TECHNICAL REVISION August 2015 Insulation PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time. © Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users’ purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized User’s client. PIP’s copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice. PRINTING HISTORY April 1999 Issued December 2005 Technical Correction Not printed with State funds February 2006 July 2007 Editorial Revision Editorial Revision March 2011 August 2015 Reaffirmation with Editorial Revision Technical Revision TECHNICAL REVISION August 2015 Insulation PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service Table of Contents 1. Introduction .................................2 1.1 Purpose ..............................................2 1.2 Scope .................................................2 2. References ..................................2 2.1 Process Industry Practices ................2 2.2 Industry Codes and Standards ..........2 2.3 Other References ...............................2 3. Definitions ...................................2 4. Requirements ..............................3 4.1 Materials .............................................3 4.2 Design and Fabrication ......................5 4.3 Installation Requirements...................7 4.4 Inspection ...........................................7 4.5 Extent of Insulation.............................7 4.6 Documentation ...................................7 4.7 Thickness Table .................................8 Data Forms INSR1000-D1– Documentation Requirements Sheet Process Industry Practices The following data forms shall be part of this Practice only if indicated on the purchaser’s completed Documentation Requirements Sheet. INSR1000-D2 – Design Parameters INSR1000-D10 – Data Sheet for General Service (Glass Fiber Mat Insulation) to 260°C (500°F) INSR1000-D11 – Data Sheet for General Service (Glass Fiber Mat Insulation) 261-538°C (501-1000°F) INSR1000-D12 – Data Sheet for General Service (Silica Aerogel Blanket Insulation) to 260°C (500°F) INSR1000-D13 – Data Sheet for General Service (Silica Aerogel Blanket Insulation) 261-538°C (501-1000°F) INSR1000-F1 – Insulation Thickness Table for Glass Felt Fiber Insulation (US Customary Units) INSR1000-F2 – Insulation Thickness Table for Silica Aerogel Insulation (US Customary Units) INSR1000-FM1 – Insulation Thickness Table for Glass Felt Fiber Insulation (SI Units) INSR1000-FM2 – Insulation Thickness Table for Silica Aerogel Insulation (SI Units) Page 1 of 8 PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service 1. TECHNICAL REVISION August 2015 Introduction 1.1 Purpose This Practice provides requirements for the installer of flexible, removable/reusable insulation covers for hot service insulation systems. 1.2 Scope This Practice describes the minimum requirements for materials, fabrication, and installation of flexible, removable/reusable hot service insulation covers, ambient to 538°C (1000°F). 2. References Applicable parts of the following Practices, industry codes and standards, and references shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles are used herein where appropriate. 2.1 Process Industry Practices (PIP) – 2.2 Industry Codes and Standards • American Society of Testing and Materials (ASTM) – ASTM C680 - Standard Practice for Determination of Heat Gain or Loss and the Surface Temperatures of Insulated Pipe and Equipment Systems by the Use of a Computer Program – ASTM C692 - Standard Test Method for Evaluating the Influence of Thermal Insulations on External Stress Corrosion Cracking Tendency of Austenitic Stainless Steel – ASTM C795 - Thermal Insulation for Use in Contact with Austenitic Stainless Steel – ASTM C871 - Standard Test Methods for Chemical Analysis of Thermal Insulation Materials for Leachable Chloride, Fluoride, Silicate, and Sodium Ions ASTM C1086 - Standard Specification for Glass Fiber Felt Thermal Insulation – – 2.3 ASTM D3776 - Standard Test for Methods for Mass per Unit Area (Weight) of Woven Fabric Other References • 3. PIP INSH1000 - Hot Service Insulation Materials and Installation Specification North American Insulation Manufacturers Association (NAIMA) – 3E PLUS Insulation Thickness Computer Program Definitions supplier: Party responsible for furnishing and/or installing the insulation system owner: The party who owns the facility wherein the installation system will be used purchaser: The party who awards the contract to the supplier. The purchaser may be the owner or the owner's authorized agent. Process Industry Practices Page 2 of 8 PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service TECHNICAL REVISION August 2015 manufacturer: Party responsible for making the insulation covers for hot insulation service 4. Requirements 4.1 Materials 4.1.1 4.1.2 4.1.3 General 4.1.1.1 Insulation and accessory materials shall be furnished in accordance with the requirements of this Practice, including the specific grade or type. 4.1.1.2 Insulation and accessory materials shall be formulated without asbestos. 4.1.1.3 Materials shall be new and shall be used prior to the expiration date. 4.1.1.4 Use of materials other than those specified in this Practice shall require prior written approval of the purchaser. Requests for substitutions shall be included as an alternate in the bidder’s proposal. 4.1.1.5 Alternative insulation materials may be specified by the purchaser on data sheets PIP INSR1000-D10, INSR1000-D11, INSR1000-D12 and INSR1000-D13, as needed. Testing 4.1.2.1 All materials shall be qualified for use on austenitic stainless steel in accordance with ASTM C795. If requested, test reports shall be furnished. 4.1.2.2 Material manufacturer shall also furnish a chemical analysis in accordance with ASTM C871 for materials. This chemical analysis shall not vary by more than 50% from the chemical analysis of the production lot tested under ASTM C692. 4.1.2.3 Unless otherwise specified in the purchase order, certification of chemical analysis is not required for each production lot from which material is furnished for this project. However, the manufacturer shall state that the chemical analysis will not vary by more than 50% from those done during the production lot tested under ASTM C795. 4.1.2.4 Testing shall be conducted by a laboratory accredited by the National Institute of Standards and Technology’s National Voluntary Laboratory Accreditation Program (NVLAB). Insulation Material 4.1.3.1 Glass Fiber Mat Insulation 1. Insulation material shall be composed of 100% selected-grade Type E glass fibers fabricated in mat form without the addition of resinous or organic binders in accordance with ASTM C1086. 2. Insulation shall be suitable for hot face temperatures to 538°C (1000°F). 3. Insulation shall have a nominal density of 128 kg/m³ (8.0 lb/ft³). Process Industry Practices Page 3 of 8 PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service 4.1.3.2 TECHNICAL REVISION August 2015 Silica Aerogel Blanket Insulation 1. Insulation material shall be flexible aerogel insulation in accordance with ASTM C1728, Type III, Grade 1A. 2. Insulation shall be suitable for hot face temperatures to 649°C (1200°F). 3. Insulation shall have a density of 160 kg/m³ (10.0 lb/ft³) to 240 kg/m³ (15.0 lb/ft³). 4.1.4 Inner Liner 4.1.4.1 Inner liner, including gussets, for operating temperatures to 260°C (500°F) shall be a fiberglass fabric impregnated with PTFE, having a minimum weight of 540 g/m² (16 oz/yd²) in accordance with ASTM D3776, and grey in color. 4.1.4.2 For operating temperatures 261°C (501°F) to 538°C (1000°F): 1. Inner liner, including gussets shall be a four-ply laminate, consisting of two layers of fiberglass cloth and two layers of 25 µm (1 mil) thick aluminum foil, with a minimum weight of 610 g/m² (18 oz/yd²). 2. Inner liner, including gussets, shall have an outer layer of knitted wire mesh, Type 304 stainless steel, 0.44 mm (0.011 inch) wire diameter, and 60 density (openings per inch / 25 mm) secured over the four-ply laminate. 4.1.5 Outer Jacket Outer jacket shall be a fiberglass fabric impregnated with PTFE, having a minimum weight of 540 g/m² (16 oz/yd2) in accordance with ASTM D3776, and grey in color. 4.1.6 4.1.7 Tie-Down Straps 4.1.6.1 Tie-down straps shall be constructed of the same material as the outer jacket. 4.1.6.2 Tie-down straps shall be fabricated using a double thickness of the fabric, with edge trim sewn in place along both edges. 4.1.6.3 Edge trim shall be applied to not leave exposed fabric edges. 4.1.6.4 Ends of the straps shall be turned under 6 to 13 mm (1/4 to 1/2 inch) and double-stitched to prevent unraveling. Drawstrings Drawstrings shall be made from 100% textured fiberglass sleeving with plain weave, 10 mm (3/8 inch) inside diameter, 0.8 mm (0.03 inch) wall thickness, and shall be suitable for 538°C (1000°F) service. 4.1.8 Thread 4.1.8.1 Process Industry Practices PTFE-coated fiberglass thread shall be used for service temperatures to 260°C (500°F). Page 4 of 8 PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service 4.1.9 TECHNICAL REVISION August 2015 4.1.8.2 Fiberglass thread shall be 0.50 mm (0.021 inch) diameter, minimum 9 kg (20 lbs.) tensile strength. 4.1.8.3 Kevlar-coated stainless steel thread shall be used for service temperatures above 260°C (500°F). 4.1.8.4 Stainless steel thread shall be minimum 0.40 mm (0.015 inch) diameter and minimum 8 kg (18 lbs.) tensile strength. Hardware All hardware such as D-rings, buckles, tags, etc., shall be type 304 stainless steel. 4.2 Design and Fabrication 4.2.1 4.2.2 Process Industry Practices Piping, Flanges, Valves, and Equipment Covers 4.2.1.1 Insulated items shall be pre-measured to assure a tight fit. Allowances for valve bonnet height, gland openings, protrusions, etc shall be included. 4.2.1.2 Force-folding or bending of covers shall not be permitted. 4.2.1.3 Covers shall be fabricated with a minimum 50 mm (2 inches) of overlap at the end flap over adjacent insulation. 4.2.1.4 Covers shall be fabricated to allow easy access to valve packing glands and flange bolts without having to completely remove the cover. 4.2.1.5 If possible, covers shall be fabricated with parting faces at the cover low point to facilitate drainage. Otherwise, a drainage grommet shall be installed at the cover low point. 4.2.1.6 Any single cover or cover piece shall not exceed 20 kg (45 lbs.) Covers with a finished weight of 20 kg (45 lbs.) or less shall be fabricated in one piece. Jacket Fabric Seam Construction 4.2.2.1 All fabric seams shall be sewn. Machine stitching shall be used wherever practical. Hand stitching shall be kept to an absolute minimum. 4.2.2.2 All cover seams shall be turned in or under and sewn to prevent any raw edges from being exposed on any surface. 4.2.2.3 Gusset-type construction shall be utilized for all cover thicknesses greater than 1 inch. 4.2.2.4 Sewing shall be double straight stitched with minimum 7 stitches per 25 mm (1 inch). Each row shall be parallel and spaced a minimum of 3 mm (1/8 inch) to a maximum of 13 mm (1/2 inch) apart. 4.2.2.5 Fabric seams shall be inside seams, except that the final closing seam may be an outside seam. 4.2.2.6 Insulation within the jacketing shall be secured with lacing hooks or insulation anchors to prevent insulation from settling within the cover. Page 5 of 8 PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service 4.2.3 TECHNICAL REVISION August 2015 Tie-Down/Anchor Strap Construction 4.2.3.1 The terminal ends of splits in covers shall be constructed with flaps or drawcord/flaps to seal the covers from wind and water. Flaps shall have no gaps where they contact adjacent insulation. 4.2.3.2 D-ring type buckles and/or hook-and-loop tie-down/anchor straps shall be used. 4.2.3.3 Lacing Hooks 1. Lacing hooks and wire shall not be used unless approved by the Purchaser. 2. If Purchaser approves the use of lacing hooks and wires, the lacing hooks shall be tufted to the cold face jacketing. 3. If lacing hooks penetrate the hot face, the hooks shall be secured by self-locking washers with a patch of the hot face jacketing material sewn over the washer. 4. A silicone rubber patch shall be placed between the washer and the cover. 4.2.3.4 Ends of straps shall be turned under 6 mm (1/4 inch) to 13 mm (1/2 inch) and double stitched to prevent unraveling. 4.2.3.5 Strap length and number of straps for covers shall be sufficient to ensure a snug and proper fit without gaps or sagging of the cover. 4.2.3.6 Tie-down strap length shall have a minimum of 150 mm (6 inches) excess length for pulling and securing. 4.2.3.7 Drawcords 1. Drawcords shall be used if terminal ends of covers need to be drawn down around adjacent insulation, valve bonnets, nozzles, etc., to seal the covers from wind and water. 2. Covers shall incorporate flaps at the terminal ends. Drawcord shall be located within this flap. 3. Tie-down/anchor straps adjacent to the covers terminal ends shall be spaced a minimum of 50 mm (2 inches) back from the drawcord flaps. 4. Cord length shall be sufficient to allow a minimum of 150 mm (6 inches) of cord to protrude from each end of the flap when it is drawn down. 5. Cut ends of braided sleeving cord shall be turned back inside the sleeving a minimum of 25 mm (1 inch) and double-stitched to prevent fraying. 6. A double stitch shall be located at the middle of the flap to secure the cord and prevent it from pulling out. Process Industry Practices Page 6 of 8 PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service 4.2.4 4.2.5 4.3 4.4 4.5 TECHNICAL REVISION August 2015 Valve Covers 4.2.4.1 Valve covers shall be designed to permit full function of the valves and shall not obscure the valve’s position indicator. 4.2.4.2 Any leak from the packing gland or flanges must be channeled out of the cover to prevent soaking the insulation. 4.2.4.3 Leak tube shall be provided for drainage when specified by purchaser. Identification Tags 4.2.5.1 Stainless steel identification tags shall be permanently attached to the outside of the cover. 4.2.5.2 The identification legend shall be mechanically embossed on the tag. 4.2.5.3 Information contained on each tag shall be specified by the purchaser. 4.2.5.4 Tags shall not be riveted directly to the cold face jacketing. 4.2.5.5 Tags shall be riveted to straps that are similar to tie-down/anchor straps. These straps shall be secured to the cold face jacketing to allow the straps to double as handles or lifting loops. 4.2.5.6 Covers utilizing multi-piece construction shall be appropriately tagged for assembly. Installation Requirements 4.3.1 All surfaces to be insulated shall be clean and dry. 4.3.2 Before insulating, any steel requiring coating shall be coated in accordance with applicable specifications. 4.3.3 Insulation shall not be installed until completion of stress relieving, chemical cleaning, pressure testing, installation of heat tracing, and authorization in writing by appropriate authority. 4.3.4 The fit of the covers shall be in accordance with the design requirements of this Practice. Inspection 4.4.1 The Purchaser reserves the right to inspect the covers during manufacture. 4.4.2 Any materials or installations that do not meet the requirements of this Practice shall be replaced or corrected. Extent of Insulation The extent of insulation shall be in accordance with the purchaser's PIP INSH1000 data sheet INSH1000-D3. 4.6 Documentation 4.6.1 Process Industry Practices Documents required to define the scope of work shall be listed on Documentation Requirements Sheet INSR1000-D1. Page 7 of 8 PIP INSR1000 Installation of Flexible, Removable/Reusable Insulation Covers for Hot Insulation Service 4.6.2 4.7 TECHNICAL REVISION August 2015 Flexible, removable/reusable insulation covers shall be provided in accordance with purchaser's data sheets PIP INSR1000-D10, INSR1000-D11, INSR1000-D12 and INSR1000-D13, as needed to specify different cover types. Thickness Table 4.7.1 Table 1 design parameters were used to compute the personnel protection thicknesses shown in the PIP INSR1000-F or PIP INSR1000-FM. 4.7.2 Users shall determine if these economic and climatic conditions are applicable to their specific location. 4.7.3 Design parameters other than those shown in Table 1 may be noted in PIP INSR1000-D2. Table 1: Design Parameters - Insulation Thickness Calculation Hot Insulation Thickness - 1998 Design Parameters Personnel Protection Design Wind Speed 1 m/s (2 mph) Personnel Protection Design Summer Dry Bulb Temperature 35°C (95°F) Personnel Protection Maximum Surface Temperature 60°C (140°F) Emittance of Existing Surface 0.9 Process Industry Practices Page 8 of 8 ASSOC. PIP: INSR1000 DOCUMENTATION REQUIREMENTS SHEET PIP INSR1000-D1 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE NO. DATE REVISION DESCRIPTION PROJECT NO. BY PAGE 1 OF 1 AUGUST 2015 CHECKED APPROVED DATE NOTES PROJECT DOCUMENT NO. FACILITY NAME LOCATION PIP DOC NUMBER / PROJ DOC NUMBER INSR1000 INSR1000-D2 INTG1000 TITLE FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE DESIGN PARAMETERS INSULATION INSPECTION CHECKLIST SELECTED MATERIALS SYSTEM DATA SHEETS GENERAL SERVICE (GLASS FIBER MAT NO INSULATION), TO 260°C (500°F) GENERAL SERVICE (GLASS FIBER MAT NO INSULATION), 261 TO 538°C (501 TO 1000°F) GENERAL SERVICE (SILICA AEROGEL NO BLANKET INSULATION), TO 260°C (500°F) GENERAL SERVICE (SILICA AEROGEL NO BLANKET INSULATION), 261 TO 538°C (501 TO 1000°F) INSR1000-D10 YES INSR1000-D11 YES INSR1000-D12 YES INSR1000-D13 YES INSR1000-F YES NO INSR1000-FM YES NO YES NO YES NO INIH0009 NOTES: REV SELECTED INSULATION THICKNESS TABLES GENERAL SERVICE, US CUSTOMARY UNITS GENERAL SERVICE, SI UNITS FLEXIBLE, REMOVABLE / REUSABLE INSULATION COVER DETAILS REMOVABLE AND REUSABLE NO INSULATION – FLEXIBLE YES YES NO YES NO YES NO YES NO YES NO ASSOC. PIP: INSR1000 DESIGN PARAMETERS PIP INSR1000-D2 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE NO. DATE PROJECT NO. REVISION DESCRIPTION BY PAGE 1 OF 1 AUGUST 2015 CHECKED APPROVED PROJECT DOCUMENT NO. FACILITY NAME LOCATION DESIGN BASIS: Ambient temperature (average summer maximum) Wind speed Maximum surface temperature Insulation finish emissivity NOTES: °C m/s °C °F mph °F ASSOC. PIP: INSR1000 DATA SHEET PIP INSR1000-D10 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE NO. DATE REVISION DESCRIPTION PAGE 1 OF 1 AUGUST 2015 BY FACILITY NAME CHECKED APPROVED PROJECT NO. LOCATION PROJECT DOCUMENT NO. SERVICE DESCRIPTION: GENERAL SERVICE (GLASS FIBER MAT INSULATION) TEMPERATURE RANGE: TO 260 °C MANUFACTURER COMPONENT INSULATION MATERIAL INNER LINER OUTER JACKET KNITTED WIRE MESH DRAWSTRINGS THREAD NOTES: (TO 500°F) THICKNESS TABLE: APPROVED MANUFACTURERS BRAND NAME MANUFACTURER DESCRIPTION TYPE E GLASS FIBER MAT, WITHOUT RESINOUS OR ORGANIC BINDERS FIBERGLASS FABRIC, PTFE IMPREGNATED, 540 g/m² (16 oz/yd²) FIBERGLASS FABRIC, PTFE IMPREGNATED, 540 g/m² (16 oz/yd²) NOT REQUIRED FIBERGLASS SLEEVING, PLAIN WEAVE, 10 mm (3/8 in.) INSIDE DIAMETER AND 0.03 in. (0.8 mm) WALL THICKNESS TEFLON-COATED FIBERGLASS THREAD, 0.50 mm (0.021 in.) DIAMETER, MINIMUM 9 kg (20 lb) TENSILE STRENGTH BRAND NAME MANUFACTURER BRAND NAME ASSOC. PIP: INSR1000 DATA SHEET PIP INSR1000-D11 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE NO. DATE REVISION DESCRIPTION PAGE 1 OF 1 AUGUST 2015 BY FACILITY NAME CHECKED APPROVED PROJECT NO. LOCATION PROJECT DOCUMENT NO. SERVICE DESCRIPTION: GENERAL SERVICE (GLASS FIBER MAT INSULATION) TEMPERATURE RANGE: 261 TO 538 °C MANUFACTURER COMPONENT INSULATION MATERIAL INNER LINER OUTER JACKET KNITTED WIRE MESH DRAWSTRINGS THREAD NOTES: (501 TO 1000°F) THICKNESS TABLE: APPROVED MANUFACTURERS BRAND NAME MANUFACTURER DESCRIPTION TYPE E GLASS FIBER MAT, WITHOUT RESINOUS OR ORGANIC BINDERS FIBERGLASS FABRIC, FOUR-PLY LAMINATE, TWO LAYERS OF FIBERGLASS CLOTH AND TWO LAYERS OF ALUMINUM FOIL, MINIMUM 610 g/m² (18 oz/yd²) FIBERGLASS FABRIC, PTFE IMPREGNATED, 540 g/m² (16 oz/yd²) KNITTED WIRE MESH, TYPE 304 STAINLESS STEEL 0.44 mm (0.011 iN.) WIRE DENSITY, AND 60 DENSITY FIBERGLASS SLEEVING, PLAIN WEAVE, 10 mm (3/8 in.) INSIDE DIAMETER AND 0.03 in. (0.8 mm) WALL THICKNESS KEVLAR-COATED STAINLESS STEEL THREAD, MINIMUM 0.40 mm (0.015 in.) DIAMETER AND MINIMUM 8 KG (18 LBS.) TENSILE STRENGTH. BRAND NAME MANUFACTURER BRAND NAME ASSOC. PIP: INSR1000 DATA SHEET PIP INSR1000-D12 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE NO. DATE REVISION DESCRIPTION PAGE 1 OF 1 AUGUST 2015 BY FACILITY NAME CHECKED APPROVED PROJECT NO. LOCATION PROJECT DOCUMENT NO. SERVICE DESCRIPTION: GENERAL SERVICE (SILICA AEROGEL BLANKET INSULATION) TEMPERATURE RANGE: TO 260 °C MANUFACTURER COMPONENT INSULATION MATERIAL INNER LINER OUTER JACKET KNITTED WIRE MESH DRAWSTRINGS THREAD NOTES: (TO 500°F) THICKNESS TABLE: APPROVED MANUFACTURERS BRAND NAME MANUFACTURER DESCRIPTION SILICA AEROGEL BLANKET INSULATION, CONFORMING TO ASTM C1728, TYPE III, GRADE 1A FIBERGLASS FABRIC, PTFE IMPREGNATED, 540 g/m² (16 oz/yd²) FIBERGLASS FABRIC, PTFE IMPREGNATED, 540 g/m² (16 oz/yd²) NOT REQUIRED FIBERGLASS SLEEVING, PLAIN WEAVE, 10 mm (3/8 in.) INSIDE DIAMETER AND 0.03 in. (0.8 mm) WALL THICKNESS TEFLON-COATED FIBERGLASS THREAD, 0.50 mm (0.021 in.) DIAMETER, MINIMUM 9 kg (20 lb) TENSILE STRENGTH BRAND NAME MANUFACTURER BRAND NAME ASSOC. PIP: INSR1000 DATA SHEET PIP INSR1000-D13 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE NO. DATE REVISION DESCRIPTION PAGE 1 OF 1 AUGUST 2015 BY FACILITY NAME CHECKED APPROVED PROJECT NO. LOCATION PROJECT DOCUMENT NO. SERVICE DESCRIPTION: GENERAL SERVICE (SILICA AEROGEL BLANKET INSULATION) TEMPERATURE RANGE: 261 TO 538 °C MANUFACTURER COMPONENT INSULATION MATERIAL INNER LINER OUTER JACKET KNITTED WIRE MESH DRAWSTRINGS THREAD NOTES: (501 TO 1000°F) THICKNESS TABLE: APPROVED MANUFACTURERS BRAND NAME MANUFACTURER DESCRIPTION SILICA AEROGEL BLANKET INSULATION, CONFORMING TO ASTM C1728, TYPE III, GRADE 1A FIBERGLASS FABRIC, FOUR-PLY LAMINATE, TWO LAYERS OF FIBERGLASS CLOTH AND TWO LAYERS OF ALUMINUM FOIL, MINIMUM 610 g/m² (18 oz/yd²) FIBERGLASS FABRIC, PTFE IMPREGNATED, 540 g/m² (16 oz/yd²) KNITTED WIRE MESH, TYPE 304 STAINLESS STEEL 0.44 mm (0.011 iN.) WIRE DENSITY, AND 60 DENSITY FIBERGLASS SLEEVING, PLAIN WEAVE, 10 mm (3/8 in.) INSIDE DIAMETER AND 0.03 in. (0.8 mm) WALL THICKNESS KEVLAR-COATED STAINLESS STEEL THREAD, MINIMUM 0.40 mm (0.015 in.) DIAMETER AND MINIMUM 8 KG (18 LBS.) TENSILE STRENGTH. BRAND NAME MANUFACTURER BRAND NAME ASSOC. PIP: INSR1000 INSULATION THICKNESS TABLE (US CUSTOMARY UNITS) PIP INSR1000-F1 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE - GLASS FIBER FELT INSULATION FACILITY NAME LOCATION NO. PAGE 1 OF 1 AUGUST 2015 PROJECT NO. PROJECT DOCUMENT NO. DATE REVISION DESCRIPTION BY CHECKED APPROVED SERVICE DESCRIPTION: GENERAL SERVICE Pipe Size or O.D. (NPS) (in.) 1 and less 1 1/2 2 3 4 6 8 10 12 14 16 18 20 24 30 36 >36 to Flat To 150 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 151 to 200 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 201 to 250 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 251 to 300 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 301 to 350 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 351 to 400 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 401 to 450 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 451 to 500 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 501 to 550 1.0 1.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 Operating Temperature, °F 551 601 651 701 to to to to 600 650 700 750 1.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.0 1.5 1.5 2.0 2.0 1.5 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.0 2.0 2.0 2.5 2.0 2.0 2.0 2.5 2.0 2.0 2.5 2.5 2.0 2.0 2.5 2.5 2.0 2.0 2.5 3.0 2.0 2.0 2.5 3.0 2.0 2.0 2.5 3.0 2.0 2.0 2.5 3.0 2.0 2.0 2.5 3.0 2.0 2.0 2.5 3.0 2.0 2.0 3.0 3.0 751 to 800 1.5 2.0 2.0 2.0 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 801 to 850 2.0 2.0 2.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 851 to 900 2.0 2.0 2.5 2.5 2.5 3.0 3.0 3.0 901 to 950 2.0 2.0 2.5 3.0 3.0 3.0 951 to 1000 2.5 2.5 2.5 3.0 3.0 to to to to NOTES: 1. Insulation thicknesses are based on design parameters in PIP INSR1000 Table 1 for personnel protection, using maximum thermal conductivity for glass fiber felt insulation in accordance with ASTM C1086. ASSOC. PIP: INSR1000 INSULATION THICKNESS TABLE (US CUSTOMARY UNITS) PIP INSR1000-F2 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE - SILICA AEROGEL INSULATION FACILITY NAME LOCATION NO. PAGE 1 OF 1 AUGUST 2015 PROJECT NO. PROJECT DOCUMENT NO. DATE REVISION DESCRIPTION BY CHECKED APPROVED SERVICE DESCRIPTION: GENERAL SERVICE Pipe Size or O.D. (NPS) (in.) 1 and less 1 1/2 2 3 4 6 8 10 12 14 16 18 20 24 30 36 >36 to Flat To 150 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 151 to 200 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 201 to 250 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 251 to 300 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.4 0.4 0.4 0.4 0.4 0.4 0.4 301 to 350 0.2 0.2 0.2 0.2 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 351 to 400 0.2 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 401 to 450 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 451 to 500 0.4 0.4 0.4 0.4 0.4 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 501 to 550 0.4 0.4 0.4 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.8 0.8 0.8 0.8 Operating Temperature, °F 551 601 651 701 to to to to 600 650 700 750 0.4 0.4 0.6 0.6 0.4 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.8 0.6 0.6 0.8 0.8 0.6 0.8 0.8 0.8 0.6 0.8 0.8 1.0 0.8 0.8 0.8 1.0 0.8 0.8 1.0 1.0 0.8 0.8 1.0 1.0 0.8 0.8 1.0 1.0 0.8 0.8 1.0 1.0 0.8 0.8 1.0 1.0 0.8 1.0 1.0 1.2 0.8 1.0 1.0 1.2 0.8 1.0 1.0 1.2 0.8 1.0 1.0 1.2 751 to 800 0.6 0.6 0.8 0.8 0.8 1.0 1.0 1.0 1.0 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 801 to 850 0.6 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.2 1.2 1.2 1.2 1.2 851 to 900 0.8 0.8 0.8 1.0 1.0 1.2 1.2 1.2 901 to 950 0.8 0.8 1.0 1.0 1.2 1.2 951 to 1000 0.8 1.0 1.0 1.2 1.2 to to to to NOTES: 1. Insulation thicknesses are based on design parameters in PIP INSR1000 Table 1 for personnel protection, using maximum thermal conductivity for silica aerogel insulation in accordance with ASTM C1728, Type III, Grade 1A. ASSOC. PIP: INSR1000 INSULATION THICKNESS TABLE (SI UNITS) PIP INSR1000-FM1 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE - GLASS FIBER FELT INSULATION FACILITY NAME LOCATION NO. PAGE 1 OF 1 AUGUST 2015 PROJECT NO. PROJECT DOCUMENT NO. DATE REVISION DESCRIPTION BY CHECKED APPROVED SERVICE DESCRIPTION: GENERAL SERVICE Pipe Size or O.D. (NPS) (in.) 1 and less 1 1/2 2 3 4 6 8 10 12 14 16 18 20 24 30 36 >36 to Flat To 75 25 76 to 100 25 101 to 125 25 126 to 150 25 151 to 175 25 176 to 200 25 201 to 225 25 226 to 250 25 251 to 275 25 Operating Temperature, °C 276 301 326 351 to to to to 300 325 350 375 25 25 40 40 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 40 40 40 25 25 25 25 25 25 40 40 40 40 40 40 40 40 40 40 25 25 25 25 40 40 40 40 40 40 40 40 40 40 40 50 25 25 40 40 40 40 40 40 40 50 50 50 50 50 50 50 25 40 40 40 40 50 50 50 50 50 50 50 50 50 50 65 40 40 40 40 50 50 50 50 50 50 65 65 65 65 65 75 40 40 40 50 50 50 65 65 65 65 65 65 65 65 75 75 40 40 50 50 50 65 65 65 65 65 75 75 75 75 75 376 to 400 40 401 to 425 40 426 to 450 50 451 to 475 50 476 to 500 50 501 to 525 65 526 to 538 65 40 50 50 50 65 65 65 75 75 75 75 75 75 50 50 50 65 65 75 75 75 75 75 50 50 65 65 75 75 75 50 65 65 75 75 65 65 75 75 65 65 75 75 65 75 75 to to NOTES: 1. Insulation thicknesses are based on design parameters in PIP INSR1000 Table 1 for personnel protection, using maximum thermal conductivity for glass fiber felt insulation in accordance with ASTM C1086. ASSOC. PIP: INSR1000 INSULATION THICKNESS TABLE (SI UNITS) PIP INSR1000-FM2 FLEXIBLE, REMOVABLE/REUSABLE INSULATION COVERS FOR HOT INSULATION SERVICE - SILICA AEROGEL INSULATION FACILITY NAME LOCATION NO. PAGE 1 OF 1 AUGUST 2015 PROJECT NO. PROJECT DOCUMENT NO. DATE REVISION DESCRIPTION BY CHECKED APPROVED SERVICE DESCRIPTION: GENERAL SERVICE Pipe Size or O.D. (NPS) (in.) 1 and less 1 1/2 2 3 4 6 8 10 12 14 16 18 20 24 30 36 >36 to Flat to 125 126 to 150 151 to 175 176 to 200 201 to 225 226 to 250 251 to 275 276 to 300 301 to 325 Operating Temperature, °C 326 351 376 401 to to to to 350 375 400 425 426 to 450 451 to 475 476 to 500 501 to 525 526 to 538 5 5 5 5 10 10 10 10 10 10 15 15 15 15 20 20 20 20 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 10 10 10 10 10 10 10 5 5 5 10 10 10 10 10 10 10 10 10 10 10 10 10 5 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 15 10 10 10 15 15 15 15 15 15 15 15 15 15 15 15 20 10 10 15 15 15 15 15 15 15 20 20 20 20 20 20 20 15 15 15 15 15 20 20 20 20 20 20 20 20 20 20 20 15 15 15 15 20 20 20 20 20 20 20 25 25 25 25 25 15 15 15 20 20 20 20 25 25 25 25 25 25 25 25 25 15 15 20 20 20 25 25 25 25 25 25 25 30 30 30 30 15 20 20 20 25 25 25 25 30 30 30 30 30 30 30 30 20 20 20 25 25 25 30 30 30 30 30 30 20 20 25 25 30 30 30 30 30 20 25 25 25 30 30 25 25 25 30 30 25 25 30 30 to to to to NOTES: 1. Insulation thicknesses are based on design parameters in PIP INSR1000 Table 1 for personnel protection, using maximum thermal conductivity for silica aerogel insulation in accordance with ASTM C1728, Type III, Grade 1A.
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )