Applications Engineering Manual Air-to-Air Energy Recovery in HVAC Systems 1 September 2020 SYS-APM003D-EN Air-to-Air Energy Recovery in HVAC Systems John Murphy, senior applications engineer Brenda Bradley, information designer Preface As a leading HVAC manufacturer, we believe that it is our responsibility to serve the building industry by regularly disseminating information gathered through laboratory research, testing programs, and practical experience. Trane publishes a variety of educational materials for this purpose. Applications engineering manuals such as this document can serve as comprehensive reference guides for professionals who design building comfort systems. This manual focuses on air-to-air energy recovery. It describes concepts and mechanical implementation, and identifies system-level characteristics for effective operation and control. We encourage you to familiarize yourself with its contents and to review the appropriate sections when designing a comfortsystem application that could benefit from airside energy recovery. ■ Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional. © 2020 Trane. All Rights Reserved SYS-APM003-EN Contents Introduction ...................................................................................................... 1 Why Recover Energy? ................................................................................ 2 Economics ................................................................................................................ 2 Compliance with Codes .......................................................................................... 2 Applications for Air-to-Air Energy Recovery ............................... 5 Basic Concepts ........................................................................................................ 5 Sensible versus Total Energy Recovery .......................................................... 5 Effectiveness Ratio ............................................................................................ 7 Balanced versus Unbalanced Airflows ............................................................ 7 Outdoor-Air (OA) Preconditioning ......................................................................... 9 Sensible versus Total Energy Recovery .......................................................... 9 Effect on First Cost .......................................................................................... 13 Effect on Operating Costs ............................................................................... 16 Other Considerations ...................................................................................... 18 Supply-Air (SA) Tempering .................................................................................. 20 Supply-Air Tempering in Mixed-Air Systems ............................................... 21 Supply-Air Tempering in Dedicated Outdoor-Air Systems ......................... 26 Effect on First Cost .......................................................................................... 32 Effect on Operating Costs ............................................................................... 33 Other Considerations ...................................................................................... 37 Energy-Recovery Technologies .......................................................... 38 Coil Loop ................................................................................................................ 38 Typical Performance ....................................................................................... 38 Capacity Control .............................................................................................. 40 Frost Prevention .............................................................................................. 41 Cross-Leakage .................................................................................................. 42 Coil Loop with Three Coils .............................................................................. 42 Fixed-Plate Heat Exchanger .................................................................................. 43 Typical Performance ....................................................................................... 43 Capacity Control .............................................................................................. 44 Frost Prevention .............................................................................................. 45 Cross-Leakage .................................................................................................. 46 Heat Pipe ................................................................................................................ 47 Typical Performance ....................................................................................... 47 Capacity Control .............................................................................................. 49 Frost Prevention .............................................................................................. 50 Cross-Leakage .................................................................................................. 50 Rotary Heat Exchanger ......................................................................................... 51 Typical Performance ....................................................................................... 52 Capacity Control .............................................................................................. 53 Frost Prevention .............................................................................................. 55 Cross-Leakage .................................................................................................. 57 SYS-APM003-EN iii Contents ARI Standard 1060 ................................................................................................ 60 Standard Rating Conditions ........................................................................... 61 Using EATR and OACF for System Design ................................................... 62 System-Level Control of Recovered Energy .............................. 65 OA Preconditioning: Dedicated OA System for Neutral-Temperature Air .................................... 68 Dedicated OA Systems for Cold Air .............................................................. 71 CV-MA Systems for Modulated-Temperature Supply Air ........................... 74 VAV-MA Systems for Constant-Temperature Supply Air ........................... 77 SA Tempering: Dedicated OA System for Neutral-Temperature Air .................................... 80 CV-MA Systems for Modulated-Temperature Supply Air ........................... 82 Applications that Combine OA Preconditioning and SA Tempering ............... 84 Dual-Function, Dedicated OA System for Neutral-Temperature Air .......... 84 Alternatives for Tempering with Sensible-Energy Recovery ...................... 88 Tempering (Recooling) in an Active-Desiccant System .............................. 88 Suggestions for Effective Airside Energy Recovery ............. 90 OA Preconditioning .............................................................................................. 90 Sensible- or Total-Energy Recovery? ............................................................ 90 Central or Local OA Preconditioning? ........................................................... 93 Minimizing Life-Cycle Cost ............................................................................. 95 SA Tempering ....................................................................................................... 98 Sensible- or Total-Energy Recovery? ............................................................ 98 Series or Parallel Arrangement? .................................................................... 98 Minimizing Life-Cycle Cost ........................................................................... 100 Glossary .......................................................................................................... 102 References ..................................................................................................... 106 Index .................................................................................................................. 108 iv SYS-APM003-EN Introduction Energy consumption costs money, uses natural resources, increases air pollution, and contributes to global warming. All of us share responsibility for prudent energy use. The mechanical heating, ventilating, and air-conditioning (HVAC) system typically accounts for much of the energy costs in a building. Heat gains and losses from various sources must be offset to create a comfortable, healthy indoor environment. Discarded heat from one location may be useful elsewhere in the building, so it is logical (often cost-effective, too) to recover energy that might otherwise be wasted … particularly in a time of rising energy costs. This manual discusses various technologies for and applications of air-to-air energy recovery in HVAC systems. ■ SYS-APM003-EN 1 Why Recover Energy? The answer to the question posed by the title of this section is twofold, at least in the context of an HVAC system: economics and compliance with local codes. Economics The energy impact of increased ventilation rates is one of several issues addressed in the U.S. EPA study, Energy Cost and IAQ Performance of Ventilation Systems and Controls (EPA402-S-01-001, January 2000). ■ Efforts to improve indoor air quality (IAQ) typically include bringing more outdoor air into the building … a practice that increases monthly utility costs by increasing the amount of heating, cooling, humidifying, and dehumidifying performed by the HVAC system. A study conducted by the U.S. Environmental Protection Agency (EPA) quantifies the economic effect of increased ventilation rates, which were defined in the 1989 version of ASHRAE Standard 62, Ventilation for Acceptable Air Quality. Depending on the building type, system type, and climate, the EPA study found that HVAC energy costs increased by 2 percent to 67 percent, while required capacities for peak cooling increased by 15 percent to 40 percent. These statistics underscore the importance of identifying opportunities to reduce consumption, particularly when the cost and availability of energy are of increasing concern. Correctly implemented, energy recovery offsets the operating-cost penalty that results from bringing more outdoor air into the building. Recovering enough energy may even allow the use of smaller mechanical heating and cooling equipment. Compliance with Codes ANSI/ASHRAE/IESNA Standard 90.1–2007 is available from ASHRAE’s online bookstore at www.ashrae.org. The companion user’s manual explains the intent and application of the standard; it also includes a complete set of compliance forms and worksheets. ■ Setting aside the logical and practical arguments for recovering energy from other areas of the building, local codes may actually mandate the practice. In the United States, the primary standard related to energy consumption in commercial buildings is ANSI/ASHRAE/IESNA Standard 90.1–2007, Energy Standard for Buildings Except Low-Rise Residential Buildings. Standard 90.1 sets minimum design requirements that encourage energy efficiency throughout the building. Affected systems include lighting, motors, HVAC, service water heating, and the building envelope. Section 6.5.6.1 of that standard requires the use of exhaust-air energy recovery when an individual fan system meets both of the following conditions: ■ Design supply airflow equals or exceeds 5,000 cfm (2.4 m ³/s) and ■ 2 Minimum outdoor airflow equals or exceeds 70 percent of the design supply airflow SYS-APM003-EN Why Recover Energy? This requirement generally applies to two types of systems: dedicated (100-percent) outdoor-air systems and mixed-air systems that serve spaces with high minimum requirements for outdoor airflow (for example, densely occupied spaces). Of course, exhaust-air energy recovery may make economic sense for systems that deliver 40-percent or less outdoor airflow by permitting equipment downsizing and consuming less new energy. Standard 90.1 mandates a minimum effectiveness of 50 percent when exhaust-air energy is required. (The inset on p. 4 lists the exceptions to this requirement; effectiveness is discussed on pp. 6 – 7.) As defined by the standard, Fifty percent energy recovery effectiveness shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and return air at design conditions. The publications listed below discuss energy recovery from refrigerant in direct-expansion refrigeration systems and from condenser water in watercooled chilled water systems. They also offer suggestions for system optimization: ■ Refrigerant Heat Recovery, Trane applications engineering manual SYS-AM-5 ■ Multiple-Chiller-System Design and Control, Trane applications engineering manual SYS-APM001EN ■ Waterside Heat Recovery in HVAC Systems, Trane applications engineering manual SYS-APM005EN ■ Chiller Heat Recovery, ASHRAE application guide ISBN 883413-99-0 ■ Further, the exhaust-air energy-recovery system must be installed with bypass dampers or other controls that permit airside economizer operation when such economizers are prescribed by Section 6.5.1.1 of the standard. Section 6.5.2 of Standard 90.1 also relates to the use of energy recovery; it limits coincident heating and cooling of the same air stream. According to Section 6.5.2.3, if space humidity is directly regulated — through the use of humidistats, for example — controls must prevent reheating, mixing of hot and cold air streams, or other means of simultaneously heating and cooling the same air. (The inset on p. 4 lists the exceptions to this requirement.) Exception E permits reheat if at least 75 percent of the energy used to reheat the air is recovered on site. Limiting the use of “new” energy for reheat will almost certainly prompt HVAC design professionals to recover heat from the cooling process when reheat is required, particularly in dehumidification applications. Potential sources of recoverable heat include: ■ Condenser water in a water-cooled, chilled water system ■ Hot refrigerant in a refrigeration system ■ Another air stream or another location in the same air stream The rest of this manual describes how air-to-air heat exchangers can be used to transfer energy within or between air streams. ■ SYS-APM003-EN 3 Why Recover Energy? ANSI/ASHRAE/IESNA Standard 90.1–2007 on Exhaust-Air Energy Recovery … 6.5.6.1 Exhaust Air Energy Recovery. Individual fan systems that have both a design supply air capacity of 5,000 cfm (2.4 m³ /s) or greater and have a minimum outdoor air supply of 70% or greater of the design supply air quantity shall have an energy recovery system with at least 50% recovery effectiveness. Fifty-percent energy recovery effectiveness shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and return air at design conditions. Provision shall be made to bypass or control the heat recovery system to permit air economizer operation as required by 6.5.1.1. Exceptions to 6.5.6.1: a) Laboratory systems meeting 6.5.7.2. b) Systems serving spaces that are not cooled and that are heated to less than 60°F (16°C). c) Systems exhausting toxic, flammable, paint or corrosive fumes or dust. d) Commercial kitchen hoods used for collecting and removing grease vapors and smoke. e) Where more than 60% of the outdoor air heating energy is provided from site-recovered or site solar energy. f) Heating systems in climate zones 1 through 3. g) Cooling systems in climate zones 3c, 4c, 5b, 5c, 6b, 7 and 8. h) Where the largest exhaust source is less than 75% of the design outdoor airflow. 4 i) Systems requiring dehumidification that employ energy recovery in series with the cooling coil. Note: Interpretation 90.1-2001-7, and the 90.1 Users Manual, provide further explanantion of the meaning of 50% energy recovery effectiveness. Both are available at www.ashrae.org. … and on Dehumidification 6.5.2.3 Dehumidification. Where humidistatic controls are provided, such controls shall prevent reheating, mixing of hot and cold air streams, or other means of simultaneous heating and cooling of the same air stream. Exceptions to 6.5.2.3: a) The system is capable of reducing supply air volume to 50% or less of the design airflow rate or the minimum rate specified in 6.2 of ASHRAE Standard 62.1, whichever is larger, before simultaneous heating and cooling takes place. b) The individual fan cooling unit has a design cooling capacity of 80,000 Btu/h (23 kW) or less and is capable of unloading to 50% capacity before simultaneous heating and cooling takes place. providing mechanical cooling. d) Systems serving spaces where specific humidity levels are required to satisfy process needs, such as computer rooms, museums, surgical suites, and buildings with refrigerating systems, such as supermarkets, refrigerated warehouses, and ice arenas. This exception also applies to other applications for which fan volume controls in accordance with Exception (a) are proven to be impractical to the enforcement agency. e) At least 75% of the energy for reheating or for providing warm air in mixing systems is provided from a site-recovered (including condenser heat) or site solar energy source. f) Systems where the heat added to the air stream is the result of the use of a desiccant system and 75% of the heat added by the desiccant system is removed by a heat exchanger, either before or after the desiccant system with energy recovery. ■ c) The individual mechanical cooling unit has a design cooling capacity of 40,000 Btu/h (12 kW) or less. An individual mechanical cooling unit is a single system composed of a fan or fans and a cooling coil capable of SYS-APM003-EN Applications for Air-to-Air Energy Recovery Air-to-air energy recovery describes the transfer of sensible heat, or sensible plus latent heat, between two or more air streams, or between two locations within the same air stream. When applied in HVAC systems, air-to-air energyrecovery devices perform one of two principal functions: ■ Precondition outdoor air brought into the building for ventilation ■ Temper, or reheat, supply air for independent control of space conditions (dry-bulb temperature, humidity) By including two separate, air-to-air energy-recovery devices, one for each function, an HVAC system can simultaneously provide preconditioning and tempering. (See “Applications that Combine OA Preconditioning and SA Tempering,” pp. 84 – 88.) Basic Concepts Let’s briefly review three fundamentals of energy recovery before discussing its application in the design of comfort systems: sensible versus total energy recovery, effectiveness ratio, and balanced versus unbalanced airflow. Sensible versus Total Energy Recovery Sensible-energy recovery refers to the transfer of sensible heat only. Adding sensible heat raises the dry-bulb temperature of an air stream; removing sensible heat lowers the dry-bulb temperature. Removing sensible heat may cause moisture to condense from the warmer air stream, but that moisture never transfers to the colder air stream. Common examples of sensible-energy-recovery devices include coil loops, fixed-plate heat exchangers, heat pipes, and sensible-energy, rotary heat exchangers (also known as sensible-energy wheels). Total-energy recovery describes the transfer of both sensible and latent heat. Latent heat is the energy stored in the water vapor of a moist air stream. Adding latent heat raises the dew-point temperature (moisture content) of an air stream; removing latent heat lowers the dew-point temperature. Common examples of total-energy recovery devices include total-energy rotary heat exchangers (also known as total-energy wheels) and fixed-membrane heat exchangers. (“Energy-Recovery Technologies,” pp. 38 – 64, further describes the sensibleand total-energy-recovery devices identified above.) SYS-APM003-EN 5 Applications for Air-to-Air Energy Recovery Fundamental Equations for Air-to-Air Energy Recovery Historically, manufacturers of air-to-air energy-recovery equipment used various methods to calculate the effectiveness of their devices. ARI Standard 1060 – 2005, Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment, normalizes the calculation of effectiveness for rotary heat exchangers, heat pipes, and fixed-plate heat exchangers by defining the “effectiveness ratio” equation shown at right. The only way to assure equitable comparisons of airside energy-recovery equipment is to require certification of performance in accordance with ARI 1060. For more information about the standard, see “ARI Standard 1060,” pp. 60 – 64. Note: ARI Standard 1060 does not apply to coil loops. ARI Standard 410 – 2001, Forced-Circulation Air-Cooling and AirHeating Coils, defines the rating requirements for individual coils. To calculate coil-loop effectiveness, use the certified coil performance in the “effectiveness ratio” equation. Effectiveness ratio. The following equation compares the amount of energy that is actually transferred with the maximum amount that could be transferred between the two air streams: · ms x1 – x2 = ----------------------------------------· m min x 1 – x 3 where, = sensible, latent, or total effectiveness · ms = mass flow rate, lb/hr (kg/s), through supply side of heatexchange device · me = mass flow rate, lb/hr (kg/s), through exhaust side of heatexchange device · m min = smaller mass flow rate (supply, · · m s ; or exhaust, m e ) x1 = entering supply air: dry bulb, °F (°C); humidity ratio, lb (water) / lb (dry air) (kg/kg); or enthalpy, Btu/lb (kJ/kg) x2 = leaving supply air: dry bulb, humidity ratio, or enthalpy x3 = entering exhaust air: dry bulb, humidity ratio, or enthalpy x4 = leaving exhaust air: dry bulb, humidity ratio, or enthalpy Sensible-heat transfer is determined by the sensible effectiveness of the device, the minimum airflow rate, and the difference between the entering dry-bulb temperatures of the two air streams: 60min Q s = C p ------------------ V min T 1 – T 3 1hr Q s = C p V min T 1 – T 3 where, = sensible heat actually transferred, Qs Btu/hr (kW) 6 = sensible effectiveness of device = density of air, lb/ft³ (kg/m³) Cp = specific heat of air, Btu/lb • °F (kJ/kg • °K) V min = smaller airflow (supply or exhaust side), cfm (m³/s) T1 = entering supply-air dry bulb, °F (°C) T3 = entering exhaust-air dry bulb, °F (°C) Note: At “standard” conditions, the product of density, specific heat, and the time conversion equals 1.085 (1.21). The minutes-per-hour factor is only needed to calculate Q s in I-P units. Total-heat transfer is determined by the total effectiveness of the device, the minimum airflow rate, and the difference between the entering enthalpies of the two air streams: 60min Q T = ------------------ V min h 1 – h 3 1hr Q T = V min h 1 – h 3 where, = total (sensible plus latent) heat actually transferred, Btu/hr (kW) QT = total effectiveness of device = density of air, lb/ft³ (kg/m³) V min = smaller airflow (supply or exhaust side), cfm (m³/s) h1 = entering supply-air enthalpy, Btu/lb (kJ/kg) h3 = entering exhaust-air enthalpy, Btu/lb (kJ/kg) Note: At “standard” conditions, the product of density and the time conversion equals 4.5 (1.2). The minutes-per-hour factor is only needed to calculate Q T in I-P units. ■ SYS-APM003-EN Applications for Air-to-Air Energy Recovery Effectiveness Ratio Figure 1. Air conditions at an energy-recovery device Effectiveness, , quantifies the performance of the heat-exchange device when it is used for energy recovery. Mathematically, the effectiveness ratio represents the amount of energy (sensible, latent, or total) that the device actually transfers divided by the maximum energy transfer possible between two air streams; see Figure 1. For a given heat exchanger geometry, effectiveness is determined at test conditions using various airflow rates. ANSI/ASHRAE Standard 84 –1991, Method of Testing Air-to-Air Heat Exchangers, provides the equation (shown in the inset on p. 6) that describes the effectiveness of an air-to-air energyrecovery device. The equation can be used to determine sensible, latent, or total effectiveness based on measurements obtained through laboratory tests. Note that the minimum mass flow rate is the smaller of the mass flow rates through either side of the heat exchanger. The amount of sensible heat transferred depends on the sensible effectiveness of the device, the minimum airflow rate, and the difference between the drybulb air temperatures entering the supply and exhaust sides of the heat exchanger. The heat-transfer equations on p. 6 express the mathematical relationships between these variables. Similarly, the amount of total energy transferred depends on the total effectiveness of the device, the minimum airflow rate, and the difference between the enthalpies of the air streams entering the supply and exhaust sides of the device. Again, minimum airflow is the smaller of the two airflows, whether supply or exhaust. Balanced versus Unbalanced Airflows Airflows are considered “unbalanced” when the rate of flow through one side of the heat exchanger differs from the rate of flow through the other side. Laboratory tests suggest that unbalanced airflows increase the effectiveness of the device. In actual operation, however, the device transfers less heat overall because the amount of heat transferred depends on the smaller of the two airflows. This irony is best explained using an example. Figure 2 (p. 8) illustrates the relationship between airflows and the effectiveness of a generic sensible-energy-recovery device. The horizontal axis represents exhaust-side airflow divided by supply-side airflow. A value of 1.0 indicates SYS-APM003-EN 7 Applications for Air-to-Air Energy Recovery sensible effectiveness Figure 2. Example of effectiveness for a sensible-energy-recovery device Figure 3. Balanced (equal) airflows exhaust airflow / supply airflow balanced airflows; a value less than 1.0 indicates that the exhaust airflow is less than the supply airflow. Q s = 0.66 1.085 10 000 cfm 96°F – 78°F Q s = 128 898 Btu/hr Q s = 0.66 1.21 4.7 m³/s 35.7°C – 25.6°C Q s = 37.9 kW Figure 4. Unbalanced (unequal) airflows Figure 3 shows how the sensible-energy-recovery device performs when operated with balanced exhaust and supply airflows, that is, with 10,000 cfm (4.7 m³/s) of air flowing through each side of the device. Sensible effectiveness at this balanced condition is 66 percent (Figure 2). Using that value to solve the sensible-heat-transfer equation indicates that the device will transfer 128,898 Btu/hr (37.9 kW) of sensible heat from the supply air stream to the exhaust air stream at standard air conditions. Figure 4 demonstrates how unbalanced airflows affect the performance of the same energy-recovery device. In this case, the supply airflow is 10,000 cfm (4.7 m³/s), but the exhaust airflow is only 7,000 cfm (3.3 m³/s). Although the imbalance increases the sensible effectiveness of the device to 79 percent, it now transfers 16 percent less sensible heat from the supply air stream to the exhaust air stream — that is, only 108,000 Btu/hr (31.9 kW). Balanced airflow is difficult to achieve in actual installations: exfiltration and local exhausts usually result in a system-level exhaust airflow that is less than the outdoor airflow brought into the building. Despite this challenge, equalizing outdoor and exhaust airflows not only affords the greatest reductions in cooling and heating capacities but also increases energy savings. Q s = 0.79 1.085 7 000 cfm 96°F – 78°F Q s = 108 000 Btu/hr Note: In most applications, an exhaust airflow that is at least 70 percent of the outdoor airflow yields an attractive payback. Q s = 0.79 1.21 3.3 m³/s 35.7°C – 25.6°C Q s = 31.9 kW 8 SYS-APM003-EN Applications for Air-to-Air Energy Recovery Outdoor-Air Preconditioning Buildings are ventilated with outdoor air to prevent the buildup of contaminants that are generated indoors. In most climates, this outdoor air imposes a sizable load on the HVAC equipment. Outdoor-air preconditioning is the process of cooling, dehumidifying, heating, and/or humidifying the outdoor air entering the system. Using air-to-air energy recovery (sometimes called “exhaust-air energy recovery”) to perform this function can significantly reduce the load on HVAC equipment as well as the energy consumed by that equipment. Energy recovery may even be required to comply with ASHRAE Standard 90.1–2007 (Section 6.5.6) and other energy codes. Figure 5. OA-preconditioning arrangements sensible heat plus moisture total-energy recovery sensible heat only sensible-energy recovery Figure 5 represents air-to-air energy-recovery arrangements that precondition outdoor air (OA) by exchanging energy with the exhaust air (EA) stream. During the cooling season, when it is hot and humid outside, the total-energy-recovery device precools and “pre-dries” (dehumidifies) the outdoor air by transferring both sensible heat and moisture to the exhaust air stream. During the heating season, when outdoor conditions are cold and dry, the same arrangement preheats and prehumidifies the outdoor air by removing both sensible heat and moisture from the exhaust air stream and releasing it into the supply air stream. Substituting a sensible-energy recovery device limits energy transfer to sensible heat; moisture (latent heat) is not recovered. As the examples that follow demonstrate, either type of recovered energy — sensible or total — can effectively precondition outdoor air. First cost and potential energy savings typically determine which type of recovery best suits a particular application. Sensible versus Total Energy Recovery A Scenario to Aid Comparison An energy-recovery device installed in a central air handler preconditions 10,000 cfm (4.7 m³/s) of outdoor air. Local exhausts for the rest rooms remove air from the building, as does the exfiltration caused by maintaining an indoor pressure that is slightly positive relative to outdoors. With only 7,000 cfm (3.3 m³/s) exhausted centrally, unbalanced airflows exist at the energy-recovery device. Table 1, p. 10, summarizes the design airflows and thermal conditions for this scenario. The rest of this section compares the energy-recovery performance of this system in two climates — Jacksonville, Florida (predominantly cooling) and Minneapolis, Minnesota (predominantly heating) — and with different energyrecovery devices: a coil loop that recovers only sensible energy and a total-energy wheel that recovers both sensible and latent energy. SYS-APM003-EN 9 Precondition Outdoor Air Applications for Air-to-Air Energy Recovery Table 1. Design parameters for examples of OA preconditioning (Figures 6 – 9) Cooling (ASHRAE 0.4%) Location1 Jacksonville, Fla. 96°F DB (35.7°C) 76°F WB (24.5°C) 31°F DB (-0.8°C) Minneapolis, Minn. 91°F DB (32.8°C) 73°F WB (22.7°C) -16°F DB (-26.5°C) 78°F DB (25.6°C) 63.5°F WB (17.5°C) 70°F DB (21.1°C) 54 °F WB (12.2 °C) Return air from the conditioned space Airflows Heating (ASHRAE 99.6%) Outdoor 10,000 cfm (4.7 m³/s) Central exhaust 7,000 cfm (3.3 m³/s) Local exhaust (rest rooms) 2,500 cfm (1.2 m³/s) Exfiltration through building envelope 500 cfm (0.2 m³/s) 1 Cooling design conditions for these locations represent the ASHRAE 0.4% design condition for sensible cooling, that is, the peak dry-bulb temperature and mean coincident wet-bulb temperature. Heating design conditions represent the ASHRAE 99.6% design condition. OA Preconditioning with Recovered Sensible Energy For this comparison, the sensible-energy recovery device in Figure 6 represents a coil loop with an effectiveness of 57 percent. During the cooling season, the coil loop preconditions the outdoor air stream by transferring sensible heat to the exhaust air stream. During the heating season, it warms the entering outdoor air with sensible heat recovered from the exhaust air. Let’s first look at the design conditions for Jacksonville, Florida, where cooling predominates. The ASHRAE 0.4-percent condition for sensible cooling design (that is, peak dry-bulb temperature and mean coincident wet-bulb temperature) is 96°F dry bulb and 76°F wet bulb (35.7°C DB, 24.5°C WB). At this condition, Figure 6. OA preconditioning with sensible-energy recovery in Jacksonville, Florida 10 SYS-APM003-EN Precondition Outdoor Air Applications for Air-to-Air Energy Recovery Figure 7. OA preconditioning with sensible-energy recovery in Minneapolis, Minnesota Cooling-season savings in Jacksonville, Fla.: Q s = 1.085 10 000 cfm 96°F – 88.8°F Q s = 78 120 Btu/hr = 6.5 tons Q s = 1.21 4.7 m³/s 35.7°C – 31.6°C Q s = 23.3 kW Heating-season savings in Jacksonville, Fla.: Q s = 1.085 10 000 cfm 47.9°F – 31°F Q s = 183 365 Btu/hr = 183 MBh Q s = 1.21 4.7 m³/s 8.8°C – – 0.8 °C Q s = 54.6 kW Cooling-season savings in Minneapolis, Minn.: Q s = 1.085 10 000 cfm 91°F – 85.9°F Q s = 55 335 Btu/hr = 4.6 tons Q s = 1.21 4.7 m³/s 32.8°C – 29.9°C Q s = 16.5 kW Heating-season savings in Minneapolis, Minn.: Q s = 1.085 10 000 cfm 6.6°F – – 16 °F Q s = 245 210 Btu/hr = 245 MBh Q s = 1.21 4.7 m³/s – 14.1 °C – – 26.5 °C Q s = 70.5 kW SYS-APM003-EN based on data from a coil selection program, the coil loop precools the outdoor air to 88.8°F DB (31.6°C). It also reduces the required cooling capacity by 6.5 tons (23.3 kW), which means lower operating costs and permits downsizing of the cooling plant. Figure 6 also shows the winter performance of the coil loop. The ASHRAE 99.6-percent condition for heating design in Jacksonville is 31°F DB (-0.8°C). This time the coil loop transfers sensible heat from the exhaust air stream to the outdoor air stream, warming it to 47.9°F (8.8°C). The recovered energy reduces the design heating capacity by 183 MBh (54.6 kW) and, in turn, reduces operating costs and permits downsizing of the heating plant. How well does the same coil loop recover sensible energy in a climate where heating predominates? Figure 7 depicts the performance of our example HVAC system in Minneapolis, Minnesota. At the sensible-cooling-design condition of 91°F DB and 73°F WB (32.8°C DB, 22.7°C WB), the coil loop precools the outdoor air to 85.9°F DB (29.9°C) and reduces the required cooling capacity by 4.6 tons (16.5 kW). At the heating design condition of -16°F (-26.5°C), recovered energy preheats the outdoor air to 6.6°F (-14.1°C), which saves 245 MBh (70.5 kW). Notice that the air that passes through the exhaust side of the coil loop reaches the saturation curve (Figure 7), indicating that moisture from the exhaust air stream is condensing on the coil surface. The small amount of latent heat removed from the exhaust air contributes to the total quantity of heat that transfers to the outdoor air stream; however, only sensible (not latent) heat is transferred. Condensation on the exhaust side of the energy-recovery device can pose a problem in cold climates. (See “Frost Prevention,” pp. 18–19.) 11 Precondition Outdoor Air Applications for Air-to-Air Energy Recovery OA Preconditioning with Recovered Total Energy Figure 8 and Figure 9 illustrate the effect of recovering total energy in the scenario described on p. 9. For this example, the energy-recovery device is a total-energy wheel with an effectiveness of 82 percent, given unbalanced airflows of 10,000 cfm (4.7 m³/s) on the supply side of the wheel and 7,000 cfm (3.3 m³/s) on the exhaust side. During the cooling season, the wheel transfers sensible and latent heat (moisture) from the outdoor air stream to the exhaust air stream, precooling and dehumidifying the incoming outdoor air. Conversely, the wheel warms and humidifies the outdoor air stream during the heating season, using sensible heat and moisture recovered from the exhaust air stream. Cooling-season savings in Jacksonville, Fla.: Q T = 4.5 10 000 cfm 39.3 – 33.3 Btu/lb Q T = 270 000 Btu/hr = 22.5 tons Q T = 1.2 4.7 m³/s 91.4 – 77.5 kJ/kg Q T = 78.4 kW Heating-season savings in Jacksonville, Fla.: Q s = 1.085 10 000 cfm 53.3°F – 31°F Q s = 241 955 Btu/hr = 242 MBh Q s = 1.21 4.7 m³/s 11.8°C – – 0.8 °C Q s = 71.7 kW Q L = 0.7 10 000 cfm 29.3 – 20.2 grains/lb Q L = 63 700 Btu/hr = 63.7 MBh Q L = 3 010 4.7 m³/s 0.0042 – 0.0029 kg/kg Q L = 18.4 kW The selection program for the wheel indicates that, at Jacksonville’s cooling design condition (Table 1, p. 10), the wheel will cool and dehumidify the outdoor air to 85.7°F DB and 69.3°F WB (29.8°C DB, 20.7°C WB). See Figure 8. Transferring moisture as well as sensible heat lowers operating costs and reduces the required cooling capacity — this time by 22.5 tons (78.4 kW). At Jacksonville’s heating design condition, the sensible energy recovered from the exhaust air stream raises the dry-bulb temperature of the entering outdoor air to 53.3°F DB (11.8°C). Preheating the outdoor air in this fashion reduces the required heating capacity by 242 MBh (71.7 kW). The total-energy wheel also humidifies the entering outdoor air with moisture recovered from the exhaust air stream, increasing the moisture content from 20.2 grains/lb to 29.3 grains/lb (0.0029 kg/kg to 0.0042 kg/kg). If the HVAC system includes a mechanical humidifier, the capacity required at design can be reduced by 63.7 MBh (18.4 kW). Figure 8. OA preconditioning with total energy recovery in Jacksonville, Florida 12 SYS-APM003-EN Precondition Outdoor Air Applications for Air-to-Air Energy Recovery Figure 9. OA preconditioning with total energy recovery in Minneapolis, Minnesota Cooling-season savings in Minneapolis, Minn.: Q T = 4.5 10 000 cfm 36.5 – 32.1 Btu/lb Q T = 198 000 Btu/hr = 16.5 tons Q T = 1.2 4.7 m³/s 84.9 – 74.7 kJ/kg Q T = 57.5 kW Heating-season savings in Minneapolis, Minn.: Q s = 1.085 10 000 cfm 40.1°F – 1°F Q s = 424 235 Btu/hr = 424 MBh Q s = 1.21 4.7 m³/s 4.5°C – – 17.2 °C Q s = 123.4 kW Q L = 0.7 10 000 cfm 21.0 – 2.0 grains/lb Q L = 133 000 Btu/hr = 133.0 MBh Q L = 3 010 4.7 m³/s 0.003 – 0.0003 kg/kg Q L = 38.2 kW Figure 9 illustrates how the same total-energy wheel performs in Minneapolis at design conditions. During the summer, the wheel cools and dehumidifies the outdoor air to 83.6°F DB, 67.8°F WB (28.7°C DB, 19.9°C WB), which lowers the required cooling capacity by 16.5 tons (57.5 kW). During the winter, the wheel heats the outdoor air to 40.1°F (4.5°C) DB, which saves 424 MBh (123.4 kW) in sensible heating capacity. The wheel also humidifies the entering outdoor air, raising its moisture content from 2 grains/lb to 21 grains/lb (0.0003 kg/kg to 0.003 kg/kg). If the HVAC system includes mechanical humidification, then operating the total-energy wheel will reduce the required humidification capacity by 133 MBh (38.2 kW). Note: We added a preheat coil upstream of the wheel for our Minneapolis example. The preheat coil warms the entering outdoor air to about 1°F (-17.2°C) to prevent frost from forming on the exhaust-side surface of the wheel. See “Frost Prevention,” pp. 18 –19 and pp. 55 – 56, for more information. Effect on First Cost The previous examples demonstrate the effects of preconditioning outdoor air with energy recovered from the exhaust air stream. Although the benefits are appealing, they are not without cost. Depending on size and complexity, adding an energy-recovery device can significantly increase the initial investment in the air handler. Additional exhaust ductwork. Except for coil loops, air-to-air energyrecovery devices require adjacent air streams. Routing most of the exhaust air SYS-APM003-EN 13 Precondition Outdoor Air Applications for Air-to-Air Energy Recovery to a central location so that the path is adjacent to that of the entering outdoor air may require more ductwork (and space) than an application without energy recovery. Even if a coil loop is used, minimizing the distance between the air streams will not only reduce piping- and glycol-related costs but also permit a smaller pump and expansion tank. Increased fan motor sizes. Adding an air-to-air energy-recovery device to precondition outdoor air increases the static pressure drop in both the outdoorand exhaust-air paths, requiring larger fan motors. It may even create the need for a powered, central exhaust fan where one was not required before. The configuration of the fans will determine the extent to which their motor sizes — and energy consumption — will increase. In a mixed-air system, the impact on the supply fan depends on the pressure drop through the outdoor-air path versus that of the return-air path. If the static pressure drop through the return-air path is greater, the supply fan need not overcome the entire static pressure drop created by the energy-recovery device. Adding a third (and even a fourth) fan could make it unnecessary to increase the sizes of the supply and exhaust fan motors. The energy costs of this approach would be nearly the same as for a two-fan system, although the installation and maintenance costs would almost certainly be higher. Heating- and cooling-plant downsizing. Whether the climate is predominantly cooling (Jacksonville, Florida) or predominantly heating (Minneapolis, Minnesota), the first-cost savings from even a modest reduction in HVAC capacity can at least partially subsidize the investment in the energyrecovery device, associated ductwork, and larger fan motors. The decision to use an air-to-air energy-recovery device for outdoor-air preconditioning requires careful consideration … and not for solely economic reasons. Downsizing the HVAC equipment, particularly in packaged directexpansion (DX) applications, avoids other system- and building-related problems that can result from overcapacity. Providing too much available cooling can cause compressors to short-cycle and create swings in supply-air temperature that not only make occupants uncomfortable but also result in inadequate humidity control. Failure to maintain appropriate humidity levels can cause microbial growth to flourish inside the building, adversely affecting occupant health and accelerating the deterioration of structural components and furnishings. Table 2 summarizes the plant-downsizing potential provided by the sensibleand total-energy recovery devices in the previous examples. Recall that unbalanced airflows through an energy-recovery device increase effectiveness but lessen the amount of heat transferred overall. Table 3 illustrates the additional first-cost savings made possible by routing the rest-room exhaust through the energy-recovery device — which reduces the airflow imbalance from 3,000 cfm to 500 cfm (1.4 m³/s to 0.2 m³/s) — rather than expelling it locally. The net savings in first cost usually makes it beneficial to route as much 14 SYS-APM003-EN Precondition Outdoor Air Applications for Air-to-Air Energy Recovery exhaust air to the energy-recovery device as possible, despite the extra expense incurred for rest-room-exhaust ductwork and exhaust-fan power. The economics of using an air-to-air energy recovery device to precondition outdoor air often hinges on downsizing both plants, cooling and heating. Some engineers hesitate to reduce the capacity of the heating plant for installations in cold climates even though the energy-recovery device makes the extra capacity redundant. (The importance of redundancy depends on the specific application.) Their reluctance often reflects concern that the failure of the energy-recovery device, usually a total-energy wheel, will leave the system without sufficient capacity to heat the building. That concern is unwarranted because the total-energy wheel only reduces the heating load of the outdoor air brought into the building for ventilation. If a mechanical failure occurs, the system operator can choose to temporarily bring less outdoor air into the building until the wheel is repaired. This observation raises another important point: An energy-recovery device that preconditions outdoor air is no less critical than the boiler or the belt on a supply fan. If the wheel breaks, repair it promptly. Table 2. Capacity reductions attributable to OA preconditioning (unbalanced airflows) Capacity Reduction Due to Recovered Energy1 Jacksonville, Florida Minneapolis, Minnesota Sensible Total Sensible Total Cooling plant 6.5 tons (23.3 kW) 22.5 tons (78.4 kW) 4.6 tons (16.5 kW) 16.5 tons (57.5 kW) Heating plant 183.0 MBh (54.6 kW) 242.0 MBh (71.7 kW) 245.0 MBh (70.5 kW) 424.0 MBh (123.4 kW) Humidification system n/a 63.7 MBh (18.4 kW) n/a 133.0 MBh (38.2 kW) 1 Capacity reductions are based on the effectiveness of the energy-recovery device, which results from the unbalanced airflows of 10,000 cfm (4.7 m³/s) outdoor air and 7,000 cfm (3.3 m³/s) exhaust air. Table 3. Capacity reductions attributable to OA preconditioning (“balanced” airflows) Capacity Reduction Due to Recovered Energy1 Jacksonville, Florida Minneapolis, Minnesota Sensible Total Sensible Total Cooling plant 7.3 tons (26.3 kW) 25.1 tons (88.3 kW) 5.2 tons (18.3 kW) 19.9 tons (69.7 kW) Heating plant 187.7 MBh (56.5 kW) 289.7 MBh (84.9 kW) 299.5 MBh (87.9 kW) 517.5 MBh (151.3 kW) Humidification system n/a 78.4 MBh (23.7 kW) n/a 161.0 MBh (46.9 kW) 1 Capacity reductions are based on the effectiveness of the energy-recovery device, which results from the nearly balanced airflows of 10,000 cfm (4.7 m³/s) outdoor air and 9,500 cfm (4.5 m³/s) exhaust air. SYS-APM003-EN 15 Precondition Outdoor Air Applications for Air-to-Air Energy Recovery Effect on Operating Costs Less energy consumed for heating and cooling. Typically, the “real” money in using air-to-air energy recovery for outdoor-air preconditioning accrues from the first-cost “subsidy” rather than lower operating costs. Still, if the first-cost subsidy from downsizing the cooling and heating plants does not entirely offset the initial investment in the energy-recovery device, operating cost savings may quickly make up the difference. Energy simulation software makes it easier to predict and evaluate how various energy-recovery devices will perform in a particular application. Such an analysis can predict the length of the payback period based on the building location, type of building, type of HVAC system, system control modes, quantity of outdoor air, airside economizer operation, and local utility rates. Interaction between different system operating modes and the airside economizer often requires the use of a whole-building economic analysis (performed with the help of DOE-2, TRACE™, System Analyzer™, or similar software). More energy consumed by fans. Whenever air passes through the air-to-air energy recovery device, the static pressure drop of the system increases and the fans, in turn, consume more energy. The magnitude of the pressure drop through the device and the configuration of the fans determine how much additional energy is consumed. The operating cost savings provided by recovered energy must exceed the increased cost of operating the fans in order to justify the cost of the energy-recovery device. A year-round, project-specific analysis must be performed to determine the overall effect on the energy consumption of the HVAC system. Proper airside economizer control. In many climates, the operation of a mixed-air system’s airside economizer can provide the benefits of “free” cooling for much of the year. While the economizer operates, air-to-air energy recovery offers no additional benefit. In fact, unless it is turned off, the energyrecovery device actually increases the cooling load by adding heat to the supply air stream. Achieving maximum energy savings and minimizing the payback period for energy recovery therefore depends on proper economizer operation as well as on proper integration of the energy-recovery device into the system control modes. (For a detailed discussion of these control modes, see “SystemLevel Control of Recovered Energy,” pp. 65 – 89.) When the HVAC system includes an airside economizer, size the air-to-air energy-recovery device to precondition only the minimum outdoor airflow required for ventilation … not the maximum airflow expected during economizer operation. (Avoiding oversizing also minimizes the first cost of the device.) To accommodate economizer operation when the energy-recovery device is idle, add bypass dampers (Figure 10) to reduce the airside pressure drop and 16 SYS-APM003-EN Precondition Outdoor Air Applications for Air-to-Air Energy Recovery Figure 10. Central air handler with economizer and energy recovery Bypass dampers divert airflow around the energy wheel during economizer operation. minimize the energy consumption of the fans. Alternatively, provide two separate paths for outdoor air: one for “ventilation” air and the other for “economizer” air. Note: Section 6.5.6.1 of ASHRAE Standard 90.1–2007 requires bypass, or some other control, to permit airside economizer operation when an economizer is required by Section 6.5.1.1. Need for capacity control. Although it is often overlooked, capacity control is a key aspect of designing an HVAC system that uses air-to-air energy recovery to precondition outdoor air. Regardless of whether sensible or total energy is recovered, modulating the capacity of the energy-recovery device prevents it from overheating the supply air when weather conditions are cold but not extreme. Consider the following example. Assume that a total-energy wheel preconditions outdoor air in a mixed-air, variable-air-volume (VAV) system that supplies air at a constant 55°F DB (12.8°C); see Figure 11. When it is 40°F DB (4.4°C) outside, the system delivers a Figure 11. Unmodulated energy-recovery capacity for OA preconditioning SYS-APM003-EN 17 Precondition Outdoor Air Applications for Air-to-Air Energy Recovery Figure 12. Modulated energy-recovery capacity for OA preconditioning supply airflow of 18,000 cfm (8.5 m³/s). With the wheel turned off, the resulting mixed-air condition would be 53.3°F (11.8°C). Activating the wheel transfers sensible heat (and moisture) from the warm exhaust air to the cool entering outdoor air, avoiding the use of mechanical heating. However, if allowed to operate at full capacity, the wheel would heat the entering outdoor air to 64.6°F (18.1°C) and, after mixing with return air from the space, produce a mixed-air condition of 67°F (19.4°C). Mechanical or economizer cooling is then necessary to obtain the supply-air target of 55°F (12.8°C). Regulating the capacity of the wheel — in this case, by modulating the exhaustside dampers (Figure 12) —can prevent overheating. Operating the wheel at less than full capacity allows it to warm the entering outdoor air to only 43°F (6.1°C), which yields 55°F (12.8°C) mixed air without the help of mechanical heating or cooling. Note: Capacity control for energy-recovery devices is important during heating operation, but is seldom required during the cooling mode. Specific control methods are discussed in “Energy-Recovery Technologies,” pp. 38 – 59. Other Considerations Although it is important to optimize life-cycle costs, other issues must be considered to effectively precondition outdoor air using air-to-air energy recovery. Frost prevention. Any air-to-air energy-recovery device that preconditions outdoor air is subject to frost buildup during very cold weather. That’s because the moisture that condenses on the exhaust-side of the device (recall Figure 7, p. 11) freezes, eventually blocking airflow, if the surface temperature of the device falls below 32°F (0°C). Device effectiveness, entering conditions, and 18 SYS-APM003-EN Precondition Outdoor Air Applications for Air-to-Air Energy Recovery Figure 13. Psychrometric comparison of frost thresholds for energy-recovery devices Saturation (moisture condensation) occurs along this curve airflows determine the outdoor temperature at which frost forms; but the threshold is much lower for total-energy-recovery devices than for devices that recover only sensible energy. Figure 13 illustrates why ... When exhaust air passes through a total-energy-recovery device, the transfer of moisture to the outdoor air stream (psychrometrically) prevents the leaving exhaust-air condition from reaching the saturation curve. Sensible-energyrecovery devices do not remove moisture from the exhaust air stream, so the leaving exhaust-air condition reaches saturation (and frosts) at a warmer outdoor condition. Note: Although the latent heat of condensation is slight, it contributes to the amount of heat that a sensible-energy-recovery device transfers to the outdoor air stream. Frost can be avoided in one of two ways: ■ Reduce the heat-transfer capacity of the energy-recovery device. This practice raises the surface temperature of the device, but limits the extent to which the heating plant can be downsized. ■ Preheat the outdoor (or exhaust) air before it enters the energy-recovery device. Permitting full-capacity energy recovery at the coldest outdoor conditions maximizes the potential downsizing of the heating plant. “Air-to-Air Energy Recovery Technologies” (pp. 38 – 59) discusses specific frost prevention methods for various air-to-air energy-recovery devices. Proximity of outdoor-air intake to building exhaust. Local codes often impose a minimum separation distance between the outdoor-air intake and the building exhaust. In applications that route the exhaust air to an indoor air handler for energy recovery, the outdoor- and exhaust-air ductwork can usually be arranged to provide the minimum separation distance. Meeting this requirement poses a greater design challenge in applications with outdoor air handlers. Note: Table 5-1 of ASHRAE Standard 62.1-2007 includes minimum separation distance requirements for the location of an outdoor-air intake. For example, SYS-APM003-EN 19 Applications for Air-to-Air Energy Recovery the standard requires positioning the outdoor-air intake at least 1 ft (0.3 m) above the ground or roof, and at least 15 ft (5 m) from any source of significantly-contaminated (Class 3) exhaust. Acceptable cross-leakage. Many types of air-to-air energy-recovery devices permit some degree of cross-leakage, although the amount of leakage is usually less than 5 percent (even for wheels) in most applications. (“EnergyRecovery Technologies,” pp. 38 – 59, discusses specific methods of reducing cross-leakage for various types of air-to-air energy-recovery devices.) Cross-leakage between the exhaust- and supply-air streams is seldom problematic in mixed-air systems: most of the air that returns from the space is recirculated as supply air anyway. Local codes that permit the recirculation of exhaust air from rest rooms usually require sufficient dilution with fresh outdoor air. Note: Section 5.17 of ASHRAE Standard 62.1-2007 limits the amount of crossleakage for different classes of air. As an example, the standard limits the crossleakage of exhaust air from restrooms (Class 2) to no more than 10 percent of the resulting supply airflow (that is, EATR cannot be greater than 10 percent; see "Exhaust Air Transfer Ratio," page 62). Figure 14. Supply-air (SA) tempering Supply-Air Tempering Supply-air tempering adds sensible heat to the air downstream of the cooling coil so that the dry-bulb temperature and humidity of the conditioned space can be controlled independently. For a more detailed discussion of the use of supply-air tempering to control space humidity, refer to the Engineers Newsletter titled “Dehumidify with Constant-Volume Systems” (ENEWS29/4). You can find it at www.trane.com/ engineersnewletters. The Trane applications engineering manual, Dehumidification in HVAC Systems (SYS-APM004-EN), also addresses this subject. It is available from the Trane bookstore at www.trane.com/bookstore. ■ 20 In the simple schematic depicted in Figure 14, the cooling coil dehumidifies the supply air, lowering the dew point sufficiently to maintain the desired space humidity. If the dehumidified supply air is so cold that it would overcool the space, then it must be reheated (or “tempered”) before delivery to prevent the dry-bulb temperature in the space from falling below the setpoint. Only systems that directly control the space humidity or supply-air dew point require supply-air tempering. Common applications include: ■ Constant-volume, mixed-air systems that directly control space humidity ■ Dedicated (100-percent) outdoor-air systems that deliver dry (low dew-point) air at a “space-neutral” dry-bulb temperature Supply-air tempering can be accomplished using either new energy — electricity, hot water, steam or gas, for example — or recovered energy from another part of the system. Moisture transfer is seldom desirable when tempering supply air, so energy recovery is typically limited to sensible heat. SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Note: To comply with ASHRAE Standard 90.1–2007 (Section 6.5.2) and related energy codes, site-recovered energy may be required for applications that include supply-air tempering. Standard 90.1 (see p. 4) limits the use of reheat in a previously cooled air stream unless at least 75 percent of the reheat energy is recovered. The rest of this section examines the effect of using air-to-air heat exchangers to temper the supply air in a constant-volume mixed-air system and in a dedicated outdoor-air system. Supply-Air Tempering in Mixed-Air Systems Table 4. Design parameters for examples of SA tempering in a mixed-air system (Figures 15–20) Cooling (ASHRAE 0.4%) Sensible Outdoor conditions1 Indoor setpoints Airflows 96°F DB (35.7°C) 76°F WB (24.5°C) Latent 84°F DB (28.8°C) 76°F DP (24.6°C) Dry-bulb temperature 74°F DB (23.3°C) Relative humidity (max limit) 60% 2 Supply 1,500 cfm (0.7 m³/s) Outdoor 450 cfm (0.2 m³/s) 1 Cooling design conditions represent the peak dry- bulb temperature and mean coincident wet-bulb temperature for sensible cooling, and the peak dew point and mean coincident dry-bulb temperature for latent cooling, in Jacksonville, Florida. To demonstrate the potential savings of tempering supply air with recovered energy, let’s examine the mixed-air HVAC system designed for a year-round school in Jacksonville, Florida. See Figure 15. The system consists of a constant-volume air handler that delivers 1,500 cfm (0.7 m³/s) of supply air to a single classroom. Outdoor air for ventilation accounts for 450 cfm (0.2 m³/s) of the supply air. At the ASHRAE 0.4-percent “sensible-design” condition — that is, peak drybulb temperature of 96°F and mean coincident wet-bulb temperature of 76°F (35.7°C DB, 24.5°C WB) — the system delivers 55.7°F (13.2°C) supply air to offset the space sensible load. Table 4 summarizes the thermal conditions and design airflows for this scenario. At part-load conditions, the constant-volume system responds to the decreasing space sensible load by supplying warmer air to the space. When the relative humidity in the space exceeds the 60-percent limit, modulation of the cooling coil’s capacity maintains the space relative humidity below the maximum limit, while modulation of the reheat coil’s capacity maintains the dry-bulb temperature at setpoint. 2 The maximum limit for indoor humidity control used in this example is 60 percent. SYS-APM003-EN Figure 15. SA tempering in a constant-volume, mixed-air HVAC system 21 Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 16. Mixed-air HVAC System with SA tempering Note: A common alternative to modulating the capacity of the cooling coil is to operate it at maximum capacity when dehumidifying. This control strategy quickly lowers space humidity, and then returns the system to the normal cooling mode. Tempering energy needed at latent design: Q s = 1.085 1 500 cfm 63°F – 59°F Q s = 6 510 Btu/hr Q s = 1.21 0.7 m³/s 17.2°C – 15°C Q s = 1.86 kW Figure 16 plots the psychrometric conditions of the outdoor air, supply air, and return air at the ASHRAE 0.4-percent design conditions. For Jacksonville, the “latent-design” condition is a peak dew point of 76°F and a mean coincident dry-bulb temperature of 84°F (24.6°C DP, 28.8°C DB). The sensible load in the space is lower at this condition than it is at the sensible-design condition. Therefore, the temperature of the supply air must be warmer — 63°F (17.2°C) in this example — to match the sensible cooling capacity with the sensible load in the space and avoid overcooling. To accomplish this, the cooling coil first dehumidifies the supply air to 59°F (15°C) in order to maintain a relative humidity of 60 percent in the space. The reheat coil then raises the dry-bulb temperature of the supply air to 63°F (17.2°C). Without the use of energy recovery, tempering the supply air requires 6,510 Btu/hr (1.86 kW) of new energy. Air-to-air recovery for supply-air tempering can be accomplished using either of two configurations: series or parallel. The next sections compare their respective performance. Series Configuration Figure 17 shows an air-to-air, sensible-energy-recovery device applied in a series, or “wraparound,” configuration within a constant-volume, mixed-air system. (Although the example depicts a coil loop, any sensible-energyrecovery device could be used.) The device removes heat from the air upstream of the cooling coil and releases it in the supply air downstream of the coil. 22 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 17. SA tempering: “Series” transfer in a constant-volume, mixed-air system Although it is described as energy “recovery,” this arrangement does not “recover” heat; instead, it transfers heat from one location to another within the same air stream. At the part-load, latent-design condition for our example classroom, mixed air enters the upstream coil of the coil loop at 77°F DB and 69°F WB (25°C DB, 20.6°C WB). The coil loop removes sensible heat from the mixed air, cooling it to 73.2°F DB (22.9°C DB), and then transfers that heat to the other side of the coil loop, downstream of the cooling coil. As shown in Figure 18, the cooling coil must dehumidify the air to 59°F (15°C) in order to keep the relative humidity in the space below the 60-percent limit. The downstream coil of the coil loop then warms the supply air to the desired dry-bulb temperature of 63°F (17.2°C). Using air-to-air energy recovery not only saves the 6,510 Btu/hr (1.86 kW) of heating energy needed for tempering, but also reduces the load on the cooling Figure 18. SA tempering: “Series” transfer in a constant-volume, mixed-air system SYS-APM003-EN 23 Temper Supply Air Applications for Air-to-Air Energy Recovery Cooling-energy savings at latent design: coil by precooling the mixed air before it enters the cooling coil. Reducing the enthalpy of the mixed air to 32.2 Btu/lb (74.9 kJ/kg) saves 6,075 Btu/hr (1.76 kW) of cooling energy. Q T = 4.5 1 500 cfm 33.1 – 32.2 Btu/lb Q T = 6 075 Btu/hr Q T = 1.2 0.7 m³/s 77.0 – 74.9 kJ/kg Q T = 1.76 kW Notice that in a mixed-air system, the use of an air-to-air energy-recovery device in a series configuration does not reduce the installed capacity of the cooling plant. At the sensible-design condition, the 55.7°F (13.2°C) air that is supplied to the space does not require tempering. Without heat transfer, no precooling occurs. Therefore, the cooling coil and cooling plant must be sized to handle the entire cooling load at the sensible-design condition. Parallel Configuration Figure 19 shows the same constant-volume, mixed-air system … but this time the air-to-air, sensible-energy-recovery device is applied in a parallel configuration. (Again, although this example depicts a coil loop, any sensibleenergy-recovery device can be used.) The device recovers sensible heat from the return air stream and releases it in the supply air downstream of the cooling coil, raising its temperature. At the part-load, latent-design condition, air returns from the space and enters the return-side coil of the coil loop at 74°F DB and 64.5°F WB (23.3°C DB, 18.1°C WB). The coil loop removes sensible heat from the return air stream, cooling it to 70.1°F DB (21.2°C DB), and then transfers this heat to the supplyside coil of the coil loop, downstream of the cooling coil. See Figure 20. At this condition, the air leaving the cooling coil must be 59°F (15°C) to maintain the relative humidity in the space below the 60-percent limit. The supply-side coil of the coil loop then heats the supply air to the desired dry-bulb temperature of 63°F (17.2°C). Like the series configuration, the parallel configuration also reduces the load on the cooling coil while saving the 6,510 Btu/hr (1.86 kW) of heating energy Figure 19. SA tempering: “Parallel” recovery in a constant-volume, mixed-air system 24 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 20. SA tempering: “Parallel” recovery in a constant-volume, mixed-air system Cooling-energy savings at latent design: Q T = 4.5 1 500 cfm 33.1 – 32.5 Btu/lb Q T = 4 050 Btu/hr Q T = 1.2 0.7 m³/s 77.0 – 75.6 kJ/kg Q T = 1.18 kW needed for tempering. By removing sensible heat from the return air, the coil loop effectively lowers the enthalpy of the mixed air from 33.1 Btu/lb to 32.5 Btu/lb (77.0 kJ/kg to 75.6 kJ/kg). The resulting savings is 4,050 Btu/hr (1.18 kW) of cooling energy. Applying an air-to-air energy recovery device in a parallel (rather than series) arrangement within a mixed-air system still does not reduce the installed capacity of the cooling plant. The supply air does not require tempering at the sensible-design condition, so no precooling occurs. Both the cooling coil and the cooling plant must therefore be sized to handle the entire cooling load at the sensible-design condition. Series versus Parallel In mixed-air systems, both series and parallel configurations reduce the heating energy required for tempering. Although the series configuration saves more cooling energy than the parallel configuration, neither permits downsizing of the cooling or heating plant. With the series configuration, outdoor conditions largely determine the condition of the mixed air that enters the energy-recovery device. As a result, the amount of heat available for transfer varies, but can be larger than the constant quantity of heat that the parallel configuration recovers from the return air stream. In other words, the series configuration benefits when the outdoor air is warmer than the return air; the parallel configuration benefits when the outdoor air is cooler than the return air. Three criteria ultimately determine which energy-recovery arrangement is the right choice for a given project … SYS-APM003-EN 25 Temper Supply Air Applications for Air-to-Air Energy Recovery ■ First cost ■ Savings in cooling and heating energy ■ Additional fan energy to overcome the static pressure drop of the energyrecovery device Supply-Air Tempering in Dedicated Outdoor-Air Systems Dedicated outdoor-air systems should dehumidify the outdoor air to a low dew point, typically 45°F to 55°F DP (7.2°C to 12.8°C). This allows the dedicated outdoor-air system to offset the space latent loads as well as the ventilation load. Dehumidifying to a low dew point provides two benefits: ■ ■ Smaller space loads, which permits downsizing of the constant-volume terminal units Virtually no condensation in the space (The cooling coil in each terminal operates dry because it handles only the sensible load.) The Trane applications engineering manual, Dehumidification in HVAC Systems (SYS-APM004-EN), addresses dedicated outdoor-air systems in detail. It is available from the Trane bookstore at www.trane.com/bookstore. ■ Dedicated outdoor-air systems that are designed to deliver dry (low dew-point), “neutral-temperature,” conditioned air also need tempering and can benefit by using air-to-air sensible-energy recovery to provide it. (An alternative approach is to deliver the dehumidified outdoor air cold — that is, not reheated to neutral, see pp.65-66.) Systems of this type typically deliver the conditioned outdoor air to ceiling plenums (when used with fan-coils, for example) or directly to occupied spaces (as in water-source heat pump applications, for example). Sensible-energy recovery may decrease the first cost and operating costs of the system when compared to using new energy for tempering. It may also enable compliance with energy standards and local codes. To demonstrate the potential for energy savings, let’s revisit the example classroom in Jacksonville, Florida. This time, a dedicated outdoor-air handler (or makeup-air unit) delivers conditioned outdoor air, CA, directly to several classrooms at a “neutral,” dry condition of 71°F DB, 53°F DP (21.7°C DB, 11.7°C DP). It conditions 450 cfm (0.2 m³/s) of outdoor air for each classroom. The capacity of the cooling coil modulates to maintain the conditioned-air dew point at setpoint; similarly, the capacity of the reheat coil modulates to maintain the conditioned-air dry-bulb temperature at setpoint. Separate, constant-volume terminals, one in each classroom, handle the space load. See Figure 21. Note: An alternative to maintaining a fixed dew point is to reset the conditioned-air dew point to maintain the humidity in the “worst-case” space below the maximum limit. In other words, the capacity of the cooling coil modulates to make the conditioned outdoor air dry enough to keep the most humid room below 60-percent relative humidity. For Jacksonville, the ASHRAE 0.4-percent peak-enthalpy design condition —that is, 42.4 Btu/lb (98.6 kJ/kg) — represents a peak wet-bulb temperature of 79°F (26.2°C WB) and a mean coincident dry-bulb temperature of 91°F (32.6°C DB). In a dedicated outdoor-air system that maintains a constant conditioned-air dew point, this is the condition at which the cooling-coil load is the highest because the enthalpy of the outdoor air is the highest. 26 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 21. SA tempering in a dedicated outdoor-air system Energy required for OA dehumidification: Q T = 4.5 450 cfm 42.4 – 22.1 Btu/lb Q T = 41 108 Btu/hr Q T = 1.2 0.2 m³/s 98.6 – 51.4 kJ/kg Q T = 11.33 kW The cooling coil dehumidifies the outdoor air to 53.5°F DB, 53°F DP (11.9°C DB, 11.7°C DP), which corresponds to an enthalpy of 22.1 Btu/lb (51.4 kJ/kg). See Figure 22. The reheat coil then warms this air to the “neutral” dry-bulb temperature of 71°F (21.7°C). Without the use of energy recovery, the system would consume 41,108 Btu/hr (11.33 kW) of new energy for dehumidification and 8,544 Btu/hr (2.37 kW) for tempering. Energy required for tempering: Q s = 1.085 450 cfm 71.0°F – 53.5°F Q s = 8 544 Btu/hr Q s = 1.21 0.2 m³/s 21.7°C – 11.9°C Q s = 2.37 kW Now, let’s examine the impact of using an air-to-air sensible-energy- recovery device to provide the heat for tempering. As for constant-volume, mixed-air systems, sensible-energy recovery can be applied in either of two configurations to temper the conditioned air in a dedicated outdoor-air system: series and parallel. Figure 22. Dedicated outdoor-air system with SA tempering SYS-APM003-EN 27 Temper Supply Air Applications for Air-to-Air Energy Recovery Series Configuration Figure 23 shows an air-to-air, sensible-energy-recovery device that is applied in a series, or “wraparound,” configuration within a dedicated outdoor-air system. (Although the example depicts a fixed-plate heat exchanger, any sensibleenergy-recovery device could be used.) The device removes sensible heat from the air upstream of the cooling coil and releases it in the air downstream of that coil. Rather than “recover” heat, the series arrangement transfers heat from one location to another within the same air stream. At the peak-enthalpy condition for our example classroom, the upstream side of the fixed-plate heat exchanger removes heat from the entering outdoor air, cooling it to 78.4°F DB, 74.6°F WB (25.8°C DB, 23.7°C WB). Because the air passing through the heat exchanger becomes saturated (Figure 24), that device removes both sensible heat and moisture from the outdoor air stream. The latent heat of condensation that is generated as moisture condenses from the air adds to the overall amount of heat transferred; however, only sensible heat —not moisture — moves to the other side of the heat exchanger. The cooling coil dehumidifies the air to a dew point of 53°F (11.7°C) and all of the heat (sensible and latent) removed from the outdoor air upstream of the cooling coil is transferred (as sensible heat only) to temper the air downstream of that coil. The resulting dry-bulb temperature of the supply air is 71°F (21.7°C). Using the air-to-air energy-recovery device as described here not only saves the 8,544 Btu/hr (2.37 kW) of heating energy needed for tempering, but also decreases the load on the cooling coil by precooling the outdoor air upstream Figure 23. SA tempering: “Series” transfer in a dedicated outdoor-air system 28 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 24. SA tempering: “Series” transfer in a dedicated outdoor-air system Cooling-energy savings: Q T = 4.5 450 cfm 42.4 – 38.2 Btu/lb Q T = 8 544 Btu/hr Q T = 1.2 0.2 m³/s 98.6 – 88.9 kJ/kg Q T = 2.33 kW of the coil. Reducing the enthalpy of the outdoor air to 38.2 Btu/lb (88.9 kJ/kg) saves 8,544 Btu/hr (2.33 kW) of cooling energy. Unlike its application in a mixed-air system, series transfer of sensible energy in a dedicated outdoor-air system enables a reduction in the installed capacity of the cooling plant. By precooling the outdoor air, the energy-recovery device lessens the load on the cooling coil — in this case, by 8,544 Btu/hr (2.33 kW). Of course, delivering the air at a “neutral” condition means that tempering is required whenever the cooling coil is dehumidifying, even at design conditions. When it is cold outside and the dedicated outdoor-air system must heat the entering outdoor air, the cooling coil is turned off. At such times, a seriesconfigured, air-to-air energy-recovery device provides no benefit. Parallel Configuration Figure 25, p. 30, shows the same dedicated outdoor-air system … but this time the air-to-air sensible-energy-recovery device is applied in a parallel configuration. (Again, although a fixed-plate heat exchanger is shown in this example, any sensible-energy-recovery device can be used.) The device recovers sensible heat from the exhaust air stream and releases it downstream of the cooling coil to temper the conditioned outdoor air. At the peak-enthalpy condition for this same classroom example, the outdoor air is cooled and dehumidified to 53°F DP (11.7°C DP) by the cooling coil. The fixed-plate heat exchanger recovers heat from the exhaust air stream and uses it to temper the air downstream of the cooling coil, warming it to 66.9°F DB (19.4°C DB). See Figure 26 on p. 30. The supplemental reheat coil further warms the conditioned air to the desired 71°F DB (21.7°C DB). SYS-APM003-EN 29 Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 25. SA tempering: “Parallel” recovery in a dedicated outdoor-air system Reheat-energy savings: Q s = 1.085 450 cfm 66.9°F – 53.5°F Q s = 6 543 Btu/hr Q s = 1.21 0.2 m³/s 19.4°C – 11.9°C Q s = 1.82 kW The air-to-air energy recovery device in the parallel configuration only saves 6,543 Btu/hr (1.82 kW) of heating energy needed for tempering at this condition. This is because the temperature of the air entering the warm side of the heat exchanger is cooler (78°F versus 91°F [25.6°C versus 32.6°C]) than in the series configuration. Also, unlike the series configuration, the parallel configuration neither reduces the load on the cooling coil, nor permits a smaller cooling plant. Why? Because the heat that is recovered from the exhaust air stream was going to be rejected from the building anyway. Cooling the exhaust air stream does not reduce the load on the cooling coil. The parallel configuration differs from the series configuration in another important way. When it is cold outside and the dedicated outdoor-air system Figure 26. SA tempering: “Parallel” recovery in a dedicated outdoor-air system 30 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 27. SA tempering: “Parallel” recovery in a dedicated outdoor-air system Heating-energy savings: Q s = 1.085 450 cfm 52.3°F – 31°F Q s = 10 400 Btu/hr Q s = 1.21 0.2 m³/s 11.3°C – – 0.8 °C Q s = 2.93 kW must heat the entering outdoor air, the parallel configuration lets the energyrecovery device use heat from the exhaust air stream to warm the entering outdoor air. To demonstrate, consider the winter design condition, which is 31°F DB (-0.8°C DB), for the example classroom in Jacksonville. The heat exchanger removes sensible heat from the 70°F (21.1°C) exhaust air and uses it to warm the entering outdoor air to 52.3°F (11.3°C); see Figure 27. The main heating coil further heats the air to the desired conditioned-air temperature. In this scenario, the parallel configuration saves 10,400 Btu/hr (2.93 kW) of heating energy, cutting operating costs and allowing the heating plant to be downsized. Applying an air-to-air energy-recovery device in a parallel configuration lets it temper supply air and precondition entering outdoor air, although it cannot perform both functions simultaneously. The device tempers the conditioned outdoor air whenever dehumidification is required and preconditions the outdoor air during the heating season. Note: In cold climates, some method of frost prevention may be required. Also, if a chilled-water cooling coil is used, some method to protect that coil from freezing may be required because the energy-recovery device adds heat downstream of the cooling coil. Series versus Parallel In dedicated outdoor-air systems that deliver neutral-temperature air, both series and parallel configurations reduce the new energy that is required for tempering. When it is hot outside, the series configuration can transfer more heat than the parallel arrangement. However, because it is less dependent on outside conditions — and because the return-air condition is relatively stable — the parallel configuration can recover a nearly constant amount heat. SYS-APM003-EN 31 Temper Supply Air Applications for Air-to-Air Energy Recovery The series configuration saves cooling energy, even allowing the cooling plant to be downsized. By contrast, the parallel configuration can be used in the heating mode, which saves heating energy and allows the heating plant to be downsized. Because it warms the ventilation (outdoor) air, a dedicated OA system that delivers neutral air requires more cooling-plant capacity than a comparable system that supplies cold air. Although series-configured energy recovery in a neutral conditioned-air system permits the cooling plant to be downsized with respect to a system with no heat recovery, the cooling plant will still be larger than for a dedicated outdoor-air system that supplies cold air. ■ The parallel configuration requires that most of the building exhaust be routed back to a central location, while the series configuration does not require this additional expense. This additional expense drives most applications to use the series configuration, unless the system includes an additional energy-recovery device to perform outdoor-air preconditioning. An example of this “dualfunction” energy-recovery system is discussed on pp. 84 – 88. As in mixed-air applications, three criteria ultimately determine which energyrecovery arrangement — series or parallel — is the right choice for a given project: ■ First cost ■ Savings in cooling and heating energy ■ Additional fan energy to overcome the static pressure drop of the energyrecovery device Note: One innovative design combines both configurations using a coil loop with three coils. When the cooling coil is active, the coil loop operates in the series configuration to save both cooling energy and reheat energy. When the cooling coil is off and the heating coil is active, the coil loop switches and operates in the parallel configuration to save heating energy. For further discussion of this concept, see pp. 42 – 43. Effect on First Cost The previous examples demonstrate the effects of tempering supply air with energy recovered from the exhaust air stream or from upstream of the cooling coil. Energy savings must be balanced with the cost of adding the energyrecovery device to the air-handling system. Depending on the size and complexity of the system, the initial investment may be significantly higher. Heating and cooling-plant downsizing. Table 5 summarizes the plantcapacity reductions obtained in the preceding examples of supply-air tempering. When used to temper supply air in a mixed-air system, air-to-air energy recovery does not reduce the capacity of either the cooling plant or the heating plant. Using air-to-air energy recovery may permit a smaller cooling or heating plant in dedicated outdoor-air systems that deliver neutral air. If applied in the series configuration, the cooling plant can be downsized because the energy-recovery device precools the air upstream of the cooling coil whenever the cooling coil is dehumidifying — even at design conditions. If the air-to-air energy-recovery 32 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Table 5. Capacity reductions attributable to supply-air tempering Energy-Recovery Configuration Reduction in Mechanical-Plant Capacity Series Parallel Mixed-air system Cooling Heating Cooling 8,544 Btu/hr (2.33 kW) Heating 10,400 Btu/hr (2.93 kW) Dedicated OA system (neutral air) device is applied in a parallel configuration, the heating plant can be downsized. During the heating mode, the energy-recovery device recovers sensible heat from the exhaust air stream and uses it to warm the entering outdoor air. Of course, when investigating the economic benefit of air-to-air energy recovery for tempering supply air, you must also consider its impact on the first cost of other system components. Increased fan motor sizes. As noted earlier in this chapter, adding an air-toair energy-recovery device to the air stream increases the static pressure loss in the air-distribution system. The configuration of the energy-recovery device and the fans will determine the extent of the pressure loss and the resulting fanpower requirements. Providing the additional power necessary may require larger fan motors. Additional exhaust ductwork. If applied in a parallel configuration to temper conditioned outdoor air, most energy-recovery devices used in dedicated outdoor-air systems require adjacent outdoor- and exhaust-air streams. This prerequisite means that most of the exhaust air must be routed back to a central location, and, therefore, typically requires more ductwork than the same system without energy recovery. This generalization does not apply to coil loops. A coil loop can recover heat from one or several exhaust air streams, none of which is adjacent to each other nor to the outdoor air stream. Of course, when the two air streams are far apart, the coil loop requires more piping and glycol as well as a larger pump and expansion tank. Effect on Operating Costs Less energy consumed for heating and cooling. Using air-to-air sensibleenergy recovery can reduce energy consumption associated with supply-air tempering. Given the complex interaction between system control modes and the humidity in the space, simulation software is often required to estimate the performance of various energy-recovery devices. Such an analysis can predict the length of the payback period based on the building location, type of SYS-APM003-EN 33 Temper Supply Air Applications for Air-to-Air Energy Recovery building, type of HVAC system, system control modes, quantity of outdoor air, airside economizer operation, and local utility rates. Need for supplemental heat. Applications that temper supply air using recovered energy may require a supplemental heating coil downstream of the energy-recovery device to achieve the desired dry-bulb temperature at all conditions. The example in Figure 25 (p. 30) illustrates one such application: a dedicated outdoor-air system with a parallel-configured energy-recovery device. The same example system, using the series configuration, would probably also need a supplemental heating coil to maintain the desired drybulb temperature at less severe outdoor conditions such as a mild, rainy day. Let’s revisit another example — this time, the mixed-air system that applies a coil loop in a series configuration (Figure 17, p. 23). As depicted in Figure 28, the condition of the outdoor air is 69°F DB, 65°C WB (20.6°C DB, 18.3°C WB). To satisfy the sensible load in the space and maintain the relative humidity below 60 percent, the supply air must be delivered at a dew point of 57.5°F (14.2°C). Furthermore, the dry-bulb temperature can be no colder than 65°F (18.3°C) to avoid overcooling the space. Operating at full capacity, the coil loop transfers heat from the mixed air upstream of the cooling coil to the air downstream of the coil, warming it to 62.8°F DB (17.1°C DB). Despite operating at full capacity, the coil loop cannot transfer enough heat to achieve the desired supply-air temperature of 65°F DB (18.3°C DB). To make up the shortfall, a supplemental heating coil is required downstream of the coil loop. Most likely, this coil will also operate during the heating mode when a heating load exists and the coil loop is turned off. Recall that in mixed-air systems, the amount of heat that can be transferred from the return air stream is more constant for parallel configurations of energy recovery than it is for series configurations. Recall, too, that the parallel configuration is less dependent on ambient conditions. When the outdoor air is warmer than the return air, the series configuration has more heat to transfer Figure 28. Mixed-air system with “series” heat transfer and supplemental heat 34 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery than the parallel configuration. When the outdoor air is cooler than the return air, the series configuration has less heat to transfer than the parallel configuration. The relationship between ambient conditions, energy-recovery configuration, and available heat for transfer also exists in dedicated outdoor-air systems. A device in the series configuration can transfer more heat when it is hot outside — but less heat when the outdoor air is cooler than the exhaust air — than a parallel-configured device. The parallel configuration is less dependent on outdoor conditions because the temperature of the exhaust air stream remains relatively constant. More energy consumed by fans. As noted earlier, the static pressure drop of the system will increase — causing the fans to consume more energy — whenever air passes through the air-to-air energy-recovery device. The amount of additional energy consumed depends on the static pressure drop through the device. The operating cost savings provided by recovered energy must exceed the increased cost of operating the fans in order to justify the operational benefit of the energy-recovery device. A year-round, project-specific analysis must be performed to determine the effect on the energy consumption of the entire HVAC system. Bypass dampers may be used to reduce the airside pressure loss when the energy-recovery device is idle, thus reducing fan energy consumption. They are particularly valuable when the energy-recovery device is applied in a series configuration. Whenever the cooling coil is turned off, the bypass dampers can save substantial fan energy. Need for capacity control. An air-to-air energy-recovery device used for supply-air tempering generally requires some method for modulating the capacity of the device. Modulation prevents the device from overheating the supply air during mild weather. To illustrate, consider the mixed-air system represented psychrometrically in Figure 29 on p. 36. The condition of the outdoor air is 90°F DB, 78°C WB (32.2°C DB, 25.6°C WB). To satisfy the sensible load without overcooling the space, the supply air must be delivered at a dry-bulb temperature of 61°F (16.1°C). Operating at full capacity, the “series” coil loop cools the mixed air to 74.4°F DB (23.6°C DB). The heat removed from the mixed air upstream of the cooling coil is transferred to the air downstream of the coil, warming the supply air to 63.5°F DB (17.5°C DB). Letting the coil loop operate at full capacity (run “wild”) overheats the supply air, causing the space to be warmer than desired. Modulating the capacity of the coil loop avoids this situation. Note: Tempering is not needed when the relative humidity in the space is lower than the maximum limit. To prevent heat transfer, the coil-loop pump should be turned off. SYS-APM003-EN 35 Temper Supply Air Applications for Air-to-Air Energy Recovery Figure 29. Unmodulated energy-recovery capacity for SA tempering (mixed-air system) A mixed-air system that tempers supply air to control space humidity generally requires very little reheat when it is warm outside and lots of reheat when the weather is cool and damp (that is, at part load). The capacity of the energyrecovery device, whether arranged in a series or parallel configuration, must be modulated to avoid transferring too much heat. The Trane application manual, Dehumidification in HVAC Systems (SYS-APM004-EN), discusses dedicated outdoor-air systems in detail, including resetting leaving air conditions to optimize system energy consumption. It is available from the Trane bookstore at www.trane.com/bookstore. ■ In a dedicated outdoor-air system that delivers “neutral” air at constant dewpoint and dry-bulb temperatures, the condition of the air leaving the cooling coil will be the same whenever the coil operates. Because this dehumidified outdoor air is then reheated to the same dry-bulb temperature, the required amount of tempering (reheat) is also constant whenever the energy-recovery device operates. In the parallel configuration, the source of heat to be recovered (the exhaust air stream) is relatively consistent, and capacity control for the energy-recovery device may not be required. In the series configuration, however, the source of heat to be transferred (the outdoor air stream) definitely fluctuates. Therefore, some method of controlling the capacity of the energyrecovery device will probably be needed to avoid overheating the conditioned outdoor air at certain operating conditions. Further, if the setpoints (either dew point, dry bulb, or both) of the air leaving the dedicated outdoor-air unit are automatically reset based on actual space conditions, a method of capacity control is required to optimize the energy use of the HVAC system. Capacity control is needed whether the energy-recovery device is arranged in the parallel or series configuration. “Energy-Recovery Technologies,” pp. 38 – 59, discusses specific capacity control methods for various air-to-air energy-recovery devices. 36 SYS-APM003-EN Temper Supply Air Applications for Air-to-Air Energy Recovery Other Considerations Several other issues must be addressed to optimize the life-cycle cost of a mixed-air or dedicated outdoor-air system that tempers supply air using air-toair energy recovery. Frost prevention. Although frost prevention is typically required for outdoorair preconditioning applications, it is seldom necessary in supply-air tempering applications. As noted earlier, when a parallel-configured energy-recovery device is applied in a dedicated outdoor-air system, frost prevention may be required in cold climates if the energy-recovery device is also used to precondition the outdoor air during the heating season. “Air-to-Air Energy Recovery Technologies” (pp. 38 – 59) discusses specific frost prevention methods for various air-to-air energy-recovery devices. Acceptable cross-leakage. Many types of air-to-air energy-recovery devices permit some degree of cross-leakage. This is seldom of concern in mixed-air systems because most of the air that returns from the space is recirculated as supply air. Cross-leakage is also a non-issue when the series configuration is used because both sides of the energy-recovery device are located in the same air stream. Only dedicated outdoor-air systems that apply air-to-air energy recovery in a parallel configuration require special attention. Leakage between the two air streams, however slight, may transfer exhaust-air contaminants to the conditioned outdoor air stream. (“Energy-Recovery Technologies,” pp. 38 – 59, discusses specific methods of reducing cross-leakage for various types of air-toair energy-recovery devices.) ■ SYS-APM003-EN 37 Energy-Recovery Technologies Additional information on these and other air-to-air, energy-recovery technologies can be found in the “Air-toAir Energy Recovery” chapter of the ASHRAE Handbook—HVAC Systems and Equipment. To order a copy, visit ASHRAE’s online bookstore at www.ashrae.org. ■ Of the methods for recovering airside energy, coil loops, fixed-plate heat exchangers, heat pipes, and rotary heat exchangers (or wheels) are the most commonly used. As summarized in Table 6, coil loops and heat pipes recover sensible energy; fixed-plate heat exchangers and wheels can recover either sensible or total energy. This chapter reviews the typical performance, advantages and disadvantages, methods of capacity control and frost prevention, and cross-leakage characteristics for each of these airside energyrecovery technologies. See Table 14 (p. 64) for a comparative overview. Table 6. Common air-to-air energy-recovery technologies Sensible-Energy Recovery For a concise comparison of the energyrecovery technologies discussed in this chapter, see Table 14 on p. 64. ■ Total-Energy Recovery ■ Coil loops ■ Heat pipes ■ Fixed-plate heat exchangers ■ Fixed-membrane heat exchangers ■ Rotary heat exchangers (also known as “sensible-energy wheels” or “heat wheels”) ■ Rotary heat exchangers (also known as “total-energy wheels” or “enthalpy wheels”) Coil Loop Figure 30. Coil loop A coil loop — also called a “coil runaround loop — consists of two or more finned-tube coils that are piped together in a closed loop; see Figure 30. A small pump circulates the working fluid (usually a solution of inhibited glycol and water) through the two coils. An expansion tank and a means for modulating capacity, either a three-way mixing valve or a variable-speed drive on the pump, complete this energy-recovery device. Coil loops are the most flexible of all air-to-air energy-recovery devices because they can transfer energy between air streams that are physically separated by some distance, which makes coil loops particularly advantageous in retrofit situations. Also, a coil loop can recover energy from multiple exhaust-air streams (using multiple exhaust-side coils). Of course, recovering energy from multiple exhaust air streams requires additional coils, more piping and glycol, and a larger pump. Typical Performance Coil-loop selections are typically based on a sensible effectiveness of 45 percent to 65 percent, assuming balanced airflow, and an airside static-pressure loss of 0.3 to 1.0 in. wg (75 to 250 Pa) per coil. The flexibility of the coil loop lets the 38 SYS-APM003-EN Coil Loop Energy-Recovery Technologies Figure 31. Sensible effectiveness versus face velocity in coil loops designer vary the number of rows, spacing and type of fins, face velocity, and fluid flow rate to optimize the device for a specific application. Figure 31 and Figure 32 depict representative coil-loop performance. Given the design flexibility of coils, coil loops can be selected for a broad range of performance requirements. ■ Adding more rows and fins to the coils increases the sensible effectiveness of the coil loop … but it also causes the fan(s) to consume more energy because it increases the static pressure loss in the air distribution system. See Figure 31 and Figure 32. In other words, the cool-loop design with the highest effectiveness may not yield the best net energy savings (that is, energy saved through recovery minus additional fan and pump energy consumed). Figure 32. Airside pressure drop versus face velocity in coil loops SYS-APM003-EN 39 Coil Loop Energy-Recovery Technologies When a coil loop is used to precondition outdoor air, for example, its payback usually can be improved by basing the coil selections on the lowest possible fluid flow rate and face velocity. Although a higher fluid flow rate will increase the sensible effectiveness of the coil loop, it will also necessitate a larger, more expensive pump and larger piping—and will increase the energy consumption of the pump. ■ To maximize net energy savings (best payback), select coils with fewer rows (four or six) and wider fin spacing (120 fins/ft). This design strategy reduces the pressure drop through the coil loop. ■ To maximize effectiveness and, therefore, the amount of heat recovered, select coils with more rows (eight) and with closely spaced fins (144 fins/ft). This design strategy generally offers the greatest downsizing potential for cooling and heating plants. Note: Turbulators inside the coil tubes improve heat transfer (and effectiveness) without requiring an increased rate of fluid flow through the coil. Position the pump upstream of the supply-side coil (Figure 30, p. 38) so that the pump’s heat of compression is applied to the fluid entering that coil. Raising the temperature difference between the fluid and the air flowing through the supply-side coil improves the heat-recovery capacity of the loop during cold weather. For a coil loop that tempers supply air and is configured in a series arrangement, use two-row coils whenever possible. Minimizing the number of coil rows lessens any adverse effect on the energy consumption of the fan. Capacity Control Providing a means of capacity control — either a three-way mixing valve or a variable-speed drive on the pump — prevents the coil loop from overheating the supply air during mild weather. A temperature sensor in the supply air stream, downstream of the supply-side coil, monitors the leaving-air temperature. The mixing valve then appropriately modulates the fluid flow rate through the supply-side coil. When less fluid flows through the supply-side coil, the loop adds less heat to the supply air stream. (If the pump is equipped with a variable-speed drive, then the capacity of the loop is controlled by modulating the fluid flow rate through the entire coil loop.) Both the mixing valve and the variable-speed drive can provide equally effective capacity control. The variable-speed drive is easier to apply, however, because the location of the three-way mixing valve is critical for proper operation during the frost prevention mode. The variable-speed drive also saves pumping energy; however, the savings potential is slight because the pump already consumes only a modest amount of energy. 40 SYS-APM003-EN Coil Loop Energy-Recovery Technologies Table 7. Considerations for recovering energy with coil loops Advantages ■ Transfers energy between air streams that are separated by distance, simplifying retrofits ■ No cross-leakage between air streams ■ Flexible design/application: Coils can be selected for the optimum amount of energy transfer, making them less expensive than other energy-recovery devices ■ Easily turned off when energy recovery is not beneficial ■ Easy to control ■ Fits readily within the casing of a packaged air handler Disadvantages ■ Transfers only sensible heat ■ May require an expansion tank to accommodate expansion and contraction of heat-transfer fluid ■ Requires design and field installation of piping, pump, expansion tank, and mixing valve (or variable-speed drive) ■ Requires maintenance of the pump Note: In outdoor-air preconditioning applications when the temperature outside is warmer than the desired supply-air temperature but cooler than the exhaustair temperature, turn off the coil-loop pump to avoid transferring unwanted heat into the supply air stream. Applying a coil loop for outdoor-air preconditioning in a mixed-air system that includes an airside economizer entails additional design considerations: ■ Size the coil loop to handle only the minimum ventilation airflow, not full economizer airflow. ■ Use bypass dampers in both air streams to reduce fan energy consumption when the coil loop is inactive. ■ Bypass dampers, if present, can also control capacity (and inhibit frost formation on the exhaust-side coil, in some climates), thereby eliminating the need for a mixing valve or variable-speed drive for the pump. For further discussion of exhaust-air bypass for capacity control, refer to “Rotary Heat Exchangers” (pp. 53 – 55). Frost Prevention In outdoor-air preconditioning applications, the same three-way mixing valve or variable-speed drive that controls the heating capacity of the coil loop can be used to prevent frost from forming on the exhaust-side coil. Frost prevention is triggered by a temperature sensor that monitors the temperature of the fluid entering the exhaust-side coil (Figure 30, p. 38). If the sensor detects a fluid temperature that is colder than 30°F to 32°F (-1.1°C to 0°C), then the three-way mixing valve redirects the warm fluid leaving the exhaust-side coil into the fluid SYS-APM003-EN 41 Coil Loop Energy-Recovery Technologies returning from the supply-side coil. A variable-speed pump can provide the same protective function by reducing the fluid flow rate through the entire loop. In either case, the protective action of the mixing valve or the variable-speed pump raises the temperature of the fluid entering the exhaust-side coil and keeps the surface temperature of the coil above 32°F (0°C) to prevent frost from forming. Both methods of frost prevention are easy to implement; however, they also limit the amount of heat that can be recovered during the coldest times of the year. Consequently, less opportunity exists to downsize heating equipment. (Preheat can effectively prevent frost formation, too; see p. 56.) Cross-Leakage Coil loops are particularly popular for applications such as hospitals and laboratories in which minimizing the risk of contamination is critical. The two air streams can be physically separated from each other, and the working fluid that transfers heat between them is isolated within a closed piping loop. Although the coil loop, by itself, cannot cause cross-leakage, it is important to identify other possible paths of contamination. If the coils of the loop are housed within a single air handler, the air-handler casing may not be leakproof. To reduce the risk of cross-leakage in this situation, arrange the supply and exhaust fans so that the pressure in the exhaust side of the air handler is less than the pressure on the supply side. (See Table 11, p. 58, for more information about minimizing the risk of cross-leakage.) Cross-contamination can also occur between the air streams if the exhaust-air outlet and the outdoor-air intake are improperly positioned or if certain wind directions can cause the exhaust air to reenter the building through the intake opening. Coil Loop with Three Coils Figure 33. Coil loop with three coils A coil loop need not be limited to only two coils. Figure 33 illustrates a design that uses a single, three-coil loop to either precondition the outdoor air or temper the supply air. (In this case, a variable-speed pump provides capacity control and frost prevention. Alternatively, these functions could be performed by several three-way mixing valves.) A two-position control valve determines which function the coil loop will perform by “converting” the loop from a parallel configuration to a series arrangement. During dehumidification, when the cooling coil dries the supply air, the control valve directs the working fluid through the coils arranged in series with the cooling coil. The cooling coil dehumidifies the passing supply air. Meanwhile, the coil loop removes sensible heat from the air upstream of the cooling coil (reducing the cooling coil load) and transfers it downstream of the cooling coil, where the recovered heat tempers the dehumidified supply air. When it 42 SYS-APM003-EN Plate Heat Exchanger Energy-Recovery Technologies functions in the series arrangement described here, this coil-loop design saves both cooling energy and reheat energy. When mechanical cooling is unnecessary and the temperature outside is cooler than the desired supply-air temperature, the same coil loop heats the entering outdoor air. The control valve redirects the working fluid through the parallel arrangement of the coil loop, which transfers heat from the exhaust-air path to the outdoor-air path, upstream of the cooling coil. (Adding recovered heat upstream of a chilled-water cooling coil, as shown in Figure 33, may provide adequate freeze protection for the coil.) A coil-loop design with three coils provides more energy savings and a greater opportunity to downsize equipment than a conventional two-coil design. Depending on the application, it may also eliminate the need to protect the cooling coil from freezing during cold weather. Together, these benefits may economically justify the additional first cost of the “extra” coil and control valve. Fixed-Plate Heat Exchanger Figure 34. Fixed-plate heat exchanger As its name implies, a fixed-plate heat exchanger consists of alternate layers of thermally conductive plates that are sealed to form separate passages for two air streams; see Figure 34. The plates are constructed from aluminum or other materials with a similarly high thermal conductivity. Unlike the coil loop, which uses separate heat-exchanging devices (coils) to collect heat from one air stream and release it into another, the fixed-plate heat exchanger “packages” both functions within the same device. Fixed-plate heat exchangers exist in various configurations, materials, and capacities; of the available flow patterns, cross-flow is the most common. The plates in most of these devices transfer only sensible heat between the two air streams. An exception is the fixed-membrane heat exchanger, which can transfer both sensible heat and moisture. Its “plates” are membranes of a paper-like material that allows moisture, as well as sensible heat, to transfer from one air stream to the other. Fixed-membrane heat exchangers are more commonly used in residential applications because of their small capacity and relatively high static-pressure drop, and because they are not self-cleaning. Typical Performance Fixed-plate heat exchangers compare favorably with other types of airside energy-recovery devices because they transfer heat directly from one air stream to another without an intermediate exchange medium. With balanced airflows, sensible effectiveness typically ranges from 60 percent to 70 percent. (For a coil loop to match the recovery capacity of a fixed-plate heat exchanger, it must be SYS-APM003-EN 43 Plate Heat Exchanger Energy-Recovery Technologies Figure 35. Sensible effectiveness versus face velocity in fixed-plate heat exchangers equipped with eight-row coils.) In outdoor-air preconditioning applications, a fixed-plate heat exchanger with a sensible effectiveness of 60 percent usually affords the best balance between the initial cost of the device and the savings it provides in operating cost. Figure 35 and Figure 36 depict representative performance for fixedplate heat exchangers. ARI Standard 1060 (p. 60) certifies the performance of these devices, enabling accurate comparisons between manufacturers and with other energy-recovery technologies. ■ Adding more plates to a fixed-plate heat exchanger increases the sensible effectiveness of the device; however, it also increases the size and weight of the device. See Figure 35 and Figure 36. More importantly, it increases the airside pressure drop, which in turn increases the energy consumption of the fan(s). The incremental improvement in actual performance seldom justifies the added first cost of additional plates. Fixed-plate heat exchangers are most commonly used in applications with airflows less than 10,000 cfm (4.7 m³/s). Adding one of these devices will increase the static-pressure drop by 0.6 to 1.4 in. wg (150 to 350 Pa) through each side of the air distribution system. Capacity Control Face-and-bypass dampers (Figure 37) are most often used to control the capacity of a fixed-plate heat exchanger. During mild weather, the face dampers modulate closed and the linked bypass dampers open to reduce airflow through the exhaust side of the heat exchanger. Positioning the dampers in this way avoids overheating the supply air by reducing the amount of heat transfer that occurs in the heat exchanger. Air therefore leaves the supply side of the heat exchanger at a lower temperature. 44 SYS-APM003-EN Plate Heat Exchanger Energy-Recovery Technologies Figure 36. Airside pressure drop versus face velocity in fixed-plate heat exchangers Bypassing air around the exhaust side of the heat exchanger forces all of the entering outdoor air to pass through the heat exchanger, which minimizes temperature stratification in the supply air stream. Frost Prevention Figure 37. Face-and-bypass dampers Of all airside energy-recovery devices, the fixed-plate heat exchanger is the most susceptible to frost because of its high sensible effectiveness and crossflow configuration. Frost prevention is only an issue if the heat exchanger is used to precondition outdoor air; it is unnecessary for supply-air tempering. As shown in Figure 38 (p. 46), frost is most likely to develop in the corner of the heat exchanger where the cold entering outdoor air recovers heat from the exhaust air on the leaving edge of the heat exchanger. In this corner, regardless of the amount of moisture in the exhaust air stream, the exhaust air is in contact with the coldest surface of the heat exchanger, which approximates the entering outdoor-air condition. This means that frost will form when the outdoor air drops below 32°F DB (0°C DB). In some climates, the same face-and-bypass dampers that control capacity can also provide frost protection. If the climate is too cold to rely on face-andbypass dampers, however, the heat exchanger should be equipped with another frost-preventing device. Some heat-exchanger manufacturers add a damper to divert exhaust air away from the cold corner when frost may occur; others create temporary warm spots using a moving plate. Another frostprevention technique requires two heat exchangers and alternates their use every 90 seconds. Finally, one can simply bypass all of the outdoor air around the heat exchanger and use supplemental heat to melt the ice. SYS-APM003-EN 45 Fixed-Plate Heat Energy-Recovery Technologies Figure 38. “Cold spot” in a fixed-plate heat exchanger RA Figure 39. “Frost-avoidance” damper Figure 39 shows an integral “frost-avoidance” damper that diverts air away from the cold corner of the heat exchanger. A temperature sensor monitors the temperature of the exhaust air leaving the cold corner of the heat exchanger. When the monitored temperature falls below the frost threshold, the frostavoidance damper closes to divert the entering outdoor air away from that corner. The temperature in the cold corner of the heat exchanger remains above freezing, which allows the heat exchanger to operate at much lower outdoor temperatures. If extremely cold outdoor temperatures are expected, add a preheat coil to warm the entering outdoor air above the frost-threshold condition. Cross-Leakage Little cross-leakage occurs between the air streams as they pass through a fixed-plate heat exchanger, but such devices are not leakproof. High-quality designs use an effective plate sealing system to minimize leakage between the air streams. If the small amount of cross-leakage is of concern, arrange the supply and exhaust fans so that the pressure on the exhaust side of the heat exchanger is less than the pressure on the supply side. (See Table 11, p. 58, for more information about minimizing the risk of cross-leakage.) Remember, too, that cross-leakage can also occur through the air-handler casing and between the building’s exhaust-air outlet and outdoor-air intake. If these openings are improperly located, or under certain wind conditions, exhaust air leaving the building may reenter through the outdoor-air intake. 46 SYS-APM003-EN Heat Pipe Energy-Recovery Technologies Table 8. Considerations for recovering energy with fixed-plate heat exchangers Advantages Disadvantages ■ Relatively high sensible effectiveness ■ Transfers only sensible energy (heat) ■ Little cross-leakage between air streams ■ Requires adjacent air streams ■ Easy to clean ■ Relatively high frost threshold ■ Heavy ■ High first cost in large applications Heat Pipe Figure 40. Heat-pipe assembly Adapted, by permission, from Innergytech Inc. Figure 41. Cross section of heat-pipe tube A heat pipe resembles a finned-tube coil; see Figure 40 and Figure 41. Each of its large tubes is an independent, sealed container that is filled with a heattransfer fluid (typically a chemical refrigerant). A partition divides the air “side” of the heat pipe into separate “evaporator” and “condenser” sections. The capillary wick structure within the pipe walls induces refrigerant flow between the “evaporator” and “condenser” without the help of a compressor or pump. Here’s how … Two air streams flow across each heat pipe: warm air flows across the “evaporator” and cool air flows across the “condenser.” The refrigerant inside the “evaporator” evaporates as it absorbs heat from the warm air. Given the comparative coolness of the air flowing over the “condenser,” the refrigerant vapor pressure is lower in that section of the heat pipe than in the “evaporator.” The difference in vapor pressures causes the refrigerant vapor to migrate from the “evaporator” to the “condenser.” Cool air flowing over the “condenser” absorbs heat from the refrigerant vapor, which causes the refrigerant to condense. The liquid refrigerant then “wicks” back to the “evaporator” section of the heat pipe and the cycle repeats. The direction of heat transfer reverses when the relative temperatures of the two air streams switch. In an outdoor-air preconditioning application, for example, when the outdoor air is warmer than the exhaust air, the “evaporator” is in the outdoor air stream and the “condenser” is in the exhaust air stream. When the outdoor air is cooler than the exhaust air, the “evaporator” is in the exhaust air stream and the “condenser” is in the outdoor air stream. Typical Performance Heat pipes are typically selected for a sensible effectiveness of 30 to 55 percent, with balanced airflow. Airside pressure drops range from 0.2 to 0.8 in. wg (50 Pa to 200 Pa), based on the number of tube rows and the number of fins. Adapted, by permission, from Innergytech Inc. SYS-APM003-EN Figure 42 and Figure 43 (p. 48) illustrate the effect of adding more rows to the heat pipe. The sensible effectiveness of the device increases, as does the fan 47 Heat Pipe Energy-Recovery Technologies Figure 42. Sensible effectiveness versus face velocity for heat pipes Figure 42 and Figure 43 depict representative performance for heat pipes. ARI Standard 1060 (p. 60) certifies the performance of these devices, enabling accurate comparisons between manufacturers and with other energy-recovery technologies. ■ energy required to overcome the additional static pressure drop. A heat pipe that is selected for maximum effectiveness and, therefore, maximum heat recovery will differ from a heat pipe that is selected for the best payback from energy savings. Consider these guidelines when choosing a heat pipe for a particular energy-recovery application: ■ To precondition outdoor air, select the heat pipe based on the lowest possible face velocity. Four or six rows of tubes usually provide optimal heat-pipe selections. Figure 43. Airside pressure drop versus face velocity for heat pipes 48 SYS-APM003-EN Heat Pipe Energy-Recovery Technologies ■ To temper supply air, choose a two-row heat pipe if the device is applied in a series (wrap-around) arrangement. Fewer rows lessens the impact on fan energy consumption. Capacity Control Heat pipes, like other devices that recover sensible energy, require a means of capacity control to avoid overheating the supply air when the weather is mild. The extent to which capacity must be controlled — partial reduction versus modulation and shutoff — determines which of two common methods is used: tilt control or face-and-bypass dampers. Tilt control partially reduces the transfer capacity of the heat pipe. Tilting the heat pipe to elevate the evaporator end of the tubes above the condenser end slows the rate at which the liquid refrigerant flows back to the “evaporator.” The steeper the tilt angle, the slower the rate of flow and the less heat that can be recovered and transferred to the air leaving the supply side of the heat pipe. Given the finite extent of tilt (usually 4° to 6°), this method provides only a limited range of capacity control; consequently, it may not prevent unnecessary heat transfer in all applications and climates. Figure 44 illustrates how tilt control can be accomplished. An actuator is attached to one end of the heat pipe. To permit free movement throughout the range of tilt, a pivot is provided at the center of the heat-pipe support and flexible connectors attach the heat pipe to the ductwork. Figure 44. Tilt-control mechanism for regulating heat-pipe capacity pivot Adapted from ASHRAE Handbook—2000 HVAC Systems and Equipment, Figure 20, page 44.17. SYS-APM003-EN 49 Heat Pipe Energy-Recovery Technologies Face-and-bypass dampers provide an alternative means of capacity control. During mild weather, the face dampers modulate closed and the linked bypass dampers open to reduce airflow across one end of the heat pipe. Fully closing the face dampers and fully opening the bypass dampers effectively turns off the heat pipe. Note: Some equipment designs use solenoid valves to regulate or stop the flow of refrigerant in the heat pipe when little or no heat is desired. Frost Prevention In outdoor-air preconditioning applications, the tilt mechanism or face-andbypass dampers that control capacity also can be used to prevent frost formation during cold weather. Reducing the capacity of the heat pipe increases the temperature at which the exhaust air stream leaves the heat pipe, which prevents frost from forming; however, it also reduces the opportunity to downsize the heating plant. The exact temperature at which frost will form depends on the amount of moisture contained in the exhaust air stream. If extremely cold weather is expected, it may be necessary to add a preheat coil to ensure that the entering outdoor air remains above the frost threshold. Table 9. Considerations for recovering energy with heat pipes Advantages Disadvantages ■ Little cross-leakage between air streams ■ Contains refrigerant ■ Relatively low maintenance ■ Transfers only sensible energy (heat) ■ Can be packaged inside an air handler ■ Requires external face-and-bypass dampers to prevent unwanted heat transfer Cross-Leakage The ARI 1060 certification program (discussed on pp. 60 – 63) shows that heat pipes are susceptible to cross-leakage. Refer to the AHRI directory of certified products at www.ahridirectory.org to find the certified performance — including cross-leakage — of specific, rated products. ■ 50 Despite the proximity required, a minimal amount of cross-leakage occurs between the two air streams that pass through the heat pipe. A solid partition separates the “evaporator” and “condenser” sections of the device, and the working fluid that serves as the heat-transfer medium is sealed within the heatpipe tubes. Risk of cross-leakage can increase, however, if the integrity of the seal around the partition degrades over the life of the device. Beyond the heat-pipe assembly, two other potential paths of cross-leakage must be considered: the casing of the air handler that typically houses the heat pipe, and the exhaust- and outdoor-air openings in the building envelope. To reduce the likelihood of cross-leakage via the air-handler casing, arrange the supply and exhaust fans so that the pressure in the exhaust end of the air handler is less than the pressure in the supply end. (For further details, see Table 11, p. 58.) SYS-APM003-EN Rotary Heat Exchanger Energy-Recovery Technologies Wind passing over a building creates turbulence that, under specific conditions, may force exhaust air to reenter the building through the outdoor-air intake. To minimize this risk, determine the proper location for the building’s exhaust- and outdoor-air openings based on atmospheric conditions and building geometry. Rotary Heat Exchanger Rotary heat exchangers, commonly called “wheels,” consist of a revolving cylinder that rotates between two air streams. Heat transfer is accomplished as the air streams pass through a matrix of channels that direct the air through the wheel in a counterflow arrangement. The nature of the heat-transfer medium determines whether the wheel will transfer only sensible heat or both sensible heat and moisture. The channels in a sensible-energy wheel (or “heat wheel”) are constructed of aluminum, copper, stainless steel, or other thermally conductive materials that do not absorb moisture. As the wheel rotates, the channels absorb sensible heat from the warmer of the two air streams and reject it to the cooler air stream. A total-energy wheel (also known as an “enthalpy wheel” or “passive desiccant wheel”) transfers both sensible heat and moisture. The matrix of channels in a total-energy wheel usually consists of a fibrous material (such as paper), plastic, or aluminum. To promote moisture transfer, the channel surfaces are coated with a desiccant material, that is, a substance that has a strong affinity for water vapor and an enormous internal surface area. While the wheel rotates through Figure 45. Total-energy wheel and examples of heat-transfer media SYS-APM003-EN 51 Rotary Heat Exchanger Energy-Recovery Technologies the two air streams, it absorbs sensible heat and moisture from the hot, humid air stream and releases it into the cooler, drier air stream. The differences between the temperature and moisture content of the two air streams creates a vapor-pressure differential that provides the driving force needed to transfer water vapor. In many climates, the ability to transfer moisture is useful year-round, dehumidifying during the cooling season and humidifying during the heating season. Typical Performance Figure 46 and Figure 47 depict representative performance for totalenergy wheels. ARI Standard 1060 (p. 60) certifies the performance of these devices, enabling accurate comparisons between manufacturers and with other energy-recovery technologies. ■ Heat-transfer capacity for a wheel is determined by the size of the channels, rotational speed, wheel diameter, wheel depth, and, in the case of a totalenergy wheel, the amount of desiccant used. Wheels have good effectiveness regardless of wheel channel shape. With balanced airflows, sensible-energy wheels typically perform at a sensible effectiveness of 60 percent to 80 percent; they also create a pressure drop that can range from 0.5 to 1.0 in. wg (125 Pa to 250 Pa). Total-energy wheels perform with a total effectiveness that typically ranges from 65 percent to 80 percent (assuming balanced airflows) and creating a pressure drop of 0.7 to 1.2 in. wg (175 to 300 Pa). In outdoor-air preconditioning applications, a total-energy wheel with an effectiveness of about 70 percent usually provides the optimal balance between first cost and operating-cost savings. Increased effectiveness requires more media and lower face velocities, necessitating a larger air handler; see Figure 46 and Figure 47. This incremental cost seldom justifies the performance improvement. Figure 46. Total effectiveness versus face velocity for total-energy wheels 52 SYS-APM003-EN Rotary Heat Exchanger Energy-Recovery Technologies Figure 47. Airside pressure drop versus face velocity for total-energy wheels Compared to other airside energy-recovery technologies, rotary heat exchangers are “self-cleaning.” Small, dry particles pass through the wheel channels; larger particles blow clear as the wheel rotates and the direction of airflow reverses. The wheel may be manufactured in a single piece or as multiple segments. Segmented wheels allow for easier removal for service (cleaning). Table 10. Considerations for recovering energy with rotary heat exchangers Advantages Disadvantages ■ Total-energy wheels transfer both sensible heat and moisture (latent energy) ■ Sensible-energy wheels transfer only sensible heat ■ High effectiveness ■ ■ Can be packaged inside an air handler May permit cross-leakage between air streams ■ “Self-cleaning” with respect to dry particles ■ Belt, motor, and bearings require periodic maintenance Capacity Control Modulating the capacity of a rotary heat exchanger is usually accomplished by diverting a portion of the air around either side of the wheel, or by varying its rotational speed using a variable-frequency drive (VFD) connected to the wheel motor. Figure 48 (p. 54) illustrates an air-handler configuration that places a conventional damper parallel to the wheel. In this arrangement, only exhaust SYS-APM003-EN 53 Rotary Heat Exchanger Energy-Recovery Technologies Figure 48. Air handler with a rotary heat exchanger and exhaust-air bypass dampers air bypasses the wheel. Forcing all of the outdoor air to pass through the wheel minimizes temperature stratification of the air leaving the wheel and may eliminate the need to protect downstream hydronic coils from freezing. After comparing the stability, reliability, cost, and flexibility of these control methods, we recommend exhaust-air bypass for modulating the capacity of rotary heat exchangers for two reasons: ■ Exhaust-air bypass provides a more linear unloading characteristic than a VFD, which simplifies capacity control and results in more stable control of the leaving air temperature. As shown in Figure 49, a VFD must slow the rotation of the wheel to 50 percent of nominal speed to achieve a 10-percent reduction in sensible effectiveness (capacity). Beyond that point, capacity drops off rapidly. ■ Exhaust-air bypass provides a wider range of capacity control. Typically, a VFD can slow the motor to 33 percent of nominal speed (a 67-percent reduction of the rotations per minute). At that rotational rate, however, the sensible effectiveness (capacity) of the wheel is still 80 percent of nominal. In mixed-air systems that include airside economizers, the same damper that allows increased exhaust airflow during the economizer mode can also modulate the capacity of the rotary heat exchanger. Note: Base the size of the rotary heat exchanger on the minimum outdoor airflow required for ventilation, not on full economizer airflow, in mixed-air applications. This design strategy lowers the first cost of the heat exchanger and, if bypass dampers are used, it avoids imposing the pressure drop of the wheel during airside economizing. 54 SYS-APM003-EN Rotary Heat Exchanger Energy-Recovery Technologies Figure 49. Typical response of capacity-control methods for rotary heat exchangers Frost Prevention Frost begins to form on a sensible wheel at a much higher outdoor temperature than on a total-energy wheel. This is because a total-energy wheel removes moisture from the exhaust air stream, which lowers the dew point and delays when the exhaust air finally becomes saturated. (See Figure 13, p. 19.) Figure 50 illustrates how to predict the dry-bulb temperature at which frost will begin to form on a total-energy wheel. On a psychrometric chart, plot the return air condition (RA); then draw a line, tangent to the saturation curve, through this point. The “frost threshold” — that is, the outdoor dry-bulb temperature at which frost formation can begin — is the point where the tangent line touches the saturation curve. Notice that frost does not necessarily form on the wheel at outdoor dry-bulb temperatures colder than 32°F (0°C). In Figure 50, for example, frost prevention only becomes necessary when the temperature outside falls below 0°F (-17.8°C). Figure 50. Determining the “frost threshold” temperature SYS-APM003-EN 55 Rotary Heat Exchanger Energy-Recovery Technologies Together, the humidity ratio of the exhaust air and the dry-bulb temperature of the outdoor air determine which of three frost-prevention methods — preheating the entering air, reducing the wheel’s capacity, or turning off the wheel — best suits a particular application. Preheat entering outdoor (or exhaust) air. Raising the dry-bulb temperature of the entering outdoor air prevents the surface temperature of the wheel from becoming so cold that frost forms on the exhaust side. Unlike other methods of frost prevention, it also means that the wheel can continue operating at full capacity — recovering as much energy as possible. The preheat coil is controlled to maintain the leaving-air temperature above the frost threshold. Note: For applications with electric preheat coils, adhere to the manufacturer’s guidelines for installation and placement to assure proper airflow across the heating elements and to minimize temperature stratification in the leaving air. Speed Control and Frost Prevention “Don’t Mix” … At least not in total-energy-wheel applications. As the rotation of a totalenergy wheel slows, both its latent and sensible effectiveness (capacity) decrease — but not at the same rate; see Figure 49 (p. 55). When the wheel begins to slow, its ability to remove moisture (latent effectiveness) from the exhaust air stream decreases faster than its ability to raise the dry-bulb temperature of the exhaust air (sensible effectiveness). The likelihood of frost actually increases because the exhaust air reaches the saturated condition more quickly. Further slowing the wheel’s rotation prevents frost, but it significantly reduces heat transfer, too. With leavingair temperatures well below freezing on the supply side of the wheel, downstream hydronic coils often need additional protection from freezing. ■ 56 Some system designs preheat the exhaust-side air stream instead of the supply-side air stream. Why? Because a hot water or steam coil can be used without fear of coil freeze-up and without adding glycol to the hot water loop. Although this design requires a slightly larger preheat coil to prevent frost, it also increases the temperature differential between the two air streams, which transfers more sensible heat to the outdoor air stream. (In specific applications, preheating the exhaust-side air stream may eliminate the need for a heating coil in the air handler.) Make sure that the air temperature leaving the preheat coil does not exceed the maximum operating temperature of the selected totalenergy wheel. Preheat is recommended for climates with extreme winter conditions, for applications in which the exhaust-air humidity ratio is high during the winter, or for systems that include mechanical humidification. When compared with other methods of frost prevention, preheat provides the most energy recovery during peak winter conditions. Reduce the capacity of the wheel (outdoor-air bypass). Moisture condenses on the exhaust side of the wheel when the exhaust air stream becomes saturated and the wheel surface is colder than 32 °F (0 °C). Therefore, another way to deter frost formation is to prevent the exhaust air from reaching the saturation curve. Transferring less total energy — that is, reducing the capacity of the wheel — yields cooler air leaving the supply side of the wheel and warmer air leaving the exhaust side. However, this method also reduces the opportunity to downsize the heating plant. As described on pp. 53 – 54, air can be diverted around one side of the wheel to reduce its capacity. Rather than place the bypass damper in the exhaust air path, however, locate it in the outdoor air path to bypass part of the outdoor air around the supply side of the wheel. This arrangement prevents the exhaust air from reaching the saturated condition by becoming too cold, but it also diverts SYS-APM003-EN Rotary Heat Exchanger Energy-Recovery Technologies cold outdoor air around the wheel. In many climates, adding an air blender will provide sufficient freeze protection for the hydronic coils downstream of the wheel. Note: When outdoor-air bypass is used for frost prevention, the same supplyside bypass damper also can provide capacity control. Outdoor-air bypass is best used in mild climates where frost conditions occur during only a few hours of the year. Freeze protection may still be required to adequately safeguard the hydronic coils downstream of the wheel. Avoid using outdoor-air bypass in systems that include mechanical humidification. Turn off the wheel. The easiest and most reliable way to prevent frost is to turn off the wheel when the outdoor temperature falls below the frost threshold. This method eliminates the opportunity to downsize the heating plant and requires full freeze protection for downstream coils, but in moderate climates, it may be the most cost-effective option for mixed-air systems that use a relatively low percentage of outdoor air. Cross-Leakage Leakage between the exhaust and supply air streams occurs in all rotary heat exchangers, regardless of their respective designs. Because some amount of cross-leakage is unavoidable, do not use wheels to precondition outdoor air for occupied spaces when highly concentrated or hazardous contaminants exist in the exhaust air stream. (An example of this type of application is a laboratory fume hood that handles a carcinogenic substance or biohazard.) Instead, use a coil loop, which has no potential for cross-leakage. A small amount of cross-leakage of air that contains rest-room exhaust is often acceptable in many applications, provided that it is sufficiently diluted with fresh outdoor air. In these instances, rotary heat exchangers can be used to recover energy from an air stream that includes rest-room exhaust. Air leaks from one side of the wheel to another along three paths: ■ Through the seals, which have a typical leakage rate of 3 percent to 5 percent ■ Through the matrix, which has a typical leakage rate of approximately 2 percent (If the matrix is fluted, leakage along this path is negligible.) ■ Via “carryover” as the wheel rotates, which represents a typical leakage rate of approximately 2 percent Each leakage path presents different application challenges and must be controlled differently. Generally, the amount and direction of cross-leakage through the seals and matrix is controlled by managing the pressure difference between the supply SYS-APM003-EN 57 Energy-Recovery Technologies Rotary Heat Exchanger and exhaust air streams. The configuration of the exhaust and supply fans with respect to the rotary heat exchanger (blow-through versus draw-through) affects this pressure difference; see Table 11. The best fan arrangement for a particular application depends on the desired performance characteristics. Table 11. Configuration versus cross-leakage through rotary heat exchangers Fan–Rotary Heat Exchanger Arrangement Differential Pressure Characteristics Draw-through exhaust, blow-through supply ■ Creates a comparatively higher static pressure in the supply path ■ Draw-through exhaust, draw-through supply ■ Direction of leakage depends on the static pressure difference between the supply and exhaust air streams Blow-through exhaust, draw-through supply ■ Creates a comparatively higher static pressure in the exhaust path OA 58 ■ Best arrangement to minimize air leakage from exhaust to supply through seals and matrix ■ Little cross-leakage through seals and matrix in most applications ■ Design system so that static pressure in exhaust path nearly equals static pressure in supply path to minimize cross-leakage ■ Promotes good airflow across the wheel with minimal leakage through seals and matrix ■ Design system so that static pressure in exhaust path nearly equals static pressure in supply path to minimize cross-leakage ■ Promotes significant leakage from exhaust to supply through seals and matrix; avoid using this arrangement Air leaks from supply path to exhaust path Blow-through exhaust, blow-through supply ■ Direction of leakage depends on the static pressure difference between the supply and exhaust air streams ■ Application Considerations Air leaks from exhaust path to supply path SA SYS-APM003-EN Rotary Heat Exchanger Energy-Recovery Technologies When it comes to controlling cross-leakage via “carryover,” fan arrangement has no effect. Instead, wheel geometry and rotational speed determine how much air the rotary heat exchanger will carry from one air stream to the other. To minimize contamination between the air streams, some rotary heat exchangers are provided with a purge section; see Figure 51. As the wheel rotates, the channels in a 5°-to-10° arc pass through the purge section. While there, the channels are flushed with outdoor air that is immediately diverted into the exhaust air stream. Although the purge section minimizes contaminant “carryover” into the supply air stream, it does nothing to mitigate leakage through the seals or matrix. It also reduces the effectiveness and associated energy savings of the wheel. Without the purge, however, there is no other means to control the “carryover” path of cross-leakage between the air streams. Most airside energy-recovery applications can tolerate a modest amount of cross-leakage. In such cases, properly arranged fans and a wheel with an effective sealing system often make a purge section unnecessary. Do not use rotary heat exchangers — with or without a purge — for applications that require absolutely no cross-leakage. As for each of the previously discussed energy-recovery technologies, the discussion of cross-leakage paths for rotary heat exchangers must include the potential path through the air-handler casing and between the building’s exhaust outlet and outdoor-air intake. Improper placement of these openings or adverse wind conditions may induce exhaust air to reenter the building through the outdoor air intake. Figure 51. Rotary heat exchanger with purge section SYS-APM003-EN 59 Energy-Recovery Technologies ARI Standard 1060 ARI 1060 or ASHRAE 84? ASHRAE Standard 84 defines the standard method for testing a fixedplate heat exchanger, rotary heat exchanger (wheel) or a heat pipe. It defines the laboratory setup and instrumentation requirements; it does not define standard test or rating conditions. The companion rating and certification standard is ARI 1060. This document defines standard conditions (temperature and humidity entering both sides of the device) and reporting requirements. It also includes a certification process that allows a manufacturer's results to be verified by an independent third party. A design engineer should specify performance based on ARI 1060, which results in certified performance. By definition, this also means that the performance was measured according to the standardized methods for testing such a device, which are defined in ASHRAE Standard 84.■ The Air-Conditioning, Heating, and Refrigeration Institute (AHRI) is a voluntary, nonprofit organization comprised of manufacturers of airconditioning, refrigeration, and heating products. Two of AHRI’s most important functions are the development of performance rating standards and the administration of performance certification programs for eligible products. Participation in the programs is voluntary and open to nonmembers of AHRI on an equal basis. Note: In 2007, the Air-Conditioning and Refrigeration Institute (ARI) and the Gas Appliance Manufacturers Association (GAMA) merged to become AHRI. More specifically for this discussion, ARI Standard 1060 –2005 defines requirements for testing, rating, and marking these factory-made energyrecovery devices: heat-pipe heat exchangers, fixed-plate heat exchangers, and rotary heat exchangers. Run-around coil loops, however, are not addressed by Standard 1060 because of the broad variability in design. Instead, ARI Standard 410 –2001, ForcedCirculation Air-Cooling and Air-Heating Coils, defines the testing, rating, and marking requirements for individual coils. To determine the performance of a particular run-around loop, simply apply the certified performance of the coils in the “effectiveness ratio” equation. (See “Fundamental Equations for Air-toAir Energy Recovery” on p. 6.) Note, too, that ARI Standard 1060 only pertains to applications in which the energy-recovery device preconditions outdoor air; it does not govern supply-air tempering. Furthermore, certification under this standard is limited solely to the energy-recovery component. That is, the certified effectiveness of an energyrecovery device does not extend to its actual performance after it is installed in a central air handler or packaged rooftop air conditioner. Historically, manufacturers used various methods to calculate the effectiveness of their air-to-air energy-recovery ventilation (AAERV) equipment, sometimes overstating performance. By normalizing the effectiveness calculation, the ARI Standard 1060 certification program: 60 ■ Fosters confidence that a certified air-to-air energy-recovery component will provide the specified performance ■ Permits equitable comparisons of energy-recovery devices from various manufacturers SYS-APM003-EN Energy-Recovery Technologies Figure 52. Seal of certified performance ■ Accurately predicts leaving air conditions by rating sensible and latent effectiveness separately (Technologies that transfer latent energy/moisture are differentiated from those that do not.) ■ Documents cross-leakage data, which permits proper air-handler design and application (including fan selection and ventilation control) ■ Permits more accurate sizing — or more appropriately, downsizing —of heating and cooling plants ■ Eliminates the need for independent testing by a third party (ARI is one of the industry’s most reputable third-part testing organizations.) Ultimately, the only way to properly compare equipment that includes an air-toair energy-recovery device to precondition outdoor air is to require certification under ARI Standard 1060. Equipment specifications should require ARI-certified performance and the ARI 1060 seal of certification (Figure 52). Standard Rating Conditions ARI Standard 1060 – 2005, Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment is available from the AHRI Web site (www.arhinet.org). The directory of AHRI-certified products is available at www.ahridirectory.org. ASHRAE Standard 84-1991 is available from ASHRAE’s online bookstore at www.ashrae.org. ■ ARI 1060 defines certified rating points that measure sensible, latent, and total effectiveness at both 100 percent and 75 percent of rated airflow. These airflow conditions represent the typical selection range for AAERV devices. The test procedure for certification uses equal airflows through the supply and exhaust sides of the device, as defined by ASHRAE Standard 84 –1991, Method of Testing Air-to-Air Heat Exchangers. Effectiveness is then calculated (using the “effectiveness ratio” equation found on p. 6) for the heating and cooling conditions summarized in Table 12. The test also measures the airside pressure drop at each rating condition. A further requirement for ARI 1060 certification is a tracer-gas test that provides two leakage measurements — the exhaust air transfer ratio (EATR) and the outdoor air correction factor (OACF) — at three different deck-to-deck pressures. Table 12. Standard rating conditions from ARI 1060 1 Condition Entering supply air Heating Cooling dry-bulb temperature 35°F (1.7°C) 95°F (35.0°C) wet-bulb temperature 33°F (0.6°C) 78°F (26.0°C) Entering exhaust air dry-bulb temperature 70°F (21.0°C) 75°F (24.0°C) wet-bulb temperature 58°F (14.0°C) 63°F (17.0°C) 1 The standard rating conditions defined in Table 1 of ARI Standard 1060 – 2005 include rates for supply and exhaust airflows, as well as pressure differentials for various performance tests. SYS-APM003-EN 61 Energy-Recovery Technologies Exhaust Air Transfer Ratio Figure 53. EATR quantifies cross-leakage Expressed as a percentage of downstream supply airflow, the exhaust air transfer ratio (EATR) helps to quantify cross-leakage from the exhaust air stream to the supply air stream. In Figure 53, the static pressure of the air leaving the supply side of the wheel is 1.0 in. wg (250 Pa) greater than the static pressure of the air entering the exhaust side. If the rotary heat exchanger in this example has an EATR of 0.6 percent, then 60.4 cfm (0.03 m3/s) leaks into the supply air stream from the exhaust side of the wheel. EATR air leakage from exhaust to supply = V2 ----------------100 SP supply – SP exhaust = 1.0 in. wg 250 Pa If the predicted cross-leakage is too high for the specific application, it may be possible to lower the EATR by rearranging the fans, adding a purge to the wheel, or using a different energy-recovery device such as a coil loop. To achieve the lowest EATR, use a blow-through fan on the supply side of the wheel and a draw-through fan on the exhaust side. Note: An arrangement that combines a blow-through supply fan with a blowthrough exhaust fan produces the least effect on fan energy consumption, although its EATR is slightly higher. Outdoor Air Correction Factor Figure 54. OACF aids supply-fan sizing The outdoor air correction factor (OACF) is defined as the supply-side airflow upstream of the wheel (V1 ) divided by the supply-side airflow downstream of the wheel (V2 ). This value is important for sizing the supply and exhaust fans and is usually small unless the pressure difference between the air streams is greater than 3.0 in. wg (750 Pa). If the system includes an outdoor-airflow monitoring station or a flowmeasuring damper, its setpoint can be adjusted to compensate for the OACF and thereby assure that the proper amount of outdoor air flows into the wheel so that the required amount of outdoor air leaves the wheel. Using EATR and OACF for System Design The arrangement of the supply and exhaust fans, relative to the energyrecovery device, determines how the EATR and OACF values are used to calculate the necessary capacity of each fan. Using the example shown in Figure 54, the draw-through exhaust fan must be sized to deliver 11,167 cfm (5.27 m³ /s). To assure that 10,000 cfm (4.7 m³ /s) of fresh outdoor air enters this example system, use a setpoint of 11,167 cfm (5.27 m³ /s) for an airflow- 62 SYS-APM003-EN Energy-Recovery Technologies monitoring station or a flow-measuring damper (such as the Trane Traq™ damper) positioned upstream of the wheel: Voa OACF OA setpoint = ------------------------------- 1 – EATR --------------- 100 Table 13 shows the equations for calculating the airflow at each station. Table 13. Fan sizing calculations Fan Airflows at Energy-Recovery Device Calculations for Fan Airflow 1 Supply-side airflow V2 : Voa EATR V2 = Voa + V2 ----------------- = ------------------------------- 100 1 – EATR ----------------- 100 Cross-leakage airflow V3 2 : Voa V3 2 = V2 – Voa = -------------------------------- – Voa 1 – EATR ----------------- 100 Exhaust-side airflow V3 : Voa V3 = Vea + V3 2 = Vea + --------------------------------– Voa 1 – EATR --------------- 100 Supply-side airflow V1 : Voa OACF V1 = V2 OACF = -------------------------------- 1 – EATR ----------------- 100 Cross-leakage airflow V1 4 : Voa OACF V1 4 = V1 – Voa = -------------------------------- – Voa 1 – EATR ----------------- 100 Exhaust-side airflow V4 : Voa OACF V4 = Vea + V1 4 = Vea + --------------------------------- – Voa 1 – EATR ----------------- 100 1 Voa represents the required outdoor airflow for proper ventilation, and Vea represents the system-level exhaust airflow required for proper building pressurization. SYS-APM003-EN 63 Energy-Recovery Technologies Table 14. Comparative overview of air-to-air energy-recovery technologies Energy-Recovery Technology Coil Loop Fixed-Plate Heat Exchanger Heat Pipe Rotary Heat Exchanger effectiveness 45 – 65% sensible 60 – 70% sensible 30 – 55% sensible 60 – 80% sensible, 65 – 80% total pressure drop through each side of the energy-recovery device 0.3 – 1.0 in. wg (75 – 250 Pa) 0.6 – 1.4 in. wg (150 – 350 Pa) 0.2 – 0.8 in. wg (50 – 200 Pa) 0.5 – 1.0 in. wg sensible, 0.7 – 1.2 in. wg total 3-way mixing valve ● Characteristic Typical performance 1 Method of capacity modulation (125 – 250 Pa sensible, 175 – 300 Pa total) ● dampers (face-and-bypass) ● (face-and-bypass) ● ● (pump motor) (wheel motor) speed control Frost prevention techniques 2 ● (exhaust-side bypass) ● (partial modulation) tilt control modest Susceptibility to frost 2 ● (face-and-bypass) highest modest high (sensible), lowest (total) ■ 3-way mixing valve ■ dampers (face-and-bypass) ■ (diverting) ■ (face-and-bypass) ■ (supply-side bypass) ■ tilt control ■ preheat coil ■ ■ ■ ■ speed control (pump motor) Likelihood of crossleakage between air streams 3 none slight slight modest 1 Per ARI Standard 1060, performance of energy-recovery devices — effectiveness and pressure drop — is based on equal airflows through the exhaust and supply sides of the device. 2 Pertains only to applications in which the energy-recovery device is used to precondition outdoor air. 3 Assessment of cross-leakage potential pertains only to the energy-recovery device. Be sure to account for other potential paths of leakage such as the air-handler casing or short- circuiting of building exhaust into the outdoor-air intake. 64 SYS-APM003-EN System-Level Control of Recovered Energy Ventilation systems can be classified according to the composition of the supply air that is eventually delivered to the conditioned space: that is, dedicated outdoor air (100-percent outdoor air) or mixed air (outdoor air plus recirculated air). Air-to-air energy recovery can be added to either type of ventilation system. For more information about dedicated OA systems, refer to the Trane Engineers Newsletter titled “Dedicated Ventilation Systems” (ENEWS-30/3). You can find it at www.trane.com/ engineersnewsletter. The Trane applications engineering manual, Dehumidification in HVAC Systems (SYS-APM004-EN) also includes a detailed discussion of dedicated outdoor-air systems. It is available from the Trane bookstore at www.trane.com/bookstore. ■ Dedicated outdoor-air systems devote an air handler exclusively to heating, cooling, humidifying, or dehumidifying all outdoor air (OA) brought into the building for ventilation. The conditioned outdoor air is then delivered directly to the occupied spaces (Figure 55) or to the outdoor/mixed-air intakes of other HVAC units (Figure 56). In either configuration, the dedicated OA system may be designed to deliver the conditioned air (CA) at either a “neutral” or cold temperature. A dedicated OA system that provides “neutral” air first dehumidifies the outdoor air to a dew point that is drier than the space; it then reheats the air to approximately room temperature, usually between 70°F and 72°F (21°C and 22°C). Often, the dedicated OA unit delivers neutral air directly to the occupied spaces, where fan-coils (for example) handle the local loads. Alternatively, the conditioned outdoor air can be ducted either to local units or into a plenum within proximity of the local units. Dedicated OA systems that are designed to provide cold air cool and dehumidify the outdoor air — typically achieving 45°F to 55°F DB (7°C to 13°C DB) — but do not reheat it. Again, systems of this type can deliver the conditioned outdoor air directly to the occupied spaces or to mixing boxes of local air-handling units such as blower-coils, small air handlers, or packaged rooftop air conditioners. A dedicated OA system that delivers cold air eliminates the heating energy associated with tempering; it also requires less cooling plant capacity than a Figure 55. Conditioned (outdoor) air, CA, delivered to occupied spaces SYS-APM003-EN Figure 56. Conditioned (outdoor) air, CA, delivered to local air-handling units 65 System-Level Control of Recovered Energy similar system that provides neutral air because there is no tempering (reheat) energy to offset. When delivered directly to the space, the cold ventilation air — which has comparatively lower dry-bulb and (usually) dew-point temperatures — reduces the sensible and latent cooling loads in the space. When delivered to local units, the cold ventilation air lowers the enthalpy of the resulting mixed air and, in turn, reduces the cooling capacity required from the coils in the local mixed-air units. Mixed-air ventilation systems, as the name implies, use an air handler to condition a mixture of outdoor and recirculated return air, and then supply the mixed air to each space. A constant-volume mixed-air system supplies the same quantity of air, usually to a single space (or zone). The temperature of the supply air is modulated to respond to the changing sensible cooling load in the space. A variable-air-volume (VAV) mixed-air system delivers supply air at a constant temperature, typically 45°F to 55°F DB (7°C to 13°C DB), to multiple VAV terminals. The VAV terminals respond to changing sensible cooling loads in each space (or zone) by modulating the airflow appropriately. What about ventilation plus energy recovery? Recall from p. 5 that the addition of an energy-recovery device typically serves one of two purposes: it either preconditions outdoor air brought into the building for ventilation, or tempers (reheats) supply air to permit independent control of the dry-bulb temperature and humidity in the conditioned space. A system can perform both functions if it includes two energy-recovery devices; see “Applications that Combine OA Preconditioning and SA Tempering” on pp. 84 – 88. Together, the composition and temperature of the supply air define four types of ventilation systems: ■ Dedicated OA systems that deliver “neutral”-temperature air (relative to room conditions). ■ Dedicated outdoor-air systems that deliver cold air ■ Mixed-air systems that modulate the temperature of a constant volume of supply air ■ Mixed-air systems that supply varying volumes of constant-temperature air Each of these ventilation systems can benefit from using air-to-air energy recovery to precondition the entering outdoor air. Budget constraints will determine whether a total- or sensible-energy recovery device best suits a particular application. When tempering supply air, however, air-to-air energy recovery only benefits systems that directly control the supply-air dew point or the humidity in the 66 SYS-APM003-EN System-Level Control of Recovered Energy space … and the benefits only exist during mechanical cooling operation. Sensible-energy recovery can provide recovered heat in compliance with energy codes and standards; when compared with alternatives that use “new” energy for tempering, it may also reduce system operating costs. (Total-energy recovery is seldom used for supply-air tempering because it transfers moisture into the dehumidified supply air.) Integrating the operation of the energy-recovery device into the control sequences for the air handler and the HVAC system is critical to realize the anticipated cost savings and reduce the payback period. The overall control strategy must also account for the psychrometric differences between total- and sensible-energy recovery. The rest of this section outlines typical system control sequences for dedicated OA and mixed-air systems that apply energy recovery for OA preconditioning and supply-air tempering; see Table 15. Each system control sequence provides profiles of the psychrometric conditions and operating characteristics that distinguish modes of control. Using total-energy recovery rather than sensibleenergy recovery requires a slightly different control strategy to account for the transfer of latent heat (moisture). Note: System configurations and control sequences other than those described in this section may require definition of additional and/or different operating modes. Table 15. Airside applications for energy recovery Ventilation System Application of Recovered Energy Composition of Supply Air Supply-Air Temperature Outdoor-Air Preconditioning Supply-Air Tempering Dedicated outdoor air neutral total (Figure 58, p. 69) or sensible (Figure 59, p. 70) sensible — series or parallel (Figure 71, p. 81) cold total (Figure 61, p. 72) or sensible (Figure 62, p. 73) 1 total (Figure 64, p. 75) or sensible (Figure 65, p. 76) sensible — series or parallel (Figure 16, p. 83) total (Figure 67, p. 78) or sensible (Figure 68, p. 79) 2 modulated Mixed air (constant volume) (outdoor air plus recirculated return air) constant (variable air volume) 1 Dedicated OA systems that deliver cold, dry ventilation air do not include a reheat function, 2 Mixed-air VAV systems, which deliver constant-temperature, cold supply air to local VAV terminals, do not require supply-air tempering at the central air handler. Although certain part-load conditions may necessitate local reheating of the supply-air within a particular space, recovering energy locally for that purpose is seldom economically feasible. SYS-APM003-EN 67 Precondition Outdoor Air System-Level Control of Recovered Energy Dedicated OA System for Neutral-Temperature Air Figure 57 illustrates a typical, dedicated OA system that delivers neutraltemperature conditioned air (CA) directly to each space. Fan-coils placed within the spaces handle the sensible load. The dedicated OA unit comprises: Does Section 6.5.2.3 of ASHRAE Standard 90.1 – 2007 (see inset on p. 4) prohibit “new energy” reheat in dedicated OA units that deliver neutraltemperature air for ventilation purposes? ■ Coils for cooling and heating ■ Constant-volume supply fan ■ Total-energy wheel (shown) or coil loop to precondition the outdoor air (A bypass damper on the exhaust side of the wheel — or a mixing valve in the coil loop — modulates capacity based on psychrometric conditions.) No, Section 6.5.2 only limits new-energy reheat by defining exceptions —that is, specific circumstances — in which its use is permitted. ■ Preheat coil for frost prevention (depending on the climate) Typically, the quantity of air supplied by the dedicated OA unit equals the minimum ventilation airflow required by ASHRAE Standard 62.1. Exception A exempts this type of unit/system from Section 6.5.2.3 because the airflow it supplies cannot be further reduced without violating the minimum limit for proper ventilation. (This exception is addressed in Example 6-YY of the user’s manual that accompanies Standard 90.1-2007) Therefore, Standard 90.1 typically will permit the use of new energy for reheat in most applications of dedicated OA units. Figure 58 and Figure 59 (p. 70) outline typical system control sequences that apply total- and sensible-energy recovery, respectively, to precondition the entering outdoor air. Economics will determine whether total- or sensible-energy recovery is the best choice for OA preconditioning in a particular application. A total-energyrecovery device offers the greatest potential to downsize mechanical cooling and heating equipment … but a sensible-energy-recovery device may be a better choice in dry climates where mechanical dehumidification is unnecessary or if cross-leakage between air streams is a concern. Figure 57. Dedicated OA system for neutral-temperature air: Total-energy recovery for OA preconditioning Examples presented later in this chapter (pp. 80 – 81 and pp. 84 – 88) show how an air-to-air, sensible-energyrecovery device can provide reheat. ■ 68 SYS-APM003-EN Precondition Outdoor Air System-Level Control of Recovered Energy Figure 58. Control sequence for a dedicated OA system: Neutral-temperature air; total-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions Comments 1 hoa hra DPToa target DPTca ■ Rotate the total-energy wheel ■ ■ Close the exhaust-side bypass damper All recovered energy lessens the mechanical cooling load ■ Modulate the cooling coil and reheat coil ■ Closing the bypass damper lets the wheel operate at full capacity for maximum recovery ■ Cooling coil enforces the CA dew-point limit; reheat coil satisfies the CA dry-bulb target ■ Wheel capacity modulates to enforce the CA dewpoint limit; cooling coil satisfies the CA dry-bulb target ■ Stopping the wheel avoids recovering unwanted heat, assuming that the target CA dew-point is a maximum limit 3 ■ Diverting the exhaust air around the wheel minimizes fan energy consumption ■ Cooling coil satisfies the CA dry-bulb target ■ Stopping the wheel avoids recovering unwanted heat, which would increase the mechanical cooling load ■ Cooling coil enforces the CA dew-point limit; reheat coil satisfies the CA dry-bulb target 2 DBToa DBTra DPToa target DPTca 3 DBTca DBToa DBTra DPToa target DPTca 4 hoa hra DPToa target DPTca Full recovery, partial cooling, partial tempering Partial recovery, partial cooling No recovery, partial cooling No recovery, partial cooling, partial tempering 5 DBToa DBTca DPToa target DPTca Partial recovery only 6 DBToa DBTcritical DPTca target DPTca Full recovery, supplemental heating 7 DBToa DBTfrost threshold Full recovery, supplemental heating, frost prevention ■ Rotate the total-energy wheel ■ Modulate the exhaust-side bypass damper to control wheel capacity ■ Modulate the cooling coil ■ Stop the total-energy wheel ■ Fully open the exhaust-side bypass damper 2 ■ Modulate the cooling coil ■ Stop the total-energy wheel ■ Fully open the exhaust-side bypass damper 2 ■ Modulate the cooling and reheat coils ■ Rotate the total-energy wheel ■ ■ Modulate the exhaust-side bypass damper to control wheel capacity All recovered energy lessens the mechanical heating load ■ Do not continuously operate the wheel at full capacity to avoid overheating/overhumidifying 4 ■ Rotate the total-energy wheel ■ ■ Close the exhaust-side bypass damper ■ Modulate the heating coil as needed Heating coil supplements the wheel capacity when outdoor conditions reach the critical temperature, satisfying the CA dry-bulb target 5 ■ Modulate the preheat coil ■ ■ Rotate the total-energy wheel Preheating the entering OA prevents frost from forming on the wheel, maximizing recovery ■ Close the exhaust-side bypass damper ■ ■ Modulate the heating coil as needed Heating coil supplements the heat recovered by the wheel, satisfying the CA dry-bulb target 1 ca = conditioned outdoor air, DBT = dry-bulb temperature, DPT = dew-point temperature, h = enthalpy, oa = outdoor air, ra = return air 2 To respond to the pressure change caused by opening the bypass damper, provide for active control of building pressurization (by modulating the exhaust fan, for example). 3 In some applications, psychrometric conditions represented in Region 3 may entail mechanical humidification. To maintain the target dew point, add moisture to the air stream by modulating the wheel capacity. Modulate the cooling coil to remove the sensible heat recovered by the wheel and maintain the desired conditioned-air dry-bulb temperature. 4 If the return-air dew point is high, it may be necessary to further reduce the capacity of the wheel to avoid overhumidifying the conditioned air. In that case, modulate the wheel capacity to maintain the target conditioned-air dew point. 5 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. SYS-APM003-EN 69 Precondition Outdoor Air System-Level Control of Recovered Energy Figure 59. Control sequence for a dedicated OA system: Neutral-temperature air; sensible-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions Comments 1 DBToa DBTra DPToa target DPTca ■ Start the coil-loop pump ■ All recovered energy lessens the cooling load ■ Fully open the mixing valve (or operate the pump at full speed) ■ ■ Modulate the cooling and reheat coils Opening the mixing valve (or full-speed pump operation) lets the coil loop operate at full capacity for maximum recovery ■ Cooling coil satisfies the CA dew-point target; reheat coil satisfies the CA dry-bulb target 2 DBToa DBTra DPToa target DPTca 3 DBTca DBToa DBTra DPToa target DPTca 4 DBToa DBTra DPToa target DPTca 5 DBToa DBTca DPToa target DPTca 6 DBToa DBTcritical DPToa target DPTca 7 DBToa DBTfrost threshold Full recovery, partial cooling, partial tempering Full recovery, partial cooling 2 No recovery, partial cooling 2 No recovery, partial cooling, partial tempering Partial recovery only 2 Full recovery, supplemental heating 2 Full recovery, supplemental heating, frost prevention 2 ■ Start the coil-loop pump ■ All recovered energy lessens the cooling load ■ Fully open the mixing valve (or operate the pump at full speed) ■ Cooling coil satisfies the CA dry-bulb target ■ Modulate the cooling coil ■ Stop the coil-loop pump ■ Dehumidification is unnecessary ■ Modulate the cooling coil ■ Stopping the coil-loop pump avoids recovering unwanted heat / increasing the cooling load ■ Cooling coil satisfies the CA dry-bulb target ■ Stopping the coil-loop pump avoids recovering unwanted heat / increasing the cooling load ■ Cooling coil dehumidifies the entering outdoor air, satisfies the desired CA dew point ■ Reheat coil maintains the CA dry-bulb target ■ Stop the coil-loop pump ■ Modulate the cooling and reheat coils ■ ■ ■ All recovered energy lessens the mechanical heating load Actuate the mixing valve (or vary pump speed) ■ Modulate the coil-loop capacity to avoid to control coil-loop capacity overheating the supply air Start the coil-loop pump ■ Supplemental heating is unnecessary because the heating load is less than coil-loop capacity ■ Start the coil-loop pump ■ ■ Fully open the mixing valve (or operate the pump at full speed) Operating the coil loop at full capacity recovers as much heat as possible from the exhaust air ■ ■ Modulate the heating coil as needed Below the critical temperature, the heating coil provides the additional heat needed to satisfy the CA dry-bulb target 3 ■ Start the coil-loop pump ■ ■ Actuate the mixing valve (or vary pump speed) ■ Modulate the heating coil as needed Modulating the coil-loop capacity to prevent frost formation on the exhaust side of the loop reduces the amount of recovered energy for heating ■ Heating coil supplements the heat recovered by the coil loop, satisfying the CA dry-bulb target 1 ca = conditioned air, DBT = dry-bulb temperature, DPT = dew-point temperature, oa = outdoor air, ra = return air 2 Certain applications may require mechanical humidification when outdoor conditions correspond to Regions 2, 4, 5, 6, or 7. 3 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. 70 SYS-APM003-EN Precondition Outdoor Air System-Level Control of Recovered Energy Dedicated OA Systems for Cold Air Figure 60 illustrates a typical, dedicated OA system that delivers cold conditioned air (CA) to the mixing boxes in multiple blower-coils, which in turn, deliver the supply air to the occupied spaces. The dedicated OA unit comprises: ■ Coils for cooling and heating ■ Constant-volume supply fan ■ Total-energy wheel (shown) or fixed-plate heat exchanger to precondition the outdoor air (A bypass damper on the exhaust-side of the wheel, or faceand-bypass dampers on the heat exchanger, modulate capacity based on psychrometric conditions.) ■ Preheat coil for frost prevention (depending on the climate) Figure 61 (p. 72) and Figure 62 (p. 73) outline typical system control sequences that apply total- and sensible-energy recovery, respectively, to precondition the entering outdoor air. Figure 60. Dedicated OA system for cold air: Total-energy recovery for OA preconditioning SYS-APM003-EN 71 Precondition Outdoor Air System-Level Control of Recovered Energy Figure 61. Control sequence for a dedicated OA system: Cold air; total-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions Comments 1 hoa hra ■ Rotate the total-energy wheel ■ ■ Close the exhaust-side bypass damper All recovered energy lessens the mechanical cooling load ■ Modulate the cooling coil ■ Closing the bypass damper lets the wheel operate at full capacity for maximum recovery ■ Cooling coil satisfies the CA dew-point target ■ Modulating the bypass damper lets the wheel recover as much as energy as possible, while maintaining the CA dew point at/below the target Full recovery, partial cooling 2 hoa hra DBToa DBTra DPToa target DPTca Partial recovery, partial cooling 3 DBTca DBToa DBTra DPToa target DPTca No recovery, partial cooling 4 hoa hra DPToa target DPTca No recovery, partial cooling 5 DBToa DBTca DPToa target DPTca Partial recovery only 6 DBToa DBTcritical Full recovery, supplemental heating 7 DBToa DBTfrost threshold Full recovery, supplemental heating, frost prevention ■ Rotate the total-energy wheel ■ Modulate the exhaust-side bypass damper to control wheel capacity ■ Modulate the cooling coil ■ Cooling coil satisfies the CA dry-bulb target ■ Stop the total-energy wheel ■ ■ Fully open the exhaust-side bypass damper 2 Operating the wheel would increase the cooling load rather than decrease it 3 ■ Modulate the cooling coil ■ Diverting the exhaust air around the wheel minimizes energy consumption of the exhaust fan ■ Cooling coil satisfies the CA dry-bulb target ■ When outdoor conditions are cool and damp, operating the wheel would transfer unwanted sensible heat and possibly moisture to the conditioned air ■ Stop the total-energy wheel ■ Fully open the exhaust-side bypass damper 2 ■ Modulate the cooling coil ■ Cooling coil satisfies the CA dew-point target ■ Rotate the total-energy wheel ■ ■ Modulate the exhaust-side bypass damper to control wheel capacity All recovered energy lessens the mechanical heating load ■ Wheel capacity is controlled to achieve the desired CA dry-bulb temperature without overheating. Do not continuously operate the wheel at full capacity: recooling overheated outdoor air will create a mechanical cooling load ■ Rotate the total-energy wheel ■ ■ Close the bypass damper ■ Modulate the heating coil as needed When outdoor conditions reach the critical temperature, operating the wheel at full “heating” capacity cannot satisfy the CA dry-bulb target 4 ■ Heating coil supplements the heat recovered by the wheel, satisfying the CA dry-bulb target ■ Preheating the entering OA prevents frost from forming on the wheel, maximizing recovery ■ Heating coil supplements the heat recovered by the wheel, satisfying the CA dry-bulb target ■ Modulate the preheat coil ■ Rotate the total-energy wheel ■ Close the bypass damper ■ Modulate the heating coil as needed 1 ca = conditioned air, DBT = dry-bulb temperature, DPT = dew-point temperature, h = enthalpy, oa = outdoor air, ra = return air 2 To respond to the pressure change caused by opening the bypass damper, provide for active control of building pressurization (by modulating the exhaust fan, for example). 3 In some applications, psychrometric conditions represented in Region 3 may entail mechanical humidification. To maintain the target dew point, add moisture to the air stream by modulating the wheel capacity. Modulate the cooling coil to remove the sensible heat recovered by the wheel and maintain the desired conditioned-air dry-bulb temperature. 4 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. 72 SYS-APM003-EN Precondition Outdoor Air System-Level Control of Recovered Energy Figure 62. Control sequence for a dedicated OA system: Cold air; sensible-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions 2 Comments 1 DBToa > DBTra ■ Close the bypass damper ■ ■ Modulate the cooling coil All recovered energy lessens the mechanical cooling load ■ Closing the bypass damper lets the fixed-plate heat exchanger operate at full capacity for maximum recovery of cooling energy ■ Cooling coil satisfies the CA dry-bulb (or dewpoint) target ■ Opening the bypass damper diverts all exhaust air around the fixed-plate heat exchanger to prevent recovery of unwanted heat ■ Cooling coil satisfies the CA dry-bulb (or dewpoint) target ■ All recovered energy lessens the mechanical heating load ■ Modulate the capacity of the fixed-plate heat exchanger to avoid overheating the supply air ■ Supplemental heating is unnecessary because the heating load is less than heat-exchanger capacity ■ Closing the bypass damper directs all exhaust air through the heat exchanger to recover as much heat as possible ■ Below the critical temperature, the heating coil provides the additional heat needed to satisfy the CA dry-bulb target 3 ■ Closing the bypass damper lets the heat exchanger operate at full capacity ■ Closing the “frost-avoidance” damper on the supply side of the heat exchanger prevents frost from forming on the exhaust side 4 ■ Heating coil supplements the heat recovered by the coil loop, satisfying the CA dry-bulb target 2 DBTca DBToa DBTra Full recovery, partial cooling No recovery, partial cooling Partial recovery 3 DBTcritical DBToa DBTca only 4 DBToa DBTcritical 5 DBToa DBTfrost threshold Full recovery, supplemental heating Full recovery, supplemental heating, frost prevention ■ Open the bypass damper ■ Modulate the cooling coil ■ Modulate the exhaust-side face-and-bypass dampers to control the capacity of the fixedplate heat exchanger ■ Close the bypass damper ■ Modulate the heating coil as needed ■ Close the bypass damper ■ Close the “frost-avoidance” damper ■ Modulate the heating coil as needed 1 ca = conditioned air, DBT = dry-bulb temperature, DPT = dew-point temperature, oa = outdoor air, ra = return air 2 Certain applications may require mechanical humidification when DPToa target DPTca. 3 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. 4 If equipped with a “frost-avoidance” damper, a fixed-plate heat exchanger can operate at outdoor temperatures as cold as -20 °F (-29 °C). Where colder conditions are expected, use a preheat coil for frost prevention. SYS-APM003-EN 73 Precondition Outdoor Air System-Level Control of Recovered Energy CV-MA Systems for Modulated-Temperature Supply Air Figure 63 illustrates a typical constant-volume, mixed-air (CV-MA) system that modulates the supply-air temperature to meet the changing load in a single space. The air handler comprises: ■ Coils for cooling and heating ■ Constant-volume supply fan ■ Total-energy wheel with exhaust-side bypass damper (shown) or coil loop with mixing valve/variable-speed pump for modulated energy recovery ■ Supply-side bypass damper to divert airflow around the energy-recovery device during economizer operation (when outdoor airflow equals full supply airflow) ■ Dry-bulb economizer (fixed “ON” point) ■ Preheat coil for frost prevention Figure 64 and Figure 65 (p. 76) outline typical control sequences that apply total- and sensible-energy recovery, respectively, to precondition the entering outdoor air. Note: Diverting airflow around the energy-recovery device during economizer operation saves fan energy by “subtracting” the related static pressure drop. As an additional benefit, the energy-recovery device can be sized to handle only ventilation airflow rather than economizer (full supply) airflow, reducing the first cost. Figure 63. CV-MA system for modulated-temperature air: Total-energy recovery for OA preconditioning 74 SYS-APM003-EN Precondition Outdoor Air System-Level Control of Recovered Energy Figure 64. Control sequence for a CV-MA system: Modulated-temperature SA; total-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions Comments 1 hoa hra 2 Full recovery, partial cooling ■ Rotate the total-energy wheel ■ ■ Close both bypass dampers All recovered energy lessens the mechanical cooling load ■ Modulate the cooling coil ■ Closing the bypass dampers lets the wheel operate at full capacity for maximum recovery ■ Cooling coil satisfies the space dry-bulb setpoint ■ Operating the wheel would increase the mechanical cooling load ■ Diverting the air around the wheel minimizes fan energy consumption ■ Cooling coil satisfies the space setpoint ■ Operating the wheel would increase the mechanical cooling load ■ Cooling coil supplements the economizer to satisfy the space setpoint ■ Economizer handles the entire cooling load ■ Supplemental heating is unnecessary because the heating load is less than wheel capacity ■ Modulating the exhaust-side bypass damper prevents overheating ■ For systems without economizers, implement this mode when DBTma DBTsa 4 ■ Closing both bypass dampers lets the wheel operate at full capacity 2 DBToa DBTecon ON hoa hra No recovery, partial cooling 3 No recovery, DBTecon ON DBToa DBTsa economizer, hoa hra partial cooling 4 DBToa DBTsa Vot minimum setpoint No recovery, economizer only 5 Vot minimum setpoint DBToa DBTcritical Partial recovery only 6 DBToa DBTcritical 7 DBToa DBTfrost threshold ■ Stop the total-energy wheel 3 ■ Fully open both bypass dampers ■ Modulate the cooling coil ■ Stop the total-energy wheel 3 ■ Fully open both bypass dampers ■ Fully open the economizer dampers 4 ■ Modulate the cooling coil ■ Stop the total-energy wheel 3 ■ Fully open both bypass dampers ■ Modulate the outdoor- (economizer) and return-air dampers 4 ■ Rotate the total-energy wheel ■ Close the supply-side bypass damper ■ Modulate the exhaust-side bypass damper to control the wheel capacity 3 Full recovery, supplemental heating ■ Rotate the total-energy wheel ■ Close both bypass dampers ■ Modulate the heating coil as needed ■ Below the critical temperature, the heating coil adds enough heat to satisfy the space setpoint 5 Full recovery, supplemental heating, frost prevention ■ Modulate the preheat coil ■ ■ Rotate the total-energy wheel Preheating the entering OA prevents frost from forming on the wheel, maximizing recovery ■ Close both bypass dampers ■ ■ Modulate the heating coil as needed Heating coil supplements the heat recovered by the wheel, satisfying the space setpoint 1 DBT = dry-bulb temperature, econ ON = economizer “ON” point, h = enthalpy, ma = mixed air, oa = outdoor air, ra = return air, sa = supply air, Vot = total (system) outdoor airflow DBTra. Basing operation on dry-bulb temperature rather than enthalpy may miss many hours of energy recovery; also, it may yield hours of wheel operation that increase the mechanical cooling load. 2 If dry-bulb (rather than enthalpy) control is used, the Region 1 control mode governs operation of the wheel when DBToa 3 Do not continuously operate the total-energy wheel at full capacity when outdoor conditions correspond to Regions 2, 3, 4, or 5. Recooling overheated air increases energy consumption at the cooling plant. 4 In a system without an economizer, omit the control modes for Regions 3 and 4. Implement Region 5 operation when DBTma < DBTsa. 5 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. SYS-APM003-EN 75 Precondition Outdoor Air System-Level Control of Recovered Energy Figure 65. Control sequence for a CV-MA system: Modulated-temperature SA; sensible-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions Comments 1 DBToa DBTra Full recovery, partial cooling ■ Start the coil-loop pump ■ All recovered energy lessens the cooling load ■ Close both bypass dampers ■ ■ Fully open the mixing valve ■ Modulate the cooling coil Opening the mixing valve (or full-speed pump operation) lets the coil loop operate at full capacity for maximum recovery ■ Cooling coil satisfies the space dry-bulb setpoint ■ Stopping the coil-loop pump avoids recovering unwanted heat , increasing the cooling load ■ Opening the bypass dampers saves fan energy by diverting airflow around the coil-loop coils ■ Cooling coil satisfies the space setpoint ■ Stopping the coil-loop pump avoids recovering unwanted heat, increasing the cooling load ■ Cooling coil supplements the economizer to satisfy the space setpoint ■ Stopping the coil-loop pump avoids recovering unwanted heat, increasing the cooling load ■ Opening the bypass dampers saves fan energy by diverting airflow around the coil-loop coils 2 No recovery, DBTecon ON DBToa DBTra partial cooling 3 DBToa DBTecon ON DPToa DBTsa No recovery, economizer, partial cooling 2 ■ Stop the coil-loop pump ■ Fully open both bypass dampers ■ Modulate the cooling coil ■ Stop the coil-loop pump ■ Fully open both bypass dampers ■ Fully open the OA (economizer) dampers ■ Modulate the cooling coil as needed 4 DBToa DBTsa Vot minimum setpoint No recovery, ■ Stop the coil-loop pump economizer only 2 ■ Fully open both bypass dampers 5 Vot minimum setpoint DBToa DBTcritical Partial recovery only 2 6 DBToa DBTcritical Full recovery, supplemental heating 7 DBToa DBTfrost threshold ■ Modulate the outdoor- (economizer) and return-air dampers ■ Economizer satisfies the space setpoint ■ Start the coil-loop pump ■ All recovered energy lessens the heating load ■ Close both bypass dampers ■ ■ Start the coil-loop pump ■ ■ Close both bypass dampers Operating the coil loop at full capacity recovers as much heat as possible from the exhaust air ■ Fully open the mixing valve ■ ■ Modulate the heating coil as needed Below the critical temperature, the heating coil adds enough heat to satisfy the space setpoint 4 ■ Start the coil-loop pump ■ ■ Close both bypass dampers ■ Actuate the mixing valve (or vary pump speed) Modulating the coil-loop capacity to prevent frost formation on the exhaust side of the loop reduces the amount of recovered energy for heating ■ Modulate the heating coil as needed ■ Heating coil supplements the heat recovered by the coil loop, satisfying the space setpoint ■ Full recovery, supplemental heating, frost prevention Modulate the coil-loop capacity to avoid overheating the supply air Actuate the mixing valve (or vary pump speed) ■ Supplemental heat is unnecessary because the to control coil-loop capacity 3 heating load is less than coil-loop capacity 1 DBT = dry-bulb temperature, econ ON = economizer “ON” point, ma = mixed air, oa = outdoor air, ra = return air, sa = supply air, Vot = total (system) outdoor airflow 2 If the system does not include an economizer, omit the control modes for Regions 3 and 4. Implement Region 5 operation when DBTma DBTsa. 3 Alternatively, the exhaust-side bypass damper can be modulated to control the capacity of the coil loop. 4 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. 76 SYS-APM003-EN Precondition Outdoor Air System-Level Control of Recovered Energy VAV-MA Systems for Constant-Temperature Supply Air Figure 66 illustrates a typical mixed-air (MA) system that delivers a variable volume of cold supply air to local, variable-air-volume (VAV) terminals. The air handler comprises: Trane engineering bulletin CLCH-PRB009-EN, Recirculation Energy Recovery Unit Controls, provides more detailed control recommendations for VAV systems. ■ ■ Coils for cooling and heating ■ Supply fan with variable-speed drive ■ Total-energy wheel with exhaust-side bypass damper (shown) or coil loop with mixing valve/variable-speed pump for modulated energy recovery ■ Supply-side bypass damper to divert airflow around the energy-recovery device during economizer operation (when outdoor airflow equals full supply airflow) ■ Economizer (comparative enthalpy control for total-energy recovery; fixed dry-bulb control for sensible-energy recovery) ■ Pressure-independent, flow-measuring damper to maintain the minimum required outdoor airflow ■ Preheat coil for frost prevention (depending on climate) Figure 67 (p. 78) and Figure 68 (p. 79) outline typical control sequences that apply total- and sensible-energy recovery, respectively, for OA preconditioning. Note: Diverting airflow around the energy-recovery device during economizer operation saves fan energy by “avoiding” the related static pressure drop. Size the energy-recovery device to handle only ventilation airflow rather than economizer (full supply) airflow, which will reduce the first cost. Figure 66. VAV system for constant-temperature air: Total-energy recovery for OA preconditioning SYS-APM003-EN 77 Precondition Outdoor Air System-Level Control of Recovered Energy Figure 67. Control sequence for a VAV system: Constant-temperature SA; total-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions Comments 1 hoa hra 2 ■ Rotate the total-energy wheel ■ All recovered energy lessens the cooling load ■ Close both bypass dampers ■ ■ Modulate the cooling coil Closing the bypass dampers lets the wheel operate at full capacity for maximum recovery ■ Cooling coil satisfies the SA dry-bulb setpoint ■ Stopping the wheel avoids transferring unwanted heat and moisture, increasing the cooling load 2 DBToa DBTsa hoa hra Full recovery, partial cooling No recovery, economizer, partial cooling 3, 4 3 DBToa DBTsa Vot minimum setpoint No recovery, economizer only 3, 4 4 Vot minimum setpoint DBToa DBTcritical Partial recovery only 3, 5 5 DBToa DBTcritical 6 DBToa DBTfrost threshold ■ Stop the total-energy wheel ■ Fully open both bypass dampers ■ Fully open the economizer dampers ■ Opening the bypass dampers saves fan energy ■ Modulate the cooling coil ■ Cooling coil supplements the economizer to satisfy the SA dry-bulb setpoint ■ Stop the total-energy wheel ■ ■ Fully open both bypass dampers Economizer satisfies the SA dry-bulb setpoint, handling the entire cooling load ■ Modulate the outdoor- (economizer) and return-air dampers ■ Opening the bypass dampers saves fan energy ■ Supplemental heating is unnecessary because the heating load is less than wheel capacity ■ Modulating the exhaust-side bypass damper avoids overheating the supply air ■ For systems without economizers, implement this mode when DBTma DBTsa ■ Closing both bypass dampers lets the wheel operate at full capacity ■ Rotate the total-energy wheel ■ Close the supply-side bypass damper ■ Modulate the exhaust-side bypass damper to control wheel capacity Full recovery, supplemental heating ■ Rotate the total-energy wheel ■ Close both bypass dampers ■ Modulate the heating coil as needed 6 ■ Below the critical temperature, the heating coil adds enough heat to satisfy the SA setpoint 7 Full recovery, supplemental heating, frost prevention ■ Modulate the preheat coil ■ ■ Rotate the total-energy wheel Preheating the entering outdoor air prevents frost from forming on the wheel, maximizing recovery ■ Close both bypass dampers ■ ■ Modulate the heating coil as needed 6 Heating coil supplements the heat recovered by the wheel, satisfying the SA dry-bulb setpoint 1 DBT = dry-bulb temperature, h = enthalpy, ma = mixed air, oa = outdoor air, ra = return air, sa = supply air, Vot = total (system) outdoor airflow DBTra. Basing operation on dry-bulb temperature rather than enthalpy may miss many hours of energy recovery; also, it may yield hours of wheel operation that increase the mechanical cooling load. 2 If dry-bulb (rather than enthalpy) control is used, the Region 1 control mode governs operation of the wheel when DBToa 3 Do not continuously operate the total-energy wheel at full capacity when outdoor conditions correspond to Region 2, 3, or 4. Overheating the outdoor air stream increases the cooling load and the energy consumption of the cooling plant. 4 If the system includes a dry-bulb (rather than comparative enthalpy) economizer, the economizer will not activate in the Region 2 control mode until DBToa DBTecon ON. If the system does not include an economizer, omit the control mode for Region 3; implement Region 4 operation when DBTma < DBTsa. 5 In mixed-air VAV systems, a total-energy wheel may provide free heat at outdoor temperatures as cold as those in Region 6, effectively extending Region 4 operation through Region 5 conditions (eliminating the Region 5 control mode). 6 If the VAV terminals include sufficient heating capacity to handle the morning warm-up function, the wheel may recover enough heat (in some climates) to eliminate the need for a centralized heating coil. 7 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. 78 SYS-APM003-EN Precondition Outdoor Air System-Level Control of Recovered Energy Figure 68. Control sequence for a VAV system: Constant-temperature SA; sensible-energy recovery for OA preconditioning Psychrometric Conditions 1 Control Mode Control Actions Comments 1 DBToa DBTra ■ Start the coil-loop pump ■ All recovered energy lessens the cooling load ■ Close both bypass dampers ■ ■ Fully open the mixing valve (or operate the pump at full speed) Operating the coil loop at full capacity (bypass dampers closed; mixing valve open / highest pump speed) maximizes the recovery of cooling energy ■ Modulate the cooling coil ■ Cooling coil satisfies the SA dry-bulb setpoint ■ Stop the coil-loop pump ■ ■ Fully open both bypass dampers Stopping the coil-loop pump avoids recovering unwanted heat , increasing the cooling load ■ Modulate the cooling coil ■ Opening the bypass dampers saves fan energy ■ Cooling coil satisfies the SA dry-bulb setpoint ■ Stopping the coil-loop pump avoids recovering unwanted heat , increasing the cooling load 2 DBToa DBTra DBToa DBTecon ON 3 DBToa DBTecon ON DPToa DBTsa 4 DBToa DBTsa Vot minimum setpoint 5 Vot minimum setpoint DBToa DBTcritical 6 DBToa DBTcritical 7 DBToa DBTfrost threshold Full recovery, partial cooling No recovery, partial cooling No recovery, economizer, partial cooling 2 No recovery, economizer only 2 Partial recovery only 2 Full recovery, supplemental heating Full recovery, supplemental heating, frost prevention ■ Stop the coil-loop pump ■ Fully open both bypass dampers ■ Fully open the OA (economizer) damper ■ Opening the bypass dampers saves fan energy ■ Modulate the cooling coil as needed ■ Cooling coil supplements the economizer to satisfy the SA dry-bulb setpoint ■ Stop the coil-loop pump ■ ■ Fully open both bypass dampers Stopping the coil-loop pump avoids recovering unwanted heat , increasing the cooling load ■ Modulate the outdoor- (economizer) and return-air dampers ■ Opening the bypass dampers saves fan energy ■ Economizer satisfies the SA dry-bulb setpoint ■ Start the coil-loop pump ■ All recovered energy lessens the heating load ■ Close both bypass dampers ■ ■ Modulate the coil-loop capacity (mixing valve, pump speed, or exhaust-side damper) 3 Modulate the coil-loop capacity to avoid overheating the supply air / creating a cooling load ■ Supplemental heat is unnecessary because the heating load is less than coil-loop capacity ■ Start the coil-loop pump ■ ■ Close both bypass dampers Operating the coil loop at full capacity (wide-open mixing valve, for example) maximizes recovery ■ Fully open the mixing valve ■ ■ Modulate the heating coil as needed Below the critical temperature, the heating coil adds enough heat to satisfy the SA setpoint 4 ■ Start the coil-loop pump ■ ■ Close both bypass dampers ■ Actuate the mixing valve (or vary pump speed) Modulating the coil-loop capacity to prevent frost formation on the exhaust side of the loop reduces the amount of recovered energy for heating ■ Modulate the heating coil as needed ■ Heating coil supplements the heat recovered by the coil loop, satisfying the SA dry-bulb setpoint 1 DBT = dry-bulb temperature, econ ON = economizer “ON” point, ma = mixed air, oa = outdoor air, ra = return air, sa = supply air, Vot = total (system) outdoor airflow 2 If the system does not include an economizer, omit the control modes for Regions 3 and 4. Implement Region 5 operation when DBTma DBTsa. 3 Alternatively, the exhaust-side bypass damper can be modulated to control the capacity of the coil loop. 4 The “critical temperature” threshold is defined by the conditioned- and return-air dry-bulb temperatures, and the effectiveness of the energy-recovery device. SYS-APM003-EN 79 Temper Supply Air System-Level Control of Recovered Energy Dedicated OA System for Neutral-Temperature Air Figure 69. Air handler with fixed-plate heat exchanger Does Section 6.5.2.3 of ASHRAE Standard 90.1 – 2007 (see inset on p. 4) prohibit “new energy” reheat in dedicated OA units that deliver neutraltemperature air for ventilation purposes? Recall from the beginning of this section (p. 66) that recovering sensible energy for supply-air tempering can benefit systems that directly control the supply-air dew point or the humidity in the space. Figure 69 shows an example of an air handler that tempers conditioned air with energy recovered by the series arrangement of a fixed-plate heat exchanger. In Figure 70, the air handler becomes part of a dedicated OA system that delivers neutral-temperature air directly to the occupied spaces. Fan-coils installed in occupied spaces handle the local sensible loads. The central air handler, which serves as a dedicated OA unit, comprises: ■ Coils for cooling and heating ■ Constant-volume supply fan ■ Fixed-plate heat exchanger (arranged in a series or “wraparound” configuration) with integral face-and-bypass dampers to modulate capacity Figure 71 outlines a typical control sequence for this system. Figure 70. Dedicated OA system for neutral-temperature air: Sensible-energy recovery for tempering No, Section 6.5.2 only limits new-energy reheat by defining exceptions —that is, specific circumstances — in which its use is permitted. Typically, the quantity of air supplied by the dedicated OA unit equals the minimum ventilation airflow required by ASHRAE Standard 62.1. Exception A exempts this type of unit/system from Section 6.5.2.3 because the airflow it supplies cannot be further reduced without violating the minimum limit for proper ventilation. (This exception is addressed in Example 6-YY of the user’s manual that accompanies Standard 90.1-2007) Therefore, Standard 90.1 typically will permit the use of new energy for reheat in most applications of dedicated OA units. Examples presented later in this chapter (pp. 80 – 81 and pp. 84 – 88) show how an air-to-air, sensible-energyrecovery device can provide reheat. ■ 80 SYS-APM003-EN Temper Supply Air System-Level Control of Recovered Energy Figure 71. Control sequence for a dedicated OA system: Neutral-temperature air; sensible-energy recovery for tempering Psychrometric Conditions 1 1 DPToa DPTca setpoint 2 DPToa DPTca setpoint DBToa DBTca setpoint 3 DPToa DPTca setpoint DBToa DBTca setpoint Control Mode Control Actions Comments Dehumidification, recovery for tempering, supplemental tempering as needed ■ Modulate the cooling coil ■ ■ Modulate the face-and-bypass dampers ■ Modulate the heating coil as needed Sensible heat transferred from the outdoor air (upstream of the cooling coil) to the air (downstream of the cooling coil) lessens the cooling and tempering (reheat) loads ■ Cooling coil dehumidifies the entering outdoor air to maintain the desired leavingcoil dew-point temperature ■ Heat exchanger satisfies the CA dry-bulb setpoint. Closing the bypass dampers lets the fixed-plate heat exchanger operate at full capacity ■ Heating coil provides the additional heat needed (if any) to satisfy the CA dry-bulb setpoint ■ Dehumidification and tempering are unnecessary ■ Cooling coil maintains the desired leavingcoil dry-bulb temperature ■ Opening the bypass dampers saves fan energy and prevents unwanted heat transfer by diverting airflow around the fixed-plate heat exchanger ■ Dehumidification and sensible cooling are unnecessary ■ Opening the bypass dampers saves fan energy and prevents unwanted heat transfer ■ Heating coil satisfies the CA dry-bulb target No dehumidification, no recovery, partial sensible cooling No dehumidification, no recovery, partial heating 2 ■ Modulate the cooling coil ■ Open the bypass dampers ■ Turn off the cooling coil ■ Open the bypass dampers ■ Modulate the heating coil as needed 1 ca = conditioned air, DBT = dry-bulb temperature, DPT = dew-point temperature, oa = outdoor air, sa = supply air 2 If the fixed-plate heat exchanger is configured for parallel (rather than series) energy recovery, it can provide sensible heating when outdoor conditions correspond to Region 3. Control actions for parallel energy-recovery during Region 3 are: ■ Modulate the face-and-bypass dampers (energy-recovery capacity) to prevent the heat exchanger from overheating the conditioned air. ■ If the capacity of the heat exchanger cannot warm the outdoor air to the desired temperature, modulate the heating coil to provide supplemental heat. ■ In cold climates, Region 3 operation may also require frost prevention if the heat exchanger is used to precondition the outdoor air. SYS-APM003-EN 81 Temper Supply Air System-Level Control of Recovered Energy CV-MA Systems for Modulated-Temperature Supply Air Constant-volume, mixed-air (CV-MA) systems that modulate the supply-air temperature must provide tempering if they directly control the dry-bulb temperature and the humidity in the space. The CV-MA system represented in Figure 72 modulates the temperature of the supply air to meet the changing load in a single space. The system also directly controls space humidity by overcooling (to dehumidify) and then tempering (reheating) the supply air. The air handler comprises: ■ Coils for cooling and heating ■ Constant-volume supply fan ■ Coil loop, arranged in a series (“wraparound”) configuration, for supply-air tempering (A mixing valve provides capacity control.) Table 16 outlines a typical CV-MA control sequence. Note: Although the reheat coil uses new energy, compliance with ASHRAE Standard 90.1 – 2007 can be achieved by sizing the coil loop to provide at least 75 percent of the required tempering (reheat) energy. Figure 72. CV-MA system for modulated-temperature SA: Sensible-energy recovery for SA tempering 82 SYS-APM003-EN Temper Supply Air System-Level Control of Recovered Energy Table 16. Control sequence for a CV-MA system: Modulated-temperature SA; sensible-energy recovery for SA tempering Psychrometric Conditions 1 Control Mode 1 Partial cooling, RHspace RHmax limit no recovery for tempering DBTspace DBTcooling setpoint 2 RHspace RHmax limit Dehumidification, partial recovery for tempering, supplemental tempering as needed 3 Partial heating, RHspace RHmax limit no recovery for tempering 3 DBTspace DBTheating setpoint Control Actions Comments ■ Stop the coil-loop pump ■ Standard cooling mode ■ Modulate the cooling coil ■ Cooling coil satisfies the space dry-bulb setpoint ■ Stopping the coil-loop pump avoids transferring unwanted heat / overheating the space ■ Modulate the cooling coil ■ Dehumidification mode 2 ■ Start the coil-loop pump ■ ■ Actuate the mixing valve (or vary pump speed) to control coil-loop capacity ■ Modulate the heating coil as needed Cooling coil overcools and dehumidifies the supply air, enforcing the maximum relativehumidity limit (60% RH, for example) in the space ■ Coil loop transfers sensible heat from the outdoor air (upstream of the cooling coil) to the overcooled supply air (downstream of the cooling coil) ■ Modulating the coil-loop capacity maintains the space dry-bulb setpoint ■ Heating coil supplements the heat recovered by the coil-loop to satisfy the space setpoint ■ Turn off the cooling coil ■ Standard heating mode ■ Stop the coil-loop pump ■ ■ Modulate the heating coil as needed Stopping the coil-loop pump prevents unwanted heat transfer ■ Heating coil satisfies the space setpoint 1 DBT = dry-bulb temperature, RH = relative humidity 2 Supply-air tempering and, therefore, air-to-air energy recovery only occur when space conditions correspond to Region 2. 3 Regardless of whether sensible energy is transferred using a series arrangement (as in the example CV-MA system described on p. 82) or recovered using a parallel arrangement, the control actions for Region 3 operation are identical. SYS-APM003-EN 83 System-Level Control of Recovered Energy Applications that Combine OA Preconditioning and SA Tempering Depending on the performance criteria, certain applications may benefit from a system design that simultaneously preconditions outdoor air and tempers supply air using two energy-recovery devices. Dual-Function, Dedicated OA System for Neutral-Temperature Air Dedicated outdoor-air systems that deliver neutral-temperature conditioned air are excellent candidates for dual-purpose energy recovery. The example in Figure 73 shows a dedicated OA unit that not only handles the sensible and latent loads of the outdoor air stream, but also sufficiently dehumidifies (lowers the dew point of) the outdoor air to satisfy local latent loads. Fan-coils installed in each space only handle the local sensible loads. The dedicated OA unit comprises: ■ Preheat coil for frost prevention (depending on climate) ■ Total-energy wheel to precondition the entering outdoor air (Exhaust-side bypass dampers provide capacity control.) ■ Cooling coil for dehumidification ■ Fixed-plate heat exchanger, in a parallel energy-recovery arrangement, for supply-air tempering (Face-and-bypass dampers provide capacity control.) Figure 73. Dual-function, dedicated OA system for neutral-temperature air 84 SYS-APM003-EN System-Level Control of Recovered Energy Figure 74. Dedicated OA unit with two energy-recovery devices ■ Heating coil for supplemental tempering ■ Constant-volume supply fan The elevation view in Figure 74 illustrates one possible physical arrangement of these components within an air-handler casing. Benefits of Dual-Function Energy Recovery Plotting psychrometric performance reveals the benefits of dual-function energy recovery for a dedicated OA system that delivers neutral-temperature conditioned air. The example in Figure 75 uses the design conditions for Jacksonville, Florida. Cooling design. The total-energy wheel cools and dehumidifies the entering outdoor air to 70.5°F DB, 62.7°F WB (21.4°C DB, 17.1°C WB). As the wheel rotates, sensible heat and moisture collected from the outdoor air transfer to Figure 75. Psychrometric performance for a dedicated OA system with dual-function energy recovery (neutral-temperature CA) HX = fixed-plate heat exchanger SYS-APM003-EN 85 System-Level Control of Recovered Energy the exhaust air stream, which was precooled by the fixed-plate heat exchanger. Precooling the exhaust air increases the amount of transferred heat. Cooling-energy savings: Q T = 4.5 10 000 cfm 39.3 – 28.3 Btu/lb Q T = 495 000 Btu/hr = 41.2 tons Q T = 1.2 4.7 m³/s 91.4 – 65.8 kJ/kg Q T = 144 kW Reheat-energy savings: Q s = 1.085 10 000 cfm 67.0°F – 53.5°F Q s = 146 475 Btu/hr = 146.5 MBh Q s = 1.21 4.7 m³/s 19.4°C – 11.9°C Q s = 42.7 kW Heating-energy savings: Q s = 1.085 10 000 cfm 62.8°F – 31°F Q s = 345 030 Btu/hr = 345 MBh Q s = 1.21 4.7 m³/s 17.1°C – – 0.8 °C Q s = 102 kW Meanwhile, the cooling coil dehumidifies the air to the desired conditioned-air dew point. When the dehumidified air passes through the fixed-plate heat exchanger, the sensible heat recovered from the exhaust air stream transfers to the conditioned air stream. If the fixed-plate heat exchanger cannot warm the conditioned air to the “neutral” target, 71°F DB (21.7°C DB) in this case, the heating coil provides the additional tempering needed. In this example, dual-function energy recovery reduces the mechanical cooling load by 41.2 tons (144 kW), a 64-percent reduction. It also reduces the “newenergy” reheat load by 146.5 MBh (42.7 kW), a 77-percent reduction. Heating design. Dehumidification and, therefore, supply-air tempering are unnecessary for Jacksonville’s heating design condition, so the fixed-plate heat exchanger is not used (that is, the bypass damper opens). Instead, the totalenergy wheel heats and humidifies the entering outdoor air and the heating coil provides the additional sensible heat needed to reach the target conditioned-air temperature, a neutral 70°F (21.1°C) in this case. In this example, the total-energy wheel reduces the sensible load on the heating coil by 345 MBh (102 kW), an 82-percent reduction. Note: Because the fixed-plate heat exchanger in this example is arranged for parallel energy recovery, it could potentially transfer heat from the exhaust air stream; however, we discourage this practice. Removing heat from the exhaust air stream reduces the capacity of the total-energy wheel and raises the threshold temperature for frost prevention. The high effectiveness of a totalenergy wheel may allow it to recover more heat, overall, without operation of the fixed-plate heat exchanger. Control Sequence Figure 76 outlines a typical control sequence for a “dual-function” dedicated outdoor-air system (Figure 73, p. 84), which uses air-to-air energy recovery for both outdoor-air preconditioning and supply-air tempering. 86 SYS-APM003-EN System-Level Control of Recovered Energy Figure 76. Control sequence for a dedicated OA system with dual-function energy recovery Psychrometric Conditions 1 Control Mode Control Actions Comments 1 h oa h ra DPToa DPTca target Full recovery for ■ preconditioning, ■ partial cooling, ■ partial recovery for ■ tempering, supplemental tempering Rotate the wheel (close the bypass damper) ■ Modulate the cooling coil ■ Modulate the face-and-bypass dampers ■ Modulate the reheat coil as needed 2 DBToa DBTra DPToa DPTca target Partial recovery for preconditioning, partial cooling, no recovery for tempering ■ Rotate the wheel (modulate the bypass damper) ■ Modulate the cooling coil ■ Open the heat-exchanger bypass damper ■ 3 DBTca DBToa DBTra DPToa DPTca target No recovery for preconditioning, partial cooling, no recovery for tempering 2 ■ ■ Wheel operation would increase the cooling load ■ Cooling coil satisfies the CA dry-bulb target ■ Bypassing the wheel and heat exchanger saves fan energy 4 h oa h ra DPToa DPTca target No recovery for ■ preconditioning, ■ partial cooling, ■ partial recovery for ■ tempering, supplemental tempering Stop the wheel (open the bypass damper) 3 ■ Wheel operation would increase the cooling load Modulate the cooling coil ■ Cooling coil maintains the CA dew point at/ Modulate the face-and-bypass dampers below the target Modulate the reheat coil as needed ■ Heat exchanger satisfies the CA dry-bulb target, with help of the reheat coil, if necessary 5 Partial recovery for DBTcritical DBToa DBTca preconditioning 4 DPToa DPTca target Stop the total-energy wheel (open the bypass damper to save fan energy) 3 ■ Modulate the cooling coil ■ Open the heat-exchanger bypass damper ■ Rotate the wheel (modulate the bypass damper) ■ Open the heat-exchanger bypass damper 6 DBToa DBTcritical DPToa DPTca target Full recovery for preconditioning, supplemental heating ■ 7 DBToa DBTfrost threshold Full recovery for preconditioning, supplemental heating, frost prevention ■ Wheel operates at full capacity for maximum recovery Cooling coil maintains the target CA dew point Heat exchanger satisfies the CA dry-bulb target with help from the reheat coil, if necessary Dehumidification, SA tempering are unnecessary ■ Wheel recovers cooling energy while maintaining the CA dew point at/below the target ■ Cooling coil satisfies the CA dry-bulb target ■ Bypassing the heat exchanger avoids unwanted heat transfer and saves fan energy ■ Wheel satisfies the CA dry-bulb target without overheating ■ Bypassing the heat exchanger saves fan energy Rotate the wheel (close the bypass damper) ■ Wheel operates a full capacity in cold weather Modulate the heating coil ■ Heating coil satisfies the CA dry-bulb target ■ Open the heat-exchanger bypass damper ■ Bypassing the heat exchanger saves fan energy ■ Modulate the preheat coil ■ Rotate the wheel (close the bypass damper) ■ ■ Open the heat-exchanger bypass damper ■ ■ Modulate the heating coil ■ Preheat coil protects the wheel from frost and maximizes energy recovery Bypassing the heat exchanger saves fan energy Heating coil satisfies the CA dry-bulb target 1 ca = conditioned air, DBT = dry-bulb temperature, DPT = dew-point temperature, h = enthalpy, oa = outdoor air, ra = return air 2 Region 3 operation described above is based on the assumption that DPTca target is a maximum limit. In applications that require mechanical humidification, modulate the wheel capacity to maintain the desired conditioned-air dew point and modulate the cooling coil to maintain the target dry-bulb temperature. 3 To respond to the pressure change caused by opening the bypass damper, provide for active control of building pressurization (by modulating the exhaust fan, for example). 4 Do not continuously operate the wheel at full capacity when Region 5 conditions exist. To avoid overhumidification when the return-air dew point is unusually high, modulate the wheel capacity to maintain the desired conditioned-air dew point; use partial recovery for tempering to achieve the target dry-bulb temperature. SYS-APM003-EN 87 System-Level Control of Recovered Energy Alternatives for Tempering with Sensible-Energy Recovery The “dual-function,” dedicated OA system introduced on p. 84 tempers supply air with sensible energy recovered by a fixed-plate heat exchanger. Substituting a coil loop, a heat pipe, or a sensible-energy wheel as in Figure 77 will not significantly alter the control sequence in Figure 76 (p. 87), provided that the design includes a means for controlling the capacity of the tempering device. Figure 77. “Dual-function” dedicated OA unit with sensible-energy wheel for tempering In contrast to a total-energy wheel, which is a passive desiccant device, an active desiccant device adds heat to “regenerate” the desiccant. The Trane applications engineering manual, Dehumidification in HVAC Systems (order number SYS-APM004EN), further discusses “active” desiccant devices. It is available from the Trane bookstore at www.trane.com/ bookstore. ■ Tempering (Recooling) in an Active-Desiccant System Figure 78 illustrates a dedicated OA system with active-desiccant dehumidification. The system includes two energy-recovery devices and uses a different psychrometric process to perform the same role as the “dualfunction,” dedicated OA system: ■ An active-desiccant wheel, which conditions the outdoor air by heating and dehumidifying the air stream rather than cooling and dehumidifying it ■ A sensible wheel, which tempers the conditioned air by recooling the air stream rather than reheating it The active-desiccant wheel removes moisture from the outdoor air stream, dehumidifying it to a low dew point; it also transfers sensible heat to the conditioned air. The dry conditioned air then passes through a sensible-energy 88 SYS-APM003-EN System-Level Control of Recovered Energy Figure 78. “Dual-function,” dedicated OA system with active-desiccant wheel wheel, which removes sensible heat and rejects it into the exhaust air stream (as shown in Figure 78) or into a separate outdoor air stream. A cooling coil further reduces the temperature of the conditioned air to a nearly neutral condition. On the regeneration side of the system, the sensible-energy wheel preheats the exhaust air stream with sensible heat recovered from the conditioned air. A gasfired heat exchanger further heats the “regeneration” air stream. Depending on the desired conditioned-air dew point, the temperature of the “regeneration” air entering the active-desiccant wheel typically ranges from 130°F to 250°F (54°C to 121°C). Increasing the regeneration temperature of the active-desiccant wheel allows it to remove more moisture from the conditioned air stream; however, it further increases the dry-bulb temperature of the conditioned air leaving this device and, therefore, requires more recooling. ■ SYS-APM003-EN 89 Suggestions for Effective Airside Energy Recovery The preceding chapters discussed how air-to-air energy recovery can reduce the costs of operating an HVAC system … and may even permit downsizing of mechanical equipment used for heating, cooling, humidification, and dehumidification. This section summarizes the key points from those chapters; it also offers general recommendations to promote the effective use of air-to-air energy-recovery devices in HVAC applications. Economic considerations, local energy codes, and other issues such as spatial constraints, maintenance requirements, and air-stream locations will ultimately determine the feasibility of air-to-air energy recovery for a particular project. OA Preconditioning When an application that preconditions outdoor air requires recovered energy to comply with ASHRAE Standard 90.1 – 2007 (see pp. 2 – 4), the total effectiveness of the air-to-air energyrecovery device must be at least 50 percent. ■ Some local codes require the use of recovered energy for outdoor-air (OA) preconditioning. Although relatively few installations are currently affected by these mandates, many more could economically benefit from this use of airside energy recovery. The benefits of preconditioning outdoor air with recovered energy accrue during both cooling and heating operation — and they are not confined to hot, humid climates. In fact, the largest economic benefits typically result in climates where both cooling and heating demands exist. Sensible- or Total-Energy Recovery? Budgetary constraints generally determine whether a sensible- or total-energy recovery device best suits a particular system design. In most climates, a totalenergy recovery device improves the opportunity for downsizing the cooling and heating equipment (and usually provides the best payback) because it recovers both sensible and latent energy. The most notable exceptions are dry climates where it is unnecessary to mechanically dehumidify the outdoor air. Certified performance permits meaningful comparisons of air-to-air energy-recovery devices. Look for equipment that bears the ARI 1060 seal (page 61), and include ARI-certified performance when specifying energyrecovery devices for OA preconditioning applications. ■ 90 Which technologies offer the best value? Trane engineers studied five airto-air energy-recovery technologies — heat pipes, sensible-energy wheels, totalenergy wheels, coil loops, and fixed-plate heat exchangers — to determine their value in OA preconditioning applications. The analysis compared the first costs (normalized) of providing a defined rate of heat transfer at various volumes of airflow. Figure 79 summarizes the results of that study. At every point of comparison, the total-energy wheels offer the best value — that is, the lowest first cost for a given quantity of transferred heat. The best value among the sensible-energy-recovery technologies depends on airflow capacity. At less than 15,000 cfm (7 m³/s), fixed-plate heat exchangers provide the best value; at higher airflows, coil loops prevail. Given the higher first costs of recovering the same amount of energy, heat pipes and sensibleenergy wheels provide the least value; however, they also deliver the required performance across a broader range of airflows. SYS-APM003-EN Suggestions for Effective Airside Energy Recovery Figure 79. Comparison of airside energy-recovery technologies for OA preconditioning Of course, intangible issues such as the condition of the exhaust air stream must be considered when selecting an air-to-air energy recovery device. Coil loops, for example, become the best energy-recovery option when crossleakage between air streams is unacceptable. Total-energy recovery in predominantly heating climates. “Only hot, humid climates justify total energy recovery because the device can function as a dehumidifier during many hours of the year.” … “Buildings in cold climates require many hours of heating, so why pay a higher price to recover total energy when sensible-energy recovery will suffice?” Too often, these misperceptions influence the design of HVAC systems that precondition outdoor air with recovered energy. When compared with sensibleenergy recovery, however, total-energy-recovery devices can provide significant operating advantages in climates where heating operation prevails: SYS-APM003-EN ■ Frost forms at a much colder outdoor temperature, which allows the total-energy-recovery device to recover more heat during cold weather and lessens the need for preheat (see p. 55). ■ The generally higher effectiveness of total-energy recovery devices saves more heating energy and permits further downsizing of the heating plant. ■ Moisture recovered by a total-energy-recovery device humidifies (as well as warms) the entering outdoor air during the heating season, which helps keep the space from becoming too dry. “Free” humidification also reduces the energy used by the mechanical humidification system and permits equipment downsizing. ■ Most heating climates include a cooling season. Applying a total-energyrecovery device enables a larger reduction in cooling-plant capacity, which can substantially reduce the first-cost premium for energy recovery. 91 Suggestions for Effective Airside Energy Recovery Table 17 compares the expected number of annual operating hours for one system when it is applied in two distinctly different climates: Jacksonville, Florida, where cooling operation prevails; and Minneapolis, Minnesota, where heating operation prevails. The mixed-air VAV system includes a comparative enthalpy-economizer and uses a total-energy-recovery device to precondition the outdoor air stream. (For a detailed description of the control sequence, see Figure 67, p. 78.) The analysis reveals two interesting points: ■ Despite the difference in climate, the total number of operating hours for the energy-recovery device —represented by Regions 1, 4, 5, and 6 — is roughly the same in both locations … 1,647 hours in Jacksonville and 1,489 hours in Minneapolis. ■ Centralizing the rest-room-exhaust airflow for the Minneapolis system significantly reduced the amount of “new” energy needed for supplemental heating. The reduction results from more hours of “free” heating provided by the energy-recovery device (Region 4) coupled with fewer hours that require supplemental heat (Region 5). Preconditioning outdoor air with recovered energy may yield even greater economic benefits in other climates where heating predominates. Table 17. Suggested control modes to precondition outdoor air in a VAV system Annual Hours of Operation 2 Psychrometric Conditions 1 Control Mode (see Figure 67, p. 78) 1 h oa h ra Full recovery, partial cooling 1,585 hr (61 %) 468 hr ( 18 %) 2 DBToa DBT sa H oa H ra No recovery, economizer, partial cooling 672 hr (26 %) 701 hr (27 %) 3 DBToa DBT sa Vot minimum setpoint No recovery, economizer only 281 hr ( 11 %) 410 hr ( 16 %) 4 Vot minimum setpoint DBT oa DBT critical Partial recovery only 62 hr [62 hr ( 2 %) ( 2 %)] 496 hr [853 hr ( 19 %) (32 %)] 5 DBT oa DBT critical Full recovery, supplemental heating 0 hr ( 0 %) 481 hr [124 hr ( 18 %) ( 5 %)] 6 DBT oa DBT frost threshold Full recovery, supplemental heating, frost prevention 0 hr ( 0 %) 44 hr (2 %) Jacksonville, Fla. Minneapolis, Minn. 1 DBT = dry-bulb temperature, h = enthalpy, oa = outdoor air, ra = return air, sa = supply air, Vot = total (system) outdoor airflow 2 Annual operation is based on 10,000 cfm (4.7 m³/s) of outdoor air and 7,000 cfm (3.3 m³/s) of system-level exhaust air. Values enclosed in brackets [ ] represent annual operation that is based on system-level exhaust air plus local exhaust air from rest rooms, for a total exhaust airflow of 9,500 cfm (4.5 m³/s). 92 SYS-APM003-EN Suggestions for Effective Airside Energy Recovery Central or Local OA Preconditioning? When the design of an HVAC system includes multiple air handlers, energy recovery for OA preconditioning can be implemented in one of two ways: ■ A single, large energy-recovery device can precondition all of the outdoor air before delivering it to the individual air handlers. Known as central OA preconditioning, this approach may reduce the first cost of the system. ■ By contrast, local OA preconditioning devotes an individual energy-recovery device to each air handler. If the energy-recovery device is packaged with supply- and exhaust-side fans, it is called an energy-recovery ventilator or ERV. Central OA preconditioning with multiple, dedicated OA systems. Figure 80 illustrates a central ERV, which preconditions the outdoor air stream using a total-energy wheel and then delivers that air to two or more dedicated OA units. Although this configuration reduces the number of wheels (not the energy-recovery capacity) for the installation, ducting the exhaust air from all of the air handlers back to a single ERV typically requires more ductwork. Control of a central OA-preconditioning ERV can be straightforward, but only if the dedicated OA units share the same operating schedule and deliver air at identical conditions (dew point, dry-bulb temperature). A more complex, less energy-efficient control sequence is needed to maintain proper building pressurization if the individual systems deliver air at different conditions: ■ The relief damper associated with each dedicated OA unit must modulate to appropriately regulate building pressure in the areas served by that unit. ■ The exhaust-side fan in the ERV must modulate to assure that none of the relief dampers reaches the wide-open position. Figure 80. Central OA preconditioning for two or more dedicated OA units SYS-APM003-EN 93 Suggestions for Effective Airside Energy Recovery Central OA preconditioning with multiple mixed-air systems. Figure 81 shows a central total-energy wheel that preconditions the outdoor air before delivering it to the OA inlet of each air handler. Unlike the example in Figure 80, however, each air handler now includes a path for recirculated return air (RRA), making it a mixed-air system. Additional ductwork is needed to carry the conditioned outdoor air from the energy-recovery ventilator to the air handlers. Of course, carrying the exhaust air from each of the air handlers back to the ERV typically requires more ductwork, too. Adding an airside economizer to each air handler further complicates the design and increases the first cost. As shown in Figure 82, each air handler requires an additional damper to modulate the economizer airflow. Installing the air handlers indoors will require another path and more ductwork to deliver the outdoor air needed for economizer cooling. The additional air paths, dampers, and complexity of maintaining proper building pressurization can pose a formidable challenge for the engineer charged with designing an HVAC system that combines central OA preconditioning and multiple mixed-air systems … especially when the air handlers include airside economizers. The system is easiest to control during extremely hot or cold weather: the wheel simply operates at full capacity. At other operating conditions, however, the air handlers may send conflicting control signals to the energy-recovery ventilator. For example, psychrometric conditions at one air handler may require partial recovery to heat the outdoor air while conditions at another air handler dictate economizer operation without recovery. Satisfying both demands will unavoidably sacrifice part of the potential energy savings. Figure 81. Central OA preconditioning for multiple mixed-air systems (without economizers) 94 SYS-APM003-EN Suggestions for Effective Airside Energy Recovery Figure 82. Central OA preconditioning for multiple mixed-air systems (with economizers) To help address the control challenges of central OA preconditioning for multiple mixed-air systems: ■ Use pressure-independent OA dampers at the air handlers to assure delivery of the proper quantity of outdoor air for ventilation. ■ Provide a means to modulate the ERV supply-side fan so that it only delivers the quantity of air required by the operating air handlers. ■ Control building pressurization directly. The relief damper at each air handler must modulate to control building pressurization in the areas served, and the ERV exhaust-side fan must modulate to assure that none of the relief dampers reaches the wide-open position. Note: Centralizing the rest-room exhaust at the ERV further complicates control of the exhaust-side fan. Minimizing Life-Cycle Cost Analyze the options. Economically, the main reason for preconditioning outdoor air with recovered energy is the opportunity to downsize cooling and heating equipment. If the first-cost savings do not entirely offset the initial investment in the energy-recovery device, operating cost savings may quickly make up the difference. Energy analysis software can make it easier to estimate the performance of various air-to-air energy-recovery technologies. Performing a whole-building analysis helps you predict the length of the payback period based on building SYS-APM003-EN 95 Suggestions for Effective Airside Energy Recovery location, type and operating schedule, as well as HVAC system type, system control, type of economizer, and local utility rates. Make sure that the analysis accounts not only for economizer operation, but also for the effects of the energy-recovery device —that is, the cooling and heating energy savings, as well as the extra fan energy needed to overcome the additional pressure drop. Only size for ventilation airflow. For mixed-air systems, size the energyrecovery device to condition only the minimum outdoor airflow required for ventilation, not full economizer airflow. This design strategy permits the selection of a smaller-capacity device, which lowers the first cost. To save fan energy, include bypass dampers or a separate path to direct airflow around the energy-recovery device during economizer operation. Strive for balanced airflows. Local exhausts, infiltration, and (potentially) cross-leakage create an imbalance between the incoming outdoor air stream and the system-level exhaust air stream. To maximize both energy recovery (which reduces operating costs) and potential downsizing of the heating and cooling plants, duct as much of the local exhaust airflow to the energy-recovery device as possible. Remember: The less disparity between the outdoor and exhaust airflows, the more energy that can be recovered. Figure 83 shows an example of a mixed-air VAV system that channels the rest-room exhaust back to a central point and mixes it with the system exhaust immediately upstream of the energy-recovery device. Because the entering air pressure on the exhaust side of the wheel changes, the system must somehow maintain constant exhaust airflow from the rest rooms to comply with building codes. A pressure-independent, flow-measuring damper — which operates in concert with the relief damper in the return air path — is the most effective way to monitor and control the total quantity of rest-room exhaust air. Figure 83. Mixed-air VAV system with centralized rest-room exhaust 96 SYS-APM003-EN Suggestions for Effective Airside Energy Recovery If the flow-measuring damper is wide open and the exhaust-side pressure is high enough that the required rest-room-exhaust airflow cannot be maintained, the relief damper modulates closed to lower the exhaust-side pressure. The exhaust fan then modulates (using a variable-speed drive, for example) to directly control the building pressure relative to outdoors. Note: Consider specifying a “minimum flow” alarm to notify the operator whenever the building pressure prevents the rest-room exhaust fans from providing the required airflow. Implement a carefully considered control strategy to lower operating costs and shorten the payback period. It is important to integrate control of the energy-recovery device with the control schemes for the unit and the system. Factory-installed controls with preprogrammed operating strategies can simplify engineering in the field and help to assure that the system delivers optimum performance. The previous section (“System-Level Control of Recovered Energy”) demonstrated the importance of devising a control strategy that accounts for the type of system, the type of recovered energy (total or sensible), and — in the case of mixed-air systems — the control and type of airside economizer. To avoid overheating the air, most systems will require a means to modulate energy-recovery capacity when the device operates in the heating mode. (See “Energy-Recovery Technologies,” pp. 38 – 64.) Unnecessarily operating the device at full capacity requires recooling and wastes energy. Common modulation methods include: ■ Mixing valves (coil loops) ■ Variable-speed drives (coil loops, rotary heat exchangers) ■ Bypass or face-and-bypass dampers (rotary heat exchangers, fixed-plate heat exchangers, heat pipes) ■ Tilt control (heat pipes) Capacity modulation of the energy-recovery device may also serve another function: frost prevention for OA preconditioning applications in cold climates. Note: For cold-climate applications, consider adding a preheat coil to ensure that the temperature of the entering outdoor (or exhaust) air remains above the frost threshold. Preheat permits the energy-recovery device to operate at full capacity during cold weather, maximizing the amount of recovered energy. SYS-APM003-EN 97 Suggestions for Effective Airside Energy Recovery SA Tempering To comply with ASHRAE Standard 90.1 –2007 (see pp. 2 – 4), an air-to-air energy-recovery device that is used for tempering supply air must be capable of providing at least 75 percent of the energy used to reheat the air. ■ “Energy” codes may actually require the use of energy recovery for supply-air (SA) tempering in specific applications — most notably in constant-volume, mixed-air systems that directly control space humidity. (See “Compliance with Codes,” p. 2.) Even where it is not mandated, however, tempering supply air with recovered energy often makes economic sense, especially for dedicated outdoor-air systems that deliver neutral-temperature air. Sensible- or Total-Energy Recovery? Supply-air tempering adds sensible heat to the air downstream of the cooling coil. Because the cooling coil also dehumidifies the passing air stream, an energy-recovery device that transfers moisture as well as sensible heat is undesirable. For this reason, sensible-energy recovery is usually the best choice for SA tempering applications. Series or Parallel Arrangement? As discussed on pp. 22 – 26 and pp. 28 – 32, sensible-energy recovery for supplyair tempering is accomplished using one of two arrangements: Figure 84. Energy-recovery arrangements for SA tempering in mixed-air systems ■ A series configuration, which relies on the air entering the cooling coil as a source for varying amounts of transferable heat ■ A parallel configuration, which can recover a relatively constant amount of heat from the return air stream. The best choice for a particular application depends, in part, on whether the HVAC system uses a mixed-air or a dedicated-outdoor-air design. Other important factors include first cost, savings in cooling and heating energy, and the additional fan energy needed to overcome the static pressure loss imposed by the energy-recovery device. Mixed-air systems. Both series and parallel configurations (Figure 84) reduce the heating energy required for tempering. Although the series configuration saves more cooling energy than the parallel configuration, neither arrangement permits downsizing of the cooling and heating plants. Outdoor conditions ultimately determine which arrangement provides the highest potential for energy savings. The series arrangement can transfer more heat if the outdoor air is warmer than the return air; but when the outdoor air is cooler than the return air, the parallel arrangement will recover more sensible energy. In many applications, cooler outdoor conditions require more tempering. 98 SYS-APM003-EN Suggestions for Effective Airside Energy Recovery Figure 85. Energy-recovery arrangements for tempering in dedicated OA systems Dedicated OA systems. Budgetary constraints often simplify the choice between series and parallel energy-recovery arrangements in dedicated OA systems that deliver neutral-temperature air. Most of these applications use the series arrangement because it avoids the expense of routing the building exhaust to a central location (Figure 85). Beyond that consideration, however, the series arrangement: ■ Is only available during cooling modes of operation ■ Transfers more heat (and saves more new “reheat” energy) than the parallel arrangement whenever the outdoor air is warmer than the exhaust air. ■ Saves cooling energy and may even reduce the required capacity of the cooling plant By comparison, the parallel arrangement: ■ Is available during cooling and heating modes of operation ■ Transfers more heat (and saves more new “reheat” energy) than the series arrangement whenever the outdoor air is cooler than the exhaust air ■ May recover enough heat from the exhaust air stream to permit downsizing of the heating plant Note: Adding a second energy-recovery device to precondition the outdoor air lessens the first-cost penalty of the parallel arrangement. (See pp. 84 – 88 for an example of a “dual-function” energy-recovery system.) Which technologies offer the best value? Trane engineers analyzed the performance of three types of sensible-energy-recovery devices — heat pipes, fixed-plate heat exchangers, and coil loops — to determine their practicality for tempering supply air. (Sensible-energy wheels were omitted from the study because the high first cost often precludes their use.) The analysis compared the first costs (normalized) of providing a defined rate of heat transfer at various airflows. Figure 86 (p. 100) summarizes the results of that study. Of the devices studied, fixed-plate heat exchangers and coil loops offer the best value for supply-air tempering. At less than 12,000 cfm (5.6 m³/s), fixed-plate heat exchangers provide the specified performance at the lowest first cost; at higher airflows, coil loops prevail. Although heat pipes perform across a broader range of airflows, their first cost is considerably higher than the other devices in the study. Initial investment, though important, is only one consideration when choosing between sensible-energy-recovery technologies. Other factors include space limitations, maintenance requirements, and (for parallel arrangements) the location and condition of the exhaust air stream. For example, a coil loop becomes the best energy-recovery option when cross-leakage is unacceptable, despite its higher first cost at low volumes of airflow. SYS-APM003-EN 99 Suggestions for Effective Airside Energy Recovery Figure 86. Comparison of airside energy-recovery technologies for SA tempering Minimizing Life-Cycle Cost Analyze the options. The economic justification for tempering supply air with recovered energy typically lies in saving as much reheat energy as possible and minimizing the negative effect on fan energy consumption. When applied in a dedicated OA system and depending on the arrangement (series or parallel), sensible-energy recovery may also reduce the required capacity of the cooling or heating plant. If so, the first cost savings from equipment downsizing can help offset the initial investment in energy recovery. Energy analysis software makes it easier to estimate and compare the cooling and heating energy savings provided by various air-to-air energy-recovery technologies. Performing a whole-building analysis will help you predict the length of the payback period based on building location, building type and operating schedule, HVAC system type, system control, and local utility rates. Make sure that the analysis accounts not only for the humidity levels inside the building during various operating modes, but also for the extra fan energy needed to overcome the pressure drop of the energy-recovery device. Implement a carefully considered control strategy. Proper control of the sensible-energy-recovery device is essential to realize the anticipated energy savings. Optimum performance depends on integrating the control schemes of the energy-recovery device and air handlers with the rest of the HVAC system. Factory-installed controls with preprogrammed operating strategies can simplify engineering in the field and help to assure that the system delivers optimum performance. “Dedicated OA System for Neutral-Temperature Air” (pp. 80 – 83) demonstrated the importance of devising an operating strategy that accounts for the type of 100 SYS-APM003-EN Suggestions for Effective Airside Energy Recovery ventilation system (mixed-air or dedicated outdoor air) and the arrangement of the energy-recovery device (series or parallel). For most systems, the control scheme must also modulate energy-recovery capacity in some way to avoid overheating the supply air. Common methods of modulation include: ■ Mixing valves (coil loops) ■ Variable-speed drives (coil loops, rotary heat exchangers) ■ Bypass or face-and-bypass dampers (rotary heat exchangers, fixed-plate heat exchangers, heat pipes) ■ Tilt control (heat pipes) Review “Energy-Recovery Technologies,” pp. 38 –64, for more information. ■ SYS-APM003-EN 101 Glossary active-desiccant wheel. Rotary device that removes moisture from the passing air stream with a desiccant-coated media and releases it to an adjacent air stream. It is typically regenerated at high temperatures from an external heat source. Also called dehumidification wheel. air handler (AHU). A piece of equipment that moves and/or conditions air for maintaining space comfort. air-to-air energy recovery. The transfer of sensible heat, or sensible plus latent heat, between two or more air streams, or between two locations within the same air stream. ANSI. American National Standards Institute (www.ansi.org) ANSI/ASHRAE Standard 62.1. Titled Ventilation for Acceptable Indoor Air Quality, this standard specifies minimum ventilation rates to minimize the potential for adverse health effects of buildings. ANSI/ASHRAE/IESNA Standard 90.1. Titled Energy Standard for Buildings Except Low-Rise Residential Buildings, this standard sets minimum design requirements that encourage energy efficiency throughout the building — that is, for the envelope, lighting, motors, HVAC, and service-water heating systems. ARI Standard 1060. Titled Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment, this standard defines the requirements for testing, rating, and marking factory-made energy-recovery devices, including rotary heat exchangers, heat pipes, and fixed-plate heat exchangers. ASHRAE. American Society of Heating, Refrigerating, and Air-Conditioning Engineers (www.ashrae.org) coil loop. An energy-recovery device consisting of two or more finned-tube coils that are piped together in a closed loop to transfer sensible heat. A small pump circulates the working fluid through the two coils. Also called coil runaround loop or runaround loop. conditioned outdoor air (CA). Outdoor air that has been heated, cooled, humidified, or dehumidified by a dedicated outdoor-air unit before being delivered directly to the conditioned space or to the mixing boxes of other local units. Also called conditioned air. constant-volume system. Type of air-conditioning system that varies the temperature of a constant volume of air supplied to meet the changing load conditions of the space. critical temperature. Psychrometric condition at which an energy-recovery device, operating at full heating capacity, can no longer maintain the target supply-air dry-bulb temperature. It is defined by the dry-bulb temperatures of 102 SYS-APM003-EN Glossary the supply air and return air, and the effectiveness of the energy-recovery device at full capacity: · m s T critical – T 2 sensible = -------------------------------------------------· m e T critical – T 3 where, sensible = sensible effectiveness m· s = mass flow rate, in lb /hr (kg/s), through the supply side of the heat-exchange device m· e = mass flow rate, in lb/hr (kg/s), through the exhaust side of the Tcritical = critical entering supply-air temperature, in °F (°C) T2 = target leaving supply-air dry bulb, in °F (°C) T3 = entering exhaust-air dry bulb, in °F (°C) heat-exchange device dedicated outdoor-air unit. An air handler used to cool, heat, dehumidify, or humidify all of the outdoor air brought into the building for ventilation. This conditioned outdoor air may be delivered directly to the conditioned spaces or to other air handlers or terminal equipment. Also called makeup-air unit or 100% outdoor-air unit. desiccant. An absorbent or adsorbent substance, liquid or solid, that removes water or water vapor from a material. Activated alumina and silica gel are two desiccants that are commonly used as drying agents in refrigerating systems. economizer air. Outdoor air brought into the building to offset the cooling load in the space. effectiveness. A measure used to quantify the performance of an air-to-air heat exchanger. Defined as the ratio of the amount of energy (sensible, latent, or total) that a device actually transfers divided by the maximum energy transfer possible between the two air streams. Also called effectiveness ratio. energy-recovery unit. An air handler or rooftop air conditioner that includes an integral (built-in) energy-recovery device for outdoor-air preconditioning. It also includes a cooling coil within the same unit casing. energy-recovery ventilator. An air handler that consists of an energyrecovery device for outdoor-air preconditioning, a supply fan, and an exhaust fan; it does not include a cooling coil. These units are typically used to precondition outdoor air before delivering it to other air handlers or rooftop air conditioners. exhaust air (EA). Air removed from the conditioned space and expelled from the building by mechanical ventilation. SYS-APM003-EN 103 Glossary exhaust-air transfer ratio (EATR). A measurement, defined by ARI Standard 1060, used to quantify cross-leakage of air from the exhaust air stream to the supply air stream. Expressed as a percentage of supply airflow. fixed-membrane heat exchanger. An energy-recovery device that consists of multiple, paper-like membranes arranged in a cross-flow configuration to transfer both sensible (temperature) and latent (moisture) heat. fixed-plate heat exchanger. An energy-recovery device that consists of multiple, thermally conductive plates arranged in a cross-flow configuration to transfer sensible heat. frost threshold. Temperature at which frost begins to form on the exhaust side of an air-to-air energy-recovery device. heat pipe. An energy-recovery device consisting of refrigerant-filled, finned tubes that transfer sensible heat between the two ends of the tubes. latent-design condition. Design dew-point and mean coincident dry-bulb temperatures, as tabulated in the ASHRAE Handbook–Fundamentals. neutral air. Air that is delivered to the conditioned space at a dry-bulb temperature and humidity ratio that does not impose a heating or cooling load in the space. outdoor air (OA). Air brought into the building — either by a ventilation system or through openings provided for natural ventilation — from outside the building. (Also called outside air or fresh air, but outdoor air is preferred. outdoor air correction factor (OACF). A measurement, defined by ARI Standard 1060, used to quantify cross-leakage of air from the supply air stream to the exhaust air stream. Expressed as the supply-side airflow upstream of the device divided by the supply-side airflow downstream of the device. outdoor-air preconditioning. The process of using an air-to-air energyrecovery device to cool, dehumidify, heat, or humidify outdoor air by transferring energy (either sensible or sensible plus latent) to and from another air stream. parallel energy recovery. A configuration that transfers heat between one air stream and a second, separate air stream. recirculated return air (RRA). Air removed from the conditioned space(s) and reused as supply air — usually after passing through an air-cleaning and -conditioning system — for delivery to the conditioned space. See also return air (RA). 104 SYS-APM003-EN Glossary return air (RA). Air removed from the conditioned space(s) and either recirculated or exhausted. See also recirculated return air (RRA) and exhaust air (EA). rotary heat exchanger. An energy-recovery device that consists of a revolving cylinder that rotates between two air streams. Air streams pass through a matrix of channels that direct air through the device in a counterflow arrangement. Rotary heat exchangers can transfer either sensible energy or sensible plus latent energy. Also called wheel. sensible-design condition. Design dry-bulb and mean coincident wet-bulb temperatures, as tabulated in the ASHRAE Handbook – Fundamentals. sensible-energy recovery. The transfer of sensible heat between two or more air streams or between two locations within the same air stream. series energy transfer. A configuration that transfers heat from one location in an air stream to a second location within the same air stream. This configuration, used only in supply-air tempering applications, reduces the need for tempering (reheating) with new energy. sensible-energy wheel. Rotary heat exchanger that transfers sensible heat from one air stream and another. Also called heat wheel. supply air (SA). Air delivered to the conditioned space by mechanical means for ventilation, heating, cooling, humidification, or dehumidification. supply-air tempering. The process of adding sensible heat to the air downstream of the cooling coil to allow independent control of latent and sensible loads in the space. Only systems that directly control supply-air dew point or space humidity are candidates for supply-air tempering. total-energy recovery. The transfer of sensible and latent (moisture) heat between two or more air streams or between two locations within the same air stream. total-energy wheel. A desiccant-coated, rotary heat exchanger that transfers sensible (temperature) and latent (moisture) heat between two air streams. The desiccant typically regenerates at room temperatures. Also called enthalpy wheel or passive desiccant wheel. variable-air-volume (VAV) system. Type of air-conditioning system that varies the volume of constant-temperature air, which is supplied to meet the changing load conditions in the space. ■ SYS-APM003-EN 105 References Air-Conditioning and Refrigeration Institute (ARI). 2005. Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Equipment, ARI Standard 1060 – 2005. Arlington, VA: ARI. American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc. (ASHRAE). 1991. Method of Testing Air-to-Air Heat Exchangers, ASHRAE Standard 84–1991. Atlanta, GA: ASHRAE. . 2004. Air-to-Air Energy Recovery. In Chapter 44, Systems and Equipment. ASHRAE Handbook series. . 2007. Ventilation for Acceptable Indoor Air Quality, ASHRAE Standard 62.1–2007. ASHRAE and Illuminating Engineering Society of North America (IESNA). 2007. Energy Standard for Buildings Except Low-Rise Residential Buildings, BSR/ ASHRAE/IESNA Standard 90.1–2007. Atlanta, GA: ASHRAE. Murphy, J. 2006. "Smart Dedicated Outdoor Air Systems," ASHRAE Journal (July): pp. 30-37. To obtain copies of Trane publications, including videocassettes, contact your local Trane office. Some publications are are also available from the Trane’s online bookstore at www.trane.com/ bookstore. ■ Trane. 2003. Designing Dedicated Outdoor-Air Systems, SYS-APG001-EN. La Crosse, WI: Inland Printing Company. . 1999. Air-to-Air (Fixed-Plate Type) Heat Exchanger Module, CLCH-EB-43 (March). . 1999. Psychrometry, TRG-TRC001-EN. Air Conditioning Clinic series. . 2000. “Air-to-Air Energy Recovery,” Engineers Newsletter Live satellite broadcast, APP-APV006-EN (October 27, videocassette). La Crosse, WI: AVS Group. . 2001. Energy Wheel Overview for Modular and T-Series Climate Changer ™ Air Handlers, CLCH-PRB0012-EN. . 2000. Recirculation Energy Recovery Unit Controls, CLCH-PRB009-EN. . 2001. “Dedicated Outdoor-Air Ventilation Systems,” Engineers Newsletter Trane publishes the Engineers Newsletter several times annually. Back issues, including the newsletters listed here, are available from the Trane Web site at www.trane.com/ engineersnewsletter. ■ 106 Live satellite broadcast, APP-APV008-EN (September 19, videocassette). La Crosse, WI: AVS Group. : Stanke, D. and Bradley, B. 2000. “Dehumidify with Constant-Volume Systems.” Trane Engineers Newsletter, volume 29, number 4. SYS-APM003-EN References : Stanke, D. and Bradley, B. 2001. “Design Tips for Effective, Efficient Dedicated Ventilation Systems.” Trane Engineers Newsletter, volume 30, number 3. : Stanke, D., Murphy, J., and Bradley, B. 2000. “Air-to-Air Energy Recovery.” Trane Engineers Newsletter, volume 29, number 5. United States Environmental Protection Agency (EPA). Indoor Environments Division, Office of Air and Radiation. 2000. Energy Cost and IAQ Performance of Ventilation Systems and Controls, EPA-402-S-01-001 (January). www.epa.gov/ iaq/largebldgs Wright, W. 1984. “Control of Coil Loop Heat Recovery Systems”, HPAC Engineering (August): pp. 69–71. ■ SYS-APM003-EN 107 Index a active-desiccant wheels 88 – 89 adjacent air streams 13 – 14, 32, 33 air blenders 57 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) 60 air-handler casing potential path for cross-leakage 50 airside pressure drop bypass dampers to reduce 35 coil loops 38 – 40 effect of outdoor-air preconditioning with recovered energy 16 effect of supply-air tempering with recovered energy 35 fixed-plate heat exchangers 44, 45 heat pipes 47 – 48 rotary heat exchangers 52 – 53 summary of typical performance for energy-recovery devices 64 ANSI/ASHRAE Standard 62.1 2 acceptable cross-leakage 20 requirements for outdoor-air intakes 19 – 20 ANSI/ASHRAE Standard 84 7 ANSI/ASHRAE/IESNA Standard 90.1 discussion about 2 – 3 economizer operation 17 excerpts from 3, 4 implications for reheat 68 reheat limitations for supply-air tempering 21, 67, 80 sizing components for heating and tempering 80, 82 ARI (see Air-Conditioning, Heating, and Refrigeration Institute) ARI Standard 1060 6, 60 – 63, 64 ARI Standard 410 6, 60 ASHRAE Standard 62.1 (see ANSI/ASHRAE Standard 62.1) ASHRAE Standard 90.1 (see ANSI/ASHRAE/IESNA Standard 90.1) auxiliary heat (see supplemental heat and reheat) b balanced airflows 7 – 8 benefits 96 – 97 building exhaust proximity to outdoor-air intake 19 – 20 building pressure 97 direct control 95 bypass dampers capacity control 53 – 55 economizer operation 3, 16 – 17, 41, 96 exhaust-air bypass for linear unloading 54 fan energy consumption 35, 41 outdoor-air bypass for frost prevention 56 – 57 c capacity control 64, 97 coil loops 40 – 41 fixed-plate heat exchangers 108 44 – 45 SYS-APM003-EN Index for frost prevention 19, 50, 56 – 57, 97 heat pipes 49 – 50 outdoor-air preconditioning with recovered energy 17 – 18 rotary heat exchangers 53 – 55 supply-air tempering with recovered energy 35 – 36 central outdoor-air preconditioning for multiple dedicated outdoor-air systems 93 for multiple mixed-air systems 94 – 95 certified performance 60 – 63 coil loops 38 – 43, 64 three-coil 32, 42 – 43 coincident heating and cooling 3 cold conditioned air defined 65 sensible-energy recovery for outdoor-air preconditioning 73 total-energy recovery for outdoor-air preconditioning 72 compressor short-cycling 14 constant-volume mixed-air systems 66 outdoor-air preconditioning 74 – 76 supply-air tempering 82 – 83 control sequences dual-function energy recovery 86 – 87 outdoor-air preconditioning with constant-volume mixed-air systems 75, 76 outdoor-air preconditioning with dedicated outdoor-air systems 69, 70, 72, 73 outdoor-air preconditioning with variable-air-volume systems 78, 79 supply-air tempering 81, 83 control strategies integration 67, 97, 100 cooling coil humidity control 21, 26 cooling-plant capacity effect of balanced airflows 8 effect of outdoor-air preconditioning 14 – 15 effect of supply-air tempering with parallel energy recovery 25, 30 effect of supply-air tempering with series energy recovery 24, 29 supply-air tempering with dedicated outdoor-air systems 32 – 33 critical temperature defined 102 – 103 cross-leakage 20, 37 air-handler casing 42, 46, 50 coil loops 42 effect of fan configuration 58 exhaust air transfer ratio 62 fixed-plate heat exchangers 46 heat pipes 50 – 51 likelihood of (table) 64 purge 59 rest-room exhaust 57 rotary heat exchangers 57 – 59 using EATR to calculate 62 – 63 see also exhaust air transfer ratio SYS-APM003-EN 109 Index d dampers summary of uses for energy recovery 64 see also face-and-bypass, flow-measuring, and frost-avoidance dampers dedicated outdoor-air systems capacity control for supply-air tempering 35 – 36 defined 65 – 66 dual-function energy recovery 84 – 88 outdoor-air preconditioning for cold air 71 – 73 outdoor-air preconditioning for neutral air 68 – 70 series versus parallel arrangements for supply-air tempering 28 – 32, 99 supply-air tempering for neutral-temperature air 26 – 32, 80 – 81, 99 tempering supply air with new energy 68 dehumidification ANSI/ASHRAE/IESNA Standard 90.1 4 in constant-volume mixed-air systems 21 – 22 in dedicated outdoor-air systems 26 with active-desiccant wheels 88 – 89 desiccant 52 see also rotary heat exchangers and active-desiccant wheels direct-expansion refrigeration systems 3, 14 DOE-2 energy analysis software 16 see also energy simulation software dual-function energy recovery benefits 85 – 86 control sequence 86 – 87 e EATR (see exhaust air transfer ratio) economic justification for energy recovery outdoor-air preconditioning 13 – 18, 95 – 97 supply-air tempering 32 – 36, 100 – 101 economizers and coil loops 41 ANSI/ASHRAE/IESNA Standard 90.1 3 coordination with energy recovery 16 – 17, 75 – 76, 78 – 79 effect on sizing energy-recovery devices 16, 41, 54, 77 implications for central outdoor-air preconditioning 94 – 95 effectiveness ASHRAE 90.1 minimum requirement for exhaust-air energy recovery coil loops 38 – 40 defined 7 equation 6 fixed-plate heat exchangers 43 – 44 heat pipes 47 – 49 implications of unbalanced airflows 7 – 8 rotary heat exchangers 52 summary of typical performance for energy-recovery devices 64 see also sensible effectiveness and total effectiveness 110 3, 4 SYS-APM003-EN Index energy-recovery arrangements 63 series versus parallel 98 – 99 energy-recovery technologies performance comparison 90 – 91, 99 – 100 summary of characteristics (table) 64 summary of common (table) 38 energy-recovery ventilator 93 energy simulation software 16, 33 exfiltration 8 exhaust air transfer ratio 61 – 63 exhaust airflow adjacent ductwork for energy recovery 13 – 14, 32, 33 local 8 exhaust-air energy recovery ANSI/ASHRAE/IESNA Standard 90.1 requirements 4 f face velocity versus sensible effectiveness 39, 44, 48 versus total effectiveness 52 face-and-bypass dampers 44, 45, 50, 64 fan motors effect of outdoor-air preconditioning on sizing 14 effect of supply-air tempering on sizing 33 fans arrangements 58, 63 energy consumption 16, 35, 62 sizing calculations 63 first cost (see initial cost of owning) fixed-membrane heat exchangers 43 fixed-plate heat exchangers 43 – 47, 64 flow-measuring dampers 62, 77, 95, 96 – 97 frost prevention 97 coil loops 41 – 42 fixed-plate heat exchangers 45 – 46 for parallel energy recovery in cold climates 31 heat pipes 50 outdoor-air preconditioning applications 18 – 19 rotary heat exchangers 55 – 57 supply-air tempering applications 37 techniques 64 wheel speed control 56 frost threshold 18 – 19, 46, 55 frost-avoidance dampers 46 SYS-APM003-EN 111 Index h heat pipes 47 – 51, 64 heat wheels (see rotary heat exchangers, sensible-energy wheels, and total-energy wheels heating-plant capacity effect of balanced airflows 8 effect of supply-air tempering with parallel energy recovery 30 – 31 supply-air tempering with dedicated outdoor-air systems 32 – 33 humidification with total-energy recovery 13, 91 i IAQ (see indoor air quality) indoor air quality 2 initial cost of owning effect of outdoor-air preconditioning with recovered energy supply-air tempering with recovered energy 32 – 33 13 – 15 l latent heat of condensation 5, 11, 19, 28 local exhaust 8, 96 – 97 local outdoor-air preconditioning 93 m microbial growth 14 mixed-air ventilation systems 66 series versus parallel arrangements for supply-air tempering supply-air tempering using recovered heat 21 – 26 mixing valves 40 – 41, 41 – 42, 64 25 – 26, 98 n neutral conditioned air 65 dedicated outdoor-air systems 32, 65 – 66, 68, 80, 84 – 88 sensible-energy recovery for outdoor-air preconditioning 70 sensible-energy recovery for supply-air tempering 81, 87 total-energy recovery for outdoor-air preconditioning 69, 87 o OACF (see outdoor air correction factor) operating costs outdoor-air preconditioning with recovered energy 16 – 19 supply-air tempering with recovered energy 33 – 37 see also economic justification outdoor air correction factor 61 – 63 112 SYS-APM003-EN Index outdoor-air intake cross-leakage from building exhaust 42, 46, 51, 59 proximity to building exhaust 19 – 20 outdoor-air preconditioning fixed-plate heat-exchanger applications 44 outdoor-air preconditioning with recovered energy ARI Standard 1060 60 ASHRAE Standard 90.1 requirements 2 – 4 capacity control to avoid overheating supply air 17 – 18 coil-loop applications 40 constant-volume mixed-air systems 74 – 76 dedicated outdoor-air systems 68 – 70, 71 – 73 defined 9 economic justification for energy recovery 13 – 18, 95 – 96 effect on initial cost of owning 13 – 15 effect on operating costs 16 – 19 energy-recovery arrangements 9 fan sizing 14, 63 fixed-plate heat-exchanger applications 44 heat-pipe applications 48 local versus centralized 93 – 95 rotary heat-exchanger (wheel) applications 52 sizing energy-recovery devices 96 variable-air-volume systems 77 – 79 p parallel arrangement benefits for supply-air tempering 24 – 26, 29 – 32, 98 – 99 effect on cooling-plant capacity 25, 30 effect on heating-plant capacity 30 – 31 implications for dual-function energy recovery 86 performance example for supply-air tempering 24 – 25, 29 – 31 payback effect of balanced airflows 8 predicting 95 – 96 performance comparison balanced versus unbalanced airflows 7 – 8 coil loops 38 – 40 energy-recovery technologies 90 – 91, 99 – 100 fixed-plate heat exchangers 43 – 44 heat pipes 47 – 49 rotary heat exchangers 52 – 53 performance examples outdoor-air preconditioning with sensible-energy recovery 10 – 11 outdoor-air preconditioning with total-energy recovery 12 – 13 supply-air tempering with parallel energy recovery 24 – 25, 29 – 31 supply-air tempering with series energy recovery 22 – 24, 28 – 29 performance ratings 60 – 63 plate heat exchangers (see fixed-plate heat exchangers) SYS-APM003-EN 113 Index preheat 19, 56, 64 see also frost prevention and auxiliary heat purge section in rotary heat exchangers 59, 62 r regeneration air 89 see also active-desiccant wheels reheat 5 implications of ANSI/ASHRAE/IESNA Standard 90.1 for supply-air tempering outdoor-air preconditioning with dedicated outdoor-air systems 68 supply-air tempering with constant-volume mixed-air systems 82 supply-air tempering with dedicated outdoor-air systems 80 rest-room exhaust centralized 14 – 15, 92, 95, 96 – 97 cross leakage 57 recirculation 20 rotary heat exchangers 51 – 59, 64 see also sensible-energy wheels and total-energy wheels 21, 80 s saturation curve 19, 55 sensible effectiveness 6 coil loops 38 – 40 equation 6 fixed-plate heat exchangers 44 heat pipes 47 – 48 sensible-energy wheels 52 sensible-energy recovery 5 constant-volume mixed-air systems 76 dedicated outdoor-air systems 70, 73 outdoor-air preconditioning 10 – 11, 90 – 91 supply-air tempering 67, 88 variable-air-volume systems 79 sensible-energy wheels 51, 52, 64 recooling in an active-desiccant system 88 – 89 see also rotary heat exchangers sensible-energy-recovery devices performance comparison 90 – 91, 99 – 100 sensible-heat transfer calculating 6 series arrangement benefits for supply-air tempering 25 – 26, 31 – 32, 99 effect on cooling-plant capacity 24, 29 performance example for supply-air tempering 22 – 24, 28 – 29 supply-air tempering 40, 49 simultaneous heating and cooling 3 114 SYS-APM003-EN Index sizing energy-recovery devices 41, 54, 77, 96 speed control 53 – 55, 64 and frost prevention 56 Standard 62.1 (see ANSI/ASHRAE Standard 62.1) Standard 90.1 (see ANSI/ASHRAE/IESNA Standard 90.1) supplemental heat 34 – 35 supply-air tempering with recovered energy capacity-control considerations 35 – 36 coil-loop applications 40 common applications 20 constant-volume mixed-air systems 21 – 26, 82 – 83 dedicated outdoor-air systems 26 – 32, 80 – 81 defined 5 economic justification for energy recovery 100 – 101 effect on initial cost of owning 32 – 33 effect on operating costs 33 – 37 frost prevention 37 heat-pipe applications 49 sensible- versus total-energy recovery 98 series versus parallel energy recovery 25 – 26, 31 – 32, 98 – 100 System Analyzer energy analysis software 16 see also energy simulation software t tilt control 49, 50, 64 total effectiveness 6 equation 6 total-energy recovery 5 constant-volume mixed-air systems 75 dedicated outdoor-air systems 69, 72 example performance for outdoor-air preconditioning humidification 13 variable-air-volume systems 78 see also total-energy-recovery devices total-energy wheels 51 – 52, 64 see also rotary heat exchangers total-energy-recovery devices in dry climates 90 in predominantly heating climates 91 – 92 outdoor-air preconditioning 9 performance comparison 90 – 91 see also total-energy recovery total-heat transfer calculating 6 TRACE energy analysis software 16 see also energy simulation software turbulators 40 12 – 13 u U.S. Environmental Protection Agency unbalanced airflows 7 – 8, 96 – 97 SYS-APM003-EN 2 115 Index v variable-air-volume systems 66 outdoor-air preconditioning 77 – 79 variable-speed drives capacity control 40 – 41, 53 – 55 frost prevention 41 – 42, 56, 64 ventilation systems 65 – 67 116 SYS-APM003-EN Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices. Trane, the Circle Logo, Let’s Go Beyond, TRACE, System Analyzer, and Traq are trademarks of Trane in the United States and other countries. ASHRAE is a trademark of the American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. ANSI is a trademark of American National Standards Institute, Inc. All trademarks referenced are the trademarks of their respective owners. © 2020 Trane All Rights Reserved SYS-APM003D-EN 09 Sept 2020 Supersedes SYS-APM003C-EN 11 March 2011 trane.com
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )