A Novel Adaptive Frequency Control Strategy for Micro Grid Priya Singh Bhakar & G. Kesava Rao Dr. Saumendra Sarangi Dept. Of Electrical Engineering, NIT Uttarakhand Srinagar, Uttarakhand, India Email: priyabhakar1995@gmail.com Kesava551@gmail.com Asst professor, Dept. Of Electrical Engineering NIT Uttarakhand Srinagar, Uttarakhand, India Email: usomsam@gmail.com Abstract—Modern strategy like use of Electronic Load Controller (ELC) to improve the system frequency is an attractive solution. However such an approach leads to decrease in efficiency of the system as part of the generated power during light load condition is dumped in resistive loads. Several approaches which are developed to improve the performance of the ELCs still have a void where they achieved a solution with a compromise of reduced efficiency. In this work, we have proposed a central control strategy to control the frequency without reducing the efficiency, where ELC and pump loads are connected in parallel. The pump load and ELC are controlled by observing the rate of change of frequency. When the ratio is positive, loads will on and the frequency will be maintained. The proposed method is tested for IEEE 7 bus system using MATLAB/SIMULINK and test results show that the scheme is able to maintain the frequency without losing the extra power. employed for the frequency regulation in micro grids, which is a basic concept drawn from micro hydro systems[2]. These controllers use a resistive load that dissipates the power in the form of heat energy which ultimately results in energy wastage. Such an approach can regulate the frequency compromising the efficiency of the system which is not desired. However in a competitive environment which demands highly efficient system, requires new development in such techniques to improve the efficiency. In the presence of renewable sources, simultaneous variation in generation and loads are observed which results into frequent voltage and frequency fluctuations. With limited performance of conventional frequency controllers, new schemes have been proposed to control the frequency which uses Electronic load controller. ELCs are fast in operation and best cost effective measures for active power balance in the system. The proposed model uses a chopper to dump the extra power (using resistive loads) which leads to energy wastage [3]. These ELCs has been continuously modified with time to achieve better performance [4]-[9]. Integrated or decoupled configuration of ELCs with STATCOM has improved the voltage and frequency of the system [4], where the authors have neglected improvement in efficiency. The efficiency of the system was compromised in few configurations that included control algorithms like least mean square algorithm, proportional resonant control algorithm, motor flux estimation algorithm [10]-[12].These algorithms provide harmonic compensation, voltage regulation and mitigation of triplen harmonics (with the use of transformers) with rejection of disturbances. The proportional resonant control algorithm improves the power quality of the system and also reduces the total harmonic distortion [10].The least mean square algorithm or Adaptive linear element based algorithm provides frequency control, load balancing and neutral current compensation [12].The available methods have left a corner where development is required to improve the efficiency and with respects to this the characteristic of the loads have been observed. In the distribution section several loads are available like heaters, water pumps, etc. Water being an essential part of the society, the pump is utilized daily to lift the water for its supply in all the cities. Water pump loads can be used in a Keywords—Distributed Generation; Micro Grid; Water Pump Load; Voltage and Frequency Regulation ; Electronic Load Controllers AbbrevationsSTATCOM-Static Synchronous Compensator ELC- Electronic Load Controller DG- Distributed Generator IGBT- Insulated Gate Bipolar Transistor FACTS- Flexible Alternating Current Transmission system BESS- Battery Energy Storage System HESS- Hybrid Energy Storage System I. INTRODUCTION The fast degradation of fossil fuel reserves has lead to the development in numerous renewable power generation techniques. The dearth of power has been lessen with the advancement in such power sources. With the penetration of small capacity renewable generations in distribution grid, existence of micro grid has evolved which can be operated in both grid and off grid modes. However, simultaneously the variation in both load and generation in such a micro grid has affected the voltage and frequency stability of the system [1]. New techniques like Electronic Load Controllers (ELC) are 978-1-5386-4318-1/17/$31.00 ©2017 IEEE Authorized licensed use limited to: Hitachi Energy. Downloaded on June 06,2025 at 10:46:04 UTC from IEEE Xplore. Restrictions apply. micro grid (work autonomously and supply water to a particular locality) that has used wind or micro hydro as distributed generator. In literature, various control strategies are developed for these pump loads [13]-[18]. Mostly such pumps are being operated for some fixed time in a day, either in morning or evening. However it is not required to operate the pump at regular fixed time and it can be done at any time in a day which may not affect water distribution. So why not operate the pump at light load condition and this can help us to maintain the frequency and manage the power which is dumped in ELC. This thought has driven us to design an automatic frequency controller for micro grid using water pump in parallel with ELC. In this paper, an electronic load controller along with a water pump load is employed for the frequency regulation. The control strategy uses the concept of rate of change of frequency for improving efficiency of micro grid. The proposed scheme is tested on a 7 bus distributed system and test results show the method is highly efficient in maintaining the system frequency where the surplus power is effectively utilized to improve the efficiency. II. SURPLUS POWER UTILIZATION BY WATER PUMP LOAD Electronic load controllers are connected near distributed generators in order to maintain the frequency constant. Earlier ELCs with resistive load were used. The surplus power was dissipated in resistor in the form of heat energy [19]. Dumping extra power in resistor was a wastage of energy and the system needed to overcome this energy wastage to improve the efficiency. Loads like battery energy storage systems (BESS) were used with ELCs to control the frequency and utilize the excess power. The use of BESS has improved efficiency to some extent. A further improvement in technology was needed as the batteries produced toxic disposals [20]. There was a need of a load that can be used in day to day life in almost every distribution grid and also consume the excess power to enhance the efficiency. Water pump is such a load that is used to raise water to certain height for distribution of water in societies, buildings, etc. Pumping water is required in every urban or rural areas. These pumps consume electrical energy to bring the water up to some height for distribution, where the energy required may be taken from grid or from renewable generations. With penetration of distributed generations in the grid, during light load condition to control the frequency, water pump can be used as loads which improve the frequency and efficiency of micro grids. However use of pump loads at light load conditions to eliminate the frequency variation will not affect normal water distribution. By consuming the excess power, the frequency is regulated along with the maintenance of the active power balance and power is also utilized without its wastage. As transient response of such system are not fast. In order to improve the frequency response, control combination of the Electronic load controller (ELC) which is faster in operation and pump load may be one of the possible option. However, in a micro grid system, loads are continuously varying in nature and this demands multiple electronic load controllers near distributed generators to maintain the active power balance of the system using adaptive control strategy. Such a control scheme regulates operation of ELC and pump load by considering the frequency and active power of the system. III. PROPOSED CONTROL STRATEGY A. Description of System An IEEE 7 bus system with distributed generators as shown in Fig. 1 is considered to observe the variations in frequency with variation in load generation of micro grid. The system consist of two DGs connected at bus number 1 (wind generator) and 6 (micro hydro generator) to provide 1.2MW power. As both the generated and load power are continuously varying, voltage and frequency fluctuations are observed in the system. To compensate these frequency variations, the system is modified with ELCs near by the DG connected to buses 6 and 1. Water pump as load is selected to mitigate the frequency fluctuations. It is tested at different buses of the system and its response is studied. For better performance of the system in order to decrease the losses and improve the system transient response, multiple water pumps are connected to bus 3 ( maximum voltage is obtained at bus 3 for connecting the pump loads after performing the load flow analysis) of the system as shown in the Fig.1. Fig. 1. Single line diagram of proposed micro grid using water pump load Control block shown in Fig. 1 may be placed at substation which is preferred to be at the centre of any region. The input Authorized licensed use limited to: Hitachi Energy. Downloaded on June 06,2025 at 10:46:04 UTC from IEEE Xplore. Restrictions apply. signal to this controller is active power and frequency collected from each bus and after every 4 second, this data is revised. Using the data, rate of change of frequency is computed and accordingly the electronic load controllers are triggered. The pictorial diagram of the proposed scheme with communication channels is shown in Fig.1. Step 5- οܲᇱ will be the difference in the total excess power and the power fed to the water pumps that results into the power which is dissipated in ELC using (3). οܲ ᇱ ൌ ο െ (3) There is possibility of multiple distributed generation sources which requires multiple electronic load controllers. If multiple pumps are available the complexity of the control algorithm will increase. In this work we have selected ELC at two locations where distributed generations are available (bus 1 and bus 6). However ELC may be placed at any point of the system. For simplicity the pump load is assumed to be connected at middle of the both the DG connected in the system. Using the generated power and load power information, total excess power is calculated and the controller determines the power to be utilised in water pump and in the electronic load controller to mitigate frequency deviation problem and accordingly the signals are generated. The ELC is operated using firing angle control of isolated gate bipolar transistor chopper. The power is dissipated in the electronic load controller as soon as the signal is given to the gate of the IGBT. This control strategy is completely automatic and no human interference is required to switch on the pump load and ELC. B. Proposed Algorithm The control algorithm is designed for the system provided in Fig.1. However it is not system specific. As system size increases the requirement of communication channel increases which in turn increases the data collected at the distribution center. This increases the computational burden which can be solved using high speed computational devices. Incase failure of communication channel, using previous data and observing the local frequency at distributed generation buses ELCs can be operated to reduce the frequency deviation. The flow diagram of the proposed method given in Fig. 2 and steps of the control strategy are given below: Step 1- Active power and frequency from all the buses are collected and the rate of change of frequency is computed. Step 2- The control algorithm is triggered for ௗ Ͳ (1) ௗ௧ ௗ Whenever is less than zero, after four seconds the ௗ௧ data from all the buses is revised. Step 3- The total excess power is calculated by equation (2) as ¨P which is the difference between generated and the load power. ¨P = െ (2) Step 4- ¨P is divided among all the pumps and the total motor pump load demand is nP (where n is the number of pumps) which is given to the controller. The motor loads are simultaneously switched ON. Fig. 2. Flow chart of control algorithm Step 6- These ELCs are controlled by the firing angle control of the IGBT chopper. ௗ Step 7- The parameter is again compared with zero. The ௗ௧ control algorithm is repeated whenever the rate of change of frequency is greater than zero. The ௗ is less than zero. algorithm will stop when ௗ௧ Authorized licensed use limited to: Hitachi Energy. Downloaded on June 06,2025 at 10:46:04 UTC from IEEE Xplore. Restrictions apply. IV. RESULTS AND DISCUSSION An IEEE 7 bus system is selected and modified as wind connected at bus 1 and micro hydro connected at bus 6 is varying in nature. The distributed generators are varied separately and also simultaneously to observe the efficiency of the proposed algorithm. Few special cases in this section are presented and simulated in MATLAB/SIMULINK to show the capability of the system. A. WITHOUT PUMP LOAD Case: Performance of proposed method for variation in wind unit To test the accuracy of the proposed algorithm, wind generation is varied at a light load condition keeping the hydro generation constant. As load varies, the frequency and active power at the buses are collected and the distribution generator bus frequency is plotted in the Fig. 3. As observed from the figure, the frequency has increased with decrease in loading. ௗ is greater than zero it will trigger the control Whenever ௗ௧ algorithm. The surplus power in this case is 20kW and is calculated using (2). The signal is transferred to the ELC connected at the bus 1 which consumes total 20kW. Fig. 3. Generation variation of wind generator without ELC Point A represents starting of the wind generation variation. The frequency is increasing with variation in wind power output at 6 seconds as seen in Fig. 3. Fig. 4. Generation variation of wind generator with ELC Point B represents starting of the frequency fluctuations. It is observed that when ELC is switched on at 60.5Hz, the variation in frequency is minimized and achieved within 0.35 seconds as observed from the Fig. 4. B. WITH PUMP LOAD Case I: Performance of proposed method for variation in wind unit The performance of the proposed method is also tested for variation in wind generation at a light load condition keeping the micro hydro generation constant. As load undergoes variations, the frequency and the active power at the buses are collected and the distribution generator bus frequency is plotted in the Fig. 5. As observed from the waveform, the ௗ frequency has increased with decreased loading. Whenever ௗ௧ is greater than zero it will trigger the control algorithm. The surplus power is 40kW, dumped power in ELC is 10kW and power fed to the motor pump loads is 30kW which are computed using (2) and (3). Signal is transferred to the ELC connected at bus 1 and water pumps connected at bus 3. This shows that the efficiency of the system has improved on comparing with previous case (without pump loads). Fig. 5. Generation variation of wind generator without ELC and water pump load Point C represents the variation of wind generation without employing electronic load controller and water pump load. The frequency has started increasing with generation variation at 6 seconds as seen in Fig. 5. Fig. 6. Generation variation of wind generator with ELC and water pump load Authorized licensed use limited to: Hitachi Energy. Downloaded on June 06,2025 at 10:46:04 UTC from IEEE Xplore. Restrictions apply. Point D represents the starting of frequency variations. It is observed that when ELC and motor pump loads are switched on after 60.5Hz, the variation in frequency is minimized and achieved within 0.45 seconds as observed from the Fig. 6. Case II: Performance of proposed method for variation in micro hydro unit The performance of the proposed method is also tested for variation in micro hydro generation at a light load condition keeping the wind generation constant. As load undergoes variations, the frequency and the active power at the buses are collected and the distribution generator bus frequency is plotted in Fig. 7. Surplus power in this case is 50kW, power consumed by ELC is 20kW and pump loads are consuming 30kW. Case III: Performance of Proposed method for variation in both Hydro and Wind geneartion Similarly the accuracy of the method is tested for variations in both micro hydro and wind generation. As the load changed, the frequency and active power at all the buses are collected and the distribution generator frequency is plotted in the Fig. 9. As observed from the figure, the frequency has increased with decrease in loading. The algorithm will be ௗ is greater than zero. The surplus power triggered whenever ௗ௧ is 60kW, power fed to ELC is 30kW and the power consumed by pump loads is 30kW which are computed using (2) and (3). The signals are transferred to the ELCs connected at bus 1, 6 and pump loads connected at bus 3. Fig. 9. Generation variation of both wind and micro hydro without ELC and water pump load Fig. 7. Generation variation of micro hydro generator without ELC and water pump load As observed from Fig. 7, the frequency has started ௗ increasing (point E) with decrease in loading. Whenever ௗ௧ is greater than zero, the control algorithm is triggered automatically and the signal is transferred to the ELC connected at bus 6 and pump loads connected at bus 3. The frequency increases (starts from point G) with variation in generation of both wind and micro hydro generators without ELC and motor pump as shown in Fig. 9. Fig. 10. Generation variation of both wind and micro hydro with ELC and water pump load Fig. 8. Generation variation of micro hydro with ELC and water pump load It is observed that when motor load and ELC are triggered at 60.5Hz, the frequency is controlled within 0.45 seconds as observed from fig 8. It is observed that when motor loads and ELCs are switched on, the frequency variation is controlled within 0.5 seconds as observed from Fig. 10. Different cases of power distribution between ELC and water pump loads are shown in Table I that hasTotal number of pumps in the system (n) - 8 Capacity of each pump- 5 Hp Authorized licensed use limited to: Hitachi Energy. Downloaded on June 06,2025 at 10:46:04 UTC from IEEE Xplore. Restrictions apply. TABLE I POWER DISTRIBUTION BETWEEN ELC AND PUMP LOADS Frequency Variation (in Hz) Number of pumps working 61.6 62.07 63 63.5 5 Power consumed by motor pump loads (kW) 17.45 Power consumed by ELC (kW) 2.55 7 8 8 24.43 30 30 5.57 20 30 Efficiency of the system increases with the use of water pump loads as seen in Table I. The frequency variations are minimized with the use of electronic load controllers and also the efficiency is improved with increasing number of pump loads. V. CONCLUSIONS This work presents a novel technique to control the frequency in a micro grid. System frequency and active power are collected at all the buses and the rate of change of frequency is computed to drive the control algorithm. ௗ Whenever is positive, the algorithm starts and accordingly ௗ௧ the electronic load controllers are triggered. The water pump along with ELC will consume excess power and also improve the system efficiency. The proposed method is tested for various cases considering variations in single and multiple distributed generators and found to be accurate. Test results shows that the frequency can be stabilized with improved efficiency within minimal time. It has been observed that both ELC and water pumps work satisfactorily for generation variation of different distributed generators. [8] R. F. de Camargo, L. G. Scherer, and R. V. Tambara, “Voltage and frequency regulation of standalone self-excited induction generator for micro-hydro power generation using discrete-time adaptive control,” IET Renew. Power Gener, vol. 10, no. 4, pp. 531–540, 2016. [9] L. G. Scherer, R. F. de Camargo, H. Pinheiro, and C. Rech, “Advances in the modeling and control of micro hydro power stations with induction generators,” IEEE Energy Convers. Cong. Expo., pp. 997–1004, 2011. [10] C. Becker Tischer, J. Tibola, L. Giuliani Scherer, and R. Camargo, “Proportional-resonant control applied on voltage regulation of standalone SEIG for micro-hydro power generation,” IET Renew. Power Gener., pp. 593–602, 2017. [11] L. G. Scherer and R. F. de Camargo, “Frequency and voltage control of micro hydro power stations based on hydraulic turbine’s linear model applied on induction generators,” Power Electron. Conf. (COBEP), Brazilian, pp. 546–552, 2011. [12] B. Singh and V. Rajagopal, “Control of standalone asynchronous generator driven by uncontrolled pico hydro turbine,” IEEE 5th Power India Conf. PICONF, pp. 1–5, 2012. [13] A. J. van Staden, J. Zhang, and Z. Zia, “A model predictive control strategy for load shifting in a water pumping shceme with maximum demand charges,” Appl. Energy, vol. 88, no. 12, pp. 4785–4794, 2011. [14] O. Alarfaj and K. Bhattacharya, “A controlled load estimator based energy management system for water pumping systems,” IEEE Trans. Smart Grid, vol. 3053, no. c, pp. 1–1, 2017. [15] P. Kumar and R. K. Pachauri, “Utilization of energy sources in hybrid PV / FC power assisted water pumping system,” no. 1, 2015. [16] T. Masuta, A. Yokoyama, and Y. Tada, “Modeling of a number of heat pump water heaters as control equipment for load frequency control in power systems,” pp. 1–7, 2011. [17] A. L. M. Mufaris, “Coordinated consumer load control by use of heat pump water heaters for voltage rise mitigation in future distribution system,” 2015. [18] U. C. Rathore and S. Singh, “Isolated 3-phase self-excited induction generator in pico-hydro power plant using water pump load in remote mountainous region of Himalayas,” IEEE Glob. Humanit. Technol. Conf. - South Asia Satell. GHTC-SAS, pp. 40–44, 2014. [19] O. Isolated, “Voltage and frequency controller for parallel operated isolated asynchronous generators,” pp. 120–125, 2007. [20] B. Singh and V. Rajagopal, “Design of a star-hexagon transformer based electronic load controller for isolated pico hydro generating system,” Int. Conf. Power Syst. ICPS, no. 153, pp. 25–30, 2009. APPENDIX REFERENCES [1] V. Rajagopal, B. Singh, and G. K. Kasal, “Electronic load controller with power quality improvement of isolated induction generator for small hydro power generation,” IET Renew. Power Gener., vol. 5, no. 2, p. 202, 2011. [2] V. Verma, P. Pant, and B. Singh, “Indirect current controlled VSC for reactive power and load control support to self-excited induction generator feeding 3-phase 4-wire isolated power system,”Jt. Int. Conf. Power Electron. Drives Energy Syst. PEDES Power India, 2010. [3] B. Singh and G. K. Kasal, “Analysis and design of voltage and frequency controllers for isolated asynchronous generators in constant power applications,” Int. Conf. Power Electron. Drives Energy Syst. PEDES, 2006. [4] R. R. Chilipi, B. Singh, G. Bhuvaneswari, S. Madishetti, and S. S. Murthy, “Static synchronous compensator-variable frequency drive for voltage and frequency control of small-hydro driven self-excited induction generators system,” IET Gener. Transm.Distrib., vol. 8, no. 9, pp. 1528–1538, 2014. [5] P. K. Goel, B. Singh, S. S. Murthy, L. S. Member, and N. Kishore, “Isolated wind – hydro hybrid system using cage generators and battery storage,” IEEE Trans, vol. 58, no. 4, pp. 1141–1153, 2011. [6] U. C. Rathore and S. Singh, “Isolated 3-phase self-excited induction generator in pico-hydro power plant using water pump load in remote mountainous region of Himalayas,” IEEE Glob. Humanit. Technol. Conf. - South Asia Satell. GHTC-SAS, pp. 40–44, 2014. [7] S. Syan and G. R. Biswal, “Frequency control of an isolated hydro power plant using artificial intelligence,” IEEE Work. Comput.Intell.Theor. Appl. Futur. Dir., pp. 1–5, 2015. 11kV, 1.2MW, 60Hz system data are provided as followsGenerators- PMSG and asynchronous generator Load- 1.2MW, 60Hz Water pump loads- 30kW (each of 5Hp) Line parametersLine 1-2 2-3 2-5 3-4 4-5 5-6 6-7 R (ohm) 1.35309 1.17024 0.8411 1.19702 1.52348 1.0882 1.25143 L(mH) 0.003516 0.003037 0.0021823 0.002141 0.0027279 0.001946 0.001946 Authorized licensed use limited to: Hitachi Energy. Downloaded on June 06,2025 at 10:46:04 UTC from IEEE Xplore. Restrictions apply.
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )