SCHEDULE OF EQUIPMENT
5000
GENERAL NOTES:
SPLIT TYPE AIR CONDITIONER ( WALL MOUNTED )
DESIGNATION QUANTITY
ACCU-2
SP-2
W.M
CAPACITY INPUT
KW
( KJ/H )
25,320
1
CONDENSER
COIL
FACE AREA ROWS FINS/ IN.
3.22
2 x 16
TYPE
NO.
PROPELLER 1
ELECTRICAL DATA
FAN
HP RPM
DRIVE
REMARKS
VOLTS PHASE HERTZ
AIR FLOW
1/6 1050 DIRECT
230
1.
CONTRACTOR IS ADVISED TO VISIT AND SURVEY THE
PLACE OF INSTALLATION.
2.
ALL AIR CONDITIONING UNITS AND VENTILATING UNITS
TO BE SUPPLIED SHALL BE NEW AND APPROVED
PRODUCTS OF REPUTABLE MANUFACTURERS. ALL AIR CONDITIONING EQUIPMENT SHALL BE
MANUFACTURED BY "HITACHI", "OR APPROVED BRAND.
3.
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO COORDINATE CLOSELY HIS WORK WITH THE OTHER
TRADES CONCERNED.
4.
REFRIGERANT SUCTION LINES SHALL BE INSULATED
WITH 25 mm THICK PREMOULDED ELASTOMERIC
RUBBER INSULATION AS MANUFACTURED BY
"ARMAFLEX", AEROFLEX OR APPROVED EQUAL.
5.
INDIVIDUAL WEATHER PROOF TYPE CIRCUIT BREAKER
SHALL BE PROVIDED PROVIDED FOR ALL
CONDENSING UNITS.
6.
ALL EXPOSED DRAIN LINES TO THE CEILING SHALL BE
PROVIDED WITH INSULATION TYPICAL TO
REFRIGERANT PIPING. (REFER TO PIPE INSULATION
DETAIL.)
7.
ALL EXPOSED DRAIN LINES TO THE CEILING SHALL BE
PROVIDED WITH INSULATION TYPICAL TO
REFRIGERANT PIPING. (REFER TO PIPE INSULATION
DETAIL.)
8.
ALL NECESSARY GOVERNMENT PERMITS SHALL BE
SECURED AND FOR ACCOUNT OF THECONTRACTOR.
9.
AS-BUILT PLANS SHALL BE PROVIDED BY THIS
CONTRACTOR AFTER COMPLETION OF WORKS.
40mm x 40mm x 6.0mm
ANGLE SUPPORT
10.
CONCRETE
FOUNDATION
ALL INSTALLATION WORKS SHALL BE DONE IN A NEAT
AND WORK- MANLIKE MANNER.
11.
ALL REFRIGERANT SUCTION LINES EXPOSED INDOORS
AND/OR EXPOSED
TO
WEATHER SHOULD
BE
PROVIDED WITH GAUGE #24 ALUMINUM
CLADDING. (SUBMIT SHOP DRAWING PRIOR TO
INSTALLATION)
12.
ALL ACCU's AND FCU's SHALL BE PROVIDED WITH
ANGULAR BAR SUPPORTS. (SUBMIT SHOP DRAWING
PRIOR TO INSTALLATION)
ALL UNIT SHALL BE BRAND NEW
AND COMPLETE WITH STD.
ACCESSORIES, READY FOR SERVICE
60
SINGLE
WINDOW TYPE AIR CONDITIONER
3000
DESIGNATION QUANTITY
SP-2
W-2
W.M
W.M
W-2
W.M
CAPACITY
( kj/h )
AIR CALCULATION
18,990
1
ELECTRICAL DATA
AMPERE
10
15
REMARKS
VOLTS
PHASE
HERTZ
230
SINGLE
60
ALL EXISTING UNIT
NOTES :
A
1.
NOTE: OPERATION SEQUENCE (A/C UNIT)
ALTERNATE EVERY 12 HOURS
SP-2 FROM 7:00 AM TO 7:00 PM
W-2 FROM 7:00 PM TO 7:00 AM
ALL EQUIPMENT ACCESORIES LIKE FILTER/DRYER, SOLENOID VALVE,
SIGHT GLASS, EXPANSION VALVE, ETC. SHALL BE INCLUDED BY THE
PURCHASE OF THE REFRIGERANT PIPING SYSTEM AND SHALL BE
INSTALLED AS PER MANUFACTURER'S INSTALLATION RECOMMENDATION.
CEILING
B
2.
SP-2 ( W.M. )
INSIDE
ALL EXPOSED REFRIGERANT AND CONDENSANTE DRAIN PIPE TO BE
INSULATED AND METAL G.I. CLADDED.
3.
AIR CONDITIONER AS SHOWN IN THE WINDOW TYPE ACU DETAIL.
1
AIRCONDITIONING LAYOUT
SIGHT GLASS
M-1
SCALE
FILTER/DRYER
1:50 M.
WALL
ACCU-2
OUTSIDE
REFRIGERANT SUCTION
AND LIQUID LINE
5000
ACCU MOUNTING
WITH VIBRATION PAD
F.F.L.
SP-2, WALL MOUNTED
F.G.L.
INSULATION WITH
METAL CLADDING
W-2
3000
DRAIN LINE TAP TO
NEAREST DRAIN
INSULATING
VALVE TYPE
4
SP-2 (WALL MOUNTED) / ACCU-2 INSTALLATION DETAIL
M-1
SCALE
NTS
FEATURES
2
LONGITUDINAL SECTION "A"
M-1
SCALE
CONCRETE WALL BY CIVIL
CONTRACTOR(TYPICAL)
1. WIRELESS LCD REMOTE CONTROLLER
2. MICROPROCESSOR-CONTROLLED
TEMPERATURE
3. VARIABLE FAN SPEED.
1:50 M.
PIPE (WITH OR WITHOUT
INSULATION)
CONCRETE GROUT BY
CIVIL CONTRACTOR
UNIT HOUSING SLOT OPENING
FOR FRESH AIR PASSAGE
GALVANIZED PIPE SLEEVE
(TWO PIPE SIZE LARGER)
WINDOW TYPE AIR
CONDITIONER
3000
GA. 20 G.I SHEET
PREPAINTED DRAIN PAN
BY MECH'L . CONTRACTOR
SP-2, WALL MOUNTED
CONCRETE SLAB
SUPPLY AIR
CONCRETE
SLAB WALL
RETURN AIR
1000
EQUIPMENT BRACKET
BY MECH'L CONT'R. (TYP.)
1000
2.70m OR AS
PER ARCHITECT
UPS
SERVER
STEEL
PLATE
50 MM THICK WOOD FRAMING
ALL AROUND UNIT WITH NAILS
OR MOUNTING BOLTS
SLOPE
MOUNTING BOLTS ON
EXPANSION SHIELD BY
MECH'L CONT'R
ELECTRICAL POWER OUTLET
(COORDINATE WITH ELECT'L
PLANS FOR LAYOUT)
DRAIN PIPE TO NEAREST
DRAIN LINE(SEE SANITARY PLAINS FOR EXACT
LOCATION)TYPICAL
DRAIN PIPE BY MECH'L
CONTRACTOR TYPICAL
WELDED TO PIPE SLEEVE
PLASTIC WEATHERPROOF HEAT
RESISTANT CAULKING COMPOUND
25MM THICK BOTH ENDS
SECTION
3
CROSS SECTION "B"
M-1
SCALE
1:50 M.
5
M-1
FCU MOUNTING DETAIL
SCALE
NTS
PROJECT :
SHEET CONTENTS:
PROPOSED:
AIRCONDITIONING LAYOUT
SCHEDULE OF EQUIPMENT
GENERAL NOTES
SP2 /ACCU INSTALLATION DET.
FCU MOUNTUNG DETAIL
WINDOW TYPE AC DETAIL
PIPE PASSING THRU WALL & FLOOR DETAIL
6
WINDOW TYPE AC DETAIL
M-6
SCALE
SUBMITTED:
NTS
REVIEWED: (AS TO THE DESIGN CONCEPT)
OAKUM
PACKING
7
PIPE PASSING THRU WALL & FLOOR DETAIL
M-1
SCALE
NTS
RECOMMENDING APPROVAL:
APPROVED:
SHEET NO.
ALLAN B. PADILLA
PROFESSIONAL MECHANICAL ENGINEER
REG. No. : 0103022
DATE ISSUED :
PTR No. :
PLACE ISSUED :
TIN : 941-524-085
ICD 4B COMMUNICATION NETWORK
LOCATION: DPWH DISTRICT ENGINEERING OFFICE
(SEE COVERSHEET FOR SIGNATURE)
(SEE COVERSHEET FOR SIGNATURE)
(SEE COVERSHEET FOR SIGNATURE)
M-1
ARNOLD I. DAGDAG
MARIANO C. DEL CASTILLO
B. ELIZABETH E. YAP
GILBERTO S. REYES
RAUL C. ASIS
GENERAL PROJECT MANAGER
NERA PHIL INC.
OIC, BUILDINGS DIVISION
BOD, DPWH
DIRECTOR III
MIS, DPWH
DIRECTOR IV
BOD, DPWH
UNDERSECRETARY
DPWH
2 13