Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SINGAPORE STANDARD SS 332 : 2007 (ICS 13.220.50; 91.060.50) SPECIFICATION FOR Fire doors (Incorporating Amendment No. 1, August 2009) Published by SPRING Singapore 2 Bukit Merah Central Singapore 159835 SPRING Singapore Website: www.spring.gov.sg Standards Website: www.standards.org.sg Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SINGAPORE STANDARD SS 332 : 2007 (ICS 13.220.50; 91.060.50) SPECIFICATION FOR Fire doors (Incorporating Amendment No. 1, August 2009) All rights reserved. Unless otherwise specified, no part of this Singapore Standard may be reproduced or utilised in any form or by any means, electronic or mechanical, including photocopying and microfilming, without permission in writing from SPRING Singapore at the address below: Head Standardisation Department SPRING Singapore 2 Bukit Merah Central Singapore 159835 Telephone: 62786666 Telefax: 62786667 Email: stn@spring.gov.sg ISBN 981-4154-58-X Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 This Singapore Standard was approved by the Building and Construction Standards Committee on behalf of the Standards Council of Singapore on 12 September 2007. First published, 1988 First revision, 2000 Second revision, 2007. The Building and Construction Standards Committee appointed by the Standards Council consists of the following members: Name Capacity : Mr Goh Peng Thong Standards Council : Er. Lee Chuan Seng Standards Council 2 Deputy Chairman : Mr Tan Tian Chong Standards Council Secretary : Mr Kenneth Lim See Khoon SPRING Singapore Members : Mr Boo Geok Kwang Singapore Civil Defence Force / Fire Safety and Shelter Department Er. Chan Ewe Jin Institution of Engineers, Singapore Mr Chan Yew Kwong Ministry of Manpower Mr Paul Fok Land Transport Authority Mr Goh Ngan Hong Singapore Institute of Surveyors and Valuers Mr Anselm Gonsalves National Environment Agency Mr Desmond Hill Singapore Contractors Association Limited Mr Joseph Lai Kuong Kiu JTC Corporation Mr Benedict Lee Khee Chong Singapore Institute of Architects Assoc Prof Leong Eng Choon Nanyang Technological University Ms Andris Leong Sou Kwan Building and Construction Authority Dr Lim Lan-Yuan Association of Property and Facility Managers Mr McDonald Low Real Estate Developers' Association of Singapore Mr Larry Ng Lye Hock Urban Redevelopment Authority Assoc Prof Gary Ong Khim Chye National University of Singapore Mr Davis Ong Wee Choon Singapore Manufacturers' Federation Er. Shum Chee Hoong Housing & Development Board Dr Tam Chat Tim Individual Capacity Dr Tan Guan Association of Consulting Engineers, Singapore Chairman st 1 Deputy Chairman nd 2 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 The Technical Committee on Architectural Works appointed by the Building and Construction Standards Committee and responsible for the preparation of this standard consists of representatives from the following organisations: Name Capacity Chairman : Mr Larry Ng Lye Hock Member, Building and Construction Standards Committee Deputy Chairman : Mr. Benedict Lee Khee Chong Member, Building and Construction Standards Committee Secretary : Mr Han Kin Sew SPRING Singapore Members : Mr Choy Kin Man TUV SUD PSB Pte Ltd Mr Gan Geok Chua Singapore Glass Association Mr Koh Boon Pock Singapore Timber Association Mr Lau Kwong Chung Singapore Institute of Architects Major Lim Lam Kwang Singapore Civil Defence Force Mr Low Leong Leong Singapore Contractors Association Limited Mr Mok Kwong Wah CPG Corporation Pte Ltd Mr Jeffery Neng Kwei Sung Building and Construction Authority Mr Felix Quek Kwang Yong Tile Association Mr See Sing Kok Institution of Engineers Singapore Mr See Sing Mun Singapore Manufacturers’ Federation Mr Tang Chee Seng Housing & Development Board Assoc Prof Tse Swee Ling National University of Singapore Mr Wong Chung Wan Setsco Services Pte Ltd Mr Goh Chun Hee Individual Capacity Co-opted Member : The Working Group appointed by the Technical Committee to assist in the preparation of this standard comprises the following experts who contribute in their individual capacity: Name Convenor : Mr See Sing Mun Members : Mr Cheong Soon Huat Mr Joseph Chng Mr Lee Kim Hock Mr Vincent Leong Kuan Yu Mr Song Yew Kee Mr Thomas Tng Mr Victor Yau 3 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 The organisations in which the experts of the Working Group are involved are: ASSA ABLOY Singapore Pte Ltd DP Architects Pte Ltd Glutz Singapore Pte Ltd Kaba Security Pte Ltd Land Transport Authority Security System Association of Singapore Singapore Civil Defence Force Singapore Institute of Architects Singapore Manufacturers’ Federation Singco (Pte) Ltd TUV SUD PSB Pte Ltd 4 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Contents Page Foreword 8 CLAUSES 1 General 9 2 Definitions 9 3 Design requirements 11 4 Determination of fire-resistance rating 17 5 Hardware requirements and test methods 18 6 Variation from prototype 19 7 Installation 23 8 Marking 25 9 Responsibility of manufacturer/owner of building (or representative) 28 10 Maintenance information system 30 ANNEXES A Fire doors and their hardware 35 B Identification tags 40 C Methods for fixing of fire door frames to existing walls 41 D Calculation for the forces of closing sliding doors 47 E Fire-resistance tests 48 F Door closer requirements and test methods 58 G Corrosion resistance 70 H An example of log book details 73 I Example of fire door certificate and schedule of evidence of compliance 74 J Example of the schedule of evidence of compliance 75 K Door coordinator devices: Requirements and test methods – EN 1158 76 L Door bolts: Requirements and test methods – EN 12051 78 M Building hardware – Lever handles and knob furniture: Requirements and test methods – EN 1906 80 N Mechanical locks and latches: Requirements and test methods – EN 12209 82 O Emergency exit devices: Requirements and test methods – EN 179 84 P Panic exit devices: Requirements and test methods – EN 1125 88 Q Single axis hinges: Requirements and test methods – EN 1935 94 R Electrically powered hold-open devices for swing doors: Requirements and test methods – EN 1155 96 S Cylinders for locks: Requirements and test methods – EN 1303 99 T Sliding door hardware: Requirements and test methods – EN 1527 101 U Bibliography 102 5 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Page TABLES 1 Lists of standards for hardware use on fire door 18 2 Limitation to size variations 19 3 Temperature rises as a function of time 54 4 Requirements for closing and opening moments, and the door closer efficiency 59 5 Overload test weight and test door friction 62 FIGURES 1 Clearance between door leaf and frame or finished floor 13 2 Form of directional arrow for sliding fire doors 17 3 Fire door frames fixed during wall construction 26 4 Terms relating to side-hung fire doors 32 5 Terms relating to locksets in side-hung fire doors 33 6 Terms relating to sliding fire doors 34 7 An example on the fixing of frames by hairpin anchors 43 8 An example on the fixing of frames by threaded anchors 44 9 An example on the fixing of frames by weld anchors for single-leaf door 45 10 An example on the fixing of frames by weld anchors for double-leaf door 46 11 Standard time-temperature curve 55 12 Furnace thermocouple assembly 56 13 Specimen surface thermocouple junction and insulating pad 57 14 Typical general arrangement of overload test apparatus 68 15 Plan view on arrangement of overload test apparatus 68 16 Flow chart of test procedure 69 17 Illustration of a swing arm door coordinator 77 18 Illustration of a single point bolt 79 19 Illustrations of lever handles and knob furniture 81 20 Illustrations of mechanical locks and latches 83 21 Illustration of a type A emergency exit device 84 22 Illustration of a type B emergency exit device 85 23 Illustrations of emergency exit devices 87 24 A panic situation 88 25 Type A panic exit device 89 26 Type B panic exit device 89 27 Types A and B panic exit devices 89 28 Overall projection of panic exit device from door face 90 29 Illustrations of panic exit devices 93 30 Illustrations of single axis hinges 95 6 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Page 31 Illustrations of hold-open devices and hold-open mechanisms 98 32 Illustrations of cylinders for locks 100 7 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Foreword This Singapore Standard was prepared by the Technical Committee on Architectural Works under the direction of the Building and Construction Standards Committee (BCSC). It is a revision of SS 332 : 2000 Specification for Fire Doors. This standard is intended to complement the fire-protection requirements for building regulations and provides only minimum requirements. This standard covers the installation and construction of the fire door assemblies. The requirements specified in this standard generally refer to materials and assemblies, which, through field experience, have been found acceptable for such application. The major revisions made in the standard are as follows: a) The test standards for various hardware, besides door closer, are included. b) Annex F on door closer requirements and test methods is updated. c) Back check on door closers is not required by the regulatory authority. d) The requirements on the clear opening area, width, height and vertical position of vision panel on fire doors are aligned with the Code of Practice for Fire Precautions in Buildings 2007 administered by Singapore Civil Defence Force (SCDF) and the Code on Accessibility in the Built Environment administered by the Building and Construction Authority (BCA). This standard is based on AS 1905.1 : 2005 – Components for the protection of openings in fireresistant wall – Fire resistant doorsets. Permission has been granted by SAI Global Ltd to reproduce Figures 1, 2, 3, 4, 5 and 6. A copy of AS 1905.1 can be purchased at http://www.sai-global.com. In preparing this standard, reference was also made to the following publications: 1. AS 1530.4 : 2005 2. BS 476 3. 4. 5. BS EN 1363 –1 : 1999 BS EN 1634-1 : 2000 BS EN 1154 : 1997 6. ISO 3008-1976 Methods for fire tests on building materials, components and structures Part 4 : Fire-resistance test of elements of construction Fire tests on building materials and structures Part 4 : 1970 Non-combustibility test for materials Part 11 : 1982 Method for assessing the heat emission from building materials Part 22 : 1987 Methods for determination of the fire resistance of nonload bearing elements of construction Fire resistance tests Fire tests of door and shutter assemblies (Method of test) Building hardware – Controlled door closing devices requirements and test methods Fire-resistance tests – Door and shutter assemblies (including Amd 1 : 1984) Acknowledgement is made for the use of information from the above publications. Attention is drawn to the possibility that some of the elements of this Singapore Standard may be the subject of patent rights. SPRING Singapore shall not be held responsible for identifying any or all of such patent rights. NOTE 1. Singapore Standards are subject to periodic review to keep abreast of technological changes and new technical developments. The revisions of Singapore Standards are announced through the issue of either amendment slips or revised editions. 2. Compliance with a Singapore Standard does not exempt users from legal obligations. 8 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Specification for fire doors 1 General 1.1 Scope This standard specifies requirements for the construction and installation of fire-resistant doorsets used to protect openings in walls and partitions which are required to resist the passage of fire. Manufacturers of fire-resistant doorsets are strongly encouraged to implement quality control system in accordance with ISO 9002. This standard also applies to transom panels over 0.5 h fire rated doors, where the panels are contained within the doorframe and form part of the doorset. A panel above a doorset, which is not contained within the door frame, is considered as being part of the wall and is therefore subject to the stability, integrity and insulation requirements set out in the Code of Practice for Fire Precaution in Buildings. A transom within a door frame may be permanently fixed to the side members of the frame or may be removable by means of mechanical fixing. This standard shall be read in conjunction with the Code of Practice for Fire Precautions in Buildings. This standard does not apply to lift-landing doors. 1.2 Normative references The referenced documents in Annex U.1 are indispensable for the application of this standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. 2 Definitions For the purpose of this standard, the terms used in describing fire doors shall be as defined or as given in Figures 4, 5 and 6. 2.1 Approved Approved by the Regulatory Authority. 2.2 Automatic Designed to close automatically through operation of an approved sensing device. 2.3 Non-combustible Deemed non-combustible when tested in accordance with BS 476 Part 4 or 11. 2.4 Non-self-latching bolt A locking bolt which does not have a chamfered front and can only be retracted or projected by hand operation. 2.5 Door stop That part of door frame against which the door leaf stops. 9 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 2.6 Doorset A complete assembly comprising: a) the door leaf or leaves with vision panel, if any, and hardware or other in-built features; b) the door frame, if any, with its fixings to the wall and, for a sliding door, with all guides and their respective fixings to lintel, wall or sill; c) a transom panel, if any, of size not exceeding 2000 mm width by 800 mm height for 0.5 h fire rated doors only; and NOTE – For transom panel exceeding the size of 2000 mm width by 800 mm height, the panel shall be considered as part of the fire resistance wall and shall conform to its fire resistance requirements. Fire rated glass is not permitted to be used to protect openings to escape staircase regardless of the size of transom panel and/or rating of fire rated door. d) for an automatic fire door, the approved heat-actuated device(s) and the closing mechanism. 2.7 Double-acting door (also called ‘pivot swing door’) A doorset whose leaf swings around one vertical side and is equally capable of opening in either direction. 2.8 Finished floor Applied to the sill of a fire door, means the final level of the sill including combustible floor covering. 2.9 Fire door A doorset (timber, metal, glass, composite, etc) single or multi leaves which, except when varied as permitted by this standard, is identical in assembly, construction and installation with a prototype that has been submitted to the standard fire-resistance test and has fulfilled all the relevant test requirements. 2.10 Fire resistance rating (FR) The time in hours for which a fire door withstands each of the respective tests for integrity and insulation in accordance with the fire-resistance test (see 2.11). 2.11 Fire resistance test The fire resistance test is as specified in Annex E. 2.12 Heat-actuated device A device which operates to effect the closure of an automatic fire door (see 3.1.4). 2.13 Recognised testing laboratory A testing laboratory accredited by Singapore Accreditation Council or, recognised via mutual recognition agreements with Singapore Accreditation Council and those deemed to be accepted by the regulatory authority. NOTE – The regulatory authority has jurisdiction to accept other testing laboratories, individuals or organisation as being capable of conducting fire test or of providing formal opinion on fire doors. 10 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 2.14 Regulatory authority Authority that is responsible for preparing or adopting regulations. 2.15 Self-closing An action by an approved device to bring the door leaf, without the assistance of electrical power, to a close fitting position after each opening. 3 Design requirements 3.1 General 3.1.1 Materials Unless otherwise specified by the Regulatory Authority, or in this section, no restriction shall be imposed on the materials used for construction of the doorset provided that: a) the tested specimen satisfies the requirements of this standard; b) no asbestos is used as core materials or facings; and c) flame retardant paints and/or coating shall not be used to make doorset achieve the required fire-resistance rating. 3.1.2 Self-closure Doorsets, including electrically powered automatic doorsets, shall be self-closing. The test method and requirements for automatic swing door operator shall comply with that of door closer, sequence selector and electrically powered door hold-open devices, where applicable. 3.1.3 Hardware and furniture 3.1.3.1 Attachment All hardware and furniture shall be attached by means of screws anchoring in metal plates, metal members, metal thread anchors, expanding thread inserts or through-screw fixing. Split-frame type expanding inserts shall not be used for fixing. 3.1.3.2 Self-latching All hardware and furniture shall function so that the door is self-latching. For double leaf doorset, where both leaves are required to be opened for escape purpose, automatic flushbolts shall be used on the inactive leaf as a substitution for latched flushbolts. The installation of automatic flushbolts on doorset shall be supported with fire resistance test evidence or otherwise assessed by a recognised testing laboratory, and approved by the Regulatory Authority. 3.1.3.3 Door Coordinator devices Door coordinator devices are required for doorsets in pairs having rebated meeting stiles, or single bevel latches, to ensure self-closure and latching of both door leaves. 3.1.3.4 Permanent marking Latches and closer bodies shall be marked in accordance with 8.5. 11 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 3.1.3.5 Lockset and flushbolts Unless the fire resistance of the prototype doorset is tested with retracted latch bolts on lockset and flushbolts, all doorsets shall remain latched by the lockset and flushbolts when the door leaves are in a closed position. 3.1.4 Sensing device All automatic fire doors shall incorporate a heat-actuated device integral with the doorset. Alternative sensing devices may be prescribed subject to the approval of the Regulatory Authority. 3.1.5 Double leaf doorset (with rebated meeting edges or astragal) fitted with panic exit device Panic exit device shall only be fitted on the active door leaf. Inactive door leaf shall be without any surface mounted hardware and fitted with automatic flushbolts. 3.2 Side-hung doors 3.2.1 Width of door seat rebate The minimum width of door seat rebate of the frame shall be as prototype tested. NOTE – As a general design guide, width can varies from 15 mm to 25 mm depending on types of door construction. 3.2.2 Clearance between door leaf and frame or finished floor Door leaves in rebated frames shall have fitting tolerances of: a) not more than 3 mm between the door leaf and frame at the two edges and at the door head in the closed position, and not more than 3 mm at the latch edge when measured in the nearclosed position at the leading edge of the leaf; and b) not less than 3 mm and not more than 10 mm between the bottom of the door leaf or door leaves and the finished floor with the door closed when measured as follows: 1) for doors leading to fire-protected stairs, fire-protected passageways, fire-protected ramps and doors in fire walls – from the finished floor as shown in Figure 1(b); 2) for other doors – from the floor covering as shown in Figure 1(a); or 3) not more than the dimension indicated in the tested prototype. NOTE – For metal and glazed doors, the gaps mentioned in 3.2.2. (a) are allowed to be increased as per prototype tested. 3.2.3 Hinges and pivots 3.2.3.1 General Hinges shall be made of steel or stainless steel, unless otherwise tested or assessed, and be accurately aligned so that the door leaf swings freely without bias in the opening direction. Split-frame type expanding inserts shall not be used. When the door leaf is installed, it shall be clear in the frame and the latch bolt shall engage freely with the striking plate. 12 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 1 – Clearance between door leaf and frame or finished floor 13 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 3.2.3.2 Frictional forces Except for doorsets incorporating floor or head springs (for which the testing of frictional forces is not practicable), when continuously applied perpendicular to the face of the door leaf at a radius of 700 mm from the pivot centre, and before the closer arm is attached, the force required: a) to move the door leaf from the fully closed position to the fully open position and return to the strike shall be not more than 2 N; and b) to bring the door leaf to the fully latched condition shall be not more than 20 N. 3.2.4 Materials for essential latching components The materials used for all essential latching components of side-hung doors shall have temperature of fusion not less than: a) for doorsets up to 2 hour fire-resistance rating – 890 oC; and b) for doorsets in excess of 2 hour fire-resistance rating – 1030 oC. Refer to 8.5.4 for essential latching components. 3.2.5 Latch handles The operating device which effects the retraction of the latch bolt shall be located at a point not more than 1200 mm above the bottom of the doorleaf, or mid height of door panel. Where knobs are used to operate the latch bolt, the clearance between the face of the knob and the face of the doorstop shall be not less than 35 mm. 3.2.6 Latch bolts The shoot of the latch bolt shall be not less than 12.5 mm and shall be adjusted to engage the bolt hole in the frame by a distance of not less than 9.5 mm past the face of the striking plate, when the door is in the latched position, unless otherwise tested or assessed. 3.2.7 Closure pressure relief o A vent, plugged with material of temperature of fusion below 100 C and located above level of oil in the hydraulic chamber shall be included for all closers that incorporate: a) packing gland type pressure seal; b) an O-ring seal with a backup seal; or c) cup seals with a backup seal. 3.2.8 Cushioned back-checking action of the closer The self-closure system may incorporate a cushioned back-checking action to prevent shock when the door is forcibly opened. This action shall not commence until the door leaf has opened to not less than 75o of opening, and shall be effective over not less than the last 5o of opening (see Note 1). NOTE 1 – The final angle of effectiveness of the cushioned back-checking action depends on the particular location where each fire door is to be installed. For the purposes of fire-resistance testing, it is recommended that the maximum opening angle of the door is assumed to be 90o. The cushioned backing action should preferably be factory set. NOTE 2 – For information regarding the selection of door closer, see Annex F. 14 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 3.3 Double-acting doors 3.3.1 Clearances Clearances between the edges of the door leaf and the wall, floor, head and frame shall be not greater than that necessary for the operation of the doorset and in no case shall these clearances exceed that specified in 3.2.2. 3.3.2 Performance A double-acting door shall be designed and constructed in such a manner that its operational performance is not inferior to that of a side hung door (see 3.2). 3.4 Hardware installed on fire doors Typical applications of hardware are shown in Annex A. 3.5 Sizes for fire doors 3.5.1 The recommended combinations for door size with respect to a single door leaf size are tabulated below: Width(mm) Height(mm) 2050 2200 2400 950 1050 1150 1250 X X X X X X X X X X X X NOTE 1 – These are recommended sizes, however other combination of sizes may be used to suit the requirements of the project. For unequal double leaf door used for exit or exit access purpose, minimum size of active leaf shall be 900 mm width and the width of the inactive leaf shall be able to accommodate a suitable door closer. NOTE 2 – In the selection of the appropriate door size, consideration for the clear width of exit doors and exit access door shall comply with the fire code requirements. NOTE 3 – The hinges and door closer for incorporation in the doorset of the selected size shall be compatible with the doorset and shall meet the expected fire resistance performance of the doorset. 3.5.2 In the selection of hinges, the following shall be taken into consideration: a) The adequacy of the hinges to support the weight of the door leaf as not to subject the door leaf to undue wear and tear or malfunctioning. b) The mounting on either timber or steel door frame shall be appropriate. c) If special mounting details are required, there shall be provisions on either door leaf or door frame or both. d) The proposed hinges and its mounting details shall be supported by fire resistance test or assessment report from a recognised testing laboratory. 15 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 3.5.3 In the selection of door closer, the following shall be taken into consideration: a) The door closer shall be of the correct power size as specified in Table 4 of Annex F for effective operation of the door leaf. b) The fire resistance performance of the door closer shall be supported by test or assessment report from a recognised testing laboratory. c) The door closer selected shall be suitable for its intended use, e.g. pressurised staircases, corridors, M & E rooms, etc. 3.6 Horizontally sliding doors 3.6.1 Overlap of opening The door leaf shall, in the closed position, overlap the clear opening with the dimension as prototype tested. 3.6.2 Clearance between leaf and wall With the door in the closed position, the average clearance between the face of the door leaf or leaves and the return of the frame or wall face within the area of required overlap at the top and sides shall be as prototype tested. 3.6.3 Clearance between the door leaf and the finished floor With the door in the closed position, the clearance between the bottom of the door leaf and the finished floor shall be as prototype tested. 3.6.4 Flush pulls and grips Where a finger pull or grip is recessed into the face of a sliding fire door, and does not provide for a retractable “D” handle, the recess shall: a) measure not less than 25 mm wide x 70 mm high; and b) offer not less than 20 mm depth of finger purchase in a plane normal to the direction of door movement, except that where the recess is undercut by not less than 5o to the plane normal to the direction of door movement, the depth of finger purchase may be reduced to 12 mm, unless prototype tested. NOTE – ‘Purchase’ is defined as a firm hold on the finger pull or grip to move the door or to prevent from slipping or leverage. Where pulls or grips are recessed into both faces of the sliding fire door, they shall be staggered in their location so as to give a clear distance of not less than 75 mm between any of their parts. They shall be located vertically so that they are neither less than 900 mm nor more than 1100 mm above the finished floor on the side from which they are visible. 3.6.5 Directional arrows All sliding fire doors shall be provided with sharply delineated arrows of the form and dimensions shown in Figure 2, which shall indicate the direction of opening of the doors. The surface of such arrows shall be not less than 3 mm above or below the plane of their surround. If not embossed in the material of the door, the arrows shall be mechanically affixed at the midpoint of the face of each door leaf at a height of neither less than 900 mm, nor more than 1200 mm, above floor level. 16 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 2 – Form of directional arrow for sliding fire doors 4 Determination of fire-resistance rating 4.1 General The fire-resistance rating of the doorset shall be determined by submitting a prototype to the standard fire-resistance test, described in Annex E. 4.2 Test mounting Doorsets intended for the protection of openings in brick, concrete block and reinforced concrete walls shall be tested when mounted in any one of such types of wall construction. Doorsets intended for the protection of openings in other types of fire-resisting walls or specific type of fire-resisting lightweight partitioning shall be tested when mounted in an opening in walls or partitioning identical in construction with that in which they are to be used. 4.3 Exposure to fire 4.3.1 General Except as provided in 4.3.3, two prototypes of a side-hung or pivoted fire door shall be tested. One prototype shall be mounted so that the door leaf swings towards the fire in the test furnace and the other prototype shall be mounted so that the door leaf swings away from the fire. Where the doorset is not latched it shall be exposed to fire tests in both dimensions. The exposed face of the doorset can also be the face that is deemed to be onerous by the recognised testing laboratory. 4.3.2 Side-hung doors symmetrical face-to-face Where, because of the symmetry of its construction face-to-face and the materials of construction of the doorset, the nature of the deflection of the door leaf relative to the door frame can be reasonably estimated, the prototype to be tested first shall be that which is mounted according to (a), (b) or (c) below, as appropriate: a) Door leaves, the framing and/or facing materials of which are subject to thermal expansion. These door leaves when heated from one side will deflect towards the fire along their horizontal centreline. Where such door leaves are latched near that centreline only, the prototype shall be tested so that the door leaves are mounted to swing away from the fire in the test furnace. b) Door leaves, the framing and/or facing materials of which are subject to thermal shrinkage. These door leaves when heated will deflect away from the fire along their horizontal centreline. Where such door leaves are latched near the centreline only, the prototype shall be tested so that the door leaves are mounted to swing towards the fire in the test furnace. 17 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 c) Door leaves, the framing and/or facing materials of which are not subject to pronounced thermal movement and door leaves which incorporate timber edge-strips. Regardless of swinging or latching arrangements, prototype having these door leaves shall be tested so that the door leaves are fully exposed to the fire, i.e. mounted to swing towards the fire in the test furnace. If the prototype performs satisfactorily in the fire test and the recognised authority is satisfied that the reverse way of swinging represents the more favourable case, it may then waive the requirement of the second test. 4.3.3 Side-hung doors not symmetrical face-to-face If the construction of the leaf of a side-hung fire door is not symmetrical from face-to-face, two identical prototypes shall be tested for fire resistance from both sides. In one test the door leaf shall be mounted to swing towards the fire in the test furnace, and in the other test the door leaf shall be mounted to swing away from the fire. 4.3.4 Horizontally sliding doors Horizontally sliding doors intended to protect openings used for general access or passage shall, regardless of construction, be tested with their suspension system exposed to the fire in the test furnace. 5 Hardware requirements and test methods 5.1 Door closer used on side-hung fire doors shall be subjected to the requirements and test method as described in Annex F. 5.2 As amended Aug 2009 Other hardware 5.2.1 Other hardware, except sliding and folding door hardware, shall be subjected to the requirements of the test standards specified in Table 1. 5.2.2 These hardware may be fitted to fire doors provided that the limitations shown for leaf mass and/or width derived from the relevant hardware product standards are not exceeded and its application on fire doors is supported by fire resistance test evidence. As amended Aug 2009 Table 1 – List of standards for hardware use on fire door S/N Hardware Max. leaf mass Max. leaf width Standards Annexes in SS 332 1 Door coordinator devices 160 kg 1600mm EN 1158 K 2 Door bolts No limit No limit EN 12051 L 3 Lever handles and knobs No limit No limit EN 1906 M 4 Mechanical locks and latches No limit No limit EN 12209 N 5 Emergency exit devices 200 kg 1300mm EN 179 O 6 Panic exit devices 200 kg 1300mm EN 1125 P 7 Single axis hinges 160 kg 1600mm EN 1935 Q 8 Electrically powered door hold-open devices 160 kg 1600mm EN 1155 R 9 Cylinders for locks No limit No limit EN 1303 S 10 Sliding and folding door hardware (for information) No limit No limit EN 1527 T 18 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 6 Variation from prototype 6.1 Size Doors of sizes different from those of tested prototype are permitted within certain limitations but the variations are dependent on product type (e.g. hinged doors and sliding doors) and length of time that the performance criteria are fulfilled. However, no alteration shall be made to the nominal thickness of the door leaf, to other dimensions of the door frame or component parts of the door leaf, or to the clearances specified in Clause 3. The limitations are shown in the following Table 2. With the increase in weight, any oversize door leaf shall be incorporated with compatible door closer and hardware. Table 2 – Limitation to size variations Door type Category ‘A’ allowances Category ‘B’ allowances Hinged doors Unlimited size reduction is permitted for all except insulated steel doors where a reduction to 50 % width and 75 % height of tested specimen is the limit of variation. Size increase is not permitted. Sliding doors Unlimited size reduction is permitted for all except insulated steel doors where a reduction to 50 % width and 75 % height of test specimen is the limit of variation. Size increase is permitted up to: 30 % height 30 % width 30 % area Unlimited size reduction is permitted for all types. Size increase is permitted up to: 15 % height 15 % width 20 % area Unlimited size reduction is permitted. Size increase is permitted up to: 50 % height 50 % width 50 % area NOTE – Category ‘A’: The classification time, in term of test period, was just reached. NOTE 2 – Category ‘B’: The classification time, in term of test period was extended in accordance with the following values before the test was terminated: a) Classification periods up to 30 min require an additional 20 % time i.e. 20 % for 15 min = 3 min 20 % for 20 min = 4 min 20 % for 30 min = 6 min b) Classification periods above 30 min require an additional minute per supplementary quarter of hour i.e. + 1 min for 45 min = 7 min + 2 min for 60 min = 8 min + 4 min for 90 min = 10 min + 6 min for 120 min = 12 min + 10 min for 180 min = 16 min + 14 min for 240 min = 20 min NOTE 3 – For Category ‘B’ doorsets, further increase in size is permissible, if in the opinion of a recognised testing laboratory that fire performance of the tested prototype shall not be reduced, subject to approval by Regulatory Authority. 19 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 6.2 Door leaf 6.2.1 Construction Substitution or addition of facing, edging, alternative material and plastic signages in the construction of the door leaf may only be made if, in the opinion of a recognised testing laboratory that such modification(s) do not reduced its fire performance, subject to approval by the Regulatory Authority. However, substitution of core material is not allowed. Reduction of core thickness may only be allowed if, in the opinion of a recognised testing laboratory that such modification(s) do not reduce its fire performance, subject to approval by Regulatory Authority. Surface mounted timber mouldings are allowed on timber door leaf. Where the paint finish is for decorative purposes, it is acceptable. 6.3 Frames Single-rebate and double–rebate door frames are interchangeable. Substitution or addition of alternative material in the construction of the door frame may only be made if, in the opinion of a recognised testing laboratory that such modification(s) do not reduce its fire performance subject to approval by Regulatory Authority. Where the paint finish is for decorative purposes, it is acceptable. No variations shall be permitted for the following items, unless assessment report is obtained from a recognised authority and subject or approval by the Regulatory Authority: a) Decrease in either dimension of the door seat rebate in which the door leaf is fitted. b) Decrease in the width of either architrave face of the door frame. c) The thickness of gauge of material used. d) The method of mounting and anchoring of the door frame in the wall opening except as noted in 7.7. e) Change of door frame material for fire doors rated one hour and above. 6.4 Wall construction For wall construction other than masonry, variation of the wall type or wall system shall not be made unless the doorset has been subjected to a full–scale fire resistance test in a wall type or system that has been the subject of a full-scale fire test, and has: a) the same (or more severe) deflection characteristics as the proposed wall; b) the same frame (and sliding-door track) and wall mounting details on the proposed wall; and c) achieved the required fire resistance level. NOTE – For example, for a drywall system the results obtained for a fire doorset, fire-tested in a 64 mm steel stud partition faced with two layers or 16 mm plasterboard may be applicable to a similar partition with greater stud depth or greater facing thickness. 20 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 6.5 Hardware 6.5.1 General Other than as permitted under 6.5.2, no hardware shall be added and no variation shall be made in the type, positioning, fixing, material, method of construction, geometry of operation, or temperature of fusion of any item of hardware fitted to a fire door unless in the opinion of a recognised testing laboratory that such modification(s) do not reduce its fire performance, subject to approval by the Regulatory Authority. NOTE 1 – Some notes on the selection of door closers are given in Annex F, Table 4. NOTE 2 – An assessment report from a recognised testing laboratory is required for cutout in excess of prototype tested doorset for installing hardware, e.g concealed door closers, cylindrical/mortise/multi-point locksets, electronics lock, electric strikes, EM lock, concealed hinges, concealed magnetic door contact, eye viewer, panic device, etc. 6.5.2 Permissible variations The following variations from the requirements of 6.5.1 are permissible: a) Variation may be made in other metallic finishes. b) A push-plate or kick-plate which was mounted on the tested prototype or was added as the result of alternative testing as described in 6.5.1 and which was not held on by or did not form part of the latchset or lockset furniture may be reduced in either dimension, but shall not vary in material of construction. c) Door closers where: d) 1) The arm configuration of a surface-mounted closer may be interchanged between regular-arm and parallel-arm but not with sliding arm. 2) The location of the door closer may be varied provided that the distance between the nearest edge of the closer and the hinge stile is not reduced, as with respect to the tested prototype. 3) An alternative closer manufactured by the same manufacturer and of a smaller closer in the same series of closers may be used provided the closer: i) is manufactured from the same materials; ii) has the same operating mechanism designs; and iii) uses the same hydraulic fluids. Locksets where: 1) The location of the latchset or lockset may be varied up to 80 mm vertically in either direction from mid height of door leaf; up to a maximum of 1200mm from the finished floor. However, for elevated doorset, the location of the latchset or lockset shall be at mid height of door leaf with a variation of up to 80mm vertically in either direction. 2) The backset of a lockset or latchset may be reduced, provided that no encroachment is made on the structural framework of the door leaf. Minor changes may be made in the operating characteristics of hardware, provided that these do not require modification of the door leaf or door frame and do not otherwise prejudice the fire resistance of the doorset. Typically, such changes are functions of key-in-knob latchsets involving a variation in the knob only and not in the essential bolt-operating mechanism. Where doubt arises as to the acceptability of such variations, the 21 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 opinion should be sought of a competent organisation acceptable to the authority that carried out the fire-resistance test on the prototype doorset. 3) 4) Where locksets or latchsets are operated by a steel shaft, their surface-mounted furniture such as handles, knobs and escutcheon plates may be varied provided that: ii) the temperature of fusion of any substitutive part is not lower than that of the corresponding part on the tested prototype. iii) any substitutive handle or knob is not so massive or asymmetrical as to introduce a turning moment about the operating shaft which exceeds 0.07 Nm, or for a substitutive lever is more than 10 percent greater than the moment induced by the corresponding part on the tested prototype; and iv) the new escutcheon plate covers adequately any hole in the door leaf formed to accommodate the lockset or latchset, but does not cover an area of the face of the door leaf which exceeds by more than 20 percent the area which was covered by the corresponding plate fitted to the tested prototype. A surface-mounted self-latching lockset may be fitted to the fire door. In addition to the tested lockset, for additional security. The hole drilled through the door leaf to accept the locking cylinder must be not larger than 32 mm diameter. The locking cylinder must be made of brass or metal of higher melting point. The head diameter of the cylinder or its escutcheon must be larger than the cylinder hole in the door leaf. The cylinder assembly must be fixed to the door leaf by steel screws through a steel mounting plate which effectively covers the hole in the door leaf. The connecting bar clearance hole in the mounting plate must be not greater than 15 mm diameter. NOTE – Where fire seals are fitted, the surface-mounted self-latching lockset shall not impede its activation. 5) e) Lockset or latchset of identical or smaller dimensions and identical material as prototype tested can be used. Hinges The fixing of hinges to door frames may be effected by welding in lieu of metal thread steel screws, and vice versa. Hinge of identical dimensions or smaller and same material as prototype tested can be used. NOTE – For timber and timber composite doorsets, the distance of the screw fixings from the centre of the leaf edge shall be similar to the tested hinges. f) Door holder Surface mounted electromagnetic door holder can be used. 6.6 Others 6.6.1 Vision panel and viewing lenses Except hardware permitted in 6.4, no vision panel or viewing lenses shall be allowed in any door leaf unless a prototype incorporating such feature has demonstrated satisfactory behaviour in a full-scale fire test conducted in accordance with Clause 4. Each vision panel shall incorporate a permanent identification mark, except for wired glass. 6.6.1.1 Vision panels Opening in door leaves to accommodate vision panel shall not be permitted unless such openings were included in the tested prototype. 22 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Vision panel incorporate in fire door to protected staircase and smoke stop/fire lift lobby shall be installed in a clear opening not exceeding 60,000mm2 and not less than 30,000mm2 with a clear width of minimum 100mm. The vision panel height shall not be less than 600mm. The vision panel shall have the requisite fire resistance rating and shall not turn opaque when subject to heat. The vision panel shall be located with the bottom edge not higher than 900mm and the top edge lower than 1500mm measured from the finished floor level. Other than fire doors to protected staircase and smoke stop/fire lift lobby, variation may be made to the width, height, bottom edge and top edge position, and clear opening area of vision panel fitted to a fire door, subject to approval by the Regulatory Authority. 6.6.1.2 Viewing lenses Openings to accommodate viewing lenses may be permitted in the door leaf of any fire door, provided that the integrity of such installation is supported by assessment report from a recognised testing laboratory. 6.6.2 Louvres (intumescent activated air transfer grille) Openings in door leaves to accommodate louvres shall not be permitted unless such openings were included in the tested prototype and its usage approved by regulatory authority. The following conditions shall also apply: a) Louvres shall be permitted only for 0.5 h fire rated doorset. b) It shall be positioned below half height of the door leaf. c) Its size shall not exceed 300 mm x 300 mm. d) Louvres opening shall be completely sealed under fire condition. e) It shall not be used at escape staircase, exit passageway and protected lobby. 6.7 For both “Category A” and “Category B” doorsets, recognised testing laboratories issuing assessment reports containing multiple design variations for the same prototype doorset shall ensure there is no cumulative effect if more than one variation is applied. 7 Installation 7.1 General The method of installation of any fire door shall be the same as that of the tested prototype, except as permitted by 4.3 and 7.7(b). 7.2 Sensing devices Any prescribed sensing device which operates to effect the closure of automatic fire doors shall be positioned within the stream of air that passes the door opening when the fire door is fully open. Where the sensing device is to be mounted on the ceiling, it shall be set back horizontally from the door opening by a maximum distance of 1.5 m, or the distance between the ceiling and the top of the door opening whichever is the greater. 7.3 Travel limiting devices Every side hung or double-acting fire door shall be protected by means of buffers, stops or other travel-limiting devices to prevent damage in any installation where the fire door or its accessories could be subjected to strain or racking through forceful or careless operation. A door closer is not 23 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 considered a travel-limiting device for the purpose of this clause. The angle subtended by the clear opening of the door shall not be less than 90°. 7.4 Counterweighing system for horizontally sliding doors 7.4.1 Protection Where a counterweighing system is used to provide automatic closure of sliding fire doors under fire conditions, this system shall be protected to ensure free operation by means of adequate guards or enclosures. Counterweights shall be not less than 150 mm clear of the floor in the door-closed position. 7.4.2 Adjustment At the time of installation, the counterweighing systems shall be adjusted as follows: a) b) Where it is necessary to pass through fire door to reach the required exit, the force required shall not exceed 110 N in order: 1) to move the door leaf from its closed position; 2) to move the door from its stationary position after the release mechanism has operated; or 3) to operate the door leaf through its full travel. In other cases, the force required shall not exceed 180 N in order: 1) to move the door leaf from its closed position; 2) to move the door from its stationary position after the release mechanism has operated; or 3) to operate the door leaf through its full travel. NOTE – Calculation for forces are shown in Annex D. 7.5 Double-acting doors Double-acting doors having two door leaves shall be installed with no sequence selector. 7.6 Door sill The sill to opening in which a fire door is mounted shall be of concrete or other material not deemed combustible when tested in accordance with BS 476 Part 4 or 11. In the case of sliding fire-resistant doorset, the sill constructed of such material shall project not less than 100 mm beyond the wall face and extend for a distance of not less that 150 mm on either side of the opening on the side of the wall on which the fire door is mounted. (See 3.3, 3.4 and Figure 1). Four-sided frame can also be used. NOTE – Materials for floor coverings which extend through a fire-resistant doorset opening are not within the scope of this standard. 7.7 Fixing of door frames Except as permitted in 7.7(b), door frames shall be fixed in accordance with 7.7(a) below. a) The door frame shall be fixed as in the prototype. 24 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 NOTE – Where the frame is incorporated in the wall as construction progresses, it is recommended that it be thoroughly and progressively grouted with mortar, as shown in Figure 3. For masonry construction, walling units and lintels should be entered as deeply as practicable into the jamb cavities, and frame head and jamb cavities should be thoroughly and progressively grouted in with mortar. In addition, frames built into masonry walling should be provided with metal anchors designed to provide positive rotational restraint to jambs about their vertical axis. Such anchors should be of similar type to and not less in number or greater in spacing than those of the tested prototype. In any case anchors should be built into mortar joints to a depth of not less than 75 mm at spacing not exceeding 400 mm vertically (see Figure 3). b) In variation to the requirements of paragraph (a) above, the door frame may be fixed in accordance with the recommended techniques described in Annex C but subject to the following conditions: 1) The fixing techniques shall apply only to doorsets whose prototype was built as described in the note to (a) above. 2) The size of the opening shall be such that the clearance between the frame and the edge of the opening does not exceed 25 mm. Where an opening is to be reduced in size to accommodate the frame, the structural adequacy and fire resistance of the added walling shall be compatible with that of the existing wall. 3) The spacing and location of anchoring points shall be equal to that of the prototype, except that additional anchoring points are permitted. 4) Adequate clearances around the frame shall be retained for the purposes of grouting the frame cavity. 5) Jamb cavities shall be fully grouted. 6) The head cavity shall be grouted in a manner that will prevent a flame passage across the top of the frame. 7) Where the frame is fixed by the method of threaded anchors (see C2.3 of Annex C) all packers shall be in position and all threaded anchors shall be fully tightened before any grout is placed. 8 Marking 8.1 General The door leaf and door frame, if any, of every fire door installed in a building shall each be marked with the information listed in 8.2 by means of identification tags in accordance with 8.3. 8.2 Information The following information shall appear on the identification tags for door frame and door leaf: a) Name of the fire door manufacturer and licensor (See Annex B); b) Fire resistance rating of the doorset; c) Identification number of the individual doorset; d) Date of manufacture; and e) Name of local licensee/supplier. NOTE – Such identification should also be recorded by the manufacturer/supplier for possible subsequent project identification for a period of 7 years. 25 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 3 – Fire door frames fixed during wall construction 26 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 8.3 Identification tags 8.3.1 Dimensions. The identification tags shall measure not less than 50 mm x 25 mm. 8.3.2 Method of marking The required information shall be etched, embossed, stamped or printed on the identification tags. Alphabetic or numeric characters shall be not less than 1.5 mm high. 8.3.3 Method of fixing The identification tags shall be firmly fixed to minimise the possibility of detachment during the service life of the fire doorsets. The tags shall be nailed, screwed, riveted or glued. Manufacturers are strongly advised to provide adequate permanent protection to the identification tags. 8.3.4 Affixing The identification tags shall be affixed only after the inspection at the manufacturing premises is completed and as follows: a) Horizontally sliding doors. The tags shall be affixed to the trailing edge of the door leaf at approximately 1.5 m above floor level and at approximately the same height on the door frame, if any. b) Side-hung and double-acting doors. The tags shall be affixed to the edge of the hinge stile of the door leaf and the jamb of the door frame at approximately 1.5 m above floor level or just below the top hinge, whichever is lower. c) Two-leafed doorsets. The tag shall be at one of the leaf. 8.4 Additional marking Additional marking to show evidence of compliance with this standard may be required by the Regulatory Authority. 8.5 Marking of locksets and closers 8.5.1 General Lockset and closer bodies shall be permanently marked by means of engraving, embossing or stamping. The marks shall be discernible to the naked eye and shall be located so that they are either directly visible or can be exposed by removal of a decorative plate or cover. 8.5.2 Lockset The following information shall be provided on the lockset for identification purposes: a) Manufacturer or the brand of the lockset shall be marked on the fore-end of the lockcase; and b) Model series number of the lockset shall be provided in packing or catalogues. 27 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 8.5.3 Closer body The following information shall be provided and marked on the door closer body for identification purposes: a) Manufacturer’s name or the brand of the closer; b) Model series number of the closer; and c) The year and week of manufacture. 8.5.4 Essential latching components In cases where alternative essential latching components (see 6.4) are available for use with the one latchset, these components shall each bear marks that enable the fire resistant doorset sponsor to identify the combination that was employed with the tested prototype. The following shall be deemed essential latching components: a) latch bolt; b) striking plate; and c) both-retaining plate. The metallic composition of these components shall be represented by the following symbols: a) Brass B b) Nickel silver NS c) Aluminum bronze AB d) Stainless steel SS e) Mild steel MS 9 Responsibility of manufacturer / owner of building (or representative) 9.1 Door manufacturer 9.1.1 General When the installation is completed, the manufacturer shall inspect each installed fire-resistant doorset and provide Schedule of Evidence of Compliance, only if can be confirmed that: a) hardware has been installed in accordance with the specified instructions of the relevant manufacturer; b) hinges are correctly positioned and aligned; c) doorset latches satisfactorily from the fully open position and from any intermediate position; d) closer, if any, demonstrates satisfactory action as specified in 3.2.8; e) on the basis of evidence of test or the opinion of a recognised testing laboratory, or both, and evidence of manufacture to the specifications of the test specimen, the doorset complies with all other requirements of this standard; and f) clearances specified in 3.2.2, 3.3.1. 3.6.2, 3.6.3, or as indicated in the prototype test report, have been met. 28 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 9.1.2 Certification When the installation of a fire resistant doorset in a building has been completed, the manufacturer shall provide to the owner (or representative) with the Certificate of Conformity for the fire doorset issued by a recognised testing laboratory and a written evidence of compliance in the form of a numbered certificate indicating that: a) an inspection has been carried out by the manufacturer to ascertain the fire-resistance doorset is installed in accordance with this standard; and b) each fire-resistant doorset is identical with the tested specimen, or where there are variations from the tested specimen, the variations are in accordance with this standard. NOTE – An example of a fire door certificate is given in Annex I. 9.1.3 Schedule of evidence of compliance The required information shall be made available from records as set out in 9.4 and shall be contained in the form of a Schedule of Evidence of Compliance confirming that the installation complies with this standard. NOTE – A sample format of the information in 9.1.4 is shown in Annex J. 9.1.4 Records and required information The manufacturer shall maintain records of doorsets which shall be made available for inspection to any person having reasonable cause for such inspection, listing the following information: a) Door identification number; b) Door location plan number with floor plan; c) Door type; d) Nominal dimensions of the door - width, height and thickness; e) Nominal dimensions of the frame – width, height and depth; f) Fire – resistance rating (FR); g) Lockset and closer type; h) Wall type; i) Miscellaneous items (for example, vision panel); j) Tested/Approved clearance between door leaf and frame, or wall, or finished floor; k) Test report/opinion reference number; l) Date of site inspection. 9.2 Owner of building (or representative) 9.2.1 Taking over and safe keeping of documents The owner of building (or representative) shall ensure that documents relating to fire doors installed in the building are received during the taking over of the building. These documents shall be properly kept and made readily available for any future references. The owner of building (or representative) shall receive the following documents: a) Fire door certificate (as shown in Annex I) issued by the door manufacturer. b) Fire doors schedule of evidence of compliance (as shown in Annex J) issued by the door manufacturer. 29 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 c) ‘Record of issue of fire door labels’ forms for the fire doors issued by an accredited testing laboratory to issue such forms. NOTE – These ‘Record of issue of fire door labels’ forms shall be kept for as long as the particular fire doors are still in existence in the building. These forms carry information on serial number of label issued to each particular fire door and the project where the fire door is being installed. d) Certificate of Conformity for the fire doorset issued by the accredited testing laboratory. e) Catalogues/brochures of hardware used. 9.2.2 Continuous performance of fire doors The owner of building (or representative) shall be responsible for the maintenance of fire door installed in the building and ensure that it is always in good working condition at all times. A routine maintenance record log book (as shown in Annex H) shall be properly kept and made readily available for any future references. If there is any repair, rectification or modification works to be carried out on the fire doors, its manufacturer shall be consulted. This is to ensure that any modifications to the fire doors are acceptable and approved by the recognised testing laboratory. The repair or rectification works also applies to all hardware used on the fire door. In the event of replacement of existing hardware due to wear and tear or damage, the owner of building (or representative) shall be able to replace the hardware with the same brand/model/make and size of hardware without going through the original manufacturer of the fire door. However, if any part of the fire door is damaged due to the removal of the existing hardware or installation of the replacement hardware, the original door manufacturer must be engaged for the rectification works. 10 Maintenance information system 10.1 Records A record system shall be provided to identify and record inspection/check and repairs carried out on the fire resistant doorsets (made readily available for inspection by Regulatory Authority). A maintenance record system may take the form of: a) A maintenance log book, covering routine inspection/check and repairs for all fire doors in a building. The maintenance log book should be kept by the building owner or management corporation. An example of the information is given in Annex H; b) Computer based record system; or c) Other permanent record system that is capable of easy interpretation or generally easily interpreted reports and is to be cross referenced against an individual fire resistant doorset. NOTE – The contents of 10.1(a) should be carefully read in conjunction with the current Fire Safety Regulations on “Duties and Responsibilities of Building Owners and Fire Safety Managers”. 10.2 Required information The following information shall be available from the record system: a) General: 1) Sufficient information to identify the building, the building owner, the sponsor of the prototype fire resistant doorset and the doorset manufacturer. 2) Dates of applied occupancy in the building. 30 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 b) 10.3 3) Manufacturer’s identification / ‘Record of issue of fire door labels’ forms. 4) Updated floor plans indicating door locations and numbers. Identification of fire resistant doorset: 1) Doorset number. 2) Type of door, full dimensions and fire resistance rating. 3) Subsequent repairs or replacements of any parts of the doorset to revert to original/approved suppliers. 4) Items of hardware and where applicable the marking that each item of hardware is required to bear Modifications and replacement of fire doors Any modifications, covering alterations and additions to fire door and its replacement shall be subjected to approval by the Regulatory Authority. 31 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 4 – Terms relating to side-hung fire doors 32 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 (c) Mortice latch with dead bolt Figure 5 – Terms relating to locksets in side-hung fire doors 33 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 6 – Terms relating to sliding fire doors 34 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex A Fire doors and their hardware A.1 Fire doors to be used for particular applications A.1.1 Fire doors to exit staircases, exit passageways, smoke stop lobbies, firefighting / fire lift lobbies. Fire doors to exit staircases, exit passageways, smoke stop lobbies, fire-fighting lobbies shall be self-closing, capable of being open readily and manually by a single action without the use of a key or a tool from the inside of the building, except that one-way locking device is allowed to be provided. These doors shall be constructed to incorporate a vision panel which shall have the requisite fire resistance rating and shall not turn opaque when subject to heat, and there shall be no cut-outs in the door leaf for louvers. A.1.2 Fire doors leading directly into individual fire compartmented residential occupancies Fire doors leading directly into individual fire compartmented residential occupancies shall be self-closing. The provision of vision panel shall not apply to exit doors of residential apartment or maisonette units and there shall be no cut-outs in the door leaf for louvers with the exception of viewing lenses. A.1.3 Fire doors to individual fire compartmented industrial or warehouse occupancies Fire doors to individual fire compartmented industrial or warehouse occupancies shall be self-closing and there shall be no cut-outs in the door leaf for louvers. A.1.4 Fire doors along paths of travel to exits in institutional or assembly buildings Fire doors along paths of travel to exits in institutional or assembly buildings shall be capable of being open readily and manually without the use of a key or a tool from the inside of the building and, where required by the Regulatory Authority, by means of emergency exit device or panic exit device. Such doors shall be self-closing and there shall be no cut-outs in the door leaf for louvers. A.1.5 Fire doors leading directly into cinemas, auditoriums, assembly halls, lecture theatres etc. Fire doors serving spaces of assembly / mass occupation such as cinemas, auditoriums, concert halls, theatres, assembly halls, exhibition halls, lecture theatres, etc., which has to be kept shut and fastened while the building or part of the building is occupied shall be fitted with panic exit device. Such doors shall be self-closing and there shall be no cut-outs in the door leaf for louvers. 35 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 A.1.6 Fire doors to service shafts Where allowed by the Regulatory Authority, fire doors to service shafts and ducts are not required to be installed with automatic self-closing devices, provided such doors are kept closed and locked at all times. A.1.7 Fire doors to plant rooms Fire doors to plant rooms within building shall be self-closing. Louvered openings permit smoke to spread ahead of a fire and shall not be incorporated in fire doors to plant rooms unless specifically approved for the particular situation. The louvered opening shall not be larger than the size in the tested prototype and shall be protected by the automatic-closing device tested in the prototype fire door assembly. A.1.8 Double-acting pivot-swung fire doors to kitchens and health care occupancy Double-acting pivot-swung fire doors to kitchens and health care occupancy shall be self-closing, without selective sequence closing device, and there shall be no cut-outs in the door leaf for vents. A.1.9 Designated fire doors to smoke stop lobbies, fire fighting / fire lift lobbies for staircase re-entry Designated fire doors to smoke stop lobbies, fire fighting / fire lift lobbies for staircase re-entry shall not be fitted with any locking devices to allow for re-entry from the staircase to the interior of the building. These doors shall be self-closing and constructed to incorporate a vision panel, which shall have the requisite fire resistance rating and shall not turn opaque when subject to heat, and there shall be no cut-outs in the door leaf for vents. A.2 Door hardware and fire code requirements for typical applications Typical applications are shown in Table A.1. 36 Table A.1 – Fire door hardware and fire code requirements for typical applications Door hardware and fire code requirements Automatic self closing device Door coordinator device for double leaf door Locking device (egress side) Without key With key Optional [1] Not allowed Optional Not allowed Emergency exit device Panic exit device Electromagnetic holdopen device Smart card, magnetic bar and electromechanical locking device Vision panel Optional Optional Optional [2] Not allowed [1],[3] Required Not applicable Not applicable Optional Not Applicable Typical applications A.1.1 Exit doors to fireprotected staircases, passageways, ramps, smoke stop lobbies, fire lift / fire fighting lobbies Required [5] Required A.1.2 Exit access doors leading directly into individual fireprotected residential occupancies Required Not applicable A.1.3 Exit access doors to individual fire-protected industrial occupancies Required [5] Required Optional Not allowed Optional Not applicable Optional Optional Optional A.1.4 Exit access doors along paths of travel to exits in institutional or assembly buildings Required [5] Required Required Not allowed Required Optional Optional Optional Optional 37 Not applicable Fire code requirement Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 2.3.9 (a) & (e) & (j) & (k); 3.9.2 (a) & (b) & (c) & (d) & (e) & (f); 3.10.3 Table A.1 – Fire door hardware and fire code requirements for typical applications Door hardware and fire code requirements Automatic self closing device Door coordinator device for double leaf door Emergency exit device Locking device (egress side) Without key Typical applications A.1.5 Required [5] Required Required Not allowed A.1.6 Fire doors to service shafts Optional [4] Optional Optional [4] A.1.7 Exit access doors to plant rooms Required Required Optional A.1.8 Required Not allowed Optional Electromagnetic hold open device With key Exit access doors leading directly into cinemas, auditoriums, assembly halls, lecture theatres, etc. Double-acting pivotswung exit access doors to kitchens and health care occupancy Panic exit device Required Optional Optional Optional Not applicable [4] Not applicable Not applicable Not Applicable Not allowed Optional Optional Optional Not allowed 38 Optional Smart card, Vision panel magnetic bar and electromechanical locking device Not applicable Optional Optional Optional Not Allowed Optional Optional Fire code requirement 2.3.9 (a) & (e) & (j) & (k); 3.9.2 (a) & (b) & (c) & (d) & (e) & (f); 3.10.3 3.9.2 (a) & (b) & (c) & (d) & (e) & (f); 3.10.3 Optional Optional 2.3.9 (a) & (e) & (j) & (k); 3.9.2 (a) & (b) & (c) & (d) & (e) & (f); 3.10.3 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Table A.1 – Fire door hardware and fire code requirements for typical applications Door hardware and fire code requirements Automatic self closing device Door coordinator device for double leaf door Locking device (egress side Without key Typical applications Designated exit doors to smoke stop lobbies, fire A.1.9 lift / fire fighting lobbies for staircase re-entry Required [5] Required Not allowed Emergency exit device Panic exit device Electromagnetic hold open device With key Not allowed Not allowed Not allowed Optional [2] Smart card, Vision panel magnetic bar and electromechanical locking device Not allowed Required Fire code requirement 2.3.9 (a) & (e) & (j) & (k) & (l); 3.9.2 (a) & (b) & (c) & (d) & (e) & (f); 3.10.3 NOTE 1 – One-way locking device such as emergency / panic exit device or thumb turn locking device or certain electro-mechanical locking device with one-way locking function is allowed to be used subject to compliance with 2.3.9 (j) of the Fire Code. NOTE 2 – Electro-magnetic or electro-mechanical hold open device shall be activated by the presence of smoke and/or the building alarm system to release the door from being held open. Fire door opening into pressurised exit staircases shall not be held open to comply with 3.9.2 (e) (ii) of the Fire Code. NOTE 3 – Access control to exit doors to staircases of Rapid Transit Systems (RTS) stations using smart card locking device, magnetic bar, electro-mechanical locking device etc. is allowed by the relevant authority. NOTE 4 – Automatic self closing device is required if fire doors to service shafts are not provided with locking device. NOTE 5 – For unequal width double leaf door, care must be taken in hardware selection and installation to ensure that door closer with parallel arm is not impeded by the presence of sequence selector 39 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex B Identification tags DOOR LEAF XYZ Door Manufacturer (S) Pte Ltd Tested to SS 332 Annexes E and F Fire Rating Door Ref Mfg Date : : : H ABC Pte Ltd Tel: 12345678 Fax: 12345678 Address : 123 EFG Road Singapore 654321 DOOR FRAME XYZ Door Manufacturer (S) Pte Ltd Tested to SS 332 Annexes E and F Fire Rating Door Ref Mfg Date : : : H ABC Pte Ltd Tel: 12345678 Fax: 12345678 Address : 123 Tractor Road Singapore 654321 (NOT TO SCALE) 40 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex C Methods for fixing of fire door frames to existing walls (See 7.7) C.1 General In cases where fire door openings must be used during the construction period of any building and it is not reasonably possible to mask or guard built-in doors and frames to such openings against possible damage at the time, or in cases where fire doors may have to be inserted in existing structures, approval may be given for the fixing of door assemblies into prepared openings in concrete or masonry walls at a time other than when the wall is built. Methods for accomplishing the above are limited by the need to provide the following: a) b) Stiffening of the frame sections by means of: 1) fully backfilling the frame cavities at jambs with cement mortar or equivalent; and 2) grouting the frame cavity at the head in a manner that will prevent a flame passage across the top of the frame. Adequate mechanical restraint for frame sections against any bowing, rotational movement or dislodgement from the wall arising from differential expansion under fire conditions, door-slam forces or the dead weight of the fire door. Where frames are exposed to corrosive environment or where they are external doors exposed to weather, all packing, shims, screws, bolts, etc, being part of the anchorage to the wall should be corrosion-resistant. The surfaces of the opening into which the frame is to be fixed and grouted should be suitably prepared to achieve a rough surface to allow good bonding with the grout. The opening should be of a size to accommodate the frame and a clearance should be provided around the frame edge to allow grouting from the side and observation of the anchorage before grouting is proceeded with. Such clearance should not exceed 25 mm. C.2 Methods C.2.1 General As an alternative to incorporating the frame in the wall as construction progresses, there are, in the trade, several recognised acceptable and practicable methods. However, none of the method has been subject to the standard fire-resistance test. The methods are as follows: a) Fixing by means of bonded hairpin anchors; b) Fixing by means of threaded anchors; c) Fixing by means of Z-shaped anchors to lightweight partition wall; and d) Fixing by means of weld anchors. 41 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 C.2.2 Fixing the frame by means of bonded hairpin anchors The frame should be fixed as follows: a) At vertical spacings not greater than those given for frame anchors in the prototype, securely fix 3.5 mm diameter corrosion-resistant steel wire anchors of a hairpin shape (see Figure 7(c)), to a depth of not less than 60 mm, either by building in or by drilling and grouting into the reveals of the opening. b) 7(c). Position the frame while the anchors are bent up as shown for the upper anchor in Figure c) When the frame is finally positioned, bend out every anchor so that each fits inside the channel formed by the frame section as shown for the lower anchor in Figure 7(c) (a special tool may be needed for this operation). d) Insert a locking bar into each anchor section, as shown in Figure 7(a). e) After plumbing and bracing, complete the installation by fully grouting the frame cavities with cement mortar or concrete. C.2.3 Fixing the frame by means of threaded anchors The frame should be fixed as follows: a) At vertical spacings not greater than those given for frame anchors in the prototype, fillet weld 25 mm x 5 mm low carbon or stainless steel connecting straps between both flanges at the back of the frame (see Figure 8(a)). b) Through the hole(s) in each strap, secure the frame into the opening by means of steel or brass threaded anchors of not less than 5 mm diameter and of sufficient length to obtain not less than 25 mm of engagement inside the reveals of the opening. Obtain true-plumb frame jambs by placing packers as shown in Figures 8(a) and 8(b). c) Provide holes in the door stop faces for the purpose of entering and tightening the threaded anchors. Where the heads of the threaded anchors are to remain exposed, provide metal sleeves as shown in Figures 8(a) (ii) and 8(a) (iv). Where the heads of the threaded anchors are to remain unexposed, fill the holes with a durable non-shrinking material and leave flush with the surface of the frame. d) Complete the installation by fully grouting the frame cavities with cement mortar or equivalent. C.2.4 Fixing of frames by means of weld anchors (for both single and double leaf doors) The frame should be fixed as follows: a) At vertical spacings not exceeding that of the prototype. Expansion anchors are fastened the wall. (For jamb depth exceeding 200 mm, two anchors are used.) (See Figures 9 and 10) b) Frame is positioned and fastened to expansion anchors by means of welding. Steel joint pieces connect diameter 9 mm vertical rod to expansion anchors. This fixing method is used on vertical and head jambs. c) After plumbing and checking, void jamb cavities are filled with cement mortar grout. d) Clearance of frame edge to structural opening to be of minimum 30 mm each side to allow for access of welding. 42 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 7 – An example on the fixing of frames by hairpin anchors 43 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 8 – An example on the fixing of frames by threaded anchors 44 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 9 – An example on the fixing of frames by weld anchors for single-leaf door 45 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 10 – An example on the fixing of frames by weld anchors for double-leaf door 46 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex D Calculation for the forces of closing sliding doors D.1 Formula to determine Force Based on British Research Establishment Report 1979 on Fire Doors and Door Closers Force required to open sliding door = Mass x Coefficient of Friction The coefficient is between 0.2 to 0.9 as mentioned in the BRE Report. D.2 To establish the force for exit sliding doors Assumptions Let us take, say 0.25 coefficient of friction for exit sliding doors and the gravitational pull as 10 m/s2. Using a weight of 45 kg, which is common for females, and children who would need to use the sliding exit door for escape purposes in an emergency. Then the force required Nearest whole number D.3 = = = 45 kg x 10 m/s2 x 0.25 112.5 N 110 N To establish the force for intermediate sliding doors Assumption Taking the coefficient of friction of 0.275 and assuming that the friction for intermediate doors is higher, and the gravitational pull remains as 10 m/s2 Therefore assuming the weight of an average adult is about 65 kg to open a fire resistant sliding door for access and not exit purposes. Then the force required Nearest whole number = = = 65 kg x 10 m/s2 x 0.275 178.75 N 180 N 47 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex E Fire-resistance tests E.1 Principle The test procedure enables the fire resistance of an element of construction to be determined on the basis of the length of time for which a specimen satisfies one or more criteria when exposed to the specified heating conditions. The performance of a door assembly is influenced by the mechanical features of construction. The results of a fire test may not always be valid for a construction having overall dimensions larger or much smaller than those of the test specimen. Oversize variation of doorset is subjected to assessment by recognised testing laboratory or unless otherwise permitted under 6.1. E.2 Furnace The furnace shall be capable of subjecting one side of the specimen to the heating condition as specified in E.2.1 to E.2.3. E.2.1 Temperature rise The temperature rise within the furnace shall be controlled so as to vary with the time within the limits specified in E.2.3, according to the following relationship: T - T0 = 345 log10 (8t+1) Where: t is the time, expressed in min. T is the furnace temperature at time t, expressed in oC. T0 is the initial furnace temperature, expressed in oC. The standard time-temperature curve representing this function is shown in Figure 11 and the relationship expressed gives the values shown in Table 3. E.2.2 Measurement of furnace temperature E.2.2.1 The furnace temperature is the average of the temperatures recorded by thermocouples arranged within the furnace. E.2.2.2 These thermocouples shall not be less than one to every 1.5 m2, or part thereof, of the exposed surface area of the test construction. In any case, the number of thermocouples shall be not less than five. E.2.2.3 The furnace thermocouples shall have measuring junctions that consist of either: a) Bare nickel chromium/nickel aluminium wires, 0.75 mm to 1.50 mm in diameter, welded or crimped together at their ends, supported and insulated from each either in a twin bore porcelain insulator except that the wires for 25 mm approximately from the weld or the crimp shall be exposed and separated from each other by at least 5 mm (see Figure 12). Such thermocouples shall be replaced after 6 h exposure or be recalibrate after every 6 h of use; or b) Nickel chromium/nickel aluminium wires contained within a mineral insulation and in a heat resisting steel sheath of diameter 1.5 mm, the hot junctions being electrically insulated from the sheath. The thermocouple hot junctions shall project 25 mm from a porcelain insulator. 48 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Each thermocouple hot junction shall be 100±10 mm from the nearest point of the test specimen at the start of the test. It shall be maintained between 50 to 150 mm from the face of the specimen during the test should any deflection or distortion of the specimen take place. E.2.3 Tolerances The percentage deviation (p) in the area under the curve of the average temperature recorded by the specified furnace thermocouples versus time, from the area of the standard time-temperature curve shall be within the following tolerances: a) ±15 % for 0< t ≤10 b) ±10 % for 10< t ≤30 c) ±5 % for t > 30 p= A− B X 100 B where: A is the area under the actual furnace time-temperature curve B is the area under the standard time-temperature curve All areas shall be computed by the summation of areas at intervals not exceeding 1 min and shall be calculated from time zero. At any time after the first 10 min of test the temperature recorded by any thermocouple in the furnace shall not differ from the corresponding temperature of the standard time-temperature curve by more than ± 100 oC. For specimens incorporating a significant amount of combustible material, the deviation of any one thermocouple shall not exceed 200 oC. E.3 Preparation of test specimen E.3.1 Dimensions The complete assembly to be tested shall be full size. When either of the dimensions of the full-size construction is larger than it is possible to accommodate in the furnace, the test specimen shall have the maximum size that can be accommodated; in such a case, the appropriate width or height shall not be reduced by more than 10 % of the overall internal size of the furnace. E.3.2 Construction The test shall be performed on a complete door assembly as intended to be used in practice, incorporating all hardware and other equipment. 1 The finish and form of the specimen shall be representative of the finish and form that would be used in practice. The door shall be tested in a wall of the type in which it is intended to be used particularly when it forms part of a prefabricated or industrialised system. When this cannot be specified, the wall may be of concrete or brick having a thickness of: a) about 100 mm for a test having an anticipated duration of 2 h or less; or 1 The term “hardware” includes such items as hinges, latches, door handles, locks, keyholes, viewing lenses, sliding gear, closing devices, electrical wiring and any other items which may influence the performance of the specimen being tested. 49 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 b) about 200 mm for tests of longer duration. The mounting of the specimen shall be representative of its use in practice so that appropriate clearances between the door and the frame or the surround exist. In the case of hinged timber doors, the clearance between the door edge and frame shall be representative of that likely to be obtained in practice and, if this cannot be specified, the clearance shall be not less than 3 mm. The clearance shall be stated in the test report. The assembly shall be fitted with the frame flush with the unexposed face of the wall unless the type of door precludes such fixing or if it is likely to reduce the severity of exposure or be unrepresentative of its use in practice. Sliding door assemblies shall be mounted in accordance with the conditions of 4.3.4. E.3.3 Conditioning Specimens containing hygroscopic materials or other materials, which can be affected by moisture, shall be conditioned to equilibrium with the prevailing conditions in the laboratory, which shall be within the following limits: a) temperature (dry bulb) : 25 oC ± 15 oC; and b) relative humidity : 60 % to 85 % Doors made entirely of metal or of metal and glass do not require any conditioning. The wall containing the door shall be constructed not less than 2 weeks before the test in the case of a brick wall or not less than 4 weeks in the case of a concrete wall. To minimise the effect on frame temperature of excessive moisture in concrete walls, it may be necessary to condition them to a state of equilibrium. E.4 Test procedure The specimen door shall be exposed on one face to the heating conditions specified in E.2. The requirements for exposure to fire are specified in 4.3. NOTE – The location of thermocouples for the measurement of furnace temperatures shall be with reference to the exposed face of the wall except in the case of sliding doors fixed on the furnace side of the wall, when the exposed door face shall be used as the reference plane. Measurements and observations specified in E.6 shall be made during the test. The test shall be terminated when the door nor longer satisfied the criteria under which its performance is being judged or at any earlier stage by prior agreement between the sponsor and the recognised authority, even if no failure under any of the criteria has occurred. E.5 Measurements and observations E.5.1 Furnace pressure The static pressure in the furnace shall be measured, for example, by using the static pressure probe. The measurements of the static pressure shall be located along a vertical axis on one side of and close to the door assembly in line with the top and bottom edges of the clear opening. The pressure shall be controlled so that by 5 min from commencement of the test a pressure gradient of 8.5±2 Pa per 1000 mm height exists together with a neutral pressure axis at a height of 500 mm above notional floor level. The pressure at the top of the specimen shall be at no time exceed a maximum of 20 Pa. 50 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 E.5.2 Unexposed face temperature The temperature of the unexposed face of the door assembly shall be measured by means of thermocouples (see Figure 13) with a maximum wire diameter of 0.5 mm, brazed to a 0.2 mm thick by 12 mm diameter copper disc. The disc shall be covered with a 30±0.5 mm x 30±0.5 mm x 2±0.5 mm (thick) insulating pad. The pad material shall have a dry density of 900±90 kg/m3, a thermal conductivity of 0.13 W/m oK ±10 % at 100 oC and shall be of a material capable of withstanding temperature of 400 oC without any change in mechanical or physical properties. The insulation pads shall be slotted or provided with holes to accommodate the thermocouple wires. The pad with the disc, may be fixed to the surface of the specimen by some mechanical means fixed through the areas outside that covering the copper disc or by the use of a heat-resisting adhesive, ensuring that no adhesive gets between the disc and the surface of the specimen. Whatever fixing means used, there shall be no significant effect on the transmission of heat through the specimen to the copper disc. Internal thermocouples for measuring cavity temperatures within the test specimens or of temperatures within materials should remain insulated as close as possible to the junction. Any bare wires shall be kept as far apart as possible to minimise electrolytic effects. All holes used for egress of the wires are to be suitably sealed against the flow of hot gases. For determining the mean temperature rise, at least five thermocouples shall be fixed on the face of the door, excluding the frame, one at the centre and the others at the centre of each quarter-section. None of these five thermocouples shall be fixed on positions with through-metal connections or closer than 100 mm to the edge of the door leaf. If insulation data are required on glazed doors or multileafed doors, the thermocouples shall be distributed as uniformly as possible. The maximum temperature rise on the unexposed face shall be determined from the five thermocouples specified above plus additional thermocouples (fixed or mobile) which may be used over through-metal connections or at other points considered to be of special interest. Temperature measurements shall also be made on the frame members on the faces parallel to the plane of the wall. Thermocouples shall be fixed at mid-height of the two vertical sides, at the centre of the head member and at any other position where higher temperatures may be expected. The thermocouples shall be located approximately 15 mm from the edge away from the door. E.5.3 Radiation from unexposed face Radiant heat flux shall be measured from the unexposed face of the specimen, by means of a radiometer of other suitable means, along an axis normal to the centre of the door and at a known distance from the edge. This distance shall be such that the field of view just covers the diagonal of the door assembly. E.5.4 Cotton pad test The passage of flames and gases through cracks, holes or other openings in or around a door shall be determined by applying a cotton pad to such openings at regular intervals during the test. The cotton pad shall not be in contact with the element but shall be held for not less than 10 s and not more than 30 s between 20 and 30 mm away from and centrally opposite any cracks, holes or other openings in or around the door. The pad shall not be re-used if it has absorbed any moisture or become charred during a previous application. The cotton pad, measuring approximately 100 mm square x 20 mm think, shall consist of new undyed and soft cotton fibres without any admixture of artificial fibres, and shall have a mass between 3 and 4 g. The pad shall be conditioned by drying in an oven at 100 °C for at least 0.5 h. The pad shall be attached by wire clips to a 100 mm x 100 mm frame of 1 mm diameter wire, to which a wire handle approximately 750 mm long is fixed. Note shall be made of the time when the first ignition of the cotton pad occurs and the position where this takes place. With doors having no, or only slight, 51 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 insulation, it may not be possible to apply this test shortly after the commencement of heating; in such cases note shall be made of the time after which it is practicable to apply this test. The use of the cotton pad test shall be discontinued at the time of loss of insulation. E.5.5 Other observation Note shall be made of the deformation of the specimen and the time when collapse of the whole or part of the specimen takes place. Note shall also be made of any flaming sustained for 10 s or more on the unexposed face and the emission of smoke. The ability of the door to be opened after the test shall be noted. E.6 Performance criteria The fire resistance of the door assembly shall be determined by one or both of the following criteria for loss of integrity and insulation. E.6.1 Loss of integrity E.6.1.1 Flaming The time shall be noted at which flaming is sustained for 10 s or more on the unexposed. E.6.1.2 Cotton pad test The time shall be noted at which the first ignition of the cotton pad occurs. When the cotton pad test cannot be used because of the level of radiation from the door, failure shall be deemed to have occurred if an unobstructed gap of 6 mm in width by 150 mm in length develops. Ignition of the pad shall be deemed to have occurred if, during application of the cotton pad test in the prescribed manner, the cotton fibres of the pad are observed to be glowing. E.6.1.3 Through gap test Failure under the gap criteria occurs when gaps or fissures in excess of either 6 mm in width by 150 mm in length, or 25 mm in diameter, develop in the specimen during the test period. These gaps criteria may be used at any location except the threshold. E.6.2 Insulation E.6.2.1 Mean unexposed face temperature – leaf The time shall be noted at which the mean unexposed face temperature of the door as measured by the thermocouples specified in E.5.2 for this purpose, exceeds the initial temperature by more than 140 0C. E.6.2.2 Maximum unexposed face temperature – leaf The time shall be noted at which the maximum temperature on the unexposed face exceeds the initial temperature by more than 180 0C. Doors incorporating glazing and doors constructed of sheet steel shall be considered to have failed to satisfy this criterion. E.6.2.3 Mean unexposed face temperature – frame The time shall be noted at which the mean temperature on the unexposed face of the frame exceeds the initial temperature by more than 140 0C. 52 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 E.6.2.4 Maximum unexposed face temperature - frame The time shall be noted at which the maximum temperature on the unexposed face of the frame exceeds the initial temperature by more than 180 0C. E.6.2.5 Radiation from door The radiation measurements from the unexposed face of the door shall be recorded. The Regulatory Authority shall be consulted in the specification of limits which are considered safe for the storage of materials and for personnel. E.7 Test report The test report shall include the following information: a) Name of testing laboratory; b) Name of sponsor; c) Date of test; d) Name of manufacturer and the trade-name (if any) of the product; e) Details of construction and conditioning of the specimen and the materials used, together with drawings; these shall be lodged with the testing authority for inclusion in the report where appropriate; clearances and gaps between the door and the frame shall be fully recorded; f) Description of fixing of the test specimen to the surrounding wall and of the joint, if any, between the door assembly and the surrounding wall; g) Description of glazing, if any; h) The side of the door exposed to heating; i) Test results: 1) furnace time/pressure chart and temperature curves; 2) time/temperature results as required by E.6.2.1, E.6.2.2, E.6.2.3 and E.6.2.4; and 3) times at which various performance criteria were no longer complied with. j) Date for establishing the effective black-body temperature of the door and for determining the distances the unexposed face at which radiation levels exceeded specified limits; k) Any other information about the performance of the specimen during the test, including the ability of the door to be opened after cooling. The results only relate to the behaviour of the specimen of the element of construction under the particular conditions of test. They are not intended to be the sole criteria for assessing the potential fire performance of the element in use nor do they reflect the actual behaviour in fires. 53 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Table 3 – Temperature rises as a function of time Time,t Elevation of temperature, T – T0 Min o C o 5 556 1001 10 659 1186 15 718 1292 30 821 1478 60 925 1665 90 986 1775 120 1029 1852 180 1090 1962 240 1133 2039 360 1193 2147 F 54 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 11 – Standard time-temperature curve 55 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 12 – Furnace thermocouple assembly 56 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 13 – Specimen surface thermocouple junction and insulating pad 57 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex F Door closer requirements and test methods F.1 General F.1.1 The door closer, when installed in accordance with the Manufacturer’s installation instructions, shall be capable of closing the test door from any angle to which it may be opened. F.1.2 The selection of door closer shall be according to Table 4. F.1.3 The door closer shall not include a manual hold-open device. F.1.4 Control regulators shall either be concealed, or operable only by means of a tool. F.1.5 The design of a door closer shall be such that it is not possible to inhibit its closing action in any way, without the use of a tool. F.1.6 Any incorporated delayed action function shall be capable of adjustment to less than 25 s, between the door closing angles of 120º and the end of the delay zone. F.1.7 The door closer shall have been incorporated in a door assembly that has satisfied the appropriate criteria of a fire test. F.2 Classification F.2.1 Door closers shall be classified according to a six digit coding system. F.2.2 Category of use (first digit) Generally, two grading shall be used: a) Grade 3 - For closing doors from at least 105º open. b) Grade 4 - For closing doors from 180º open. F.2.3 Number of test cycles (second digit) Only one test duration is identified, i.e. Grade 8 - 500,000 test cycles. F.2.4 Test door mass (third digit) Seven test door mass grades and related door closer power sizes are identified according to Table 4. Where a door closer provides a range of power sizes both the minimum and the maximum sizes shall be identified. Example: The following marking denotes a door closer with a range of power sizes from size 2 to size 5: 3 8 5 2 58 1 1 0 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.2.5 Fire behaviour (fourth digit) Two grades are identified: a) Grade 0 - not suitable for use on fire door. b) Grade 1 - suitable for use on fire door. F.2.6 Safety (fifth digit) All door closers are required to satisfy the Essential Requirement of safety in use. Therefore, only Grade 1 is identified. NOTE – Safety in use as defined in CEN CPD Council Directive , refers to the construction work designed and built in such a way that it does not present unacceptable risks of accidents in service or in operation such as slipping, falling, collision, burns, electrocution, and injury from explosion. F.2.7 Corrosion resistance (sixth digit) Five grades of corrosion resistance are identified: a) Grade 0 : No defined corrosion resistance. b) Grade 1 : Mild resistance. c) Grade 2 : Moderate resistance. d) Grade 3 : High resistance. e) Grade 4 : Very high resistance. Table 4 – Requirements for closing and opening moments, and the door closer efficiency Door closer power size Recommended door leaf width Test door mass mm max. kg 1 <750 2 3 4 5 6 7 850 950 1100 1250 1400 1600 Closing moment between 0º and 4º 20 Nm min. 9 Nm max. <13 40 60 80 100 120 160 13 18 26 37 54 87 <18 < 26 < 37 < 54 < 87 < 140 between 88º and 92º Nm min any other angle of opening Nm min. Opening moment between 0º and 60º Nm max. Door closer efficiency between 0º and 4º % min. 3 2 26 50 4 6 9 12 18 29 3 4 6 8 11 18 36 47 62 83 134 215 50 55 60 65 65 65 NOTE 1 – Where the actual size and mass of door to which the door closer is to be fitted relates to two sizes of door closers, the larger power size of door closer should be used. NOTE 2 – The door widths given are for standard installations. In the case of unusually high or heavy doors, windy or draughty conditions, or special installations, a larger power size of door closer should be used. 59 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.3 Requirements F.3.1 Durability F.3.1.1 A single action door closer shall be able to close a test door conforming to F.4.2, from an opening of 90o, for minimum of 500,000 test cycles. F.3.1.2 A double action door closer shall be able to close a test door conforming to F.4.2 from an opening of 90o, for a minimum of 250,000 test cycles in each direction. F.3.1.3 After the initial 100,000 test cycles, the door closer shall be capable of stopping the test door before the 90º open position when tested in accordance with F.5.2.8. F.3.2 Closing moment and efficiency After 5,000 test cycles and after 500,000 test cycles, the measured closing moments and efficiency shall not be less than the values stated in Table 4, for the particular power size of closer being tested. F.3.3 Opening moment After 5,000 test cycles the maximum measured opening moment shall not be more than the values stated in Table 4, for the particular power size of closer being tested. F.3.4 Closing time After 5,000 test cycles and after 500,000 test cycles, the closing time, from a door opening angle of 90º, shall be capable of adjustment to 3 s or less, and 20 s or more. After 500,000 test cycles, the closing time set at 5,000 test cycles shall not have increased by more than 100 %, or decreased by more than 30 %. F.3.5 Angles of operation The door closer, when installed according to the Manufacturer’s standard installation instructions shall permit the test door to open according to its grade under F.2.2 and on closing shall control the door from a minimum angle of 70º down to the closed position. F.3.6 Overload performance at 5,000 and 500,000 test cycles The door closer shall be capable of withstanding the closing overload tests of F.5.2.7.4 and F.5.2.9.4 and where relevant F.5.2.7.5. F.3.7 Fluid leakage Throughout the test, there shall be no leakage of fluid from the door closer. F.3.8 Damage Throughout the test, there shall be no damage to the door closer or its arms that would adversely affect its performance. F.3.9 Latch control (optional) A door closer , if incorporated with a separate control during the final stage of door closing e.g. to enable accelerated closing to overcome the resistance of a latch bolt, shall be effective over a maximum range of 15º from the closed position, and shall be adjustable. 60 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.3.10 Delayed closing (optional) F.3.10.1 If provided with a delayed closing function, the door closer shall be capable of adjustment, by means of a separate regulator, such that the closing time from 90º to the end of the delay zone, at an ambient temperature of 20 ºC, is not less than 20 s. The delay zone shall not extend below the 65º open position. The moment required to override manually the delay action shall not exceed 150 Nm when tested in accordance with F.5.2.7.5. F.3.10.2 When tested in accordance with F.5.2.7.5, the delay time at the conclusion of 5,000 cycles shall be between 10 s and 30 s. F.3.11 Adjustable closing force (optional) If provided with an adjustable closing force function, the door closer shall comply with the performance requirements of F.3, at both the minimum and maximum power settings claimed by the Manufacturer. The settings shall be tested using different door closer. F.3.12 Zero position (for double action door closers only) The amount of free play at the zero position of a new door closer shall not exceed 3 mm, and after 500,000 test cycles shall not exceed 6 mm, when tested in accordance with F.5.2.9.6. F.3.13 Corrosion resistance F.3.13.1 The requirements in Annex G for different type of materials used, shall be met, and classify accordingly (See F.2.7). F.3.13.2 After being subjected to the relevant salt spray test, the closing moment of the door closer shall be not less than 80 % of the closing moment measured prior to the test (See F.6). F.3.13.3 The acceptance conditions defined in G.1.7, shall be met for all surfaces of the door closer which are visible when the door closer is fitted in service. F.4 Test apparatus F.4.1 General F.4.1.1 Single action door closers The test apparatus shall consist of a test door mounted in a frame, capable of manual opening to 180º and with automatic actuating means. F.4.1.2 Double action door closers The test apparatus shall consist of a test door mounted in a frame, capable of manual opening to at least 120º in each direction and with automatic actuating means to enable the required opening angle in alternate directions. F.4.1.3 Actuating means The actuating mechanism shall be adjustable to open the test door smoothly to 90º in one direction, in a time of between 2 s. and 3 s, and allowing the test door to fully close under the control of the door closer under test. It shall apply an opening force at a distance of between 500 mm and 700 mm from the vertical axis of rotation of the door. The actuating means shall not impede the return of the test door to the fully closed position, under the action of the door closer being tested. 61 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.4.2 Test door F.4.2.1 The test door shall be 2,000 mm high, and of any width between 750 mm and 1,200 mm except that, for door closers which do not carry the mass of the door or act as a door pivot, the test door may be between 400 mm and 2,000 mm high. It shall have means of attaching weights so that the door mass can be adjusted to suit the power size of door closer under test. The test door and frame shall be of sufficient rigidity such that no visible distortion takes place during the test sequence. F.4.2.2 The position of the centre of gravity shall be nominally at the mid-height position of the test door leaf, and 500 mm from the vertical axis of the hinges or pivots. F.4.2.3 The test door shall be mounted vertically, on hinges or bearings or, in the case of door closers that pivot the door, on the unit under test. Supporting hinges or bearings forming a part of the test apparatus shall be such that the moment to overcome friction shall not exceed the values stated in Table 4. The moment shall be determined by measuring the maximum force in Newtons required to slowly (not faster than 1º/s) open and close the test door fully, the force being applied perpendicular to the door face. The frictional moment is expressed as the product of the measured force and its distance in metres from the vertical axis of rotation. F.4.2.4 Means shall be provided for recording the number of operating cycles of test door. F.4.3 Force measurement A force gauge or comparable device, with an accuracy of 1.5 % of reading or better shall be provided for determining the opening and closing moments. F.4.4 Closing overload test apparatus F.4.4.1 The apparatus shall comprise a cable/pulley/mass system as illustrated in Figures 14 and 15. F.4.4.2 The overload test weight shall be in accordance to Table 5. Table 5 – Overload test weight and test door friction Door closer power size Test door mass (kg) Overload test weight (kg) Test door friction Nm max 1 2 3 4 5 6 7 20 40 60 80 100 120 160 15 18 21 24 27 30 33 0.1 0.2 0.3 0.4 0.5 0.6 0.8 NOTE – Door closers under size 1 and 2 are NOT considered suitable for use on fire doors. 62 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.4.4.3 The cable shall be of steel, having a diameter of between 4 mm and 6 mm, and shall be attached as shown in Figures 14 and 15. The pulleys shall have a minimum diameter of 150 mm and shall be fitted with free-spinning ball or needle roller bearings F.4.4.4 The angle between the cable and the face of the test door when it is opened at 90º ± 5º shall be 30º ± 5º, and when the door is in the closed position, shall be 90º ± 5º. F.4.4.5 Means shall be provided by which the test door can be suddenly released from an open position of 90º. F.4.4.6 Means shall be provided for stopping the falling weights, when the test door reaches 15º from the closed position, in such a manner that further closing of the test door is not impeded by the weight or the pulling cable. F.4.4.7 An energy absorbing stopper may be fitted to the test apparatus at 5º open position to stop the test door at the closed position. F.5 Test methods F.5.1 Sampling F.5.1.1 Three different samples shall be used for testing (Refer to Figure 16): a) Test sample A for general requirements; b) Test sample B for mechanical performance and durability; and c) Test sample C for corrosion resistance. F.5.1.2 For door closers incorporating an adjustable closing force facility, samples A and B shall each consist of two units, one adjusted to the minimum, and the other adjusted to the maximum power size claimed by the manufacturer. Sample C shall be adjusted to its minimum power size. In each case, the door closer shall be adjusted so that its minimum closing moment between 0º and 4º are as near as possible to the values specified in Table 4. F.5.2 Durability test F.5.2.1 Apply weights to the test door so that its total mass and centre of gravity are in accordance with Table 4 and F.4.2.2, for the particular power size of closer being tested. F.5.2.2 Mount the door closer on the test apparatus according to the manufacturer’s standard installation instructions. F.5.2.3 Open the test door to the maximum angle permitted by the closer under test and verify that the door closer complies with F.3.5. F.5.2.4 Adjust the door closer regulator (s) such that the test door closes smoothly from 90º to fully closed within a time of between 3 s to 7 s. If the closer has an additional regulator for the latch control, adjust this to provide a smooth transition from closing to latching speed and to provide a positive but not slamming action. Backcheck or delayed action closers shall have that feature set to its minimum effect or rendered inoperable. F.5.2.5 Adjust the actuating mechanism according to F.4.1.3. Ensure that the test door has returned fully to the closed position before initiating the next opening operation. 63 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.5.2.6 Continue cycling for a total of 5,000 test cycles. In the case of double action door closers, continue alternate cycling in each direction for a total of 5,000 test cycles. F.5.2.7 Tests at 5,000 test cycles F.5.2.7.1 Calculation of opening/closing moments Record the ambient temperature. Allow the door closer to cool to within 2 ºC of ambient temperature. Adjust the closing time regulator(s) to a fully open position and measure both the opening and closing forces of the door closer. The forces are measured by slowly (not faster than 1º/s) opening and closing the test door using the force gauge positioned perpendicular to the door face when the door is in an open position from 0º to 4º and from 88º to 92º. In each case the maximum value is to be noted. Take the average of three readings. Use the same method to open the door to a 60º opening. Note the maximum opening force obtained during this procedure. Take the average of three readings. Allow the door to close from its maximum opening angle permitted by the closer under test to 2º and note the minimum closing force obtained during its travel. Take the average of three readings. In the case of double action door closers this procedure shall be carried out in each direction. Calculate the opening and closing moments in each case as the product of these average gauge readings and the distance of the force gauge in metres from the vertical axis of the hinges or pivots. Verify that the values of the opening/closing moments are in accordance with Table 4 for the particular power size of the closer being tested. F.5.2.7.2 Efficiency Calculate the door closer efficiency as a percentage as follows: Efficiency = CF × 100 OF Where CF = Average of maximum closing force between 0o and 4o OF = Average of maximum opening force between 0o and 4o Verify that the value of the efficiency is in accordance with the values stated in Table 4 for the particular power size of door closer being tested. F.5.2.7.3 Closing time Adjust the closing time regulator(s) as necessary and verify that the closing time from 90º is capable of adjustment to 3 s or less and 20 s or more according to F.3.4. F.5.2.7.4 Closing overload test Adjust the closing time from 90º open to 10 s. Hold the test door open at 90º with the cable and weights attached, according to F.4.4, Figure 14 and 15, and then release the door, allowing the weights to fall. This test shall be carried out 10 times. NOTE – The falling mass is stopped when the door is 15º open, the door continuing to close under its own momentum until it is stopped by the energy absorbing stop at 5º or the frame at 0º, or in the case of double action closers, until it stops of its own accord. 64 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.5.2.7.5 For delayed closing door closers only Adjust the door closer to the maximum delay time and open the test door to 90º. With a force gauge positioned perpendicular to the door face, measure the force and calculate the moment required to move the test door out of the delay zone in a time of between 2 s and 5 s. The closer shall be rejected if the required moment is greater than 150 N m or less than twice the 90º closing moment stated in Table 4 for the particular power size of closer being tested. Restabilise the door closer to a temperature of 20 ºC, and open the test door to 95º. Verify that the closing time from 90º to the end of the delay zone can be adjusted to at least 20 s in accordance with F.3.10. Adjust the test door actuating mechanism to open the test door smoothly to 95º in a time of between 2 s and 4 s, allowing the test door to close under the control of the door closer under test. Adjust the door closer to a delay time of 20 s from 90º to the end of the delay zone. Ensure that the test door returns fully to the closed position, and after a waiting period of 270 s start the next opening operation. Continue cycling to a total of 500 test cycles. During the last 5 cycles of the test, measure the delay time from 90º to the end of the delay zone and verify that each measurement is between 10 s and 30 s. F.5.2.8 Continuation of cycling tests F.5.2.8.1 All door closers except those incorporating backcheck function Reset the closing time regulator(s) in accordance with F.5.2.4 and record the time. The regulator(s) shall remain unaltered until completion of F.5.2.9.1. Resume the cycling test to a total of 500,000 test cycles. F.5.2.8.2 For door closers incorporating backcheck function Reset the closing time regulator(s) in accordance to F.5.2.4, except that the backcheck function is tested by setting up the actuating means of the test apparatus in such a way that it can accelerate the door to an opening angle of 50º at such a rate that it will: a) achieve an opening angle of 110º without backcheck effect in operation (for door closers with adjustable backcheck); or b) have an angular velocity of 1 rad/s ± 10 % at an opening angle of 60º (for door closers with fixed backcheck and for door closers with an opening angle of less than 110º). (NOTE - 1 rad =180º / π ) F.5.2.8.3 For door closers incorporating an adjustable backcheck function With the same setting of the test apparatus as obtained in F.5.2.8.2, adjust the backcheck action to arrest the test door at the 80º open position and continue the cycling test for a total of 100,000 test cycles. Allow the door closer body surface to cool to within 2 ºC of the original ambient temperature recorded in F.5.2.7.1 and verify that the test door is arrested before the 90º open position. The adjustable backcheck shall not be readjusted prior to this test. Upon completion remove the backcheck action and reset the test apparatus in accordance with F.4.1. Continue cycling for a further 400,000 test cycles. 65 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.5.2.8.4 For door closers incorporating a fixed backcheck function With the same setting of the of the test apparatus as obtained in F.5.2.8.2, the test door shall be arrested by the backcheck at the 90º open position or less. Continue the cycling test for a total of 100,000 test cycles. Allow the door closer body surface to cool to within 2 ºC of the original ambient temperature recorded in F.5.2.7.1 and verify that the test door is arrested before the 90º open position. Continue cycling for a further 400,000 test cycles with the test apparatus set to open the test door to an opening angle of between 70º and 75º. F.5.2.9 Tests at 500,000 test cycles F.5.2.9.1 Closing time Allow the door closer body surface to cool to within 2 ºC of the original ambient temperature recorded in F.5.2.7.1 and measure the time taken for the test door to close from 90º to the fully closed position. The door closer shall be rejected if this time is more than 2 times or less than 0.7 times the original value set in F.5.2.8. F.5.2.9.2 Calculation of closing moments and efficiency Repeat the tests of closing moments and efficiency specified in F.5.2.7.1 and F.5.2.7.2. Verify that the values of minimum closing moments and efficiency are not less than the values stated in Table 4. Door closers with adjustable closing force are considered acceptable if, after adjustment, they can achieve at least the values stated in Table 4. F.5.2.9.3 Closing time Adjust the door closer regulator(s) to give the minimum closing speed and verify that the closing time from 90º open to fully closed is not less than 20 s. F.5.2.9.4 Closing overload tests Carry out a further ten closing overload tests according to F.5.2.7.4. F.5.2.9.5 For delayed closing door closers only Restabilise the door closer to a temperature of 20 ºC, and open the test door to 95º. Verify that the closing time from 90º to the end of the delay zone can be adjusted to at least 20 s in accordance with F.3.10. F.5.2.9.6 For double action door closer only Remove the door closer from the test door and carry out the following test. Allow the closer to stabilise to ambient temperature and attach an indicator strap to the door closer spindle carrying a pointer 300 mm long measured from its tip to the spindle centre. Apply a moment of 5 Nm to the spindle in each direction and measure the deflection of the pointer from the zero position. The closer shall be rejected if the total measured free play exceeds 6 mm. 66 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 F.6 Corrosion resistance The tests shall be conducted according to F.6.1 to F.6.4. F.6.1 General F.6.1.1 Apply weights to the test door so that its total mass and centre of gravity are in accordance with Table 4 and F.4.2.2, for the particular power size of closer being tested. F.6.1.2 Mount the door closer on the test apparatus according to the manufacturer’s standard installation instructions. F.6.2 Calculation of closing moments F.6.2.1 Adjust the closing time regulator(s) to a fully open position, open the door to at least 95º, and measure the closing forces of the door closer. The forces are measured by slowly (not faster than1º/s) allowing the door to close using the force gauge positioned perpendicular to the door face when the door is in an open position from 92º to 88º and from 4º to 0º. In each case the maximum value is noted. Take the average of three readings. F.6.2.2 Allow the door to close from its maximum opening angle permitted by the closer under test and note the minimum closing force obtained during its travel. Take the average of three readings. F.6.2.3 Calculate the closing moments in each case as the product of these average gauge readings and the distance of the force gauge in metres from the vertical axis of the hinges or pivots. F.6.3 Salt spray test Remove the door closer from the test apparatus and carry out a salt spray test according to G.1.6, for the grade of corrosion resistance claimed. F.6.4 Verification of closing moments After completion of the salt spray test and within a maximum time of 24 h, reinstall the door closer on the test apparatus and repeat the procedure described in F.6.2. Verify that the door closer meets the requirements. F.6.5 Tolerance Throughout this test method the following tolerances shall apply, unless otherwise stated: a) mass in kg: ± 2 %; b) length in mm: ± 2 %; c) angular position: ± 2º; d) force in N: ± 2 %; e) time in s: ± 5 %; f) temperature in ºC: ± 2 ºC; and g) moment in Nm: ± 2 %. The ambient temperature of the test environment shall be controlled throughout the tests to between 15 ºC to 30 ºC. 67 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 14 – Typical general arrangement of overload test apparatus Figure 15 – Plan view on arrangement of overload test apparatus 68 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Requirements Start Choose 2 of each of sample A and B Set to min. and max. power size Yes Adjustable force closer ? F.5.1 F.3.1.2 No SAMPLE(S) A SAMPLE(S) B SAMPLE C (General requirements) (Mechanical performance and Corrosion resistance durability) Test apparatus adjustment (5,000cycles) F.5.2.1.3 F.5.2.5.6 F.3.2, F.3.5 Opening/closing moments Efficiency Closing time Closing overload(10x) F.5.2.7.1 F.5.2.7.2 F.5.2.7.3 F.5.2.7.4 F.3.2, F.3.3 F.3.2 F.3.4 F.3.6 Yes General requirements F.1 Delayed action closer ? No Yes Backcheck closer ? No Annex D Closing moment (<150Nm) F.5.2.7.5 Closing time (>20s) Durability of delayed closing (>10 s < 30 s) Durability F.5.2.8.1-7 Open with backcheck (100 000cycles) Open without backcheck (400 000cycles) Durability (500,000 cycles) Closing moment (100 %) F.6.2 Closing moment (>80%) F.6.2 Salt spray test Closing time Closing moments Efficiency Maximum closing time Closing overload (10x) F.6.3 F.5.2.9.1 F.5.2.9.2 F.5.2.9.2 F.5.2.9.3 F.5.2.9.4 Yes Delayed action closer ? F.3.11 F.3.1.3 F.3.1 F.3.13 F.3.13.1 F.3.13..2 F.3.4 F.3.2, F.3.3 F.3.2 F.3.4 F.5.3.6 Closing time (>20s) F.5.2.9.5 F.3.10 Zero position Free play (<6mm) F.3.12 No Yes Double action closer ? No F.5.2.9.6 F.3.12 Finish Figure 16 – Flow chart of test procedure 69 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex G Corrosion resistance G.1 Requirements G.1.1 General requirements The requirements of one of the grades (classes) within G.1.2 to G.1.7 shall be met on the significant surfaces of all hardware. The following requirements shall not apply to Grade (Class) 0 finishes for which no defined corrosion resistance is relevant. G.1.2 Electrodeposited nickel plus chromium If coated with electrodeposited nickel plus chromium or with copper plus nickel plus chromium the requirements of the appropriate service condition number of ISO 1456 shall be met as follows: a) Grade (Class) 1 : ISO 1456 service condition number 1 (mild) b) Grade (Class) 2 : ISO 1456 service condition number 2 (moderate) c) Grade (Class) 3 : ISO 1456 service condition number 3 (severe) d) Grade (Class) 4 : ISO 1456 service condition number 4 (exceptionally severe) G.1.3 Electrodeposited nickel If coated with electrodeposited nickel the requirements of the appropriate service condition number of ISO 1458 as follows: a) Grade (Class) 1 : ISO 1458 service condition number 1 (mild) b) Grade (Class) 2 : ISO 1458 service condition number 2 (moderate) c) Grade (Class) 3 : ISO 1458 service condition number 3 (severe) c) Grade (Class) 4 : Not applicable - no such grade in ISO 1458 NOTE – Some people are susceptible to an allergic reaction if in prolonged contact with uncoated nickel plate. This possibility may be avoided by coating nickel plate with a suitable clear lacquer. G.1.4 Electrodeposited zinc on iron or steel If coated with electroplated zinc on iron or steel, the requirements of the appropriate classification code of ISO 2081 plus a chromate conversion coating meeting the requirements of the class of ISO 4520 specified to match that classification, as follows: a) Grade (Class) 1 : ISO 2081 classification code Fe/Zn5 + ISO 4520 class 1A, 1B, 2C or 2D b) Grade (Class) 2 : ISO 2081 classification code Fe/Zn8 + ISO 4520 class 1A, 1B, 2C or 2D c) Grade (Class) 3 : ISO 2081 classification code Fe/Zn12 + ISO 4520 class 2C or 2D c) Grade (Class) 4 : As specified for Grade (Class) 3 with the additional requirement that the minimum local thickness of zinc shall be 16 µm 70 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 G.1.5 Anodised oxide coating on aluminium If coated with an anodised oxide coating on aluminium, the requirements of the appropriate class of ISO 7599 shall be met as follows: a) Grade (Class) 1 : ISO 7599 class AA 5 b) Grade (Class) 2 : ISO 7599 class AA 10 c) Grade (Class) 3 : ISO 7599 class AA 10 d) Grade (Class) 4 : ISO 7599 class AA 15 NOTE – Aluminium foundry alloys that contain a high proportion of alloying elements such as copper, zinc or silicon are subject to anodising problems when anodised to film thicknesses greater than 8 µm (notably darkening of or striations in the anodic film). However, film thicknesses in range of 5 µm to 10 µm may be suitable for service in Grade (Class) 2 or Grade (Class) 3 situations when frequent cleaning of the anodised surface can be guaranteed, when the fitting can easily be replaced, or when some deterioration of the surface finish can be accepted. Otherwise, such foundry alloys which have been anodised to a film thickness less than 10 µm should not be specified for fittings intended for service in situations other than Grade (Class) 1. G.1.6 Neutral salt spray If uncoated or protected with a surface coating not specified in G.1.2 to G.1.5 the article shall be exposed to a neutral salt spray (NSS) test in accordance with ISO 9227 for the duration specified below: +1 a) Grade (Class) 1 : 24 h 0 h b) Grade (Class) 2 : 48 h 0 h c) Grade (Class) 3 : 96 h 0 h d) Grade (Class) 4 : 240 h 0 h +1 +4 +4 G.1.7 Acceptance conditions Coated finishes shall withstand exposure for the time specified without corrosion of the base metal substrate visible to unaided normal or corrected vision excepting one spot per 650 mm2 of significant surface and without any spots larger than 1.5 mm in any direction. The degree of blistering of organic coatings shall be not worse than density 2 and the size of any blisters shall not exceed size 3 as designated in ISO 4628-2. Uncoated metals shall show no sign of tarnish, visible to unaided normal or corrected vision as blackening or discoloration of the surface. NOTE 1 – Corrosion of the base metal substrate should not be confused with surface staining of its finish. In the case of steel substrates corrosion is rust of a reddish brown appearance. Corrosion of aluminium or zinc alloy substrates is white and corrosion of brass or bronze substrates is green. After any corrosion test required by the relevant clause references the product shall be capable of functioning normally. NOTE 2 – For hardware which is assembled from dissimilar materials electrochemical (galvanic) corrosion may occur. The neutral salt spray test specified in G.1.6 is recommended as a useful method for checking such assemblies. If corrosion which affects the functionability or appearance is apparent at the end of the appropriate period of neutral salt spray testing, steps should be taken to eliminate the contacts between dissimilar materials. The absence of any such corrosion is usually an indication of satisfactory corrosion resistance in service. 71 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 G.2 Test conditions The test methods necessary to ensure compliance with Clause G.1 shall be those specified in the relevant ISO standards invoked in that clause, except that: a) Any corrosion tests required shall be carried out on products assembled as normally supplied. b) When the specimen under test is a product which does not have a substantially flat surface which can be oriented as specified in ISO 9227, then the product shall be oriented in the test cabinet in its normal attitude in use. Within this restriction the product shall be placed so as to minimise the disruption of flow of the atmosphere within the test cabinet. 72 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex H An example of log book details Routine Maintenance Record Date Nos. of doors Location/ storey Work done/ minor defects reported Report by Repair by Date of minor repair 12.5.05 10 Storey 1 Inspected all doors with defective ones reported as follow: OKE - - Staircase 1 Hinge damaged OKE LBL 14.5.0 5 Replaced hinge Plant room Lockset faulty OKE LBL 14.5.0 5 Changed cylinder Remarks - 26.5.05 1 Sty 2/Stc 2 Pivot arm of door closer broken. Tenant LBL 27.5.0 5 Replaced door closer 12.6.05 10 Storey 5 Inspected all doors with defective ones reported as follows: OKE - - - Staircase 3 Vision panel’s glass pane cracked. OKE ABC Co. 20.6.0 5 Door supplier replaced glass pane. Corridor near #0812 Lockset jammed and door locked Tenant #08-12 Teo Lock smith 5.7.05 Unlock and repaired 1.7.05 1 NOTE 1 – All minor repair works done shall be recorded. NOTE 2 – No alteration or addition works are allowed on any fire door, unless approve by Regulatory Authority. NOTE 3 – Other information such as fire-rating, inspected label number can be included in appropriate column. NOTE 4 – Damaged fire doors shall be replaced with approval from Regulatory Authority. NOTE 5 – The visual inspection of fire door is preferably done on a monthly basis. 73 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex I Example of fire door certificate and schedule of evidence of compliance FIRE DOOR CERTIFICATE Certificate Number 12345 Project Name __________________________________________________________________________ Building Plan No. __________________________________________________________________ We, an approved company listed under the Product Listing Scheme, herein certify the fire doorsets identified on the attached Schedule of Evidence of Compliance have been inspected and labelled in accordance with Singapore Standard SS 332 : 2007 in respect to Clause 9.0, and comply in respect to supply, labelling and installation in accordance with the aforesaid Standard. Name of Manufacturer _____________________________________________________________ Authorised Signature _____________________________________________________________ Date _____________________________________________________________ 74 When completed , this schedule is to be attached to and become part of the FIRE DOOR CERTIFICATE, which it supports. The fire doorsets identified in this schedule comply with SS 332 : 2007 in respect to the supply, labeling and installation of the doorsets. Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 75 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex K Door coordinator devices : Requirements and test methods – EN 1158 K.1 General K.1.1 With reference to the standard, EN 1158, it provides the requirements and test methods for door coordinator devices for double leaf swing doors fitted with door closers or door closers which contain door coordinator devices installed on double leaf swing doors. K.1.2 The door coordinator devices shall meet the additional requirements as described in Annex A of EN 1158. The door coordinator device shall be installed in a full sized door assembly, which meet the fire resistance test requirements of EN 1634-1 or Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on the fire resistance of the complete door assembly. It is not necessary for the product to be operable after such a fire test. Door closers that contain door coordinator devices shall by itself conform to the requirements of EN 1154 or Annex F of this standard. As amended Aug 2009 K.2 Requirements K.2.1 Requirements for door coordinator devices are as stated in Clause 5 of EN 1158. K.2.2 The test apparatus and methods are as specified in Clauses 6 and 7 of EN 1158 respectively. K.2.3 Classification shall be at least as stated in K.3. K.3 Classification K.3.1 Door coordinator devices are classified according to a six digit coding system. K.3.2 The specifications for each digit are according to EN 1158, except for the digits stated in the following clauses. K.3.3 The category of use (first digit in the classification) shall be Grade 3. K.3.4 The test duration (second digit in the classification) shall be 50,000 test cycles (Grade 5). K.3.5 The test door mass (third digit in the classification) shall cover 5 door mass grades with door coordinator varying from size 3 to 7. K.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1. K.4 Typical example K.4.1 A typical example of door coordinator device is shown in Figure 17: 76 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 17 – Illustration of a swing arm door coordinator 77 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex L Door bolts : Requirements and test methods – EN 12051 L.1 General L.1.1 With reference to the standard, EN 12051, it provides the requirements and test methods for single point bolts for securing or increasing the security of doors in buildings. Spring engaging bolts, and bolts with locking facility are included; if they are device for securing, or helping to secure, a door in the closed position, comprising a suitably guided moving member, operable from the protected side only by hand or foot, either directly using a knob or slide, or indirectly using a lever/handle or rack and pinion mechanism. L.1.2 In this standard, door bolts are only allowed to be installed on the inactive/passive door leaf of a double leaf doorset. L.1.3 The door bolt devices shall meet the additional requirements as described in Annex B of EN 12051. The bolt shall be installed in a full sized door assembly, which meet the fire resistance test requirements of EN 1634-1 or Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on the fire resistance of the complete door assembly. It is not necessary for the product to be operable after such a fire test. The selection of the bolts for different construction of fire doors shall be as described in Annex D of EN 12051. As amended Aug 2009 L.1.4 Door bolts include manual and automatic flush bolts. As amended Aug 2009 L.2 Requirements L.2.1 Requirements for door bolts are as stated in Clause 4 of EN 12051. L.2.2 The test apparatus and methods are as specified in Clause 5 of EN 12051. L.2.3 Classification shall be at least as stated in L.3. L.3 Classification L.3.1 Door bolts are classified according to a seven digit coding system. L.3.2 The specifications for each digit are according to EN 12051, except for the digits stated in the following clauses. L.3.3 The category of use (first digit in the classification) shall be Grade 3. As amended Aug 2009 L.3.4 The test duration (second digit in the classification) shall be 10,000 test cycles (Grade 3) except for automatic door bolt which shall be 50,000 test cycles (Grade 4). L.3.5 There shall be no requirement for door mass (third digit in the classification). L.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1. 78 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 L.4 Typical example L.4.1 A typical example of door bolt is shown in Figure 18. Figure 18 – Illustration of a single point bolt 79 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex M Building hardware – Lever handles and knob furniture : Requirements and test methods – EN 1906 M.1 General M.1.1 With reference to the standard, EN 1906, it provides the requirements and test methods for spindle and fastening elements, operating torques, permissible free play and safety, free angular movement and misalignment, durability, static strength and corrosion resistance for sprung and unsprung lever handles, knobs for doors, push pads and similar in combination with backplates or roses operating latches. M.1.2 This European Standard is applicable only to lever handles and knobs and other devices that operate a latch or a lock. This standard may be applied to lever handle and knob furniture used for exit doors which are used on escape routes in residential and small office applications. M.1.3 The lever handles and knob furniture shall have been subjected to a successful fire test from both sides, according to EN 1634-1, or EN 1634-2, and EN 1634-3, or fulfils the requirements of table C.1 in EN 1906, Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on the fire resistance of the complete door assembly. It is not necessary for the product to be operable after such a fire test. As amended Aug 2009 M.2 Requirements M.2.1 Requirements for the lever handles and knob furniture are as stated in Clause 5 of EN 1906. M.2.2 The test apparatus and methods are as specified in Clauses 6 and 7 of EN 1906 respectively. M.2.3 Classification shall be at least as stated in M.3. M.3 Classification M.3.1 Lever handles and knob furniture are classified according to an eight digits coding system. M.3.2 The category of use (first digit in the classification) shall be Grade 3. M.3.3 The test duration (second digit in the classification) shall be Grade 7, 200 000 test cycles. M.3.4 There is no requirement on door mass (third digit in the classification) M.3.5 The fire resistance grade (fourth digit in the classification) shall be in accordance to table of C.1 of EN 1906, suitable for use on fire doors. 80 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 M.4 Typical examples M.4.1 Some typical examples of lever handles and knob furniture are shown in Figure 19. (i) Lever handle on rose (ii) Knob on rose (iii) Lever handles and knobs on plates Figure 19 – Illustrations of lever handles and knob furniture 81 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex N Mechanical locks and latches : Requirements and test methods – EN 12209 N.1 General N.1.1 With reference to the standard, EN 12209, it provides the requirements and test methods for mechanical locks and latches for durability, strength, and function of mechanically operated locks and latches and their locking plates for use in doors, window doors and entrance doors in buildings. N.1.2 The mechanical locks and latches shall meet the additional requirements as described in Annex A of EN 12209. The mechanical locks and latches shall have been subjected to a successful fire test from both sides, according to EN 1634-1 or EN 1634-2 or Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on the fire resistance of the complete door assembly. It is not necessary for the product to be operable after such a fire test. Where there is a latching function, it shall conform to 5.1.2 of EN 12209, and there shall be no means of inhibiting the latching function, other than by a key controlled deadbolt. As amended Aug 2009 N.2 Requirements N.2.1 Requirements for the mechanical locks and latches are as stated in Clause 5 of EN 12209. The test shall only be conducted on the latch bolt. N.2.2 The test apparatus and methods are as specified in Clause 6 of EN 12209. N.2.3 Classification shall be at least as stated in N.3. N.3 Classification N.3.1 Mechanical locks and latches are classified according to an eleven digit coding system. N.3.2 The specifications of each digit are according to EN 12209, except for the digits stated in the following clauses. N.3.3 The category of use (first digit in the classification) shall be Grade 3: For use by the public where there is little incentive to exercise care and where there is a high chance of misuse, e.g. public doors. N.3.4 The test duration (second digit in the classification) shall be 100, 000 test cycles; 25 N load on latchbolt (Grade L). N.3.5 There shall be no requirement for door mass (third digit in the classification). N.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1. 82 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 N.4 Typical examples N.4.1 Some typical examples of mechanical locks and latches are as shown Figure 20: Mortice Lock Narrow Stile Lock Rim Lock Nightlatch Figure 20 – Illustrations of mechanical locks and latches 83 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex O Emergency exit devices : Requirements and test methods – EN 179 O.1 General O.1.1 With reference to the standard, EN 179, it provides the requirements and test methods for emergency devices mechanically operated by either a lever handle or a push pad. O.1.2 Emergency exit devices are not applicable in situation where panic situation is likely to arise; For example places of mass assembly, Panic Exit Device with horizontal bar or rod across face of door shall be used and reference should be made to EN 1125. O.1.3 The referred standard EN 179 does not cover specific devices intended for use by severely disabled. Due to the wide ranges of disabilities, such devices and their performance should be agreed between specifier and manufacturer. O.1.4 Two categories of emergency exit devices (see Figures 21 and 22) are permissible: a) Type A – Emergency exit devices with lever handle operation. Figure 21 – Illustration of a Type A emergency exit device 84 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 b) Type B – Emergency exit devices with push pad operation. Figure 22 – Illustration of a Type B emergency exit device O.1.5 To maximise the width of the escape route and the limitation on projection, W as shown in Figures 21 and 22 is of high importance. O.1.6 To provide ease of use, the hinged or pivoted door shall not exceed 200 kg in mass, 2,500 mm in height and 1,300 mm in width. For hinged door, the selection of the door closer shall be in accordance with Table 4. As amended Aug 2009 O.1.7 The Emergency exit devices shall have been subjected to a successful fire test from both sides, according to EN 1634-1 or EN 1634-2 or Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on the fire resistance of the complete door assembly. It is not necessary for the product to be operable after such a fire test. O.2 As amended Aug 2009 Requirements O.2.1 Requirements on design of emergency exit devices are as stated in 4.1 of EN 179. O.2.2 Requirements on performance of emergency exit devices are as stated in 4.2 of EN 179. 85 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 O.2.3 For pressurised door, 4.2.1 of EN 179 shall be superseded by the Code of practice for fire precautions in buildings 7.2.2 (c) where the force required to open any door against the combined resistance of the pressurising air and the automatic door-closing mechanism shall not exceed 110 N at the door handle. O.2.4 The test apparatus and methods are as specified in Clauses 5 and 6 of EN 179 respectively. O.2.5 Classification shall be at least as stated in O.3. O.3 Classification O.3.1 Emergency exit devices are classified according to a nine digits/characters coding system. O.3.2 The specifications for each digit are according to EN 179, except for the digits stated in the following clauses. O.3.3 The category of use (first digit in the classification) shall be Grade 3. As amended Aug 2009 O.3.4 The test duration (second digit in the classification) shall be 100,000 test cycles (Grade 6). O.3.5 The door mass shall be of any grades (third digit in the classification). O.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1. As amended Aug 2009 O.3.7 The safety grade (fifth digit in the classification) shall be Grade 1. O.3.8 The Projection of emergency exit device (eighth digit in the classification) shall be evaluated to allow specifier to determine its impact on door width clearance. O.3.9 The Type of operation for emergency exit device (ninth character in the classification) shall be evaluated to aid specifier in selection of device. O.4 Typical examples O.4.1 Some typical examples of emergency exit devices are shown in Figure 23. 86 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 (i) Mortise type (ii) Rim type modular (iv) Rim 2 points (iii) Rim type single point (v) Rim type 3 points (vi) External trims for panic exit devices Figure 23 – Illustrations of emergency exit devices 87 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex P Panic exit devices : Requirements and test methods – EN 1125 P.1 General P.1.1 With reference to the standard, EN 1125, it provides the requirements and test methods for panic devices mechanically operated by either a horizontal push bar or horizontal touch bar specifically designed for panic situation, as illustrated in Figure 24. Figure 24 – A panic situation P.1.2 The referred standard EN 1125 does not cover specific devices intended for use by severely disabled. Due to the wide ranges of disabilities, such devices and their performance should be agreed between specifier and manufacturer. P.1.3 Two Categories of Panic Exit Devices are permissible: a) Type A – Panic exit devices with push bar operation (Figures 25 and 27). b) Type B – Panic exit devices with touch bar operation (Figures 26 and 27). 88 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Figure 25 – Type A panic exit device Figure 26 – Type B panic exit device Figure 27 – Types A and B panic exit devices 89 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 P.1.5 To maximise the width of the escape route and the limitation on projection, W as shown in Figure 28 is of high importance. Figure 28 – Overall projection of panic exit device from door face As amended Aug 2009 P.1.6 For ease of use, the hinged or pivoted door shall not exceed 200 kg in mass, 2,500 mm in height and 1,300 mm in width. accordance with Table 4. For hinged door, the selection of the door closer shall be in P.1.7 The panic exit devices shall have been subjected to a successful fire test from both sides, according to EN 1634-1 or EN 1634-2 or Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on the fire resistance of the complete door assembly. It is not necessary for the product to be operable after such a fire test. As amended Aug 2009 P.2 Requirements P.2.1 Requirements on design of panic exit devices are as stated in 4.1 of EN 1125. P.2.2 Requirements on performance of panic exit devices are as stated in 4.2 of EN 1125. P.2.3 For pressurised door, 4.2.1 of EN 1125 shall be superseded by the Code of practice for fire precautions in buildings 7.2.2 (c) where the force required to open any door against the combined resistance of the pressurising air and the automatic door-closing mechanism shall not exceed 110 N at the door handle. P.2.4 The test apparatus and methods are as specified in Clauses 5 and 6 of EN 1125 respectively. P.2.5 Classification shall be at least as stated in P.3. P.3 As amended Aug 2009 Classification P.3.1 Panic exit devices are classified according to a ten-digit/character coding system. P.3.2 The specifications for each digit are according to EN 1125, except for the digits stated in the following clauses. P.3.3 The category of use (first digit in the classification) shall be Grade 3. 90 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 P.3.4 The test duration (second digit in the classification) shall be 100,000 test cycles (Grade 6). As amended Aug 2009 P.3.5 The door mass shall be of any grades (third digit in the classification). P.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1. P.3.7 The safety grade (fifth digit in the classification) shall be Grade 1. P.3.8 The projection of panic exit device (eighth digit in the classification) shall be evaluated to notify its impact on door width clearance. P.4 Typical examples P.4.1 Some typical examples of panic exit devices are shown in Figure 29. (i) Mortise type (ii) Mortise type with 2 vertical latches 91 As amended Aug 2009 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 (iii) Rim type single point (iv) Rim 2 points (v) Rim type 3 points 92 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 (vi) Concealed vertical rod (vii) External trims for panic exit devices Figure 29 – Illustrations of panic exit devices 93 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex Q Single axis hinges : Requirements and test methods – EN 1935 Q.1 General Q.1.1 With reference to the standard, EN 1935, it provides the requirements and test methods for single-axis hinges, of lift-off or fixed pin type, for use on doors. It includes tests for static loads, shear strength and allowable wear during durability cycling for the following hinges: a) mounted on the edge of the door leaf and opening in one direction only; and b) whose axis of rotation is within 30 mm of an edge of the movable element for a door leaf mass of up to 160 kg. Q.1.2 Although the fastenings used to fix hinges to door assemblies are not covered by this standard, if the type of fastening to be used is supplied or specified by the manufacturer, such fastenings are used for the tests. Q.1.3 Single axis hinges shall meet the additional requirements as described in Annex B of EN 1935. The hinges shall be installed in a full sized door assembly, which meet the fire resistance test requirements of EN 1634-1 or Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on the fire resistance of the complete door assembly. It is not necessary for the product to be operable after such a fire test. As amended Aug 2009 Q.2 Requirements Q.2.1 Requirements for single axis hinges are as stated in Clause 5 of EN 1935. Q.2.2 The test apparatus and methods are as specified in Clauses 6 and 7 of EN 1935 respectively. Q.2.3 Classification shall be at least as stated in Q.3. Q.3 Classification Q.3.1 Single axis hinges are classified according to eight digits coding system. Q.3.2 The specifications for each digit are according to EN 1935, except for the digits stated in the following clauses. Q.3.3 The category of use (first digit in the classification) shall be any of the four grades identified in Annex A of EN 1935. As amended Aug 2009 Q.3.4 The test duration (second digit in the classification) shall be 200,000 test cycles (Grade 7). Q.3.5 The test door mass (third digit in the classification) shall be 60 kg (Grade 3) 94 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Q.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1 with additional requirements as specified in Annex B of EN 1935. Q.3.7 The safety grade (fifth digit in the classification) shall be Grade 1. Q.4 Typical examples Q.4.1 Some typical examples of single axis hinges are shown in Figure 30. Figure 30 – Illustrations of single axis hinges 95 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex R Electrically powered hold-open devices for swing doors : Requirements and test methods – EN 1155 R.1 General R.1.1 With reference to the standard, EN 1155, it provides the requirements and test methods for separate hold-open devices and also for hold-open mechanisms incorporated in a door closer. R.1.2 Electrically powered hold-open devices for swing doors manufactured according to this European Standard can hold a swing door at a fixed position. Interruption of the electrical supply to the hold-open devices will cause the door to close positively under the control of the door-closing device. Door closers shall conform to the requirements of EN 1154. R.1.3 This referred standard EN 1155 does not cover the electrical supply or control unit, smoke or fire detection elements and other external interfaces that may be used in combination with these electrically powered hold-open devices to form an electrically controlled hold-open system. As amended Aug 2009 R.2 Requirements R.2.1 Requirements on design of electrically powered hold-open devices are as stated in 5.1 of EN 1155. R.2.2 Requirements on performance of electrically powered hold-open devices are as stated in 5.2 of EN 1155. R.2.3 The test apparatus and methods are as specified in Clauses 6 and 7 of EN 1155 respectively. R.2.4 Classification shall be at least as stated in R.3. R.3 Classification R.3.1 Electrically powered hold-open devices are classified according to a six-digit coding system. R.3.2 The specifications for each digit are according to EN 1155 except for the digits stated in the following clauses. R.3.3 The category of use (first digit in the classification) shall be Grade 3. R.3.4 Two test durations are identified (second digit in the classification): a) Grade 5 : 50,000 test cycles. For all electrically powered separate hold-open devices. Refer to Figure 31(a). b) Grade 8 : 500,000 test cycles. For all electrically powered hold-open and free-swing door closers and devices that contain operating arms. Refer to Figure 31 (b) and (c). 96 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 R.3.5 Test door mass – 5 door mass grades and related hold-open power sizes (third digit in the classification) are identified according to Table 1 of EN 1155 as shown below: Hold-open power size 3 4 5 6 7 Recommended door leaf width (mm) max. 950 1100 1250 1400 1600 Test door mass (kg) Overload test drop weight (kg) Test door friction (N-m) max. 60 80 100 120 160 15 18 21 27 36 0.3 0.4 0.5 0.6 0.8 R.3.6 The fire resistance grade - suitability for use on fire/smoke compartmentation doors (fourth digit in the classification) shall be Grade 1. R.3.7 The safety grade (fifth digit in the classification) shall be Grade 1. R.4 Typical examples R.4.1 Some typical examples of separate hold-open devices and hold-open mechanisms incorporated in a door closer are shown in Figure 31. (a) Electromagnetic door holders - either floor or wall mounted they will hold the door in the open position. Under fire alarm conditions the device is deactivated and the door will close automatically under the action of a conventional overhead door closer or floor spring. (b) Electromagnetic door closers Figure 2: Electromagnetic Doorcontrolled Closers are electromagnetically are electromagnetically controlled overhead overhead door closers, fitted to the door closers, fitted to the door. The unit can door. The unit can provide a ‘hold provide a ‘hold open’ facility whereby the open’ whereby the door door is facility held in the open position. On is held in the open position. On operation of operation of the fire alarm or smoke the fire the alarm or smokeisdetector, the detector, electromagnet deactivated electromagnet is deactivated the and the door will close automaticallyand under conventional spring action. door will close automatically under conventional spring action. 97 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 (c) Electrically powered free-swing device incorporated into floorspring mechanism - the device prevent the door closing mechanism from closing the leaf and the door moved freely as though there is no closing mechanism fitted. On operation of the fire alarm or smoke detector, the device release the closer mechanism allowing it to close the door leaf. Figure 31 – Illustrations of hold-open devices and hold-open mechanisms 98 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex S Cylinders for locks : Requirements and test methods – EN 1303 S.1 General S.1.1 With reference to the standard, EN 1303, it provides the requirements and test methods for cylinders for locks for the strength, security, durability, performance and corrosion resistance of cylinders and their original keys. S.1.2 The cylinders for locks shall meet the additional requirements as described in Annex A of EN 1303. The cylinders for locks, shall have been subjected to successful fire test, according to EN 1634-1: 2000 or EN 1634-2 or Annex E of this standard, or otherwise assessed by a recognised testing laboratory, to prove the effect of the product on fire resistance of the complete door assembly. It is not necessary for the cylinder to operate after the fire test. S.2 As amended Aug 2009 Requirements S.2.1 Requirements for cylinders for locks are as stated in Clause 4 of EN 1303. S.2.2 The test apparatus and methods are as specified in Clause 5 of EN 1303. S.2.3 Classification shall be at least as stated in S.3 S.3 Classification S.3.1 Cylinders for locks are classified according to an eight digit coding system. S.3.2 The specifications for each digit are according to EN 1303, except for the digits stated in the following clauses. S.3.3 The category of use (first digit in the classification) shall be Grade 1: For use by people with a high incentive to exercise care and with a small chance of misuse. S.3.4 The test duration (second digit in the classification) shall be 100, 000 test cycles (Grade 6). S.3.5 There shall be no requirement for door mass (third digit in the classification). S.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1. 99 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 S.4 Typical examples S.4.1 Some typical examples of cylinders for locks are as shown in Figure 32. Euro profile Rim profile Scandinavian/Australia profile Figure 32 – Illustrations of cylinders for locks 100 Swiss profile Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex T As amended Aug 2009 Sliding door hardware : Requirements and test methods – EN 1527 T.1 General T.1.1 With reference to the standard, EN 1527, it provides the requirements and test methods for all principal components for sliding doors. Cycle tests, static load, initial friction and corrosion resistance tests are included for fittings and track only. T.1.2 This standard covers door gear for all industrial and residential sliding doors but does not cover sliding doors round the corner and light bottom sliding doors. T.2 As amended Aug 2009 Requirements T.2.1 Requirements for sliding door hardware are as stated in Clause 5 of EN 1527 for sliding doors. T.2.2 The test apparatus and methods are as specified in Clause 6 of EN 1527 for sliding doors. T.2.3 Classification shall be at least as stated in T.3. T.3 Classification T.3.1 Sliding doors and their fittings are classified according to a nine digits coding system. T.3.2 The specifications for each digit are according to EN 1527 except for the digits stated in the following clauses. T.3.3 There is no grade identified for sliding door under category of use (first digit in the classification). T.3.4 The test duration (second digit in the classification) shall be 10,000 test cycles (Grade 3). T.3.5 The test door mass (third digit in the classification) shall be any of the four grades identified in EN 1527. T.3.6 The fire resistance grade (fourth digit in the classification) shall be Grade 1. T.3.7 There is no grade identified for sliding door under safety (fifth digit in the classification). As amended Aug 2009 T.3.8 Deleted T.3.9 The category of door (eighth digit in the classification) shall be Grade 1, to denote that it is for sliding door. 101 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Annex U Bibliography U.1 Normative references BS 476 Fire tests on building materials and structures Part 4 : 1970 Non-combustibility test for materials Part 11 : 1982 Method for assessing the heat emission from building materials EN 179 : 1997 Building hardware – Emergency exit devices operated by a lever or push pad – Requirements and test methods EN 1125 : 1997 Building hardware – Panic exit devices operated by a horizontal bar – Requirements and test methods EN 1154 : 1996/A1:2002 Building hardware – Controlled Requirements and test methods EN 1155 : 1997 Building hardware – Electrically powered hold-open devices for swing doors – Requirements and test methods EN 1158 : 1997 Building hardware – Door coordinator devices – Requirements and test methods EN 1303 : 1998 Building hardware – Cylinders for locks – Requirements and test methods EN 1634-1 : 2000 Fire resistance tests for door and shutter assemblies. Fire doors and shutters EN 1634-2 : 2004 Fire resistance and smoke control tests for door and shutter, openable windows and elements of building hardware – Fire resistance characterisation test for elements of building hardware. EN 1634-3 : 2004 Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies EN 1670 : 2007 Building hardware. Corrosion resistance. Requirements and test methods EN 1906 : 2004 Building hardware – Lever handles Requirements and test methods EN 1935 : 2002 Building hardware – Single-axis hinges – Requirements and test methods EN 12051 : 1999 Building hardware – Door and window bolts – Requirements and test methods EN 12209 : 2003 Building hardware – Locks and latches – Mechanically operated locks, latches and locking plates – Requirements and test methods ISO 1456 : 1988 Metallic coatings – Electro deposited coatings of nickel plus chromium and of copper plus nickel plus chromium ISO 1458 : 1988 Metallic coatings – Electro deposited coatings of nickel ISO 2081 : 1988 Metallic coatings – Electroplated coatings of zinc on iron or steel ISO 4520 : 1981 Chromatic conversion coatings on electroplated zinc and cadmium coatings 102 door closing devices – and knob furniture – Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 ISO 4628-2 : 1982 Paints and Varnishes – Evaluation of degradation of paint coatings – Designation of intensity, quality and size of common types of defect – Part 2 : Designation of degree of blistering. ISO 7599 : 1983 Anodising of aluminium and its alloys – General specification for anodic oxide coatings on aluminium ISO 9002 : 1994 Quality Systems – Model for quality assurance in production, installation and servicing ISO 9227 : 1990 Corrosion tests in artificial atmospheres – Salt spray tests U.2 Other standards for information EN 1527 : 1998 Building hardware – Hardware for sliding doors and folding doors – Requirements and test methods EN 14637 : 2003 Building hardware – Electrically controlled hold-open systems for fire/smoke door assemblies – Requirements, test methods, application and maintenance European Standard WI 33315 : 2004 (Draft) Building hardware – Locks and latches – Part 4: Multipoint locks and their locking plates – Requirements and test methods EN 14846 : 2003 Building hardware – Locks and latches – Electromechanically operated locks and striking plates – Requirements and test methods EN 13633 : 2003 Building hardware – Electrically controlled panic exit systems for use on escape routes – Requirements and test methods EN 13637 : 2003 Building hardware – Electrically controlled emergency exit systems for use on escape routes – Requirements and test methods 103 As amended Aug 2009 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 SPRING SINGAPORE SPRING's mission is to enhance the competitiveness of enterprises for a vibrant Singapore economy. We work to nurture a pro-business environment that encourages enterprise formation and growth, facilitate the growth of industries, enhance productivity & innovation and capabilities of enterprises, and help increase access to markets and business opportunities. Our vision is to nurture a host of dynamic and innovative Singapore enterprises. Strategic Thrust 1: Nurture a pro-business environment that encourages enterprise formation and growth SPRING takes on the role of a steward to nurture a pro-business environment. In this role, SPRING helps to ensure that there is a conducive environment for enterprises to form, compete and grow. SPRING promotes the review and removal of rules and regulations that stifle enterprises. It also facilitates enterprise access to key factor inputs like land, labour, technology and finance. Strategic Thrust 2: Facilitate the growth of industries SPRING adopts an integrated cluster development approach in enhancing the vibrancy and competitiveness of selected industries. Strategic Thrust 3: Enhance productivity & innovation and capabilities of enterprises SPRING helps enterprises to enhance their productivity & innovation and capabilities. These include equipping enterprises with capabilities to upgrade their know-how, and creating conditions that encourage a productivity & innovation and service focus in enterprises. Focused assistance will be provided for promising enterprises. Strategic Thrust 4: Increase access to markets and business opportunities SPRING helps enterprises gain access to markets by reducing technical barriers to trade, providing quality assurance for Singapore products/services and linking local enterprises to business opportunities, both locally and overseas. SPRING Singapore 2 Bukit Merah Central Singapore 159835 Tel: 6278 6666 Fax: 6278 6667 E-mail: queries@spring.gov.sg Website: http://www.spring.gov.sg ABOUT THE NATIONAL STANDARDISATION PROGRAMME SPRING is also the national standards body in Singapore. Under the national standardisation programme, SPRING Singapore helps companies and industry to meet international standards and conformity requirements by creating awareness of the importance of standardisation to enhance competitiveness and improve productivity, co-ordinating the development and use of Singapore Standards and setting up an information infrastructure to educate companies and industry on the latest developments. SPRING Singapore is vested with the authority to appoint a Standards Council to advise on the preparation, publication and promulgation of Singapore Standards and Technical References and their implementation. 104 Licensed by SPRING Singapore to FREDERICK NEO/MR, ONG&ONG PTE LTD Singapore Standards eShop Order No: 6800015731/Downloaded:2011-07-19 Single user licence only, copying and networking prohibited SS 332 : 2007 Singapore Standards are in the form of specifications for materials and products, codes of practice, methods of test, nomenclature, services, etc. The respective standards committee will draw up the standards before seeking final approval from the Standards Council. To ensure adequate representation of all viewpoints in the preparation of Singapore Standards, all committees appointed consist of representatives from various interest groups which include government agencies, professional bodies, tertiary institutions and consumer, trade and manufacturing organisations. Technical References are transition documents developed to help meet urgent industry demand for specifications or requirements on a particular product, process or service in an area where there is an absence of reference standards. Unlike Singapore Standards, they are issued for comments over a period of two years before assessment on their suitability for approval as Singapore Standards. All comments are considered when a technical reference is reviewed at the end of two years to determine the feasibility of its transition to a Singapore Standard. Technical References can therefore become Singapore Standards after two years, continue as Technical References for further comments or be withdrawn. In the international arena, SPRING Singapore represents Singapore in the International Organisation of Standardisation (ISO), the Asia-Pacific Economic Co-operation (APEC) Sub-committee for Standards and Conformance (SCSC) and in the ASEAN Consultative Committee on Standards and Quality (ACCSQ). The Singapore National Committee of the International Electrotechnical Commission which is supported by SPRING Singapore, represents Singapore in the IEC. 105
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )