUMP: VLS – VLH Level: 1=User (Site manager); 2=Service Manager; 3=Manufacturer; n.c.=not care Valid for EPROM 031B10210-I02 Index Meaning Read/Write Range 1 Water inlet temperature (RWT) Read -50.0 ÷ +105.0 °C 2 Water outlet temperature (LWT) Read -50.0 ÷ +105.0 °C 4 External air temperature (OAT) Read -50.0 ÷ +105.0 °C 5 System #1 defrost temp. Read -50.0 ÷ +105.0 °C 6 System #2 defrost temp. Read -50.0 ÷ +105.0 °C 7 System #1 high pressure transducer Read 0.0 ÷ 30.0 bar 8 System #2 high pressure transducer Read 0.0 ÷ 30.0 bar 9 Regulation temperature (RWT or LWT) Read -50.0 ÷ +105.0 °C 10 Fan speed index Read 0.0 ÷ 10.0 11 Cooling LWT compressor stop threshold Read/Write -20.0 ÷ +20.0 °C 12 Heating LWT compressor stop threshold Read/Write 20.0 ÷ + 60.0 °C 13 Antifreeze setpoint Read/Write -15.0 ÷ +10.0 °C 17 Discharge pressure setpoint Read/Write 10.0 ÷ 24.0 bar 20 Maximum Discharge pressure Read/Write 10.0 ÷ 28.0 bar 21 Discharge pressure limit Read/Write 18.0 ÷ 28.0 bar 22 High temperature heating Read/Write 0.0 ÷ 99.9 °C 23 Low temperature heating Read/Write 0.0 ÷ 99.9 °C 26 Minimum cooling setpoint limit (mCS) Read/Write 5.0 ÷ 12.0 °C 27 Maximum heating setpoint limit (MHS) Read/Write 30.0 ÷ 55.0 °C 53 RWT cooling setpoint Read/Write mCS+2 ÷ 20.0 °C 54 LWT cooling setpoint Read/Write mCS ÷ 20.0 °C 55 RWT heating setpoint Read/Write MHS-5 ÷ 40.0 °C 56 LWT heating setpoint Read/Write MHS ÷ 40.0 °C 57 RWT glycol cool setpoint Read/Write -15.0 ÷ 20.0 °C 58 LWT glycol cool setpoint Read/Write -15.0 ÷ 20.0 °C 59 Band Read/Write 1.0 ÷ 10.0 °C 60 Neutral zone Read/Write 1.0 ÷ 6.0 °C 61 Low speed setpoint Read/Write -20.0 ÷ 0.0 °C 62 Low speed differential Read/Write 0.0 ÷ 99.9 °C 64 DPOFFSET (night mode) Read/Write 0.0 ÷ 8.0 bar 65 TMAX (night mode) Read/Write -20.0 ÷ 50.0 °C 67 Minimum tandem air temperature setpoint Read/Write -20.0 ÷ 99.9 °C 68 Minimum tandem air temperature differential Read/Write 0.0 ÷ 99.9 °C 25 VLS/VLH 09/05 Index Meaning Read/Write bit = 0 bit = 1 1 Heating operation Read Cool Heat 3 System #1 compressor #1 Read off On 4 System #1 compressor #2 Read off On 6 System #2 compressor #1 Read off On 7 System #2 compressor #2 Read off On 9 Fan Read off On 11 4-way valve Read off On 12 System #1 alarm Read run Alarm 13 System #2 alarm Read run Alarm 14 Pump Read not run Run 15 RWT/LWT temperature control Read/Write RWT LWT 16 Automatic restart Read/Write no Yes 17 Enable operation with glycol Read/Write no Yes 22 Disable system #1 Read/Write off On 23 Disable system #2 Read/Write off on 24 Enable chiller/heatpump remote selection Read/Write no yes 29 Enable B5 probe (it means unit is heatpump) Read no B5 yes B5, hp 33 Unit on Read off on 34 On/Off from supervisor Write off on 40 System #1 antifreeze Read no alarm yes alarm 41 System #2 antifreeze Read no alarm yes alarm 42 System #1 low pressure Read no alarm yes alarm 43 System #2 low pressure Read no alarm yes alarm 44 System #1 high pressure Read no alarm yes alarm 45 System #2 high pressure Read no alarm yes alarm 46 Compressor #1 overload Read no alarm yes alarm 47 Compressor #2 overload Read no alarm yes alarm 48 Compressor #3 overload Read no alarm yes alarm 49 Compressor #4 overload Read no alarm yes alarm 50 Fan overload Read no alarm yes alarm 51 B1 faulty probe Read no alarm yes alarm 52 B2 faulty probe Read no alarm yes alarm 54 B4 faulty probe Read no alarm yes alarm 55 B5 faulty probe Read no alarm yes alarm 56 B6 faulty probe Read no alarm yes alarm 57 B7 faulty probe Read no alarm yes alarm 58 B8 faulty probe Read no alarm yes alarm 59 Compressor #1 maintenance Read no maint. yes maint. 60 Compressor #2 maintenance Read no maint. yes maint. 61 Compressor #3 maintenance Read no maint. yes maint. 62 Compressor #4 maintenance Read no maint. yes maint. 63 Flow switch alarm Read no alarm yes alarm 67 Enable night mode Read/Write off on 69 Winter Read/Write Cooling Heating 26 VLS/VLH 09/05 Index 1 Meaning System #1 state Read/Write value/range Read 0 = off System #1 state 1 = pumpdown System #1 state 2 = 1 comp running System #1 state 3 = 2 comp running System #1 state 4 = sys in alarm 2 System #2 state Read 3 Machine state Read as per sys 1 status 0 = on Machine state 1 = off by alarm Machine state 2 = off by supervisor Machine state 3 = off by low OAT Machine state 4 = off by remote Machine state off 9 Pump stand-by time Read/Write 01 – 24 hours 10 Pump power off delay Read/Write 00 – 60 sec 11 Flow switch alarm delay under steady conditions Read/Write 00 – 99 sec 12 Flow switch alarm delay at the start-up Read/Write 00 – 99 sec 25 Pump hours (high part) Read/Write * 26 Pump hours (low part) Read/Write * 27 Compressor #1 hours (high part) Read/Write * 28 Compressor #1 hours (low part) Read/Write * 29 Compressor #2 hours (high part) Read/Write * 30 Compressor #2 hours low part) Read/Write * 31 Compressor #3 hours (high part) Read/Write * 32 Compressor #3 hours (low part) Read/Write * 33 Compressor #4 hours (high part) Read/Write * 34 Compressor #4 hours (low part) Read/Write * 37 Night mode start hour (PM) Read/Write 00 – 12 38 Night mode start minutes Read/Write 00 – 59 39 Night mode end hour (AM) Read/Write 00 – 12 40 Night mode end minutes Read/Write 00 – 59 Note *: running hours range is between 000000 and 999999. Generally Low Part means the last 3 figures: XXX999; and high part is the first 3 figures: 999XXX. 27 VLS/VLH 09/05
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )