Switchsync® PWC600 Version 3.0 Product guide Document ID: 1MRK511825-BEN Issued: October 2024 Revision: B Product version: 3.0 © 2024 Hitachi Energy. All rights reserved. Copyright This document and parts thereof must not be reproduced or copied without written permission from Hitachi Energy, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document are furnished under a license and may be used or disclosed only in accordance with the terms of such license. Third Party Copyright Notices For detailed information about the third party copyright, refer to PWC600 OSS licenses declaration (1MRK511836-UEN). Trademarks Switchsync, Relion, and PCM600 are registered trademarks of Hitachi Energy. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest Hitachi Energy representative. Disclaimer This document contains information about one or more Hitachi Energy products and may include a description of or a reference to one or more standards that may be generally relevant to the Hitachi Energy products. The presence of any such description of a standard or reference to a standard is not a representation that all the Hitachi Energy products referenced in this document support all the features of the described or referenced standard. In order to determine the specific features supported by a particular Hitachi Energy product, the reader should consult the product specifications for that Hitachi Energy product. In no event shall Hitachi Energy be liable for direct, indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor shall Hitachi Energy be liable for incidental or consequential damages arising from the use of any software or hardware described in this document. Hitachi Energy may have one or more patents or pending patent applications protecting the intellectual property in the Hitachi Energy products described in this document. The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy assumes no responsibility for any errors that may appear in this document. All people responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including compliance with any applicable safety or other operational requirements. Any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. Products described or referenced in this document are designed to be connected and to communicate information and data through network interfaces, which should be connected to a secure network. It is the sole responsibility of the system/product owner to provide and continuously ensure a secure connection between the product and the system network and/or any other networks that may be connected. The system/product owners must establish and maintain appropriate measures, including, but not limited to, the installation of firewalls, application of authentication measures, encryption of data, installation of antivirus programs, and so on, to protect these products, the network, its system, and interfaces against security breaches, unauthorized access, interference, intrusion, leakage, and/or theft of data or information. Hitachi Energy performs functionality testing on released products and updates. However, system/ product owners are ultimately responsible for ensuring that any product updates or other major system updates (to include but not limited to code changes, configuration file changes, third-party software updates or patches, hardware change out, and so on) are compatible with the security measures implemented. The system/product owners must verify that the system and associated products function as expected in the environment in which they are deployed. Hitachi Energy and its affiliates are not liable for damages and/or losses related to security breaches, any unauthorized access, interference, intrusion, leakage, and/or theft of data or information. This document and parts thereof must not be reproduced or copied without written permission from Hitachi Energy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by Hitachi Energy in accordance with the product standards EN 60255-26 for the EMC directive, EN 60255-1 & EN 60255-27 for the low voltage directive, and EN 50121-5 for Railway applications (Emission and immunity of fixed power supply installations and apparatus). The product is designed in accordance with the international standards of the IEC 60255 series. 1MRK511825-BEN Rev. B Table of contents Table of contents Section 1 Introduction........................................................................................................ 3 1.1 1.2 1.3 1.4 1.5 1.5.1 1.6 1.6.1 1.6.2 This manual................................................................................................................................3 Intended audience......................................................................................................................3 Related documents.................................................................................................................... 3 Document revision history.......................................................................................................... 3 Product documentation.............................................................................................................. 4 Product documentation set.......................................................................................................4 Document symbols and conventions..........................................................................................4 Symbols....................................................................................................................................4 Document conventions.............................................................................................................5 Section 2 Application......................................................................................................... 6 2.1 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.3 2.4 2.5 2.5.1 2.5.2 2.5.3 2.6 2.6.1 2.6.1.1 2.6.1.2 2.6.1.3 2.6.1.4 2.6.2 2.6.3 2.7 2.7.1 2.7.2 2.7.3 Introduction.................................................................................................................................6 Load applications....................................................................................................................... 6 Capacitor bank......................................................................................................................... 6 Shunt reactor............................................................................................................................7 Power transformer....................................................................................................................7 Power cable .............................................................................................................................8 Transmission line .....................................................................................................................8 Variable applications................................................................................................................ 9 Controlled switching targets ...................................................................................................... 9 Circuit breaker properties......................................................................................................... 10 Optimization of accuracy.......................................................................................................... 11 Parameter compensation....................................................................................................... 11 Adaptive correction.................................................................................................................11 Target optimization for controlled closing .............................................................................. 12 Monitoring and supervision...................................................................................................... 13 Electrical operations monitoring............................................................................................. 13 Circuit breaker electrical status......................................................................................... 13 Detection of electrical switching instants...........................................................................14 Detection of re-ignitions/re-strikes.....................................................................................14 Interrupter wear................................................................................................................. 14 Mechanical operations monitoring..........................................................................................14 Coil circuit supervision............................................................................................................15 Requirements on external equipment...................................................................................... 15 Circuit breaker........................................................................................................................ 15 Current transformers.............................................................................................................. 15 Voltage transformers.............................................................................................................. 15 Section 3 Product description......................................................................................... 16 3.1 3.2 Introduction...............................................................................................................................16 Function principle..................................................................................................................... 16 Switchsync® PWC600 Product guide 1 © 2024 Hitachi Energy. All rights reserved. Table of contents 1MRK511825-BEN Rev. B 3.3 3.3.1 3.3.2 3.4 3.4.1 3.4.2 3.4.3 3.4.4 User interfaces......................................................................................................................... 18 Web interface (WHMI)............................................................................................................18 Local HMI (LHMI)................................................................................................................... 19 Communication ....................................................................................................................... 19 Communication protocols.......................................................................................................19 Data exchange....................................................................................................................... 19 Communication ports............................................................................................................. 19 Time synchronization..............................................................................................................20 3.4.5 3.5 Cyber security........................................................................................................................ 20 PCM600 tool.............................................................................................................................20 Section 4 Hardware description...................................................................................... 22 4.1 4.2 4.3 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.8 4.4 4.4.1 4.4.2 Overview.................................................................................................................................. 22 Available hardware slots and slot numbering........................................................................... 22 Hardware modules................................................................................................................... 22 Power supply module PSN1...................................................................................................22 Communication and processing module CB40...................................................................... 22 Binary input module BILD.......................................................................................................23 Relay binary output module BORO........................................................................................ 23 Static output module BOSO................................................................................................... 23 Current transformer input module AIC4................................................................................. 23 Current input terminals CTT1 and CTT5................................................................................ 23 Voltage transformer input module AIV4..................................................................................23 Mounting alternatives............................................................................................................... 24 Rack mounting....................................................................................................................... 24 Flush mounting.......................................................................................................................24 Section 5 Certification and Connection diagrams.........................................................26 5.1 5.2 Certification ............................................................................................................................. 26 Connection diagrams............................................................................................................... 26 Section 6 Technical data.................................................................................................. 27 6.1 6.2 6.2.1 6.2.2 6.2.3 6.3 6.4 6.5 IED........................................................................................................................................... 27 Energizing quantities, rated values and limits.......................................................................... 28 Environmental conditions....................................................................................................... 28 Analog inputs..........................................................................................................................28 Influencing factors.................................................................................................................. 29 Hardware modules................................................................................................................... 30 Electrical safety........................................................................................................................ 33 Connection system...................................................................................................................33 Section 7 IED Ordering and Accessories....................................................................... 35 7.1 7.2 Ordering................................................................................................................................... 35 Accessories.............................................................................................................................. 35 Section 8 Application data............................................................................................... 37 Section 9 Glossary............................................................................................................38 2 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 1 1.1 Section 1 Introduction Introduction GUID-5FDC7075-8302-4253-8A6E-CD464782B60F v1 This manual GUID-3BD5C6C4-16F8-430B-8DB0-133A6E61EF08 v2 This product guide provides information about PWC600 product, such as application usage, feature packages available with the product, information about hardware and hardware packaging including adherence to type test standards. The product guide also provides information about customizing the product and creating a product order code. 1.2 Intended audience GUID-D9A380F0-449B-424C-9F20-279C7E946CEF v1 This document addresses personnel requiring an overview of the product, its capabilities and performance properties, as well as defining a product configuration. Important: Commissioning a point-on-wave controller such as Switchsync PWC600 requires comprehensive knowledge on controlled switching in power systems, to assess and fully validate the performance of the controlled switching system. Aside from well-known occupational hazards inherent to working in an energized substation, improper commissioning may introduce additional risks such as damage to neighboring primary equipment, accelerated equipment wear, or even severe physical harm to substation personnel. Commissioning of PWC600 shall include live switching operations and shall be performed only by qualified personnel that is knowledgeable about this type of controller, technology, and field of implementation. 1.3 Related documents GUID-42926503-028A-4885-96EA-39CE83211411 v9 Table 1: Related documents 1.4 Documents Document ID User manual 1MRK511778-UEN Quick start guide 1MRK511826-UEN Technical manual 1MRK511779-UEN Communication protocol manual ED.1, ED.2 and ED.2.1 1MRK511828-UEN IEC 61850 data model desc Ed.2 and Ed.2.1 1MRK511829-WEN Type test certificate 1MRK511827-TEN Cybersecurity deployment guideline 1MRK511835-UEN OSS licenses declaration 1MRK511836-UEN Document revision history GUID-D5A1AF37-7CD2-4517-B5FC-08795AD7D67D v1 Table 2: Document revision history Document revision Date Product version History A 2024-10 3.0.1 Document not released. B 2024-10 3.0.1 First release Switchsync® PWC600 Product guide 3 © 2024 Hitachi Energy. All rights reserved. Section 1 Introduction 1MRK511825-BEN Rev. B 1.5 Product documentation 1.5.1 Product documentation set GUID-39A9874F-CDA5-4901-A382-39EB4090780A v1 GUID-3F2E67EF-154A-4BAC-A07D-9B6FF433325A v2 Decommissioning Deinstalling & disposal Maintenance Operation Commissioning Installing Engineering Quick start Planning & purchase This manual is part of the product documentation covering specific workflows or activities, as shown in Figure 1. Quick start guide Product guide User manual Technical manual Communication protocol manual Cybersecurity deployment guideline GUID-790ED0F7-3EE4-4809-AB34-8C73B4A845BC V1 EN-US Figure 1: The intended use of manuals throughout the product lifecycle 1.6 Document symbols and conventions GUID-EE2DDA74-F449-4560-A2A6-13C99E3F5475 v1 The following symbols and document conventions are used throughout the documentation: 1.6.1 Symbols GUID-73E89D47-0DD2-462E-A19B-7C7AD70E7014 v1 The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that, under certain operational conditions, the operation of damaged equipment may result in degraded process performance, leading to personal injury or death. It is important that the user fully complies with all warning and cautionary notices. 4 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B 1.6.2 Section 1 Introduction Document conventions GUID-E264C946-19E6-434B-BCFA-4A6B8B1FF4ED v2 • Abbreviations and acronyms used in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. • Dimensions are provided in millimeters unless otherwise specified. • Usage of terms • The term IED (Intelligent Electronic Device) is used in this manual interchangeable with PWC600 as a product within that device category. • The term HMI refers to : • LHMI refers to physical Local Human Machine Interface that comprises a 7" touch screen with indication and status LEDs. • WHMI refers to Web-based Human Machine Interface. It is accessible via any modern web browser, locally through a service port or remotely through the access points LAN/WAN. Switchsync® PWC600 Product guide 5 © 2024 Hitachi Energy. All rights reserved. Section 2 Application 1MRK511825-BEN Rev. B Section 2 2.1 Application Introduction GUID-9EF14101-C2F3-4722-BF9F-A12644F91211 v4 Switchsync® PWC600 is a point-on-wave controller, which is used to reduce electrical stresses imposed on the circuit breaker as well as on the switched load during energization and de-energization operations. Switchsync PWC600 can be used for controlled switching of all major load applications including reactors, capacitor banks, cables, transformers, and transmission lines, each with various design and connection configurations. Circuit breaker closing and opening commands that are not time critical are routed through Switchsync PWC600. The device (IED) then issues individual commands to the circuit breaker poles depending on the load to be switched, considering its connection and design configuration. Recommended switching targets for common load types are programmed into the software tools. PWC600 is able to dynamically select one out of several controlled switching scenarios, which is relevant, for example, for the middle (tie) breaker in a 1½ CB arrangement. After completion of a controlled switching operation, Switchsync PWC600 compares the actual with the target switching instants. The results are used to optimize the estimated operating times of the circuit breaker in the next operation. This process is known as “adaptive correction”; it compensates for systematic changes in the circuit breaker’s operation characteristics. Deterministic changes in operating times due to internal or external parameters, such as auxiliary voltage, idle time, ambient temperature, drive energy, can also be compensated using individual compensation curves. Respective sensor signals are either embedded in the IED itself, or they can be received from remote sources via IEC 61850 analog GOOSE messages. Switchsync PWC600 is capable of calculating the expected remaining life of the circuit breaker in terms of number of operations and electrical interrupter wear (ablation of arcing contacts, erosion of nozzles). This is based on interrupted primary current and status signals of CB auxiliary contacts. On every supervised signal, Switchsync PWC600 can generate warnings and alarms when crossing assigned limits. Such conditions can be indicated visually by LEDs on the LHMI, electrically by alarm contacts on the IED, or remotely via its Ethernet communication interfaces. Each supervision alarm can be individually enabled or disabled. 2.2 Load applications GUID-A3C989DF-31D3-4A17-B39B-55E2EC9F455B v2 Switchsync PWC600 is designed for point-on-wave switching (also known as controlled switching) of capacitor banks, reactors, transformers, transmission lines, and power cables. For each type of equipment and its design and connection configuration, the Switchsync Setting Tool (SST) proposes controlled switching strategies based on CIGRE recommendations. These switching strategies can be directly adopted by the user or modified as needed. This provides full flexibility in accommodating load applications other than the pre-defined ones. The following load applications are included in PWC600 along with recommended switching strategies. 2.2.1 Capacitor bank GUID-B74BC808-1076-41B2-9FF3-813908409C08 v2 Non-ideal energization of a capacitor bank may result in high transient inrush currents and, in turn, high switching overvoltages. To minimize inrush currents, energization shall be performed near gap voltage zero of each pole of the circuit breaker connected to the capacitor bank. In this regard, the connection configuration of the capacitor bank shall be considered for deciding the optimum switching targets for individual poles of the circuit breaker. 6 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 2 Application Controlled de-energization is typically not needed, given that most modern CBs show a very low probability of re-strikes; however, in some cases, an increased safety against re-strikes may be preferred. Controlled opening targets are set to ensure sufficient arcing time such that an adequate gap is achieved between contacts at the time of arc extinction. The time between arcing contact separation until natural current zero where arc is expected to be quenched is known as “arcing time”. Consequently, arcing times shall be determined considering the expected natural current zero across individual poles of the circuit breaker based on the connection configuration of the capacitor bank. 2.2.2 Shunt reactor GUID-08C3C3E9-EEC5-4D7C-BED4-0E96FE9B660C v2 When de-energizing a reactor, interaction between the reactor's inductance and stray capacitances will cause oscillating voltage transients with frequency in the range of kHz. Generally, for the latest generation of CBs, current is interrupted in the vicinity of a natural current zero in each pole with very low value of chopping currents. Consequently, the voltage transient across the breaker (TRV) may not have too high magnitude, but will have a very short rise time in the range of a millisecond. This can lead to breakdown of the dielectric withstand of the contact gap and hence, reappearance of the current through arcing. This phenomenon is known as a re-ignition and is not desirable because it may be harmful to both shunt reactor and circuit breaker. Controlled opening is used to minimize the probability of unwanted re-ignitions by ensuring sufficient gap between the arcing contacts at the time of natural current zero, where the arc is expected to be quenched. The needed arcing time shall be evaluated considering the last half-cycle length (which may be extended or shortened due to interaction between phases) and probable overvoltage across the contact gap in each CB pole post successful interruption. Controlled energization of reactors may be implemented to reduce the asymmetry in charging current due to an initial DC component. It is worth noting that reactor cores do not typically saturate and hence, the charging current will have sinusoidal waveshape (power frequency only) with exponentially decaying DC component. The energization target is gap voltage peak for each individual CB pole. Certain magnetic reactor designs or electrical connection configurations will create inter-phase coupling effects upon switching. These include 3-limb core design, which causes magnetic coupling between phases, Y (ungrounded) or delta connection schemes, or grounding through a neutral impedance. The switching targets for the individual CB poles should be evaluated considering these effects. 2.2.3 Power transformer GUID-5454F0D7-59EF-4C4C-A6E6-83D70D13E1ED v1 During no-load energization of a transformer, controlled switching is used for reducing inrush currents and, consequently, voltage distortion in the power system. In a weak grid, this distortion can lead to considerable voltage dip. If the transformer is directly connected to a long transmission line, it may create temporary overvoltage due to resonance of the line capacitance with the transformer inductance. This can even lead to nuisance tripping of other equipment connected to the same grid. The latest generation of power transformers exhibits very low levels of no-load losses (in range of 0.5-1% of the full load current). To achieve the same with optimum design, the magnetizing curves of transformer cores are dimensioned for high operating flux densities having the saturation point just above the rated voltage of the transformer. This may lead to very steep rise in magnetizing inrush current in case of just a small level of asymmetry in the operating flux. In addition, inter-phase coupling effects – either because of electrical coupling (due to at least one delta connected winding) or of magnetic coupling (through a three-limb core) – will result in inter-dependency between resultant fluxes linking with individual phase windings. Therefore, asymmetry in resultant flux of one phase will impact the resultant flux linkage and, hence, inrush current in other windings. In this context, the fluxes linking with individual phases are termed as “dynamic fluxes”. It can be well appreciated that achieving symmetrical flux upon energization requires consideration of residual fluxes in the core observed during the previous de-energization, of the interphase dependency (dynamic fluxes) based on winding configurations (vector group), and of the core design type (3 limb, 4/5 limb or single-phase bank) of the transformer. Consequently, the controlled energization strategy shall aim at energizing the individual poles on the reference voltage waveform in such a way that the resultant dynamic fluxes will be symmetric. To mitigate magnetic inrush current, no-load energization of Switchsync® PWC600 Product guide 7 © 2024 Hitachi Energy. All rights reserved. Section 2 Application 1MRK511825-BEN Rev. B a transformer should be performed at a phase angle where the source side flux matches the transformer side flux. This will create symmetric resultant flux in each limb, avoiding core saturation and resulting in minimized magnetizing current. PWC600 offers two approaches to considering residual flux while deciding controlled energization targets. 1. Residual flux “locking”: In this method, controlled opening is used to set a repeatable pattern of residual fluxes during transformer de-energization. The subsequent closing for individual poles is targeted in such a way that the resultant fluxes will have minimum level of asymmetry. Therefore, this method comes with fixed controlled energization targets. 2. Residual flux evaluation (PWC600-HT and -HLT models only): If inductive voltage transformers are directly connected to any winding of the transformer (primary, secondary, or tertiary if applicable) in two or more phases, their outputs can be used to evaluate the actual residual fluxes arising in the core. This is achieved by converting the measured voltages to limb voltages (which produce the fluxes in each transformer limb). During de-energization, the limb voltages are integrated to obtain phase-wise residual fluxes. This is done for every manual, automatic, or protection trip of the transformer CB based on transformer voltage amplitude. By matching the prospective dynamic fluxes with the evaluated residual fluxes, PWC600 evaluates phase-wise optimal making targets for the next controlled energization. Therefore, in this method controlled de-energization is not necessary. 2.2.4 Power cable GUID-FE8A6406-D763-476F-9606-0BA1A2795AC4 v3 For discharged power cables, controlled energization is used to minimize the switching overvoltage especially at the far end of the cable. To achieve this, like capacitor bank, energization is targeted at gap voltage zero in the individual CB poles. Long cables are often compensated with shunt reactors at one or two ends to minimize reactive power pull during off-load operation. In such conditions, energizing at voltage zero may cause high asymmetry of the current through the circuit breaker with no zero crossings for several power cycles. This “missing current zeros” phenomenon carries the risk of circuit breaker failure in case of protection trip shortly after energization of the cable. Therefore, the energization targets shall be shifted away from voltage zero to ensure acceptable asymmetry of the inrush currents, based on the highest expected degree of compensation. Similar to capacitor banks, controlled opening is typically not needed when switching power cables. Nevertheless, controlled de-energization (excluding fault trip) can be applied for ensuring re-strike free operation of the circuit breaker, in case excessive switching overvoltages are envisaged through system studies. 2.2.5 Transmission line GUID-07553B18-F198-4D33-BBF4-4DBED30E49AE v1 Controlled energization of a no-load transmission line is applied to minimize the switching overvoltage along the line, especially at the far end. To achieve this, energization is targeted at gap voltage zero in the individual CB poles. Controlled switching can also be applied during auto-reclosing of a line breaker. Here, the trapped charge on the line must be considered in determining the optimal reclosing targets. For an uncompensated line, this trapped charge voltage has the form of a slowly decaying DC; only when inductive voltage transformers are connected to the three phases of the line, they will usually drain the charge by the time of reclosing so that the line can be considered discharged. For a shunt compensated line, the trapped charge in the line capacitance will oscillate with the reactor inductances, forming a complex beat pattern across the CB; finding the optimal reclosing targets requires sophisticated signal processing algorithms. In either case, reclosing should not be executed before any secondary arc along the line is extinguished. 8 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 2 Application Long transmission lines are often compensated with shunt reactors at one or two ends to minimize the reactive power pull during off-load operation. In such conditions, energizing or reclosing at gap voltage zero may cause high asymmetry of the current through the circuit breaker with no zero crossings for several power cycles. This “missing current zeros” phenomenon carries the risk of circuit breaker failure in case of protection trip shortly after re‑energization of the line. Therefore, the energization targets and reclosing targets shall be shifted after voltage zero to ensure acceptable asymmetry of the inrush currents, based on the highest expected degree of compensation. Similar to capacitor banks, controlled opening is typically not needed when switching transmission lines. Nevertheless, controlled de-energization (excluding fault trip) can be applied for ensuring re-strike free operation of the circuit breaker. 2.2.6 Variable applications GUID-10FB53BF-40D7-45DA-A44C-9F4523D178F9 v3 In a 1½ circuit breakers arrangement, the middle (tie) breaker is connected to a load on each end. The same is applicable to every breaker in a ring layout. These two loads may be of the same type but more often they are different. The traditional approach to optimize controlled switching of both loads was to install two point-onwave (POW) controllers for the breaker, together with a hardware logic for transferring control to the appropriate POW controller. PWC600 can accommodate these functionalities in a single device through a feature called Setting Groups, which allows automatic selection of different parameter sets based on external signals or conditions. Variable applications, where setting groups are beneficial, include: • For the tie breaker in 1½-CB or ring arrangements, automatically select the appropriate reference source and switching strategy depending on the status of adjacent switches and/or voltage sources. • In a double-busbar arrangement, select the appropriate busbar VT as reference, without the need for external circuits for switching the VT signals. • For power transformers, if the residual flux "locking" strategy is used, apply a fallback strategy for closing (assuming zero residual flux) whenever the CB was opened not by PWC600. • For loads with variable electrical configuration, e.g. switchable earthing of neutral point, apply the optimal switching strategy in all cases. • For any application, bypass the controlled switching functionality whenever an external or internal binary signal is asserted. • For FAT or similar situations, where the actual CB is switching low voltage, provide a set of alternate CB settings (e.g. RDDS) that does not interfere with the original settings to be applied in the highvoltage grid. 2.3 Controlled switching targets GUID-AF07CFBC-6418-42BB-8221-F047EF309C32 v1 On arrival of a Close or Open command, PWC600 calculates the optimal switching targets for each CB pole. The calculations are based on the load to be switched, its connection and design configuration, and the switching duty considering operating time variations and external parameter variations. Controlled energization of most load types is targeted at fixed phase angles, which are defined by settings. For two load types, the making targets are determined dynamically. 1. Power transformer with residual flux: The target angles depend on the residual fluxes calculated at the time of de-energization. 2. Auto-reclosing on transmission line: The making targets are determined from the gap voltage across the open CB. As the gap voltage signal is typically non-periodic, the reclosing targets are not specified as phase angles but rather as time instants relative to the incoming Close command. Switchsync® PWC600 Product guide 9 © 2024 Hitachi Energy. All rights reserved. Section 2 Application 1MRK511825-BEN Rev. B Controlled switching targets in Switchsync PWC600 are defined with respect to a reference signal. • For load energization (controlled CB closing), primary voltage is always used as reference. Voltage measurement may be single-phase or three-phase, for phase-to-ground or phase-to-phase voltage. • For load de-energization (controlled CB opening), either the primary source voltage (same as for closing operations) or the load current may be used as reference. Current measurement must be taken from all three phases, and the CT secondary current should not be lower than 50 mA. • For controlled reclosing on a transmission line, the voltage across the circuit breaker is used as reference. This gap voltage is internally calculated from the source voltage and line voltage signals. Both measurements must be phase-to-ground voltage in all three phases. The selected reference signal can be used only when its amplitude is sufficiently high. For signal levels below the "dead value" threshold in any connected phase, the IED will declare missing reference signal. If it receives a controlled switching command in this condition it will fall back to a user-defined contingency action of either unsynchronized switching (bypass) or blocking the CB operation. For all controlled switching except reclosing on transmission line, the individual switching targets are specified as phase angles of the intended electrical switching instants, relative to a positive-going zero crossing of the selected reference signal. For common controlled switching applications, the optimal switching targets are predefined in the engineering tool “Switchsync Setting Tool” (SST): The user just needs to specify the type of load, its electrical connections (vector group) and possibly few other design or application parameters. With this information, the tool chooses the recommended controlled switching strategies from its built-in database and presents them as default values. The user may directly adopt the proposed switching targets, or adapt them to any special targeting requirements in the application. Whenever the making target is specified as 0° or 90°, PWC600 optimizes the actual target instants to accommodate the electrical and mechanical characteristics, such as RDDS and mechanical scatter, of the controlled circuit breaker. This ensures the best possible controlled switching results even with a non-ideal circuit breaker. 2.4 Circuit breaker properties GUID-57DE7EE4-C3A9-4447-870E-A39470A9612F v4 Knowledge of key parameters of the circuit breaker is essential for successful controlled switching. The required parameters are usually separate for Close and Open operations: • Mechanical behavior under nominal conditions (timing, accuracy) • Dielectric properties (RDDS, re-ignition free window) • Impact of external influences, such as DC control voltage or temperature, on operating times (compensation curves) • Permitted limits on deviation from default values • etc. Some of these parameters are defined by the circuit breaker design; these can be provided in advance. Others are specific to each pole and are ideally obtained on site during (or prior to) commissioning. For each circuit breaker model in Active life cycle phase, and for some older models as well, Hitachi Energy’s CB factory can provide an XML file containing the relevant design-related parameters. Importing this file into Switchsync Setting Tool (SST) relieves the user from the need to individually obtain and enter these parameters. In case no such file is available for the actual circuit breaker model, the user may manually enter the required data into SST. For acquisition of pole-specific parameters prior to live switching, Switchsync PWC600 provides a “CB timing test mode”. With the main contacts temporarily connected to dedicated inputs, offline switching operations are controlled and evaluated by the IED. The operating times thus learned can be adopted in regular operation. 10 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B 2.5 Section 2 Application Optimization of accuracy GUID-B20C6CAD-C82A-40DC-90BC-4BE38AC20621 v3 The operating times (switching times) of the circuit breaker may change with certain parameters, such as time (age), temperature, idle time since the last operation, and DC control voltage. To optimize the controlled switching performance against such changes, Switchsync PWC600 provides two features, namely, parameter compensation and adaptive correction. Based on these features, the release instants of the circuit breaker are adjusted for optimal targeting during controlled switching operations. 2.5.1 Parameter compensation GUID-65F87814-1CA3-46DC-94B8-AC8FBD53595B v4 The Switchsync PWC600 IED has the facility to compensate for the influences of external and internal parameters, namely, DC control voltage, idle time, temperature, drive pressure, spring charge, and an additional user-defined parameter. For each of these, it applies individual parameter compensation curves consisting of parametric variation vs. required operating time correction. Separate curves are provided for Close and Open operations. The individual compensation values are added up to yield a total compensation value for each CB pole. The factory provided files of Hitachi Energy circuit breakers include the relevant compensation curves for the respective CB type, where available. During engineering in Switchsync Setting Tool, the user only needs to specify which sensors are connected to the IED. Accordingly, the compensation functions are activated. It is possible to enable, disable or modify individual compensation curves manually. Sensor signals are either embedded in the IED itself, or are received from external acquisition devices (such as ABB RIO600) via analog GOOSE messages over IEC 61850 station bus. See Table 3 below. Table 3: Compensation facilities in pre-configuration Parameter Sensor Qty. Inputs to IED DC control voltage Voltage sensor 1 DC supply on PSN module Idle time Internal calculation based on status of CB auxiliary contacts 3 Binary inputs on BILD module Stored energy in CB drive Binary level contacts 3 Binary inputs on BILD module Temperature Temperature sensor (e.g. Pt100) connected to external acquisition device 1 or 3 Analog GOOSE Drive pressure Pressure sensor connected to external acquisition device 1 or 3 Analog GOOSE Additional quantity (user-specified) Sensor for additional quantity, connected to external acquisition device 1 or 3 Analog GOOSE Compensation values are continuously updated. Thus, the actual compensation value is available at the time when a controlled switching operation is executed. Furthermore, each sensor signal is checked against supervision thresholds, and an alarm can be raised on crossing a limit. 2.5.2 Adaptive correction GUID-D28BECD1-2961-4CCF-8E91-AA5F407FC292 v5 After completion of a controlled switching operation, Switchsync PWC600 acquires the actual instants when the switching took place. For this purpose, it analyzes the primary analog signals (load current, load voltage) and the timing of binary signals from precision position sensors or accurate auxiliary contacts in the CB drive, as available. The instants of inception or interruption of the primary signals are determined using adjustable detection thresholds. The actual switching instants are compared with the target instants; the difference is called Target Error. It is the basis for adaptive correction and other monitoring features. For closing operations, a fraction of each target error is used as correction value, to update the estimated CB operating time for the next controlled closing operation. Switchsync® PWC600 Product guide 11 © 2024 Hitachi Energy. All rights reserved. Section 2 Application 1MRK511825-BEN Rev. B For opening operations, detection of a re-strike or re-ignition in any phase will increment the target arcing time for the respective phase by 1 ms in the next operations. If the cumulated correction value exceeds the threshold, an alarm is raised and further CB operations will be blocked until the cause has been investigated and remedied. This is to protect the circuit breaker from failure due to repeated unwanted re-ignitions. 2.5.3 Target optimization for controlled closing GUID-18B30EA1-8409-42E8-9EE3-AD170AB449FA v1 To achieve best possible performance considering dielectric and mechanical scatter, the difference in pre-strike voltage at both boundaries of the target making window shall be minimized. Consequently, the final (strategic) making target is slightly shifted from the ideal target: forward for gap voltage zero target and back for gap voltage peak target. Figure 2 and Figure 3 demonstrate the shift of the strategic making target (T1) and the offset of the mechanical closing target (T4) from the shifted making target. GUID-5EBFA381-5CA7-4434-A8E7-27482F100704 V1 EN-US Figure 2: Switching target optimization for controlled closing, voltage peak targeting 12 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 2 Application GUID-D6E84FDA-C729-4AF2-A002-66F3B1A4A3FF V1 EN-US Figure 3: Switching target optimization for controlled closing, voltage zero targeting Whenever the making target is specified as 0° or 90°, PWC600 optimizes the actual target instants as described above. For any other making target, no optimization is done but the actual target instants are constrained to the range spanned by the strategic targets for 0° and 90°. 2.6 Monitoring and supervision GUID-27ABFF2E-40DA-449A-A997-BA4C950B49E8 v4 All signals acquired by the Switchsync PWC600 IED are primarily used for execution and optimization of controlled switching operations. In addition, the same signals can be used for monitoring and supervision of the circuit breaker’s switching performance and its aging (due to number of operations or interrupter wear). On receiving a switching command, the available compensation signals are evaluated for compensation values. After issuing a switching command, the IED monitors the input signals for status changes. The sequence of these events is evaluated to determine actual operating times and further conditions such as re-ignitions/re-strikes. All these data are recorded in the operation log. Various supervision alarms have been pre-defined to indicate if the associated parameter crosses the limit. Each alarm can have two stages: warning and alarm, for which user can define the limits, and which can be individually enabled or disabled. 2.6.1 Electrical operations monitoring GUID-151481B3-1CEE-4B9C-AA78-C0129ABFFCA2 v5 Following every controlled switching operation, certain parameters are extracted from the recorded feedback signals, which can be selected as CB current or load voltage. 2.6.1.1 Circuit breaker electrical status GUID-6E5CBC2A-F24A-47E7-B61D-7358535E3EE9 v6 Switchsync PWC600 attempts to detect electrical status change of the circuit breaker (current making or current interruption) from the primary current or load voltage signals. The strategies employed vary by the set load type. Switchsync® PWC600 Product guide 13 © 2024 Hitachi Energy. All rights reserved. Section 2 Application 1MRK511825-BEN Rev. B • For capacitor bank and shunt reactor type loads, it is assumed that load current is generally above dead-band value when energized. • Power transformers exhibit very low magnetizing currents when energized. These currents are usually too low for reliable electrical operation detection. Electrical status detection is therefore based on load voltage only. 2.6.1.2 Detection of electrical switching instants GUID-7008CCA4-9F5E-47CF-BA63-3B49FD6A26FE v3 Detecting the precise instant of current making or current interruption is crucial to maintaining optimal accuracy by adaptive correction, and for faithful reporting of the controlled switching success. For detecting the actual instants when the selected electrical feedback signal starts or stops, PWC600 checks the signal against two adjustable thresholds to ensure optimal flexibility. PWC600 further converts the detected instants of current making and current interruptions into electrical operating times and actual switching angles. These values are recorded in the operation log and used for further monitoring and adaptation purposes as described above. For controlled switching of electrically or magnetically coupled transformers using the residual flux locking method, additional measures are needed to correctly detect the making instants. 2.6.1.3 Detection of re-ignitions/re-strikes GUID-0E3DD850-E940-4FA6-9F05-58D61FA61B0B v2 During opening, the circuit breaker is usually expected to interrupt the primary current at its natural zero. If current starts flowing again after that current zero, this is called a re-ignition (for inductive loads) or re-strike (for capacitive loads). The steep voltage front of current restart may damage the interrupter, hence it is desirable to avoid such events. In every controlled opening operation, Switchsync PWC600 checks the electrical interrupting time from the load current signal (when available). If final current interruption is observed more than 1/8 power cycle later than expected, this is interpreted as re-ignition or re-strike, which will raise a warning and trigger adaptive correction as described above. 2.6.1.4 Interrupter wear GUID-A553BE40-D5C1-4F8D-8A5D-B5E7A15D5E47 v5 In new condition, a circuit breaker is rated for a certain number of mechanical operations, interrupting no or very low currents. It is also rated for a certain (low) number of operations interrupting maximum fault current. Between these extremes, the interrupted current in every Open operation causes some erosion of the contacts and ablation of the nozzles, until the CB loses its ability to reliably switch off currents. This interrupter wear characteristic is often given in form of a curve. Switchsync PWC600 calculates interrupter wear as the equivalent number of mechanical operations that the circuit breaker has lost after interrupting a specific current. This individual value and the cumulated interrupter wear are recorded in the operation log. Upon reaching the limits specific to each breaker type, a warning or alarm can be raised. 2.6.2 Mechanical operations monitoring GUID-F94B9AFB-2C6E-46CD-BC21-D29F309AC847 v5 Following every switching operation, certain parameters are calculated from recorded instants of precision position sensor or accurate auxiliary contacts changeover. Most relevant are the actual mechanical operating times (closing time, opening time), which can be used for adaptive correction in case no suitable primary feedback signal is available. 14 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B 2.6.3 Section 2 Application Coil circuit supervision GUID-74377389-26D2-4181-8063-EBB21097FA7D v2 The six precision binary outputs for controlling CB closing and opening operations feature additional circuitry for supervising the status of the respective CB trip and close coil circuits. This Trip Circuit Supervision (TCS) functionality is optional and not required for controlled switching. When activated, the TCS continuously injects a small DC current into the coil circuit and measures the resulting voltage at its terminals. If the voltage is too low this indicates an open circuit, which will raise an alarm if enabled. 2.7 Requirements on external equipment 2.7.1 Circuit breaker GUID-71B616B6-64F8-4AA5-A1F4-A85F71534DDD v1 GUID-0CD5D324-F032-4182-B458-1DEA9BC800D2 v3 To achieve good controlled switching results, the controlled circuit breaker must exhibit stable and predictable switching behavior, as required by the application. General recommendations are given in CIGRE Technical Brochure 757 (2019). Detailed values need to be agreed with the manufacturer. Therefore, Switchsync PWC600 is generally sold only with Hitachi circuit breakers. 2.7.2 Current transformers D0E2407T201305141628 v7 The current transformer ratio is selected based on the power system data, for example, maximum load. Optimal accuracy of controlled switching operations can be achieved when the phase displacement does not exceed ±1 electrical degree at nominal current. For controlled switching of capacitor banks, measuring cores should be used to properly render the nominal load current. CTs of accuracy class 1 (IEC) / 1.2 (ANSI) or better are recommended. For controlled switching of shunt reactors, power transformers, transmission lines, or cables, protection cores should be used to prevent saturation. CTs of accuracy class 5P (IEC) / C (ANSI) or better are recommended. 2.7.3 Voltage transformers D0E2397T201305141628 v6 In most cases, inductive or capacitive voltage transformers can be used. For measuring the voltage on a transmission line or power transformeror transmission line, inductive VTs are recommended as they usually have better accuracy in rendering the switching transients. Specifically for controlled switching of a transformer using the residual flux estimation method , inductive VTs are mandatory to ensure accuracy in residual flux estimation. For optimal accuracy of controlled switching operations, the phase displacement should not exceed ±1 electrical degree at nominal voltage. VTs with a measuring core of class 1 or better are recommended for most types of loads. Only for line switching, protection cores of class 3P or better should be used in the line VTs. Capacitive voltage transformers (CVTs) should fulfil the requirements according to IEC 61869-5 regarding ferro-resonance and transients. Switchsync® PWC600 Product guide 15 © 2024 Hitachi Energy. All rights reserved. Section 3 Product description 1MRK511825-BEN Rev. B Section 3 3.1 Product description Introduction GUID-C33EF884-02BA-4253-A6EB-6305F2472820 v1 GUID-B5FC3CED-4D7B-4F92-BA26-A9FAD91B0DDB v5 Switchsync PWC600 is a point-on-wave controller for high-voltage circuit breakers. Its purpose is to delay circuit breaker operation commands such that current inception or current interruption occurs at a phase angle that minimizes stress on the switched load, the circuit breaker, and/or the power system. The PWC600 device (IED, intelligent electronic device) is usually installed in the control room in the bay control cabinet, where all required signals are present. PWC600 version 3.0 can be ordered in four variants: 1. PWC600-M (multi-purpose model) for capacitor banks, shunt reactors, power cables, and power transformers – all kinds of loads that are always switched at the same phase angles. It also supports setting groups for dynamically applying different switching strategies e.g. for two loads connected to the same circuit breaker. 2. PWC600-HT (transformer switching model) includes all features of PWC600-M and additionally offers estimation of residual fluxes in power transformers for optimal energization in all operating conditions. This functionality is provided by the TRAFOSWT application function, which is available only with the appropriate license. 3. PWC600-HL (transmission line switching model) includes all features of PWC600-M and additionally offers controlled fast reclosing on transmission lines, taking into account trapped charges and secondary arcs. This functionality is provided by the TLINESWT application function, which is available only with the appropriate license. 4. PWC600-HLT includes all features and license options of the PWC600-M, -HT, and -HL models. It is therefore suitable for all controlled switching applications supported by Hitachi Energy. The hardware of all these models is mostly identical except for the number of I/O modules, see Section 4. From the outside, the product models are distinguished by the order code, which is printed and encoded in the QR code on the label attached to the housing 3.2 Function principle GUID-443A69F3-F594-406C-A808-ED266F45BA41 v4 The connection of PWC600 in a power system and its high-level functioning principle can be understood from Figure 4. Upon receiving an Open or Close command at its binary input (BI) or via IEC 61850 GOOSE message, PWC600 evaluates the optimal controlled switching instants for each phase from a primary reference signal. In most cases, the reference is taken from a source side voltage transformer (1). The evaluation considers the design and connection configuration of the load as well as the dielectric and mechanical characteristics of the circuit breaker. Consequently, PWC600 issues a synchronized opening or closing command through its static outputs (SO) to the respective operating coil (2) (3) of each circuit breaker pole. Note that protection trips need to bypass PWC600 in order to be executed without delay. 16 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 3 Product description GUID-05D763D8-FD9D-4F99-9F13-60334985111D V1 EN-US Figure 4: Overview of PWC600 integration in a power system PWC600 also monitors the electrical and mechanical status and health of the circuit breaker as well as the performance of controlled switching during the previous operation. This information is obtained by detection the instants of inception or interruption of the primary feedback signal, which can be load current (4) or load side voltage (5). If no suitable primary feedback signals are available, monitoring is based on the changeover instants of CB auxiliary contacts NO / 52a (6) and NC / 52b (7). From the available feedback signals, PWC600 calculates the target error (difference between expected switching time and actual switching time from last operation) and applies a timing correction in the next operation. This process is known as “adaptive correction”. PWC600 also has a facility for measuring CB operating times during pre-commissioning through temporary connections to the primary contacts of individual circuit breaker poles. Figure 5 shows a block diagram of the interfaces to PWC600. The source side voltage, load side voltage and load current are connected to respective analog input modules. Incoming Open or Close commands and output commands to the circuit breaker coils are connected to the binary input & output modules. Also, the pole-wise auxiliary contacts and spring charge level (applicable for specific drive designs) indicators are connected to binary input modules. The power supply to the PWC600 is provided to the Power supply module. Alarms related to the health of the circuit breaker as well as the performance of controlled switching operations can be generated by relay contacts on the Binary output modules. The PWC600 IED continuously monitors itself and in event of any internal failure, generates Internal relay failure alarm. The user may interact with PWC600 through the local user interface (LHMI) or through a web interface (WHMI). Like for all Relion IEDs, settings and configuration of PWC600 are prepared in PCM600 tool. Switchsync® PWC600 Product guide 17 © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Close command in Open command in Binary input modules Auxiliary contacts NO/52a and NC/52b (3 phases) CB main contacts (3 ph.) Setting groups control Auto-recloser active Fault indication (3 phases) Breaker control Operation monitoring Alarms & recording PWC600 Spring charge (3 phases) Binary output modules Target evaluation Power supply module Load current (3 phases) Communication interfaces Load voltage (3 phases) Close cmd. out (3 phases) LHMI Controlled Switching Source voltage (1 or 3 ph.) Monitoring, Recording Analog input modules Section 3 Product description Open cmd. out (3 phases) Alarms & warnings Internal relay status DC supply Ethernet station bus Redundant station bus Local service port Configuration & Settings GUID-8FE6C8E8-6132-4B06-BF30-2B6460CC5551 V1 EN-US Figure 5: External interfaces of PWC600 device 3.3 User interfaces GUID-DA31E614-A7EA-45DE-B496-B7AA88A308AC v5 The user can interact with Switchsync PWC600 in several ways. • Web interface (WHMI) via web browser • Various tools in Hitachi Protection and Control Manager PCM600, installed on a PC • If ordered: Local Human-Machine Interface (LHMI) on the front panel of the IED, featuring LCD touchscreen and status LEDs 3.3.1 Web interface (WHMI) GUID-CDD825EE-01D0-4139-B413-E9AD0812AADE v1 The Web-based Human Machine Interface (WHMI) can be accessed locally and remotely: Locally by connecting a laptop to the IED, and remotely over LAN/WAN. GUID-92FB8D9A-166E-42A7-AF4C-AE27FBC41B58 V1 EN-US Figure 6: Web-based Human Machine Interface (WHMI) 18 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B 3.3.2 Section 3 Product description Local HMI (LHMI) GUID-1981E1F2-83AB-40C1-9325-66A89B915EF5 v1 The optional Local Human Machine Interface (LHMI) comprises a 7" color screen with touch sensing, located on the front panel of the IED. 15 programmable indicator LEDs are arranged to the right of the screen. GUID-D51BB030-1A5B-4B59-97AB-6DD661D339B3 V1 EN-US Figure 7: Local Human Machine Interface (LHMI) 3.4 Communication 3.4.1 Communication protocols GUID-1A9D66B3-C34D-450F-9478-ADFED5D6769A v1 GUID-ACE8FB3B-68A0-45E3-968C-BC994337E656 v1 The IED supports communication protocols IEC 61850-8-1 (editions 1.0, 2.0, 2.1) and HTTPS over Ethernet. All operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal communication (GOOSE) between the IEDs, is only enabled by the IEC 61850-8-1 communication protocol. 3.4.2 Data exchange GUID-BAF4E280-9FA6-42AE-B0F8-2BD01BF0958A v1 Waveform (disturbance) files are accessed using IEC 61850 or the Web interface. Disturbance files are also available to any Ethernet based application in the standard COMTRADE format. The IED can send binary signals to other IEDs (so called horizontal communication) using the IEC 61850-8-1 GOOSE (Generic Object Oriented Substation Event) profile. Binary GOOSE messaging can, for example, be employed for protection and interlocking-based protection schemes. The IED meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard. Furthermore, the IED supports the sending and receiving of analog values using GOOSE messaging. Analog GOOSE messaging enables fast transfer of analog measurement values over the station. The IED interoperates with other IEC 61850 compliant IEDs, tools and systems and simultaneously reports events to five different clients on the IEC 61850 station bus. 3.4.3 Communication ports GUID-8679037E-CE8E-408D-9C51-FE1F310BAA44 v1 All communication connectors, except for the Service Port on the front panel, are placed on the integrated communication module. The IED is connected to Ethernet-based communication systems via RJ-45 or fibre-optic LC connectors. Up to four Ethernet ports (SFPs) can be provided to enable redundant communication (PRP and RSTP). Switchsync® PWC600 Product guide 19 © 2024 Hitachi Energy. All rights reserved. Section 3 Product description 3.4.4 1MRK511825-BEN Rev. B Time synchronization GUID-69F6090D-0186-4881-B070-9FF2A4FFF4AE v1 The IED supports the following time synchronization method: • SNTP (simple network time protocol) 3.4.5 Cyber security GUID-B105F342-21E5-4416-B80A-10C2173FB957 v1 Switchsync PWC600 is compliant to the IEEE 1686 standard for cyber security of intelligent electronic devices (IEDs), and certification to additional standards is in preparation. Some of the built-in security features include, • Secure communication protocols (FTPS, HTTPS) • Hardening of the access points and communication ports • Protection against denial-of-service attacks • User management with role-based access control • Password policies for user accounts • User activity logging The full compliance statements are found in the Cybersecurity deployment guideline (1MRK511766UEN) for more information 3.5 PCM600 tool D0E808T201305141540 v4 Hitachi Protection and Control IED Manager PCM600 can be downloaded for free from the Hitachi Energy Grid Automation Software Library https://softwarelibrary.hitachienergy.com. It offers all the necessary functionality to work throughout all stages of the IED life cycle. • Planning • Engineering • Commissioning • Operation and disturbance handling • Functional analysis With the individual tool components, you can perform different tasks and functions. PCM600 can operate with various topologies, depending on the customer needs. Switchsync PWC600 comes with a default pre-configuration that covers most controlled switching applications. Necessary adjustments to the actual installation are done by settings. These settings are preferably entered and modified by a dedicated PCM600 tool, Switchsync Setting Tool (SST), see Figure 8. If necessary, the application configuration can be viewed and modified using other tools in PCM600. Switchsync PWC600 3.0 requires PCM600 version 3.1 or higher, with the latest Service Packs installed. 20 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 3 Product description GUID-B4A696F1-7DB6-48AD-8878-36DB68E95219 V1 EN-US Figure 8: Switchsync Setting Tool (SST) in PCM600 Switchsync® PWC600 Product guide 21 © 2024 Hitachi Energy. All rights reserved. Section 4 Hardware description 1MRK511825-BEN Rev. B Section 4 4.1 Hardware description GUID-FE591AA9-2442-40E6-A843-7D914B07F1A6 v1 Overview GUID-DDB240CD-D96B-41C4-AB38-60711E8A5C8B v1 PWC600 3.0 is based on a modular hardware architecture but comes in a pre-defined configuration depending on the product model (Section 3.1). The housing is designed for installation in a 19" rack, full width, 3U high. The hardware modules are arranged on the rear panel of the IED and can be exchanged by the user. 4.2 Available hardware slots and slot numbering GUID-566E1F7E-3A2F-4C06-8B97-38D41C653F97 v1 Table 4 shows the position of the hardware modules in the IED. Table 4: Position of the hardware modules in the IED Module Description PSN1 Power supply module 101 Module position / Slot number CB40 Communication and processing module 103 BOSO Static output module 105, 106 BILD Binary input module 107, 108, 109 (PWC600-HT, -HL, -HLT) BORO Binary output module 110 (PWC600-HT, -HL, -HLT) AIV Analog input voltage module 306, 307 AIC Analog input current module 308 CTT Current connector terminal 308.X1 GUID-8B0B6ACA-B006-40FE-B1FE-BCC2BDAF69C0 V1 EN-US Figure 9: Rear view slots of 3U, 1/1 x 19" IED 4.3 Hardware modules 4.3.1 Power supply module PSN1 GUID-269955FA-9F48-4EF6-92D0-C3E7D9765813 v2 GUID-5675D3BC-2067-4CB7-AC69-4786407166FB v1 The power supply is used to provide the correct internal voltages and full galvanic isolation between the product and the battery system. An internal failure alarm output is available. Alternative connectors of ring-lug or compression type can be ordered. 4.3.2 Communication and processing module CB40 GUID-0B37B97D-5E98-4816-A983-35D079E3E3C8 v1 The CB40 is a high-performance CPU module based on a dual-core ARM processor. It has four SFP cages for Ethernet communication. Up to four SFP transceivers for optical 100BASE-FX or galvanic RJ45 100BASE-TX communication can be mounted in the SFP cages. Only approved SFP transceivers 22 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 4 Hardware description are compatible. Application code and configuration data are stored in flash memory, and non-volatile RAM is used to store log data. The CB40 is equipped with a real-time clock that uses a capacitor to keep track of the time when the IED is not energized. 4.3.3 Binary input module BILD GUID-F3C39019-0974-481E-AC4B-1B0C99FF1795 v1 The binary input module has 8 galvanically isolated inputs. Nominal input voltage can be selected in PCM600 configuration tool and can be used for the input of logical signals to any of the functions. They can also be included in the disturbance recording and event-recording functions. This enables extensive monitoring and evaluation of the operation of the IED and all associated electrical circuits. 4.3.4 Relay binary output module BORO GUID-3EA7007A-E7A5-47A9-88C0-160F6E3FD127 v1 The relay binary output module has 12 independent output relays and is used for signaling purpose. 4.3.5 Static output module BOSO GUID-F4D45AC2-DBA7-4D52-8E02-9B2B4BA1E01A v1 The static output module has four fast, heavy-duty static outputs with configurable TCS (Trip Coil Supervision) and two changeover output relays for use in applications with standard making/breaking requirements. 4.3.6 Current transformer input module AIC4 GUID-BCAB807B-57B4-43CF-92E5-9CC0D2673755 v1 The AIC4 input module is used to galvanically separate and adapt the secondary currents generated by the instrument transformers. The module has four current inputs. 4.3.7 Current input terminals CTT1 and CTT5 GUID-9DC46B6A-C34F-40D8-8821-7F8B4F449926 v1 The CTT1 and CTT5 current input terminal cartridges are inserted into the AIC4 current input module and contain four calibrated, maintenance-free current inputs for either compression or ring-lug mount. As the calibration data are directly stored on the cartridge, the inputs can be exchanged directly. 4.3.8 Voltage transformer input module AIV4 GUID-978A08C7-974F-478C-87C8-7CA09753591E v1 The AIV4 input module is used to galvanically separate and adapt the secondary voltages generated by the instrument transformers. The module has four voltage inputs. Ring-lug or compression type terminal blocks can be ordered. Switchsync® PWC600 Product guide 23 © 2024 Hitachi Energy. All rights reserved. Section 4 Hardware description 4.4 1MRK511825-BEN Rev. B Mounting alternatives GUID-756830E4-CA6F-4630-A98C-0FA737C8664E v1 PWC600 is delivered in a 3U, 1/1 19" case with rack mounting kit. The relevant dimensions are shown below. 4.4.1 Rack mounting GUID-4E0D98A4-3C23-4F7B-A5AA-16428532BDFF v1 GUID-416EED36-4E2D-47D2-8D20-C808F5825157 V1 EN-US Figure 10: 3U, 1/1 x 19” size rack mounting Table 5: Rack mounting 4.4.2 Case size (mm) A B C D E F 3U , 1/1 x 19” 436 121.87 212.55 480 131.5 57.15 Flush mounting GUID-71039B9B-BF22-4DE9-9C02-684C6D023B5E v1 The flush mounting kit offers protection of the front panel according to IP54. It can be ordered as an optional accessory. 24 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 4 Hardware description $ ' ( PWC600 ) & % GUID-0861292C-BB87-47B1-BAFC-5613BD35ACD6 V1 EN-US Figure 11: 3U, 1/1 x 19” size flush mounting Table 6: Flush mounting Case size (mm) A B C D E F 3U, 1/1 x 19" 131.5 442 220.25 122.5 436 482.8 Switchsync® PWC600 Product guide 25 © 2024 Hitachi Energy. All rights reserved. Section 5 Certification and Connection diagrams Section 5 5.1 1MRK511825-BEN Rev. B Certification and Connection diagrams GUID-E02C5BB3-901F-4318-A164-A4549C649F27 v1 Certification GUID-8ABF79EA-13B7-4FB2-B81D-7E27048B32CA v1 The list of certifications for PWC600 is provided below. Table 7: Certifications list 5.2 Certificates Reference IEC 61850 Ed2 level A1 certificate issued by DNV GL 10452508-DSO 24-4133 IEC 61850 Ed2.1 level A1 certificate issued by DNV GL 10452508-DSO 24-4136 Connection diagrams GUID-BD136D34-BDAD-464F-A78A-39053525F4D7 v1 The connection diagrams are delivered in the IED Connectivity package as part of the product delivery. The latest versions of the connection diagrams can be downloaded from http://www.hitachienergy.com/protection-control. Connection diagram, PWC600 version 3.0, 1MRK009111-AA. 26 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 6 Technical data Section 6 6.1 Technical data GUID-F5B8732A-C881-40E6-B796-FB4D22F57690 v1 IED GUID-889158F8-97B7-4F3A-A73E-511A3345177B v2 Table 8: Case Front plate Sides, top and bottom Material Aluminium Surface treatment Powder coated Color NCS-S-1000-N Material Aluminium Surface treatment Powder coated Color Grey RAL 7024 GUID-BB74744A-670B-4FE4-A55B-64054C9248B4 v2 Table 9: Water and dust protection level according to IEC 60529 Device side IP class Front (Device front with status LEDs) IP40 Front (with LHMI) IP40 (Rack mounting kit) IP54 (Flush mounting kit with IP54 mounting seal) Sides, top and bottom IP40 Rear side IP20 with screw compression type IP10 with ring lug terminals GUID-5C026638-C641-4936-91D9-4110144B23D9 v1 Table 10: Impact test rating Description Reference standard Class Impact resistance test IEC 61010-1 IK06 GUID-D41D4A7E-079B-4D29-B34C-906DD7776C8E v1 Table 11: Weight and dimension of the IED with and without the mounting kit Type of structure Without mounting kit With rack mounting kit with Flush mount kit 3U, 1/1x19" LLED 3U, 1/1x19" LHMI Weight (kg/Lb) ≤ 8.4kg/18.52 lb ≤ 8.4kg/18.52 lb Dimensions (WxHxD) (in mm) 442x131.5x220.25 442x131.5x220.25 Weight (kg/Lb) ≤ 8.55kg/18.85 lb ≤ 8.55kg/18.85 lb Dimensions (WxHxD) (in mm) 480x131.5x220.25 480x131.5x220.25 Weight (kg/Lb) ≤ 905kg/19.95 lb ≤ 9.05kg/19.95 lb Dimensions (WxHxD) (in mm) 482.8x131.5x220.25 482.8x131.5x220.25 Switchsync® PWC600 Product guide 27 © 2024 Hitachi Energy. All rights reserved. Section 6 Technical data 1MRK511825-BEN Rev. B 6.2 Energizing quantities, rated values and limits 6.2.1 Environmental conditions GUID-B4EF00D1-88DD-418D-AD78-09B981F6E5A8 v1 GUID-4299FA96-9A23-4FFD-80BF-9DB0331DCF24 v1 Table 12: Environmental conditions Description IED type Value For IEDs with LHMI Operating temperature range -25°C to +70°C Reduced display brightness may occur for temperatures above +55°C. Short-time service temperature range -40°C to 70°C (< 16 h) Reduced display performance may occur for temperatures below -25°C. Relative humidity <97%, non-condensing Atmospheric pressure 70 kPa to 106 kPa Altitude up to 3000 m Transport and storage temperature range -40°C to +85°C For Device front with status LEDs Operating temperature range -40°C to +70°C Short-time service temperature range -40°C to +85°C (< 16 h) Degradation in MTBF outside the temperature range of -40°C to +70°C. 6.2.2 Relative humidity <97%, non-condensing Atmospheric pressure 70 kPa to 106 kPa Altitude up to 3000 m Transport and storage temperature range -40°C to +85°C Analog inputs GUID-027C911A-459A-41C3-ABAB-4A3E17823541 v1 All current and voltage data are specified as RMS values at rated frequency. GUID-4FAA2B93-FBFF-4D08-89CC-93B9E708321A v1 Table 13: AIC4 - Energizing quantities, rated values and limits for protection and measurement current inputs Description Value Frequency Rated frequency fr 50/60 Hz Operating range fr ±10% Current inputs Rated current Ir 1 A or 5 A Table continues on next page 28 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 6 Technical data Description Value Operating range (0 - 100)×Ir Thermal withstand 100×Ir for 1 s 30×Ir for 10 s 10×Ir for 1 min 4×Ir continuously Dynamic withstand 250×Ir one half wave Burden < 15 mVA at Ir = 1 A < 100 mVA at Ir = 5 A Measurement accuracy (amplitude/ phase) IEC 61869-13 5.6.1301.1 Temperature range -30 °C / +55 °C Accuracy class = 0.1 KImin = 5% KImax = 400% (Ir = 1 A) KImax = 200% (Ir = 5 A) Temperature range -40 °C / +70 °C Accuracy class = 0.2 KImin = 5% KImax = 400% (Ir = 1 A) KImax = 200% (Ir = 5 A) Protection accuracy IEC 61869-13 5.6.1301.2 KImin/4 Ir < 0.2% < 10 arcmin KImin Ir < 0.1% < 5 arcmin Ir < 0.1% < 5 arcmin KImax Ir < 0.1% < 5 arcmin KImin/4 Ir < 0.4% < 20 arcmin KImin Ir < 0.2% < 10 arcmin Ir < 0.2% < 10 arcmin KImax Ir < 0.2% < 10 arcmin Accuracy class = 2 TPM KSSC = 70 TI = DC GUID-5E902F95-6A9B-4C92-B04A-0288603A3BEB v1 Table 14: AIV4 - Energizing quantities, rated values and limits for protection and measurement voltage inputs Description Value Frequency Rated frequency fr 50/60 Hz Operating range fr ±10% Voltage inputs* Rated voltage Ur = 100, 110, 120, 125, 220 V Operating range 0 - 360 V Thermal withstand 550 V for 1 min 450 V continuously Burden < 25 mVA at 110 V < 100 mVA at 220 V Measurement accuracy (amplitude/ phase) IEC 61869-13 5.6.1302 Temperature range -30 °C / +55 °C Accuracy class = 0.1 FV = 1.5 (2 - 20) V < 0.2% < 10 arcmin (20 - 360) V < 0.1% < 5 arcmin Temperature range -40 °C / +70 °C Accuracy class = 0.2 FV = 1.5 (2 - 20) V < 0.4% < 20 arcmin (20 - 360) V < 0.2% < 10 arcmin *) all values for individual voltage inputs 6.2.3 Influencing factors GUID-9D52DEB1-9344-4677-A4F4-10B9BF2EE43C v1 GUID-87AC0C1D-FC70-4C7D-ADAA-B48EEC1E1C37 v1 Table 15: Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, operate value +20 ±5°C -40°C to +70°C +85°C permissive 16hrs 0.02%/°C Relative humidity Operative range 45 – 75% 0 – 95% 10 – 90% – Switchsync® PWC600 Product guide 29 © 2024 Hitachi Energy. All rights reserved. Section 6 Technical data 1MRK511825-BEN Rev. B Table 16: Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal range Influence Ripple, in DC auxiliary voltage Operative range max. 2% Full wave rectified 15% of EL 0.01%/% ±20% of EL 0.01%/% Auxiliary voltage dependence, operate value Interrupted auxiliary DC voltage 90 – 250 V DC ±20% No restart Correct behaviour at power down Interruption interval 0 – 50 ms 0–∞s 110 – 250 V DC Restart time 6.3 < 300 s Hardware modules GUID-1E889716-FACD-4F09-B2D8-32014AAD6FDE v1 GUID-1A5FF058-8AB5-4FC9-8CCC-083E3DE8E657 v1 Table 17: Binary input module BILD Function or quantity Rated Value Number of inputs 8 Input DC voltage RL 24 – 250 V DC, ±20% Typical continuous input current 24/30 V DC 3.1 mA 48/60 V DC 1.6 mA 110 V DC 1.0 mA 125 V DC 1.0 mA 220/250 V DC 0.9 mA 48/60 V DC high inrush 1.6 mA 110 V DC high inrush 1.0 mA 220/250 V DC high inrush 0.9 mA Counter input frequency1) 24/30 V DC 30 pulses/s max 48/60 V DC 15 pulses/s max 110 V DC 8 pulses/s max 125 V DC 7 pulses/s max 220/250 V DC 6 pulses/s max 48/60 V DC high inrush 9 pulses/s max 110 V DC high inrush 4 pulses/s max 220/250 V DC high inrush 3 pulses/s max Oscillating signal discriminator Blocking settable 1– 40 Hz Release settable 1– 30 Hz Debounce filter Settable 1 – 25 ms2) Binary input operate time (Debounce filter set to 1 ms) < 3 ms Timestamping accuracy 220/250 V DC hi inrush < 100 μs < 1 ms Table Note: 1) If the actual counter frequency is higher than that specified in this table but lower than the oscillation block limit, the module will still count the correct number of pulses, but the inrush current will be periodically turned off to protect the input from overheating. 2) For compliance with surge immunity when the binary input is configured for 24/30 V DC, minimum debounce filter time setting of 3 ms is required. 30 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 6 Technical data GUID-66ECBAD4-3005-4472-B0DA-96DAA7E31855 v1 Table 18: Relay binary output module contact data (reference standard: IEC 61810-2) BORO Function or quantity Rated Value Binary outputs 12 Max system voltage 250 V AC/DC Min load voltage 24 V AC/DC Test voltage across open contact 1 min 1000 V rms Current carrying capacity Per relay, continuous 8A Per relay, 1 s 10 A Per process connector pin, continuous 12 A Max number of operations Inductive load L/R ≤ 40 ms 1000 Resistive load 2000 No load 30 million Making capacity at inductive load with L/R > 10 ms 0.2 s 30 A 1.0 s 10 A Making capacity with resistive load 0.2 s 30 A 1.0 s 10 A Breaking capacity for AC, cos j > 0.4 250 V/8.0 A 120 V/8.0 A Breaking capacity for DC with L/R ≤ 40 ms 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A Operating time < 6 ms A maximum of 72 outputs may be activated simultaneously with influencing factors within the nominal range. After 6 ms, an additional 24 outputs may be activated. The activation time for the 96 outputs must not exceed 200 ms. A maximum of 50% of outputs per module should be activated continuously. GUID-8F2DE045-9E39-412F-A725-284284C67876 v1 Table 19: Hybrid output module data (reference standard: IEC 61810-1): Static binary outputs BOSO Function or quantity Rated Value Max system voltage 250 V DC Min load voltage 12 V DC Number of outputs 4 Impedance open state (TCS de-activated) High impedance TCS Current, activated state 1 mA ±20% Current carrying capacity: Continuous 8A 1.0 s 20 A Making capacity at capacitive load with the maximum capacitance of 0.2 μF: 0.2 s 35 A 1.0 s 20 A Making capacity for DC with L/R > 10 ms: 0.2 s 35 A Table continues on next page Switchsync® PWC600 Product guide 31 © 2024 Hitachi Energy. All rights reserved. Section 6 Technical data 1MRK511825-BEN Rev. B Function or quantity Rated Value 1.0 s 20 A Making capacity at resistive load 0.2 s 35 A 1.0 s 20 A Breaking capacity for DC with L/R ≤ 40 ms (Auto-reclose scheme) (On ≤ 0.2 s) 0.2 s – on 0.2 s – off 0.2 s – on 20 s – off 0.2 s – on 30 s – off 0.2 s – on 120 s – off (for thermal dissipation) 24 - 60 V / 30 A 110 - 125 V / 20 A 220 - 250 V / 10 A Breaking capacity for DC with L/R ≤ 40 ms 6A (According to IEC 61810-1) 4 operations/min and 2 min pause for thermal dissipation Max number of operations Resistive load 100000 No load 30 million Operating time < 1 ms Table 20: BOSO - Hybrid output module data (reference standard: IEC 61810-1): Electromechanical relay outputs Function or quantity Rated Value Binary outputs 2 Max system voltage 250 V AC/DC Min load voltage 24 V AC/DC Test voltage across open contact 1 min 1000 V rms Current carrying capacity Per relay, continuous 8A Per relay, 1 s 10 A Per process connector pin, continuous 12 A Max number of operations Inductive load L/R ≤ 40 ms 1000 Resistive load 2000 No load 30 million Making capacity at inductive load with L/R > 10 ms 0.2 s 30 A 1.0 s 10 A Breaking capacity for AC, cos j > 0.4 250 V/8.0 A Breaking capacity for DC load L/R ≤ 40 ms 48 V/1 A 110 V/0.4 A 125 V/0.35 A 220 V/0.2 A 250 V/0.15 A Operating time < 6 ms GUID-D10C19D4-05EF-410C-A4E2-74412E5AD464 v1 Table 21: Power supply module PSN1 Function or quantity Rated Value Auxiliary DC voltage EL 110 – 250 V DC, ±20% Power consumption <30 W (3U 1/1 casing, including 4 SFP) Supply interruption bridging time 50 ms Auxiliary DC power protection MCB with characteristic curve Z or B Table continues on next page 32 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 6 Technical data Function or quantity Rated Value IRF output (NO/NC) 1 Max IRF voltage 250 V AC/DC Min IRF load voltage 24 V AC/DC Test voltage across open contact 1 min 1000 V rms Current carrying capacity Per relay, continuous Per relay, 1 s 8A 10 A IRF Relay Operating time <20 ms GUID-29F73A4A-B769-4F8A-ACF2-248C7F4C05F8 v1 Table 22: SFP - Optical ethernet ports Quantity Rated Value Number of channels Up to 4 single or 2 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-FX Type of fiber 62.5/125 um, 50/125 um multimode OM1, OM2, OM3, OM4 Length up to 2 km Wave length 1310 nm, Class 1 laser safety Optical connector Type LC Communication speed Fast Ethernet 100 Mbit/s Table 23: SFP - Galvanic RJ45 6.4 Quantity Rated Value Number of channels Up to 4 single or 2 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-TX Type of cable Cat6 SF/UTP, Cat6 S/FTP or Cat6 SF/FTP Length <3m Connector Type RJ45 Communication speed Fast Ethernet 100 Mbit/s Electrical safety GUID-E1542253-5990-4899-8845-38EA5B07B0D1 v1 GUID-CE3CB002-1320-4DC9-8632-A18D5A5BC200 v1 Table 24: Electrical safety according to IEC 60255-27 6.5 Category Value Equipment class I (protective earthed) Overvoltage category III Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected) Connection system GUID-1DBE3545-41DE-4FC5-B720-DC596B1A180C v1 GUID-973DAA0D-355C-4926-8FA4-20B04E07DD7C v1 Table 25: CT and VT circuit connectors Connector type Rated voltage and current Maximum conductor area Screw compression type 250 V AC, 20 A 4 mm2 (AWG11) 2 × 2.5 mm2 (2 × AWG13) Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG11) Switchsync® PWC600 Product guide 33 © 2024 Hitachi Energy. All rights reserved. Section 6 Technical data 1MRK511825-BEN Rev. B GUID-9C450CBE-5F81-41EB-B2BD-E9A7377F4289 v1 Table 26: Auxiliary power supply and binary I/O connectors Connector type Rated voltage Maximum conductor area Screw compression type 250 V AC 2.5 mm2 (AWG13) 2 × 1 mm2 (2 x AWG17) Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG13) 34 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 7 7.1 Section 7 IED Ordering and Accessories IED Ordering and Accessories GUID-DCB3052D-3EAC-4583-8C42-ADDD2DD45A7E v1 Ordering GUID-07F921FA-5108-4E1B-ACAD-6D89289A3765 v1 Switchsync PWC600 is delivered in the following configuration: • Full-width 19" housing, 3 U high • Power supply module PSN01 for 110 – 250 V DC, • Communication & processing module CB40 with two optical (LC) and two electrical (RJ45) Ethernet SFP modules, • 2 static output modules BOSO, • 2-3 (depending on product model, see below) binary input modules BILD, • Binary output module BORO (only in product models PWC600-HL, -HT, and -HLT), • 2 analog voltage input modules AIV4, • Analog current input module AIC4 with terminal block CTT1 or CTT5. For a specific order, the following options need to be specified. Parameter Options Product version 3.0.1 Product model PWC600-M, PWC600-HT, PWC600-HL, PWC600-HLT Front panel Local HMI (LHMI), blank plate with status LEDs CT secondary rating 1 A, 5 A Terminals for analog and power supply inputs Compression type, ring-lug type The delivery package includes: • IED according to the ordering options, • 19" rack-mounting kit, • Paper folder containing the PWC600 Quick Start Guide and order specific documents. 7.2 Accessories GUID-6EAD65BF-58E4-4458-92CB-14406A9A2616 v1 The following accessories can be ordered with the IED. Table 27: Configuration and monitoring tools Function description Ordering number Hitachi PCM600 1MRK003395-FA Table 28: Mounting kits Function description Ordering number 19" rack mounting kit 1MRK020421-BA Flush mounting kit with IP54 mounting seal 1MRK020421-GA Switchsync® PWC600 Product guide 35 © 2024 Hitachi Energy. All rights reserved. Section 7 IED Ordering and Accessories 1MRK511825-BEN Rev. B Table 29: Hardware accessories Function description Ordering number Locking rib kit, for IED product version 3.x 1MRK020370-SA Slot cover, for IED product version 3.x 1MRK020081-13 USB A-C cable, 2m, for IED product version 3.x 1MKC950015-2 USB C-C cable, 2m, for IED product version 3.x 1MKC950015-3 USB C-C cable, 1m, with top screw, for IED product version 3.x 1MKC950015-4 Card removal tool, for IED product version 3.x 1MRK020081-43 36 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. 1MRK511825-BEN Rev. B Section 8 Section 8 Application data Application data GUID-9E3B88C5-7203-4020-8DD9-27C5A227EF8E v1 In order to provide the best suited products and services for your application, we require the following data on every circuit breaker to be controlled by PWC600. Item No Question 1 Bay number or identifier Details on one bay 2 Voltage level of the substation [kV] (for transformer: specify nominal system voltage for all windings) 3 CB model including nominal gas pressure, type of drive, and with or without grading capacitors (in multi-break CBs) 4 Nominal frequency [Hz] 5 Load to be switched Connection configuration / vector group (For transformer: specify for side of charging and voltage level of charging side) For power transformer: vector group or connection type of each winding For shunt reactor grounded through reactor or resistor (NGR): impedance of NGR Core construction (only for reactor or transformer) Power rating of the load [MVA / MVAR] - lowest and highest values For transmission line or power cable: Length of line/cable [km] For transmission line or power cable: Type of reactive compensation For transmission line or power cable: Lowest and highest degree of shunt compensation [%] Nominal load current [A] (for transformer, enter nominal value from side of energization; for cable or line, enter no-load charging current) 6 Environmental conditions Indoor / Outdoor Minimum ambient temperature of CB [°C] Maximum ambient temperature of CB [°C] Altitude is above 3000 m Other special conditions / needs 7 Grid short circuit current [kA] or power [MVA] (if available); else specific performance requirement from customer like permissible voltage variation on the grid 8 Turns ratio of the CT to be connected to the controlled switching relay 9 Accuracy class of the CT cores chosen 10 Source VT: turns ratio Source VT type Which primary phase(s) of the source VT will be connected to the point-on-wave controller 11 Load VT: turns ratio, which phase(s); Load VT type For transformers, add to which winding the VT is connected 12 Further information/Remarks Attach protection SLD showing positions and ratings of CTs/VTs, and customer specification if available. Switchsync® PWC600 Product guide 37 © 2024 Hitachi Energy. All rights reserved. Section 9 Glossary 1MRK511825-BEN Rev. B Section 9 Glossary AC Alternating current ACT Application configuration tool within PCM600 ANSI American National Standards Institute BI Binary input BILD Binary input module low density BORO Relay binary output module BOSO Static binary output module CB Circuit breaker CB40 Communication and processing module D0E688T201305141612 v9 COMTRADE Standard Common Format for Transient Data Exchange format for Disturbance recorder according to IEEE/ANSI C37.111, 2013 / IEC 60255-24 CT Current transformer CTT Current input terminal DC Direct current EMC Electromagnetic compatibility GOOSE Generic object-oriented substation event IEC International Electrotechnical Commission IEC 61850 Substation automation communication standard IEEE Institute of Electrical and Electronics Engineers IED Intelligent electronic device I/O Input and Output hardware modules IP 1. Internet protocol. The network layer for the TCP/IP protocol suite widely used on Ethernet networks. IP is a connectionless, best-effort packet-switching protocol. It provides packet routing, fragmentation and reassembly through the data link layer. 2. Ingression protection, according to IEC 60529 LAN Local area network LED Light-emitting diode LHMI Local Human Machine Interface PCM600 Protection and control IED manager PRP Parallel redundancy protocol PSN1 Power supply module RSTP Rapid spanning tree protocol (RSTP) SFP Small form-factor pluggable (abbreviation) Optical Ethernet port (explanation) SNTP Simple Network Time Protocol - Time synchronization TCS Trip circuit supervision VT Voltage transformer WAN Wide area network WHMI Web-based Human Machine interface 38 Switchsync® PWC600 Product guide © 2024 Hitachi Energy. All rights reserved. Hitachi Energy Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website 1MRK511825-BEN https://hitachienergy.com © 2024 Hitachi Energy. All rights reserved.