Cooling Load Calculation
Title:
Determination of the cooling load calculation for condition space
Objective:
Cooling load calculation may be used to accomplish one of the
following objectives;
(a) Provide information for equipment selection, system sizing, and
system design
(b) Provide data for evaluating the optimum possibilities for load
reduction
(c) Permit analysis of partial loads as required for system design,
operation and control.
Design Parameters:The critical inputs during estimating the cooling load are:
(i)
Location ( Latitude, Elevation, Outdoor temperature and
relative humidity)
(ii)
Type of room structure
(iii)
Internal conditions ( Indoor temperature and relative humidity)
(iv)
Design Time
(v)
Building enclosure
(vi)
Internal loads
Description: For estimating cooling loads, one has to consider the unsteady
state processes, as the peak cooling load occurs during the day
time and the outside conditions also vary significantly throughout
the day due to solar radiation. In addition, all internal sources add
on to the cooling loads and neglecting them would lead to
underestimation of the required cooling capacity and the
possibility of not being able to maintain the required indoor
conditions. This cooling load calculations are inherently more
complicated. The size of a cooling system for a boat is determined
of the basis of the desired indoor conditions that must be
maintained based on the outdoor conditions than exist at that
location.
Procedure: The heat gain in the space depends on the condition of the space
and need to calculate the following data:
a. The temperature difference between outside temperature and
the desired temperature of conditioned space
b. The type of construction and the amount of insulation on roof
and walls
c. Shade is on building's windows (glass)
d. Size of the room and surface area of the walls
e. The amount of air leaks into indoor space from the outside
(Infiltration plays a part in determining the air conditioner
sizing)
f. The number od occupants
g. Activities and other equipment within a building
h. Amount of lighting in the room
i. Heat the appliances generate
j. Total amount of heat gain from the serving various space plus
any loads external to the spaces
Theory:
The rate of heat gain through the exterior structure (Wall, Roof,
Glass)
Q = U A CLTDc
CLTDc = [(CLTD + LM)K + (78 – tR)+ ( ta – 85)]f
Where,
Q = Cooling load for wall, roof, glass, BTU/hr
A = Area of wall, roof, glass, ft2
CLTDc = Corrected cooling load temperature difference, °F
LM = Correlation for latitude and month
tR = Inside temperature, °F
ta = Average temperature, °F
The rate if heat gain through the interior structure ( Partition,
Ceiling, Floor)
Q = U A TD
Where,
Q = Cooling load for partition, ceiling, floor, BTU/ hr
A = Area of partition, ceiling, floor,ft2
TD = Temperature Difference between the inside and outside
condition, °F
Solar heat gain through the glass
Q = SHGF × A × SC × CLF
Where,
Q = Solar radiation cooling load for glass, BTU/hr
A = Area of the glass, ft2
SC = Shading Coefficient
SHGF = Maximum solar heat gain factor, BTU/hr ft2
CLF = Cooling load factor for glass
The rate of heat gain from lighting
Q = 3.4× W × BF × CLF
Where,
Q = Cooling load from lighting, BTU/hr
W = Lighting capacity, watts
BF = Ballast Faster
CLF = Cooling load factor for lighting
The rate of heat gain from people
Qs = qs × n × CLF
Ql = ql × n
Where,
Qs, Ql = Sensible and latent heat gained ( load)
qs, ql = Sensible and Latent heat gained per person
n = number of person
CLF = Cooling load factor for people
The rate of heat gain from equipments
Best obtained from manufacturers
Can be reduced by using Capture Hood
Usually is sensible, but may have a latent component
Ventilation and Infiltration
Qs = 1.1 × CFM × TC
Ql = 0.68 × CFM × ( w'o - w'i)
Where,
Qs,Ql = Sensible and Latent heat gained from ventilation air,
BTU/hr
CFM = Air flow rate (ft3/min)
TC = Temperature Difference between the inside and outside
condition,°F
( w'o - w'i) = Outside and inside humidity ratio, gr/lb.da
Heat transfer to the surroundings
Fc = 1 - 0.02K
K = ( UwAw + UgAg)/L
Where,
Fc = multiplier to correct each room sensible heat gain
K = unit length conductance, BTU/hr-ft2-F
Uw,Ug = Heat transfer coefficient, BTU/hr-ft2-F
Aw,Ag = area of wall, glass,ft2
L = exterior wall length, ft