2342 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012 High-Voltage Insulators Mechanical Load Limits—Part II: Standards and Recommendations IEEE Lightning and Insulator Subcommittee Working Group on InsulatorsTask Force on Insulator Loading A. C. Baker, R. A. Bernstorf, E. A. Cherney, R. Christman, R. S. Gorur, R. J. Hill, Z. Lodi, S. Marra, D. G. Powell, A. E. Schwalm, D. H. Shaffner, G. A. Stewart, and J. Varner Abstract—This paper reviews and discusses the rated strength of insulators as defined in ANSI, CSA, and IEC product standards. The definition of rated strength, which for a particular insulator, requires reference to the tests and acceptance requirements given in the appropriate standard for that insulator is discussed. An insulator may not exhibit noticeable changes at loads sufficient for the initiation of irreversible damage, referred to as its damage limit. The significance of this is discussed in the paper as insulator application loads which must be below the damage limit of the insulator and be made in accordance with the relevant standard, including consideration of the allowable variation in strength implied by strict conformance to the standard. Damage limits for ceramic and composite insulators based on the minimum allowable strength according to the current standards are given. Index Terms—Ceramic insulators, composite insulators, damage limit, glass insulators, high-voltage (HV) insulators, insulator standards, polymer insulators, porcelain insulators. I. INTRODUCTION HE IEEE Lightning and Insulator Subcommittee Working Group on Insulators formed a task force to develop loading recommendations for high-voltage (HV) insulators that are produced to conform with American National Standards Institute (ANSI), Canadian Standards Association (CSA), or International Electrotechnical Commission (IEC) product standards, and that satisfy ANSI or CSA line load and strength regulations. In a companion paper, ANSI and CSA overhead line load and strength requirements were reviewed and discussed and a basis for limiting loads to prevent irreversible damage to the insulators was presented [1]. Mechanical strength ratings for ceramic and composite high voltage insulators given in ANSI, CSA, and IEC product standards are defined by the tests and acceptance requirements given in the appropriate standard for a particular insulator and are not minimums or guaranteed strengths. T Manuscript received February 27, 2012; accepted May 15, 2012. Date of publication June 22, 2012; date of current version September 19, 2012. Paper no. TPWRD-00200-2012. A. C. Baker, Task Force Chair, is with K-Line Insulators, Rochester, NY 14624 USA (e-mail: tbaker@k-line.net). R. A. Bernstorf. Working Group Chair, is with Hubbell Power Systems, Wadsworth, OH 44281 USA (e-mail: rabernst@hps.hubbell). Color versions of one or more of the figures in this paper are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/TPWRD.2012.2200509 Insulators may not exhibit noticeable changes, deformation or otherwise, at loads sufficient for the initiation of permanent damage and assignment of damage limits requires that the minimum strengths allowed for individual units by the standards be considered. II. INSULATOR STANDARDS ANSI, CSA, and IEC insulator standards specify minimum performance requirements for new insulators subjected to specific electrical and mechanical tests, and dimensional requirements for service interchangeability. Required tests are classified as: • Type or Design Tests performed once for a given design which depends on the insulator design, materials, manufacturing process, and technology. • Sample (quality conformance) Tests performed on random samples taken from an offered lot to verify the characteristics of an insulator that can vary with the manufacturing process and materials and qualify the lot for acceptance. • Routine Tests performed on each insulator produced with the intent of eliminating insulators with manufacturing defects from a lot. Sample tests include strength rating verification, visual inspection, verification of dimensions, and galvanizing thickness. Mechanical tests, intended to verify the assigned strength rating according to the relevant standard, are the most important with regard to providing recommendations on service loading limits. Mechanical strength tests performed on a specified number of samples, selected at random from a given lot, are loaded to either the ultimate strength failing load tests or withstand tests depending on the particular standard and type of insulator. Results of such tests are sufficient to determine if the lot conforms to the requirements for the relevant strength rating, but an estimation of the expected strength variation of the entire lot requires additional information about the production process for the insulators. For those with an average strength requirement, and if produced under conditions that allow statistically relevant conclusions to be made, a normal frequency distribution of strength is expected and a lower limit for the strength of insulators in a lot can be estimated. Absent such controlled conditions, a meaningful conclusion regarding the expected strength variation for units in the lot is not possible. Sample test requirements and lot acceptance criteria for standards published by the three organizations are reviewed here 0885-8977/$31.00 © 2012 IEEE BAKER et al.: HV INSULATORS MECHANICAL LOAD LIMITS—PART II 2343 TABLE I CURRENT ANSI C29 HV INSULATOR STANDARDS MECHANICAL TESTS AND LOT ACCEPTANCE CRITERIA [2]–[12] Fig. 1. ANSI C29.2 minimum acceptance requirement for M&E tests. of insulator has two ultimate strength sample test requirements as given in Table I. Lot acceptance criteria based on a historical standard deviation for past production assumes a statistically controlled production process though exact process specifications cannot be included in ANSI product standards [13], [14]. The strength variation for units produced in such a process can be represented by a normal distribution curve and the expected strength variation can be expressed by the area under the curve bounded by a given number of standard deviations from the sample average. The standard deviation for any sample from a lot of insulators is most likely about equal to the historical standard deviation, and assuming it is equal, the requirement for the average combined strength of the ten samples mechanical and electrical from the lot can be represented by the normal frequency distribution curve as shown in Fig. 1 and for a lot minimally satisfying the sample test requirement expressed as Rating with the objective of estimating the allowable low strength of units in lots that are in strict conformance with the standards where possible, and to provide a basis for assigning damage limits to prevent irreversible insulator damage while satisfying ANSI and CSA overhead line load and strength requirements. A. ANSI HV Insulator Standards The ANSI C29 series of insulator standards includes 13 product standards pertaining to specific types of insulators, and two test standards providing details for conducting the tests required in the product standards. Only those standards pertaining to HV insulators, and listed in Table I, are in the scope of this discussion. Spool, strain, pin, and indoor apparatus types of insulators are not included. It is improper to specify commercial terms and conditions in ANSI standards so lot sizes are not defined [13], and the specific numbers of samples to be taken from a lot offered for acceptance, regardless of the number of units in the lot, for each type of insulator are given in Table I. 1) Ceramic Insulators: Suspension Type (ANSI C29.2): ANSI C29.2 defines ceramic suspension-type insulators to be wet-process porcelain or toughened glass insulators. Lot acceptance criterion for this type (1) The factor 1.2 in (1) is based on the current C29.2 standard [4] and may change with the next revision of this standard. Referring to standard normal curve tables, for a lot that minimally satisfies (1), the area under the curve below the rated value is about 11.5% of the total area (representing all of the units in the lot), so the M&E strength of about 11.5% of the units in a lot minimally acceptable according to ANSI C29.2 could be below the rated value. The possible minimum strength for suspension insulator units that could be in an acceptable lot according to C29.2 is dependent on the coefficient of variation for the manufacturing standard deviaprocess. The distribution curve bounded by basis) includes 99.99% of the units in the lot and so tions the possible low strength value for the lot is (2) where is the rated M&E value and is the coefficient of variation for the manufacturing process. A four standard deviation basis was chosen because it is the current CSA requirement and accommodates a comparison of standards as discussed later [18]. For ceramic insulator manufacturing, this coefficient is typically in the 5 to 15% range [15], [16] and units with 2344 TABLE II POSSIBLE LOW STRENGTH UNITS AS A PERCENT OF THE M&E RATING IN LOTS MINIMALLY ACCEPTABLE ACCORDING TO C29.2 TABLE III POSSIBLE LOW STRENGTH UNITS AS A PERCENT OF RATED STRENGTH IN LOTS MINIMALLY ACCEPTABLE ACCORDING TO C29.7, C29.8, OR C29. 9 strengths as a percent of the rated value as low as that shown in Table II could be in insulator lots minimally acceptable according to C29.2. Line Post (ANSI C29.7) and Apparatus Type (ANSI C29.8 and C29.9): The ultimate strength sample test requirements for line post and apparatus-type wet-process porcelain insulators are also given in Table I. Lot and specified sample sizes for these types of insulators tend be much smaller than for suspensions. Extracting statistically valid conclusions for a lot based on small sample test results is problematic, but, by definition, about half , could the insulators in a minimally acceptable lot have strengths less than the rated value. The strength distribution for line post and apparatus-type insulators, given the same assumption about the manufacturing process as before, could also be expected to be like that shown in Fig. 1. Even though none of the three test samples can have a value below 85% of rating, a minimally acceptable lot may contain insulators with strengths considerably below rating as shown in Table III. 2) Composite Insulators: ANSI C29.12, C29.13, C29.17, and C29.18 standards relate to composite insulators, defined as those having a fiberglass-reinforced resin matrix core and an elastomeric outer housing. These four standards share a common ultimate strength sample test requirement and conformance is demonstrated by the ability of one to three samples, depending on the relevant standard, to withstand the rated strength load without failure. The rated strength is a value, assigned by the manufacturer, which must be justified by prototype tests that are performed once for each design of an insulator. Suspension Type (ANSI C29.12 and C29.13): ANSI C29.12 refers to composite suspension insulators intended for use on transmission lines 70 kV and above. A prototype core time-load test for this type of insulator requires that three units be subjected to an ultimate strength tensile test, and three additional insulators must withstand a 96-h tensile test at 60% of the average strength obtained for the first three. The manufacturer’s assigned specified mechanical load (SML) rating, justified by the prototype test, is confirmed by SML withstand quality conformance tests on three randomly selected samples from an offered lot. The test is passed if no failure below SML IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012 occurs. The test load is then increased to failure to provide historical data to further justify the manufacturer’s choice of the SML value. A routine 10 s test at 50% of SML is required for each insulator in the lot. ANSI C29.13 distribution class composite suspension insulators are intended for use on lines 69 kV and below. Prototype tests require that three insulators each must withstand rated tensile and torsion test loads. For the tensile test, after withstand at the rated value, the load is increased to failure to provide data to support the manufacturer’s choice of the SML value. Three samples randomly selected from any lot offered for acceptance must also be subjected to a tensile test and must withstand the SML rating. Sample tests for composite-type suspensions insulators are load withstand tests and on a minimum basis, other than helping to verify the manufacturer’s choice of SML rating, cannot be used to estimate the possible low strengths values in a given lot. However, an extensive time-load test, discussed in [1], provides a basis for a damage limit for composite suspension-type insulators. Line Post Types (ANSI C29.17 and C29.18): ANSI C29.17 composite line posts are intended for use on lines 70 kV and above. Prototype core time-load tests for these line posts require that three units be subjected to a cantilever load for 96 h at 40% of the specified cantilever load (SCL), or the routine cantilever load (RCL) if it is greater. After the load test, dissection and dye penetration examination of the units near the base end must not show any evidence of cracking or delamination in the fiberglass rod. Three units must also be subjected to, and withstand, the specified tensile load (STL). Ultimate strength sample tests include a cantilever strength verification test and a specified tensile load test. By agreement a cantilever breaking load (CBL) may be performed. The cantilever strength verification test involves loading the post to 40% of the SCL and monitoring the line end deflection of the post, which must not increase more than about 3% after 1 min under load. If performed, the CBL is the maximum bending loading attainable and must be greater than or equal to the SCL. Composite line post insulators exhibit considerable deflection under bending loads making cantilever routine tests difficult to carry out on a production line basis, and the routine test specified is a tension test. The specified tension load (STL) withstand sample test is specified to provide a basis for the routine test. As for other sample tests, after withstand at the rated tension value is demonstrated, the load may be increased to failure to provide data to support the choice of the STL. ANSI C29.18 distribution class composite line posts are intended for use on lines 69 kV and below. A prototype tensile test, with withstand at the STL load, followed by a load increase to failure to support the choice of STL is required. The ultimate strength sample test for this class line post requires that a cantilever breaking load test on one randomly chosen sample from the lot to be greater than, or equal to, the SCL. Sample tests for composite-type post insulators, like for suspensions, are rated load withstand tests and on a minimum basis, other than helping to verify the manufacturer’s choice of SCL rating, cannot be used to estimate the possible low strengths values in a given lot. Extensive time-load tests similar to those BAKER et al.: HV INSULATORS MECHANICAL LOAD LIMITS—PART II TABLE IV CANADIAN HV INSULATOR STANDARDS MECHANICAL TESTS AND LOT ACCEPTANCE CRITERIA 2345 load strength the condition that and standard deviation must satisfy (3) for suspensions provide a basis for a damage limit for composite post-type insulators. B. CSA HV Insulator Standards CSA HV insulator standards apply to ceramic, toughened glass, annealed glass, and composite insulator types. New CSA standards for distribution voltage class composite insulators under development will be based on current Canadian Electrical Association (CEA) purchase specifications LWIWG-01(96) and LWIWG-02(96). Current CSA insulator standards, including the two CEA specifications, are listed in Table IV [17]–[24]. The number of samples required for lot acceptance tests depends on the lot size since there is no restriction regarding lot size specification for Canadian standards. However, a minimum number of samples, regardless of lot size, is required for ceramic or glass suspensions, and for station posts, the number of samples to be taken is by agreement between manufacturer and purchaser. The specified lot size ranges for composite insulators are given in the table. 1) Ceramic and Glass Insulators: Ceramic-type insulators refer only to wet-process porcelain insulators in CSA standards. If made of glass, suspension-type insulators must be toughened glass but station post types may be toughened or annealed glass. Suspension Types (CSAC411.1 and C1325): CSA standards for ac and dc porcelain and toughened glass suspension insulator require randomly selected samples from lots offered for acceptance to be subjected to a failing load test. A minimum of 15 samples is equally divided into three groups for the various sample tests, with 10 of the units subjected to the failing load test. For the lot to be acceptable, the sample average failing and no individual value may be below the rated value. In this that case, for a minimally acceptable lot, the minimum value could be expected in such a lot, regardless of the coefficient of variation for the production process, is at least the rated value; a significant difference compared to ANSI C29.2 requirements. Station Post Type (CSA C156.1): The standard for porcelain and glass station post insulators specifies that the number of samples to be selected at random from an offered lot for ultimate strength tests be by agreement between the manufacturer and purchaser. For lot acceptance, each sample so chosen must at least withstand the specified failing load. A minimum withstand requirement precludes a determination of the minimum strength of units that might be contained in such a lot. 2) Composite Insulators: Composite insulators in CSA and CEA standards currently include transmission class suspensions, and distribution class suspensions and line posts. Transmission Suspension Type (CSA C411.4): CSA C411.4 covers composite suspensions intended for use on lines 69 kV and greater and requires a core time-load test as described before for ANSI transmission class composite suspension insulators to confirm the SML rating assigned by the manufacturer. Randomly chosen samples from a lot offered for acceptance must pass an SML withstand test. Distribution Class-Type Insulators: In both CEA LWIWG-01 (suspensions) and CEA LWIWG-02 (line posts), a maximum lot size of 3000 units is specified with a sample of two selected for ultimate strength sample tests; for lots less than 300 units, the number of samples is to be negotiated. The suspension test samples are subjected to an SML test as previously described, and the line posts to a cantilever load test. In each case, the test is continued until failure, with the requirement that failure does not occur before reaching the rated load value. As for ANSI, lot sample tests in CSA composite insulator standards are rated load withstand tests not suitable for establishing damage limits. Time-load tests discussed in [1] provide the basis for damage limits for this type of insulator. C. IEC HV Insulator Standards IEC HV insulator standards include porcelain, toughened glass, annealed glass, and composite-type insulators. A list of the standards, with the ultimate strength sample test requirements and acceptance criteria, and routine mechanical tests for each type, is given in Table V [25]–[30]. According to IEC insulator standards given in Table V, the number of randomly chosen test samples from a lot offered for acceptance depends on the particular standard and the number of units in the lot. The minimum number where specified, or a number of samples for typical lot sizes, are assumed in the following discussion. Porcelain and glass suspensions and line posts sample tests are ultimate strength failing test and an evaluation of the expected strength variation in a given lot can be 2346 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012 TABLE V IEC HV INSULATOR STANDARDS MECHANICAL TESTS AND LOT ACCEPTANCE CRITERIA TABLE VI CONSTANTS c TABLE VII POSSIBLE LOW STRENGTH UNITS AS A PERCENT OF SFL IN LOTS MINIMALLY ACCEPTABLE ACCORDING TO IEC 60383 OR IEC 1325 made. For porcelain and glass station posts, and all composite insulators, samples are only required to withstand the specified ultimate strength rating for strict compliance with the relevant standard, and a statistical evaluation of the possible strength variation for units in the lot cannot be made for these types. 1) Porcelain and Glass Insulators: Ceramic-type insulators refer only to electrical-grade porcelain insulators in IEC standards, and two types of suspension insulators are included; Class A, in which the length of the shortest puncture path through solid insulating material is at least equal to half the arcing distance, and Class B, in which the shortest puncture path through solid insulating material is less than arcing distance. A long rod insulator, not commonly used in North America, is an example of Class A, and a cap and pin suspension insulator is an example of Class B. Only Class B suspension insulators are considered here. Suspension and Line Posts (IEC 60383 and IEC 1325): IEC 60383 for ac porcelain, toughened glass, or annealed glass suspension or line post-type insulators, and IEC 1325 for dc porcelain and toughened glass suspension insulators, require that samples for ultimate strength tests have an average strength so that and standard deviation (4) where SFL is the specified failing load and is a constant dependent on the number of samples required to be tested. If this requirement is not met, a re-test of the lot is allowed, provided the average does not fail to satisfy (4) by a factor no more than with the values for the two constants for different sample sizes given in Table VI. Acceptance of a lot that only meets the minimum requirement of (4) leads to a possibility of having some units in the lot with strengths significantly below the rated value. As before, assuming a statistically controlled manufacturing process and coefficients of variation of 5%, 10%, and 15%, the possible low basis, strengths of units as a percent of the rated value on a that could be in such a lot according to IEC 60383 or 1325 are given in Table VII. Station Posts (IEC 60168): Ultimate strength sample tests for porcelain and glass station posts are satisfied if the specified mechanical failing load is reached in the test, and statistical analysis of the distribution of strengths for lots minimally acceptable is not possible. 2) Composite Insulators: Composite insulators, as defined in IEC, consist of a fiberglass rod core, a polymeric housing, and end fittings. As in ANSI and CSA composite insulator standards, ratings in IEC standards are values assigned by the manufacturers that must be confirmed by various design tests. A number of randomly chosen samples from insulator lots, as specified in IEC 61109 (suspensions) or 61952 (line posts), are subjected to the appropriate test with a minimum requirement that the samples must withstand the rated load. III. OVERHEAD LINE COMPONENT STRENGTH COORDINATION Strength coordination for overhead line components is aided by referencing component strength characteristics on a compatible basis, which, except for insulators, is generally minimum breaking strength [1]. Currently, HV insulators are applied on the basis of rated mechanical strength only having meaning with respect to the standard the insulators were produced to meet. Establishing a minimum strength limit for insulators in a particular lot requires an evaluation of the allowable strength variation in the relevant standard, and, depending on the standard, can require a consideration of manufacturing process variations. A summary of the minimum requirements for ultimate strength sample tests for insulators in strict compliance with ANSI, CSA, and IEC insulator standards is given in Table VIII. 1) Ceramic Insulators: Porcelain and glass suspension-type insulators conforming to ANSI and CSA standards, and suspensions and line posts conforming to IEC standards, must have, for randomly chosen samples from a lot offered for acceptance, an average strength and standard deviation so that (5) where is the rated strength value, and is a constant specified in the relevant standard. If the coefficient of variation for the BAKER et al.: HV INSULATORS MECHANICAL LOAD LIMITS—PART II 2347 TABLE VIII ANSI, CSA, AND IEC INSULATOR STANDARDS MINIMUM STRENGTH REQUIREMENTS FOR SAMPLE TESTS TABLE IX DAMAGE LIMITS FOR CERAMIC INSULATORS • Long-term service continuity for weather-related loads. • Coordination of line component failure limits to ensure safety and contain damage. The first objective requires that the highest anticipated loading event must not initiate irreversible damage to the insulator. For the second, the loading event must not exceed the minimum ultimate strength expectation for the insulators. In both cases, the recommendations must be made with respect to the relevant standards for the rated strength of the insulators. A. Ceramic Insulators process that produced the insulators is then, on a basis, the lowest expected strength for units in the lot for a lot that minimally meets the standard is (6) As the constant approaches a value of 4, the variation becomes of less importance provided the process is capable of producing units with normally distributed strengths. Ceramic apparatus and line post-type insulators conforming to ANSI standards must have, for randomly chosen samples, an average strength at least equal to the rated value. For CSA and IEC, none of the samples can have strengths below the SCL rating, but for ANSI, strengths less than rating are acceptable provided no sample is below 85% of the rated value. The lowest expected strength for units in a lot minimally acceptable on a basis in these cases is (7) The lower limit of expected strengths from (6) or (7), provided the coefficient of variation is known or can be adequately approximated, can be a basis for coordinating the minimum breaking strength of porcelain and glass insulators with other line components. 2) Composite Insulators: The common requirement in composite insulator standards that samples chosen from offered lots must at least withstand the rated strength level suggests that the lower limit for expected strengths, if is known, is also minimally given by (7) and could provide a basis for coordinating the minimum breaking strength of composite insulators with other line components. IV. LOAD LIMIT RECOMMENDATIONS Mechanical load limit recommendations for HV insulators should recognize two objectives: Irreversible damage to porcelain and glass insulators can be expected if loads exceed more than 70–80% of the strength of the insulator (the damage limit) [1]. The strength of a particular insulator must be inferred from the assigned rating and the requirements to satisfy that rating. General recommendations must be based on an assumption that the insulators meet the minimum requirements for a particular standard, and for ceramic insulators, the damage limit can be defined as (8) is defined by (6) or (7). For those standards where where a value of the constant is not defined, a value of zero for the constant was assigned as indicated in (7). The damage limits according to (8) for ceramic insulators, as a percent of rating, in lots minimally meeting ANSI and CSA standards, with manufacturing process variations in the 5–15% range, are given in Table IX, where is the rated strength according to the relevant standard. The constant is equal to either the allowed variation, expressed as a number of standard deviations, specified by the standards or assigned a value of 0 when not specified. Higher values for can be required by individual customer specifications, and Table IX would be modified accordingly. This subject will be covered in a future paper. Routine mechanical tests should not, of course, be conducted at the damage limit level and, therefore, except as a guide for normal everyday loads, cannot be used to determine maximum loading capability. The strength percentage of insulator strength ratings allowed for use in ANSI C2 (NESC) given in [1, Table 1] should not be increased without revising the relevant ANSI standards to support an increase. In general, the past practice of limiting maximum service loads to not exceed the routine test load for insulators has given satisfactory performance [31]. B. Composite Insulators Ultimate strength QC tests for composite insulators in ANSI,CSA and IEC standards for lot acceptance are withstand 2348 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 4, OCTOBER 2012 tests on small sample sizes which precludes a statistically-based recommendation. However, the concept of a damage limit below which irreversible damage does not occur, is well established for composites [32]. 1) Suspension Type: The damage limit for suspension-type composite insulators is about 65% of the short-term tensile strength, and the manufacturer-assigned SML rating is less than, but based on, this strength. As discussed in [1], a minimum short term of 105% of the SML was assumed to develop a guaranteed 1-min withstand strength curve. This corresponds to a damage limit (9) for suspension-type composite insulators. 2) Post Type: Manufacturers typically provide a maximum design cantilever load (working load limit) for composite posttype insulators. As discussed in [1], to establish a damage limit for posts, it is recommended that a design test should be a 96-h cantilever test at 110% of the MWL with the post then dissected and examined to ensure no damage to the rod occurred. This corresponds to a damage limit (10) V. CONCLUSIONS The rated mechanical strength of HV insulators for use on overhead lines manufactured to conform to ANSI, CSA, or IEC product standards only has meaning in the context of the individual standard upon which the rating is based. It does not imply minimum or guaranteed strength. According to the standards, insulators are judged to be in conformance with the requirements for a mechanical strength rating of a particular standard based on samples taken at random from a given lot and subjected to ultimate strength tests. Individual units in a lot could have strengths below the rated value, and the lot could still satisfy requirements for the lot to be accepted. If a normal distribution of strength for the insulators in a lot can be assumed, and the sampling rate and acceptance requirements are suitable for a statistical evaluation, the possible low strength limit for units in the lot can be estimated. The sampling requirements for ceramic (electrical-grade porcelain and toughened glass) HV insulators in ANSI, CSA, and IEC insulator standards are suitable for statistical evaluation of the strength distribution for lots of these types of insulators. The standards for composite insulators only require that a small sample withstand the rated mechanical load, and a statistical evaluation of the strength distribution in a lot is not possible. To provide long-term service continuity, the highest anticipated mechanical loading event for an insulator must not initiate irreversible damage to the insulator. The load at which irreversible damage is initiated is the damage limit of the insulator. For ceramic insulators, the damage limit is about 70% of the possible low strength for insulators based on a statistical evaluation of sample test results for a given lot. Depending on the standard, and the coefficient of variation for the process that produced the lot, this damage limit for suspension insulators corresponds to 34% to 70% of the insulator rated strength. The damage limit concept for composite insulators utilizing a resin-reinforced fiberglass rod is well established and corresponds to 65% of the rated strength for composite suspension insulators and 55% of the rated strength for composite post-type insulators. The methods for determining allowable in-service loads discussed in the companion paper and the avoidance of irreversible damage in HV insulators will provide long-term service continuity and strength coordination with other line components for safety and damage containment. REFERENCES [1] A. C. Baker, R. A. Bernstorf, E. A. Cherney, R. Christman, Z. Lodi, R. S. Gorur, R. J. Hill, S. Marra, D. G. Powell, A. E. Schwalm, D. H. Shaffner, G. A. Stewart, and J. Varner, “High voltage insulators mechanical load limits—Part I, overhead line load and strength requirements,” IEEE Trans Power Del., vol. 24, no. 3, Jul. 2012. [2] ANSI C29 High Voltage Insulator Standards Nat. Elect. Manuf. Assoc., Roslyn, VA. [3] ANSI C29 Electrical Power Insulators—Test Methods, C29.1-1988 (R2009). [4] ANSI C29 Wet-process Porcelain & Toughened Glass Suspension Type, C29.2-1992 (R2009). [5] ANSI C29 Wet-Process Porcelain Insulators-High Voltage Line Post Type, C29.7-1996 (R2010). [6] ANSI C29 Wet-Process Porcelain-Apparatus Cap & Pin Type, C29.81985 (R2010). [7] ANSI C29 Wet-Process Porcelain Apparatus Post Type, C29.9-1983 (R2010). [8] ANSI C29 Composite Insulators-Test Methods, C29.11 (Under Revision). [9] ANSI C29 Insulators-Composite-Suspension Type, C29.12-1997 (R2002). [10] ANSI C29 Insulators-Composite-Distribution Deadend Type, C29.132000. [11] ANSI C29 Insulators-Composite-Line Post Type, C29.17-2002. [12] ANSI C29 Insulators-Composite-Distribution Line Post Type, C29.182003. [13] “Standardization policies and procedures of the National Electrical Manufacturers Association,” Jul. 7, 2008. [14] “ASTM Manual on Presentation of Data and Control Chart Analysis,” Special Tech. Publ. (STP) 15D, 7th ed. [15] E. A. Cherney, “Failures of porcelain line post insulators on the Ontario Hydro distribution system,” presented at the Can. Elect. Assoc. Spring Meeting, Montreal, QC, Canada, Mar. 1988. [16] R. S. Gorur, E. A. Cherney, and J. T. Burnham, Outdoor Insulators. Phoenix, AZ: Ravi S. Gorur Inc., 1999. [17] Canadian Standards Assoc. (CSA), “CAN/CSA high voltage insulator standards,” Etobicoke, ON, Canada. [18] CAN/CSA AC Suspension Insulators: Wet-Process Porcelain and Toughened Glass, CSA-C411.1-2010, 2010. [19] CAN/CSA Ceramic or Glass Insulator Units for dc Systems, CSA-C1325-1999, 1999. [20] CAN/CSA Ceramic and Glass Station Post Insulators, CSA-156.11986, 1986. [21] CAN/CSA Composite Suspension Insulators for Transmission Applications, CSA-C411.1-1998, 1998. [22] Canadian Elect. Assoc., Canadian Electrical Association (CEA) Purchase Specifications. Montreal, QC, Canada. [23] Dead-End/ Suspension Composite Insulator for Overhead Distribution Lines, LWIWG-0.1, CEA, 1996. [24] Line Post Composite Insulator for Overhead Distribution Lines, LWIWG-0.2, CEA, 1996. [25] IEC, “IEC International Standard,” Geneva, Switzerland. [26] IEC International Standard Insulators for Overhead Lines-Ceramic or Glass Insulator Units for a.c. Systems-Definitions, Test Methods and Acceptance Criteria, IEC 60383. [27] IEC International Standard Ceramic or Glass Insulator Units for d.c. Systems, IEC 1325. BAKER et al.: HV INSULATORS MECHANICAL LOAD LIMITS—PART II [28] IEC International Standard Tests on Indoor and Outdoor Post Insulators of Ceramic Material or Glass for Systems With Nominal Voltages Greater Than 1 000 V, IEC 60168. [29] IEC International Standard Insulators for Overhead Lines—Composite Suspension Insulators for a.c. Systems With a Nominal Voltage Greater Than 1 000 V—Definitions, Test Methods and Acceptance Criteria, IEC 61109. 2349 [30] IEC International Standard Insulators for Overhead Lines-Composite Line Post Insulators for a. c. Systems With a Voltage Greater Than 1 000 V—Definitions, Test Methods and Acceptance Criteria, IEC 61952. [31] CIGRE, “Study and conclusions from the results of the inquiry on insulators: Information and damages,” CIGRE SC22-03, Oct. 1981. [32] IEEE Guide for Application of Composite Insulators, IEEE Standard 987.
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )