COMMONLY FACED O&M PROBLEMS OF THERMAL POWER STATIONS 1.0. BOILER & AUX (COAL, OIL, GAS FIRED): 1.1. Operational Problems ( Common ) 1.2. Mech. Systems 1.2.1. 1.2.2. 1.2.3. 1.2.4. 1.2.5. 1.2.6. 1.2.7. 1.2.8. 1.2.9. 1.2.10. 1.2.11. 1.2.12. 1.2.13. 1.2.14. 1.2.15. 1.2.16. 1.3. Controls & Instrumentation : 1.3.1. 1.3.2. 1.3.3. 1.4. Pressure Parts, Furnace & Second PASS Safety valves Isolating valves ( motorised & manual) Controlled circulation pumps Control valves Soot blowers systems Superheater & Reheater Spray System Milling system (Bowl mills & tube mills) Burner tilting system Coal piping Oil/Gas firing system Rotary Air preheaters FD,PA and ID Fans Electrostatic precipitator Water Chemistry System HP Bypass system (SULZER MAKE) FSSS Secondary Air Damper Control Aux. PRDS Electrical System : 1.4.1. 1.4.2. HT Motors ESP Controls 1.1. Common Operational Problems of Boiler & Auxiliaries: 1.1.1. Frequent trips on flame failure 1. 2. 3. 4. 5. 6. 7. 1.1.2. Furnace draft fluctuations along with flame scanner flickering: 1. 2. 3. 4. 5. 6. 7. 8. 1.1.3. Check for proper functioning of draft control on `Auto’ Check for disturbed flame condition Check for proper functioning of CMC/Fuel master control on Auto Check for proper functioning of PA header pressure auto control Check for proper functioning of secondary air flow auto Control Check for proper functioning of SADC on auto control Check for furnace trough sealing Check for any boiler tube leakage Main Steam/HRH steam temperature low/high: 1. 2. 3. 4. 5. 6. 7. 8. 1.1.4. Check for proper combustion Check for correct total air flow Check for correct coal air ratio Check for correct wind box to furnace DP Check for proper functioning of SADC Check for healthiness of flame scanners Check for flame failure circuit in FSSS Check for correct total air flow Check for correct burner tilt position Check for correct feed water temperature at Economiser inlet Check for slagging/scaling (external) on water wall, SH & RH tubes Operate wall blowers/LRSB at regular interval as per requirement Check for inside scaling in water walls & SH/RH tubes Check for choking of SH/RH attemperator nozzles/passing of SH/RH spray control valves Check for any undesired steam outlet due to passing of safety valves, drain valves, vent valves High unburnt carbon in flyash/bottom ash: 1. 2. 3. 4. 5. Check for proper and stable combustion Check for plugged coal pipes and ensure equal distribution in all four coal pipes Check and adjust the fineness of coal Maintain adequate total air flow (secondary air flow + PA flow) Maintain proper oxygen in flue gas. Cross check UCB instruments with local sampling 6. 7. 8. 9. 10. 11. 12. 13. 14. 1.1.5. Tripping of boiler on RH protections due to closure of HP/LP Bypass during start ups: 1. 2. 3. 4. 5. 6. 1.1.6. Maintain stable combustion Study RH protection logic Initially keep HP/LP Bypass valves on manual mode. After stable combustion and sufficient flow only they should be put on Auto Check for proper functioning of these valves on Manual and Auto’ Check protection closing circuit for any malfunctioning Maintain correct HP Bypass downstream temperature Unit load not increasing to rated load : 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 1.1.7. Ensure that burner tilt of all four corners is at same position. Maintain correct mill outlet temperature. Tune SADC as per requirement to optimize flame condition Carryout clean air flow test/hot traverse if required Check and optimise ball charge (Only for Tube mills) Check and replace worn out mill liners Check for proper mill clearances Maintain proper mill level (Only for Tube mills) Check classifier/reject chute for bypassing of coal air mixture Check for correct parameters of main steam/HRH steam i.e. pressure, temperature, flow Check for correct quantity of coal Check for proper combustion/flame condition Check for correct total air flow/Oxygen and CO in flue gas Check for calorific value, fixed carbon, ash content, moisture etc. of coal Check for correct feed water temperature at economiser inlet Check for correct fineness of coal Inspect mill and replace worn out liners and internals Check for correct mill output and take remedial measures to get optimum output Check for any boiler tube leakage Check for undesired steam outlet due to passing of safety valves, drain valves, vent valves. Attend all valve leakages Check for very dirty furnace due to deposition of slag/scale on water wall/SH/RH tubes High stack Emission : 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 1.1.8. Tripping of Unit on high/low drum level : 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.1.9. Check for functioning of all ESP fields Check for correct total air flow, Oxygen and CO in flue gas Check for correct flue gas temperature at ESP Check for proper rapping frequency Check for proper current settings Check for proper gas flow distribution in the pass during shut down Check for proper fixing of deflector plates of hoppers during shut down Check for eroded guide vanes/splitters during shut down Check for proper fixing of screen plates during shut down Check for proper closure of manhole doors, inspection doors etc. to prevent air ingress Check for proper functioning of ash handling system Check for high ash content in coal Check for sudden opening/leakage of waterwall/economiser tube Check for tripping of any one of running BFPs Check for malfunctioning of drum level auto control Check for closure of any valve in feed water circuit Check for opening of HP Bypass valve on fast opening mode. Check for sudden throw off/raising of load Check for tripping of two/three coal elevations simultaneously Check for disturbance in combustion Check for malfunctioning of drum level transmitters Frequent tube failures : 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Avoid sudden stress to boiler tubes Maintain rate of pressurisation/de-pressurisation as recommended during hydraulic test of boiler Maintain rate of rise/drop of temperature as recommended during start-up/shut down (follow start up curve) Monitor drum/SH/RH metal temperatures during start up/shut down DON’T TAKE MILLS INTO SERVICE UNLESS FLOW IS ESTABLISHED THROUGH REHEATER Maintain proper water chemistry regime as per recommendations. Check for tube thickness for any erosion. In case of erosion, tubes must be replaced Check for deposits/scales inside the tubes. If found, contact BHEL for further analysis and chemical cleaning. Check for possibility of choking Check for foreign materials/obstructions in the connected headers 1.1.10. Boiler drum pressure dropping suddenly : 1. 2. 3. 4. 5. 6. 7. 1.1.11. High DM Water make up : 1. 2. 3. 4. 5. 6. 1.1.12. Check for any boiler tube leakage Check for leakages from glands and bonnets of valves Check for passing of safety valves Check for passing of drain valves Check for passing of vent valves Check for optimum opening of CBD valves Boiler water silica level High : 1. 2. 3. 4. 5. 6. 1.1.13. Check for proper DM water quality Check for correct chemical regime in boiler drum Check that CBD valves are operative Check the CBD lines for any possible choking Check for any condenser tube leakage Check for proper opening of CBD valves Sudden reduction of load : 1. 2. 3. 4. 5. 1.1.14. Check for interruption of coal to the furnace due to choking in the burner Check for tripping of feeder/mill Check for disturbed combustion inside furnace Check for any boiler tube leakage Check for opening of boiler drains, vent, safety valves Check for choking in mills/drop in air flow through mill Check for malfunctioning of auto control of CMC/Fuel master control Check whether it is momentary due to grid disturbance or due to malfunctioning of turbine governing system Check for drum pressure. If the trend is increasing, take appropriate measures to stabilize drum pressure by reducing/cutting off fuel input to furnace. If necessary, cut off mills, one by one. Check for drum level. See whether auto control is able to maintain drum level. Otherwise take it on manual control. Check for furnace draft Check for secondary air flow, oxygen in flue gas. Ash build up in bottom ash hopper and water walls : 1. 2. 3. 4. 5. 6. 1.1.15. Check for proper functioning of bottom ash evacuation system Check for proper functioning of clinker grinder system Check for proper functioning of scrapper conveyor wherever provided Check for any choking of ash evacuation/disposal pipes Don’t allow building up of ash level in case of non-functioning of ash evacuation and associated systems. In case problem is persisting and ash level has started building, boiler must be stopped and ash/clinker is to be removed. High Flue Gas temperature at APH outlet : 1. Check for excess Air and total Air flow 2. Check for fineness of coal 3. Check for fouling of water walls, superheaters, reheaters etc. 4. Check for proper heat transfer in Air preheaters 5. Check for dampers position of Air preheaters 6. Check for Burner tilting system and bring it downwards. 7. Switch over to lower elevation mills. 8. Check for proper Air distribution and functioning SADC 9. Check for leakages through peep holes, manholes, seal water trough etc. 10. Check for tube failures. 1.1.16. Low Boiler efficiency : 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.1.17. Check for excess air flow Check for the reasons for high air preheater outlet flue gas temperature Check for higher unburnt carbon in bottom ash and fly ash Check for proper combustion and high `CO’ in flue gas Check insulation/refractory to arrest heat loss Check for entry of excess water/moisture alongwith coal. Arrest where possible. Check the fineness of coal Check for proper Air distribution and functioning of SADC. Check for steam/water leakages and tube failures. High excess Air flow : 1. 2. 3. 4. 5. Check the Air flow distribution and functioning of SADC Check the combustion Check the fouling of superheater, reheater and HTSH surfaces Check for air ingress through peep holes, manholes, seal trough etc. Check the reliability of air flow and O2 measurements 6. 7. Check the fineness of coal and functioning of mills. Set for proper air flow and O2 in Automatic combustion control. 1.2. Mechanical System : 1.2.1. Pressure Parts : 1.2.1.1. Water Wall tube failure : 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.2.1.2. Superheater/Reheater/Economiser/Tube failure: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 1.2.1.3. Check for deposits inside the tube. Analyse the deposits. Check for indications for overheating of the failed tube and the nearby tubes. Check the tube thickness of the failed tube and also nearby tubes. Check the healthiness of nearby wall blowers for steam passing Check for possibility of choking/loss of adequate flow through the tube In case of scales/chemicals deposits/Rust contact BHEL for further analysis and chemical cleaning Check for foreign materials/obstructions in water wall ring headers Check for possibility of failure of weld joint Check the orifices of the tubes in the ring header in case of controlled circulation boilers. Check for indications for overheating of the failed tubes and the nearby tubes Check for failure of weld joint Check the tube thickness of the failed tube and the nearby tubes Check the healthiness of nearby long retractable soot blower for steam passing Check for possibility of choking/loss of adequate flow through the tubes Check for foreign materials/obstructions in the connected headers Check the tube material for usage of proper grade material In case of scales/chemicals deposits/rust contact BHEL for further analysis and remedial measures Check the spacing and alignment of coils around the failed tube Check the availability/healthiness of tube shields/cassette baffles Unloading/overloading of hangers : 1. 2. 3. Verify the correctness of the hanger as per hanger schedule Reset all the hangers of the connected header, pipe, pressure part to the cold set values. Measure the hot value of the hanger and report to Engineering for analysis. 1.2.1.4. Fast erosion of water walls, superheaters, Reheaters & Economisers tubes: 1. 2. 3. 4. 5. 1.2.1.5. Distortion/dislocation of Buck stay structures: 1. 2. 3. 1.2.1.6. Check for possibility of local explosions and take preventive measures for recurrence. Check for expansion obstructions Contact BHEL for review of design Erosion of headers in Flue Gas path : 1. 2. 1.2.1.7. Check the operation of wall blowers/LRSBS w.r.t. possibility of steam erosion Provide additional tube shields/baffles for the tubes where there is faster erosion. Check the healthiness of existing tube shields/baffles Use erosion prevention methods around burner blocks, wall blowers etc. Contact BHEL for flow model studies Check for any longstanding steam/water leakages from Hand holes etc. Apply additional refractory for the affected position after consulting BHEL. Ash Deposits over water walls/superheaters/reheaters/economisers: 1. 2. 3. 4. Check the operation of wall blowers and LRSBS. Reset the schedule to prevent excessive deposits Check the combustion parameters Check the fineness of coal. Check the healthiness of secondary Air damper system 1.2.2. Safety Valves (Spring Loaded and Electromatic): 1.2.2.1. Set pressure/blow down got disturbed: 1. 2. 3. 4. 1.2.2.2. Missing of Blowdown rings lock pins: 1. 2. 1.2.2.3. Check the lower ring setting and also upper ring Check for erosion of seat/disc during shut down Check the position of lift collar and its locking Check overlap collar/orifice healthiness during shut down Safety valve did not, reset after floating 1. 2. 3. 4. 5. 1.2.2.5. Check for looseness of lock pins of all safety valves which can lead to falling of lock pins Replace the lockpins after proper setting of upper and lower rings. Valves passing/valves simmering: 1. 2. 3. 4. 1.2.2.4. Check for loosening of lock nut of pressure adjusting nut Check for lower and upper lock pins looseness/non-availability / breakage Check for disturbance of overlap collar setting Reset the set pressure/blowdowns. Check for disturbed lift collar position. Check for missing lock pin of lift collar Check for loose locknut of pressure adjusting nut Reduce the pressure till the safety valve resets Correct the lift collar, pressure adjusting nut positions Refloat the safety valve Blowdown adjustment could not be done with upper ring : 1. 2. 3. Check for seat/disc erosion during shut down Check overlap collar and its orifice Adjust overlap collar position one notch at a time and reset blowdown. 1.2.4. Controlled Circulation Pumps (600 MW) Boilers : 1.2.4.1. CC Pump differential pressure low : 1. 2. 3. 4. 1.2.4.2. Sudden rise in cavity temperature : 1) 2) 3) 4) 5) 6) 1.2.4.3. 3) 4) 5) 6) Arrest the leakages at the earliest, if possible Open the purge water to motor to make up the loss and prevent boiler water entry into motor Ensure the availability of cooling water to coolers If the leakage is from weld/flange joint and can not attended by normal means, on line sealing methods can be resorted to. If needed isolate the pump or stop the Boiler and attend to the leakages Ensure that cavity temperature is maintained below 60 Deg.c. to prevent damage to the motor High differential temperature across the pump (with pump not in operation) : 1. 2. 1.2.4.5. Check for leakages/back charging from the cavity of motor towards purge water line Check for leakages in the impulse piping of cavity water pressure Check for external leakages/tube leakages of the motor coolers Check for accidental opening/passing of drain valve of purge line before motor Check for failure of cooling water to motor coolers Check for leakages from the bushings Water leakages from the motor/motor cooler 1) 2) 1.2.4.4. Check whether Direction of rotation is proper Check for healthiness of the DP Transmitters and the connected control system Check for choking/leakages in DP transmitter impulse lines Ensure discharge valve is open Open the warm line and wait for reduction in differential temperature Check for plugging of warm up line Leakage from cooler (High pressure side) circuit: 1. Start the purging immediately 2. 3. 4. 5. Stop the motor If leakage can not be arrested, isolate the pump/stop the boiler Try for `ON LINE SEALING’ methods to arrest the leakage or attend OFF line. Prevent rise of cavity temperature beyond 60 Deg.C. to protect motor. 1 1.2.6 Soot Blower System 1.2.6.1 Wall Blowers 1.2.6.1.1. Soot blower valve head does not open 1. 2. 3. 4. 5. 6. 1.2.6.1.2. Blower Pressure/Flow is flow/high : 1. 2. 3. 1.2.6.1.3. Inspect the stem for any pitting/bending/damages Inspect the valve body for any dirt & clean. Inspect the valve seat for any dent/scratch. Lap the seat with disc. Check whether the spring is struck up or lost its strength. Blower is jammed/not operating : 1. 2. 3. 4. 5. 6. 7. 1.2.6.1.5. Check the pressure setting bolt Check the operation of pressure control valve at soot blower station Maintain recommended pressure Soot blower valve head does not close after blowing: 1. 2. 3. 4. 1.2.6.1.4. Check & set the pressure setting bolt. Check the gland tightness. Check whether valve stem is jammed/bent. Check the valve seat for any damages. Check the limit switches. For further service , contact maint. Engg. Check the swivel tube fouling with shroud tube. Check the swivel tube /guide rods for cleanliness. Check that gland packing is not too tight . Check the swivel tube against any pitting . Check the limit switch setting. Check oil level in gear box For further service ,contact Motor becomes overloaded : 1. 2. 3. 4. Check the tightness of gland packing Check the cleanliness of swivel tube,guide rods , rack & pinion. Check oil level in gear box Check healthiness of motor/cable/MCC 1.2.6.2. Long Retractable Soot Blowers 1.2.6.2.1. Soot blower jamming : 1. . 1.2.6.2.2. 2. 3. 4. 5. 6. Motor Overload : 1. 2. 3. 4. 5. 6. 1.2.6.2.3. Check the oil level & oil quality Vibration while operating : 1. 2. 1.2.6.2.7. Check & tighten the chain properly Grinding sound in Gearbox : 1. 1.2.6.2.6. Check for any weak links. Check whether circlips in chain links are properly available. Check that chain is not too tight Chain is coming out of housing : 1. 1.2.6.2.5. Check whethert lance tube is fouling with boiler tube or wall sleeve. Check the tightness of gland bush /gland packing. Check the setting of overload relay/MCC. Check the accumulation of dirt over the rails. Check the motor for insulation & winding . Check the cables for any damage. Failure of Traverse Chain : 1. 2. 1. 1.2.6.2.4. Check for any physical obstruction of travelling carriage with housing . Check for limit switch failure Check the gland tightness. Check for lance tube fouling with boiler tube or wall sleeve. Check whether scrapper plate bolt is broken . Check oil level in gear box Check for any obstruction of travel carriage in housing Check for proper chain tension Sootblower overrun : 1. 2. Check for traverse chain failure. Check the limitswitches ,timer setting. 3. 4. 1.2.6.2.8. Overheating of Lance Tube : 1. 2. 3. 4. 1.2.6.2.9. 2. Check the quality of packing ,tightness ,wear of packing etc., Check stem for any scratches, dents etc. For further service , contact Valve seat leakage : 1. 2. 3. 1.2.6.2.12. Check the quality of packing, tightness ,wear & tear of glands etc., Check the feed pipe for any surface defects such as scratches ,dents etc., Steam leakage through valve stem : 1. 2. 3. 1.2.6.2.11. Check the blowing pressure & verify whether valve opening bolt is available. Check the operation of valve stem . Check the flue gas temperature for any increase. Check whether flow protection is in service Steam leakage through travelling carriage : 1. 1.2.6.2.10. Check for any failure of contactor & contactor reverse coils. Check whether thermal overload relay for traverse motor has operated/fuses are blown and find out the causes. Check the gland packing for proper tightness Disassemble and inspect the valve disc and valve seat for any damage /corrosion. Check whether valve opening bolt is pressing while the travelling carriage is in home position . Limit switch failure : 1. 2. 3. 4. Check the limit switch contacts for quality Check the failure of internal parts such as springs ,locking notches etc., Check the assembly /direction for correctness . Check for any accumulation of foreign material /dirt in limit switch. 1.2.7. Excessive superheater/ Reheater spray: 2. 3. Check the healthiness and position of burner tilting system. Bring the tilts down Check fineness and proximate analysis of coal 4. 5. 6. 7. 8. 9. Check the proper functioning of spray flow meter Increase wall blowers operation frequency Reduce excess Air to the rated value Check windbox/primary air pressure Operate lower elevation mills Tune Automatic Superheater/Reheater temperature control 1.2.8.2. Bowl Mills : 1.2.8.2.1. Abnormal Noise/vibration in Separator Body. 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.2.8.2.2. Abnormal Noise in Mill side : 1. 2. 3. 4. 5. 1.2.8.2.3. 3. 4. 5. 6. 7. Check for worm shaft bearing failure Check for improper surface contact of some teeth of worm wheel and worm shaft Interference of pump hub with bushing Check for worn out/dry coupling Check for failure of vertical shaft bearings Check for temperature rise of any bearing Check for lubrication of upper vertical shaft bearing Overflow of oil from Mill Base/pressurisation of Mill base. 1. 2. 3. 4. 5. 1.2.8.2.5. Check for touching of scrapper with stationary parts Check for skirt assembly touching the mill bottom Check for breakage of scrapper assembly Check for presence of foreign material under scrapper Check for accumulation of coal in pyrite hopper and mill side Abnormal Noise in Mill Base : 1. 2. 1.2.8.2.4. Check for ingress of foreign material in the Mill Check for roller touching the bowl. Check for Bowl assembly touching the stationary parts. Check for proper compression of springs Check for Journal spring assembly bearing failure Check for increase of feeder speed to increase the coal flow to the Mill Check for loosening of separator body bolts Check the correctness of bull ring segments Check the bull-ring segments for excessive wear Check for Air leakage through Dust guard/Mechanical face seal into gear box Check for damages of mechanical face seal/Dust Guard Seal Check for opening of upper bearing cover Check for oil cooler tube puncture Check for excess oil level in mill base Hot Air dust leakage from cored holes of mill base : 1. 1.2.8.2.6. No return oil from vertical shaft upper radial bearing (Internal Lubrication Mill) 1. 2. 3. 4. 1.2.8.2.7. Check for damage of gasket or use of improper gasket Check for loose/missing bolts Use of proper sealing after proper cleaning of the making surfaces Mill Base Oil Temp High : 1. 2. 3. 4. 5. 6. 1.2.8.2.11. Check for puncture of oil cooler tubes. Check for breakage/leakage of return oil line Check for vertical shaft oil seal in upper bearing housing Oil leakage from flanges : 1. 2. 3. 1.2.8.2.10. Check for improper/damaged gland packing Air vent pipe of Mill base closed/plugged Oil leakage from cored holes of Mill base : 1. 2. 3. 1.2.8.2.9. Check for plugging of vertical shaft hole Check for plugging/breakage of return oil line Check the clearance between the pump and the hub Check for plugging of holes in the lower bearing housing Oil leakage from worm shaft packing gland 1. 2. 1.2.8.2.8. Check mechanical face seal/dust guard seal Check for choking of oil cooler pipes Check whether cooling water is charged with adequate pressure Check for proper oil level Check the quality of the oil. Check mechanical impurities and moisture in oil Check the matching of worm and worm gear Check for worn out damaged bearings Mill Coal Spillage high : 1. 2. 3. Check for healthiness of rolls and then clearance with respect to Bowl Check the wear out of Bull Ring segment, Bull Ring segment, worm wheel, Bowl extension ring etc. Check for the Jammed rolls 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 1.2.8.2.12. Non uniform spring deflection : 1. 2. 3. 1.2.8.2.13. Check setting of classifier Check alignment of classifier vane Check for puncture/plugging of classifier cone Check for wear out of Roller and Bull Ring segments etc. Check Ring Roll clearance Maintain proper air flow and mill outlet temperature Check for air bypassing of separator body liner Check for journal spring compression High Pulveriser Fuel Fineness 1. 2. 3. 1.2.8.2.16. Check Dust Guard and Mechanical Face seal Check the oil seal of upper bearing housing Low pulveriser Fuel Fineness : 1. 2. 3. 4. 5. 6. 7. 8. 1.2.8.2.15. Check unequal spring compression Check for unequal roll wear Check for improper ring-roll clearance Mill base oil contamination: 1. 2. 1.2.8.2.14. Maintain proper air flow Check for water ingress along with coal Check for pyrites along with coal Check for damaged vane wheel assembly Check the clearances between vane wheel w.r.t. separator body Avoid over-loading of Mill Maintain proper Mill outlet temperature Reset Ring roll clearance, Journal head and Pr Spring seat clearance Check Journal spring compression Check the setting of the classifier Check for journal spring compression Check setting of classifier Recheck sampling technique Mill Fires : 1. 2. 3. Choking of Mill with coal Filling of pyrite hopper and mill bottom with coal Spill over of coal to mill inlet air duct 4. 5. 6. 7. 8. 9. 10. 1.2.8.2.17. Vertical shaft failure : 1. 2. 3. 4. 5. 6. 7. 8. 1.2.8.2.18. Check for low quality of coal Check for high moisture in coal Check and set classifier setting Check spring compression Maintain proper air flow and mill outlet temperature Check ring roll clearances Check for worn out parts Check plugging of coal pipe and closure of one or more mill discharge valves. Mill Discharge valve not operating : 1. 2. 3. 4. 5. 1.2.8.2.20. Check for the equal spring compression Do not use roller with unequal wears Check for breakage of one of the spring Check for entry of heavy foreign material in the mill Check for improper locking of spring assembly Check for improper ring roll clearance Check for jamming of rolls Check for jamming of Trunion Bushing Low Mill output : 1. 2. 3. 4. 5. 6. 7. 8. 1.2.8.2.19. Maintain proper air flow Check for improper classifier settings Check for excessive ingress of water along with coal leading to improper grinding Check for wear-out of parts. Check for closure of MDV and plugging of coal piping Check for quality (high volatile matter) of coal Maintain proper mill outlet temperature Check the clearance between top and the body Check the seals of the power cylinder Check for proper compressed air pressure Arrest leakages in compressed air tubing Check the operation of solenoid valve and the control system Classifier vane not operating 1. 2. 3. 4. Check the clearances between classifier vanes and separator Check the classifier vane shaft straightness Check uniformity in the length of the link lever Check for damage to bearings and oil seals 1.2.8.2.21. Oil leakage from journal assembly 1. 2. 3. 1.2.8.2.22. Journal Oil Contamination : 1. 2. 3. 4. 5. 1.2.8.2.23. Check for improper surface contact between bull ring and bowl Check for heavy foreign material ingress in mill Check for excessive wear of bull ring Check for any mill fires Check for material quality Worm shaft bearing failure : 1. 2. 3. 4. 5. 6. 7. 1.2.8.2.27. Check for inadequate clearance between skirt and mill bottom Check for warpage of skirt causing rubbing Check for Mill fires and inadequate insulation Bull Ring segment Crack : 1. 2. 3. 4. 5. 1.2.8.2.26. Check for entry of heavy foreign material in Mill Check spring compression Check ball bearing failure Mill bottom cracking : 1. 2. 3. 1.2.8.2.25. Check for quality of oil Check for damaged seals Check for damage of bearings Check oil level Check for oil filling cap missing/loosening Spring Adjusting Stud failure 1. 2. 3. 1.2.8.2.24. Check for damage of oil seal (O ring) Check for damage for upper journal assembly lip seal Check for damaged journal shaft (seating area of oil seal) Check the quality of oil and replace the oil id needed Check the quality of the bearings Check the bearing housing damage Check for improper installation methods Check for excessive backlash in worm gear Check for improper matching of worm and worm gears Check for damage of thrust bearing spring Vertical Shaft Gear Lub lock nut failure 1. 2. 3. 1.2.8.2.28. Insulation cover plate warpage : 1. 2. 3. 1.2.8.2.29. Check for damage to cover plate due to fire Check for improper expansion clearances between segments of cover plate Check the quality of the cover plate material Roller Assembly Slipping into Mill : 1. 2. 3. 1.2.8.2.30 Check for failed worm shaft bearings Check for proper matching of worm shaft and worm gear Check for damaged bearings Check for keeper plate screw failure Check for journal shaft Pin/Lock nut failure Check for improper lubrication Frequent Oil Filter choking : 1. 2. 3. Check mechanical face seal Check that proper filter is used Check the quality of the oil (mechanical impurities) 1.2.9. Burner tilting system : 1.2.9.1. Burner tilts fail to operate 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 1.2.9.2. Breaking of shear pins of one or more sections : 1. 2. 3. 4. 5. 6. 7. 8. 1.2.9.3. Check for adequate compressed air pressure and also clean air filter. Check that compressed air is free of moisture & mechanical impurities Arrest leaks in compressed air tubing and also signal air tubing Check for synchronised installation of the sections of each corner burner tilting mechanism Check for failed shear pins Check for distorted coal and air buckets (tips) in shut down Check for fouling of coal, air nozzles in shut down Check for damaged oil gun/flame scanner assemblies in shut down Check for centering and proper clearances of coal nozzles and buckets in shut down Check for damages of linkage mechanism during shut down Check for proper alignment of power cylinder with burner tilting mechanism Do not exceed design firing rate per elevation Lubricate in pins of linkages and coal/air buckets during overhaul Check the connected control system Check for jamming/distortion of linkage mechanism Check for fouling of buckets with each other and also with stationary parts. Check for fouling of coal buckets (tips) with nozzles Check for centering of coal nozzles w.r.t. coal buckets. Check for distortion/overheating of coal buckets/nozzles Check for erosion of coal nozzles/buckets Check for free movement of coal/air buckets Check for proper clearances of linkages, coal/air buckets (tips) Erosion of coal nozzles/buckets/burner panels 1. 2. 3. Check for proper velocities of coal/air mixture. Carryout clean air flow test/hot traverse Check the erosion properties of coal Carry out hard facing of coal nozzles/buckets/burner panels etc. in consultation with BHEL 1.2.10. Coal Piping : 1.2.10.1. Unequal flow through four pipes of any elevations : 1. 2. 3. 4. 5. 6. 7. 1.2.10.2. Check for full opening of mill outlet gates Check for full opening of isolating gates at burner inlet Check for coal deposits in coal pipes Ensure purging of all four pipes during every start up and shut down of mills Check for proper closing of purge air dampers (for tube mills) during mill operation Check for erosion of orifices in coal pipes. Replace them Carry out clean air flow test and ensure that variation in flow through four coal pipes is within limits Explosions in coal pipes (for tube mills) : 1. 2. 3. Ensure proper PA flow through coal pipes to avoid setting of coal dust in coal pipes Ensure purging of all four pipes with adequate PA flow during every start up and shut down of mills Maintain adequate mill outlet temperature 1.2.11. Oil Firing system : 1.2.11.1. Oil firing system : 1.2.11.1.1. LDO/HFO pump is not developing adequate pressure : 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 1.2.11.1.2. HFO circulation from FOPH to boiler and back not getting established: 1. 2. 3. 4. 5. 6. 7. 1.2.11.1.3. Check for proper line up of the system i.e. the required valves are open. Check whether strainers are clean Check for adequate level in LDO/HFO tank Check for proper setting of pumps relief valve Check for optimum opening of pressure control valve and proper functioning on auto Check for proper functioning of team tracing / electrical heat tracing for HFO system Check for adequate temperature for HFO system Check for any air pockets in the system. Vent out air from filter vents Check for DP across filter Check for water contamination in HFO system Check for mechanical impurities in HFO system Check for solidification/choking of oil in the lines Check for correct line up of the system through short/long recirculation Check for correct pump discharge pressure (refer 1.2.11.1.1.) Check for proper functioning of steam tracing/electrical heat tracing along with the lines Check for DP across all filters in the circuit. Clean filters if required Check for air locking in system. Vent out entrapped air Check for correct temperature of oil at pump suction and heaters outlet Check for any solidification in the lines (for LSHS). Oil gun not proving: 1. 2. 3. 4. 5. 6. Check for gun choking Check for HEA ignitor spark Check for correct position of HEA spark Check for healthiness of flame scanners Check for correct pressure of atomizing medium Check for correct pressure of LDO/HFO 7. 8. 9. 10. 11. 12. Check for correct temperature of HFO Check for correct secondary air flow Check Wind box pressure and furnace draft Check for proper line up for oil guns w.r.t. manual isolating valves and local gun maintenance switch Check the permissives for oil gun are available. Check for proper functioning of FSSS system 1.2.12. ROTARY AIR PREHEATERS : 1.2.12.1. Excessive Air leakage from Air side (Primary/Secondary) to Flue Gas side 1. 2. 3. 4. 1.2.12.2. Excessive Noise/Vibrations from Air Preheater 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.2.12.3. Check seal gaps which may be too less Check whether secondary/primary Air side dampers are open Check whether Air preheater is in bottled up condition Check for foreign objects over rotor Check for bad bearings Check whether there is water/Mechanical Impurities in lub oil of bearings. Check for any loosening of seals Check the main drive and the pin rack alignment. Check for low lub oil level in bearings Rotor does not turn : 1. 2. 3. 4. 5. 6. 7. 1.2.12.4. Inspect all seals (Radial/leaf/Axial/static) Adjust the seal gaps as specified Replace the damaged/distorted seals Check O2 % in Fluegas at Air preheater outlet Check the Drive unit Check the oil level in Hydraulic coupling. Also check for blown fuse of hydraulic coupling. Check for foreign objects on rotor Check for bearing damages Check whether the drive pinion fell down from its position Check Electrical system/Air motor problems Check for excessive ash accumulation over the rotor Drive Unit overheats : 1. 2. 3. 4. 5. 6. 7. Check lubrication in drive unit Check for bad seals/rubbing seals Check for drive pinion/pin rack rubbing Check for foreign objects/Ash accumulation over rotor Check the condition of bearings Check for expansion problems Check for low lub oil level in bearings 1.2.12.5. Support bearings/Guide bearing lub oil temperature too high : 1. 2. 3. 4. 5. 1.2.12.6. Lub oil Foamy : 1. 2. 1.2.12.7. 2. 3. 4. 5. 6. Excessive Ash accumulation (which is normally wet) over the heating elements. Oil/Ash deposits in heating elements, particularly cold end/middle basket. Operate the soot blower (if necessary continuously) Water wash OFF line, if soot blower is not effective If water washing is not effective, take out the heating elements and clean them Check for damaged/eroded heating elements Fluctuations in Main drive Ammeter current : 1. 2. 3. 4. 1.2.12.9. Check for Air entry into lub oil system on the suction side of the pumps Check for the quality of oil. Replace lub oil if necessary Excessive pressure drop across Air Preheater 1. 1.2.12.8. Check the quality of lub oil. Check for water/mechanical impurities in lub oil. Ensure cooling water availability to lub oil coolers Check whether lub oil pumps not operating/pumps not developing pressure leading to no lub oil circulation Check for excess hot air leakage around the bearings. Arrest the hot air leakage Check for damaged bearings Check & adjust seal gaps Replace damaged/distorted seals Check the bearings for damages Check whether there is water mechanical impurities in lub oil Abnormal increase in Air/Flue gas temperatures or in temperatures detected by Fire Sensing Scanners 1. 2. 3. Check for possibility of fires inside the air preheater In case of fire, stop the boiler and isolate the air preheater. Stop all fans. Quench the fire using large quantities of water. Do not use CO2 Foam/steam. 4. 1.2.12.10. Increase in gas outlet temperature and steady fall in Air preheater outlet temperature. 1. 2. 3. 1.2.12.11. 2. Check for lub oil level/quality of lub oil Dismantle and service the air motor Replace the damaged components Ensure the working of the lubricator/filter in the compressed air line Melting of thermal plug and draining of oil from Fluid coupling : 1. 2. 1.2.12.16. Check Air leaks/flue gas leaks over the pin rack. Arrest the leakages Replace the damaged pin rack Jamming of Air Motor : 1. 2. 3. 4. 1.2.12.15. Check for filter choking. Clean/replace the filter Check for closed valves. Line up the system properly Check for damaged lub oil pump Check for availability of lub oil in the bearing Check for quality of lub oil Erosion of PIN RACK : 1. 1.2.12.14. Check for dampers position. One or more dampers might have closed. Check for rotor rotation. Check for rotor stoppage alarms. Isolate the Air preheater in case rotation stopped Excessive pressure build up/No pressure build up of lub oil pumps: 1. 2. 3. 4. 5. 1.2.12.12. Refer `Air preheaters fires’ Section of O&M manual Check for free rotation of Main drive and the rotor. Replace the thermal plug and maintain proper oil level. Heavy ash accumulation over rotor, on flue gas side 1. 2. 3. Check for tube leakages in second pass, which leads to wetting/ accumulation of ash Check for plugging of hopper below economiser Check for fouled air preheater elements 1.2.12.17. Oil deposits in heating elements, especially in cold end baskets : 1. 2. 3. 4. 1.2.12.18. Check the combustion of oil guns Check the operation of soot blower Check the water washing system and its nozzles. Water wash the elements when flue gs temperature is below 100 Deg.C. after stopping the boiler. In case of heavy choking, take out the elements and clean Soot blower not functioning : 1. 2. 3. 4. 5. Check and trouble shoot electrical/mechanical problems Check whether swivel tube got free from the gear box Check the alignment of swivel tube Replace the damages parts Operate the soot blower atleast once in eight hours 1.2.13. FD, PA & ID Fans : 1.2.13.1. FD Fan (Axial Reaction Type with Blade Pitch Control) : 1.2.13.1.1. High Vibrations : 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 1.2.13.1.2. Unquite running : 1. 2. 3. 4. 1.2.13.1.3. Check for any deposits on impeller, rotor etc. Check bearing clearances/bearings healthiness Check for touching rotating parts with the stationary parts. Check the clearances. Check the impeller clearances w.r.t. casing and correct High bearing temperatures of bearings of Fan/Motor : 1. 2. 3. 4. 5. 1.2.13.1.4. Check the looseness of bearing pedestal bolts, impeller hub bolts, blades fixing bolts, coupling bolts etc. Check proper seating of lub on shaft flange Check whether any balance weights of the blades fell down Check whether the blades are installed serially as per the punch marks and of the same series. Check whether there are deposits over the impeller, over the blades, etc. Check the alignement with motor Check for any abnormal sound from the bearings of Fan and Motor Check for any temperature rise of the bearings. Carryout vibration analysis to pinpoint possible reason. In case it is unbalance, carry out balancing to correct the vibrations Check that lubrication is proper. Check oil level, flow, pressure etc. Check the functioning of lub oil system and cooler. Check the quality of oil and impurities in oil (Moisture/mechanical impurities) Check for bearing damages Check alingment Fan attains fall-load immediately after starting/no control on Fan output: 1. 2. Check whether impeller blades are in full open position Check whether servomotor got free from the actuator. If so, reconnect and set the operation of blades with the actuator. 3. 1.2.13.1.5. Blade pitch control inoperative : 1. 2. 3. 4. 1.2.13.1.6. Check the setting of servomotors of the fans and correct Check the control systems and ensure the blade pitch controls operation is in Unison Large pressure fluctuations in control oil pressure : 1. 2. 3. 4. 5. 1.2.13.1.9. Check the servomotor and replace the damaged seals Two Fans operating in parallel do not absorb same power : 1. 2. 1.2.13.1.8. Check the actuator and the connected control system Check whether control oil pressure is adequate Check whether servomotor is operative Check whether blades are jammed Control Oil leakage from Servomotor : 1. 1.2.13.1.7. Check the setting of servomotor w.r.t. actuator. If found disturbed, reset it. Check that the speed of the actuator is matching with that of servomotor Check the position of manual recirculation valve Check the setting of pressure relief valve Check for leakages in the servomotor and control oil system Check the N2 pressure in accumulator Frequent drop in oil level in the tank : 1. 2. 3. 4. 5. Check the leaks in lub oil system Check the leakages in control oil system Check for damaged seals of bearing housing Check the damage of seals of servomotor Check the cooler for any leakages 1.2.13.1.10. Water Contamination in lub oil : 1. Check the cooler for any lube leakages, by HT Rectify the leaking tubes 1.2.13.1.11. Drop in oil pressure : 1. 2. Check the filter elements Check for leakages in lub oil/control oil system 3. 4. 5. Check the operation/setting of recirculation valve/pressure relief valves Check the lub oil pressure control valve For further service/advice contact……… 1.2.13.2. PA Fans : 1.2.13.2.1. PA Fans (Axial Reaction Type with Blade Pitch Control) 1.2.13.2.1. High Vibrations : 1. 11. 12. 13. 14. 15. 16. 17. 18. 19. 1.2.13.2.2. Unquiet running : 1. 2. 3. 4. 5. 1.2.13.2.3. Check for any deposits on impeller, rotor etc. Check bearing clearances/bearings healthiness Check for touching rotating parts with the stationary parts. Check the clearances. Check the impeller clearances w.r.t. casing and correct High bearing temperatures of bearings of Fan/Motor : 1. 2. 3. 4. 5. 1.2.13.2.4. Check the looseness of bearing pedestal bolts, impeller hub bolts, blades fixing bolts, coupling bolts etc. Check proper seating of hub on shaft flange Check whether any balance weights of the blades fell down Check whether the blades are installed serially as per the punch marks and of the same series. Check whether there are deposits over the impeller, over the blades, etc. Check the alignement with motor Check for any abnormal sound from the bearings of Fan and Motor Check for any temperature rise of the bearings. Carryout vibration analysis to pinpoint possible reason. In case it is unbalance, carry out balancing to correct the vibrations Check that lubrication is proper. Check oil level, flow, pressure etc. Check the functioning of lub oil system and cooler. Check the quality of oil and impurities in oil (Moisture/mechanical impurities) Check for bearing damages Check alignment Fan attains fall-load immediately after starting/no control on Fan output: 1. 2. 3. 1.2.13.2.5. Blade pitch control inoperative : 1. 2. 3. 4. 1.2.13.2.6. Check the setting of servomotors of the fans and correct Check the control systems and ensure the blade pitch controls operation is in Unison Large pressure fluctuations in control oil pressure : 1. 2. 3. 4. 5. 1.2.13.2.9. Check the servomotor and replace the damaged seals Two Fans operating in parallel do not absorb same power : 1. 2. 1.2.13.2.8. Check the actuator and the connected control system Check whether control oil pressure is adequate Check whether servomotor is operative Check whether blades are jammed Control Oil leakage from Servomotor : 1. 1.2.13.2.7. Check whether impeller blades are in full open position Check whether servomotor got free from the actuator. If so, reconnect and set the operation of blades with the actuator. Check the setting of servomotor w.r.t. actuator. If found disturbed reset it. Check that the speed of the actuator is matching with that of servomotor Check the position of manual recirculation valve Check the setting of Relief valve Check for leakages in the servomotor and control oil system Check the N2 pressure in accumulator Frequent drop in oil level in the tank : 1. 2. 3. 4. 5. Check the leaks in lub oil system Check the leakages in control oil system Check for damaged seals of bearing housing Check the damage of seals of servomotor Check the cooler for any leakages 1.2.13.2.10. Water Contamination in lub oil : 1. Check the cooler for any lube leakages, by HT Rectify the leaking tubes 1.2.13.2.11. Drop in oil pressure : 1. 2. 3. 4. Check the filter elements Check for leakages in lub oil/control oil system Check the operation/setting of recirculation valve/pressure relief valves Check the lub oil pressure control valve 1.2.13.3. ID Fans : 1.2.13.3.1. High Vibrations : 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.2.13.3.2. High bearings temperatures of the bearings of Fan & Motor : 1. 2. 3. 4. 5. 6. 1.2.13.3.3. Check the leakages of the lub oil system Check the damaged seals of the bearing housing Check the cooler for any leakages For further service/advice contact……… Water Contamination in lub oil : 1. 2. 1.2.13.3.6. IGV inoperative Check inlet/outlet gate Check other gates/dampers of the gas path Frequent drop in oil level in the tank : 1. 2. 3. 4. 1.2.13.3.5. Check the correctness of lubrication. Check oil level, flow, pressure etc. Check the functioning of lub oil system and cooling water system Check the quality and impurities in oil (moisutre/mech impurities) Check for bearing damages and clearances Check alignement Check for any mechanical rubbing Fans could not be loaded : 1. 2. 3. 1.2.13.3.4. Check for any looseness of bearing pedestal bolts, impeller hub bolts, coupling bolts etc. Check for deposits over the impeller Check for uneven erosion of the impeller Check the alignment with the motor Check for the clearances between rotating and stationary parts and correct Check the bearings for any damages. Check the bearing clearances Check for any temperature rise of bearings Carry out vibration analysis to pin-point possible cause In case of unbalance, carryout balancing to correct the vibrations Check the cooler of the lub oil system for any leakages Check for water leakages in the Fan bearings, lub oil tank Drop in oil pressure : 1. 2. Check filter elements clean/replace Check the operation/setting of the recirculation valve/ pressure relief valves 1.2.14. Electrostatic Precipitator: 1.2.14.1. Field Trips on Undervoltage: 1. 2. 3. 4. 5. 6. 7. 8. 1.2.14.2. Rapping Motor Trips on Overload : 1. 2. 3. 4. 5. 6. 7. 1.2.14.3. Check for IR value and winding resistance of motor Check for functioning of Motor & Gearbox after decoupling Check for alignment of Gearbox with rapping system Check the rapping shaft alignment during shut down Check for dislocation of internals Check for over-filled hoppers Check for blown fuses, overload relay healthiness in MCC Heaters are not operating : 1. 2. 3. 4. 1.2.14.4. Check electronic controller/High voltage rectifier transformer for Rated Voltage build up on no load Check the functioning of the Ash disposal system Check the functioning of collecting & Emitting rapping mechanism Check for cracks in support, bushing insulator Check for cracked shaft insulator in shut down Check for shorting in the field like snapped loose wire in shut down Check for overfilled hoppers and distorted emitting system in shut down Check for any bent collecting electrodes in shut down Check for any blown fuse Check for terminals in MCC/Field JBS for any burnout Check for any short circuit in heating elements/cables For further service/advice contact….. Excessive sparking/flash over in fields : 1. 2. 3. 4. 5. 6. Check for S&T settings in the Electronic Controller and adjust, if needed Check for excessive current settings Check for any loose connections at transformer HT side, including disconnecting switch. Check for snapped emitting electrodes and collecting to emitting electrodes gaps in shut down Check the functioning of rapping system Check the functioning of ash disposal system and overfilled hoppers. 1.2.14.5. High Stack Emission : 1. 2. 3. 4. 5. 6. 7. 8. 9. Check for proper rapping frequency Check for proper current settings Check for high flue gas temperature Check for proper gas flow distribution in the pass during shut down Check for eroded guide vanes/splitters during shut down Check for proper fixing of defector plates of hoppers during shutdown Check for proper functioning of ash handling sysgtem Check for proper fixing of screen plates during shut down Check for proper closure of manhole doors, inspection doors etc. to prevent air ingress. 1.2.15. Water Chemistry : 1.2.15.1. Phosphate dozing is ineffective in PH control of boiler water: 1. 2. 3. 1.2.15.2. Phosphate dozing is not reaching drum water : 1. 2. 3. 4. 5. 6. 1.2.15.3. Check the healthiness of pumps Check for plugging of piping Check for proper setting of relief valves. Check for plugging of nozzles inside the drum Check for passing of NRV of standby pump. Check the quality of phosphate Scales/rust formation over water walls/superheater tubes. 1. 2. 3. 1.2.15.4. Check the Boiler pressure Check for phosphate hideout beyond boiler pressure of 180 Kg/Cm2. Resort to all volatile treatment, taking all precautions Check for improper water chemistry regime/Improper dozing over a length of time. Check the operation of DM plant and quality of DM water Contact BHEL for remedial actions like chemical cleaning etc Feed Water/Condensate PH/Conductivity could not be maintained : 1. 2. 3. Check the quality of Ammonia/Hydrazine Check for healthiness of pumps and ensure pump is developing adequate pressure Check for possibility of leakage condenser tubes. 1.3. Controls & Insatrumentation (Boiler & Aux.) 1.3.1 FSSS 1.3.1.1 COMMON SYSTEM 1.3.1.1.1 Purging not possible / gets interrupted 1. 2. 3. 4. 5. Check if any scanners are detecting or are on the verge of detecting flame. Check that all fuel valves/gates are closed and correct feedback is available at the respective panel as well as at the unit panel. If SADC was in auto earlier, it might have reverted to too low opening. Confirm its position. Adjust the air flow suitably and ensure its permissives are available steadily. Confirm that the burner tilt is normal (horizontal) 1.3.1.2. OIL FIRING 1.3.1.2.1 Trip valves not operating 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.3.1.2.2 Check that all permissives are available at the respective panel. Check the isolating valves feedback. Check for proper voltages. Check the healthiness of the coil. Confirm that no other trip commands (software as well as hardwired) are present. Check proper air supply at the field. Ensure that there are no leakages. Check the filter and air lock relays. Check the position of the speed adjusting valve. Check the solenoid valve for proper port change over. Check the valve & actuator for leaks, punctured diaphragm, mechanical obstructions etc. Oil firing not possible (not taking start). 1. 2. 3. 4. Check that all permissives are available at the respective panel. Confirm availability of all panel power supplies. In case of first guns, check interlocks like nozzle tilt, air flow etc. Check corner-wise permissives like position of the LGM switch, status of the limit switches of gun, scavenge valve, oil valve, manual valves etc. 5. 6. 7. 8. 1.3.1.2.3 Check proper air supply at the corner(s). Check for leakages, choked filters/ air lock relays, needle valve etc. Ensure that the scanner of the respective corner is not sensing flame already. Confirm at which step the sequence gets interrupted. Check the suspected valve as in 1.2.1.1 (ii) 5 to 9. Oil firing not stable. 1. 2. 3. 4. 5. 6. 7. 8. Confirm the pressure of fuel and atomizing media and the fuel temperature in case of heavy oils. Check for restricted opening of the valves. Check for possible choking of the gun. Check that scanner supply is ON and settings are in order. Check the ignitor for proper travel and spark. Visually check the nozzle and flame from opposite corrner. Maintain the windbox pressure, differential pressure and proper opening of corresponding auxiliary damper. Check the healthiness of the electronic modules and field inputs. 1.3.1.3. COAL FIRING 1.3.1.3.1 Coal firing not possible(Not taking start). 1. 2. 3. 1.3.1.3.2 Coal firing sequence gets interrupted 1. 2. 1.3.1.3.3 Confirm that the inter panel communication is healthy. Check all permissives at the corresponding panel (PA permit, ignition start permit, no protection trip, closed status of all PA dampers, brake position, luboil protection etc) Confirm that start command is issued from the panel. Confirm how far the start sequence proceeds and where it gets blocked. Check the interlocks of individual steps. Coal firing not stable / trips frequently. 1. 2. Identify the cause of trip and the individual cause as per appropriate check list. If the indicated cause appears spurious / unreasonable, check for healthiness of control panel cards , communication and data integrity. 1.3.1.3.4 Trips on ignition energy / flame failure 1. 2. 3. 4. 5. 1.3.2 Check that PA pressure is maintained. Confirm that sufficient ignition support is available. Confirm that scanners are all in service and detect a reasonable level of flame. Confirm the frequency setting of the fire ball scanners are as per recommendation. Check the SADC for proper damper position. 1.3.2. SECONDARY AIR DAMPER CONTROL (SADC) 1.3.2.1. No output from the panel. 1. 2. 3. 1.3.2.2. Output not varying. 1. 2. 3. 4. 1.3.2.4. Check the signal to the output cards separately and establish it. Check the output cards separately. Check the field cabling for earth faults, short circuits and proper polarity. Check for any overriding protective interlocks ( e.g, ID-FD fans off, MFT, furnace to WB DP high.) Damper opening not matching with the demand 1. 2. 3. 4. 5. 6. 7. 8. 9. 1.3.2.5. Check the control panel for proper functioning. Check the power supply and the healthiness of cards in the panel. Confirm data transfer between console, I/O cards and processor. Ensure correct air supply to the I/P (current to pressure ) transmitters. Check the cabling for polarity, healthiness of connections Check the current input and signal output at the I/P outlet port. Check the signal tubing for leakages. Conduct pressure decay test if doubt persists. Check the damper separately for mechanical freeness. Check the power cylinder air supply for proper quality and pressure. After ensuring proper signal and power air supplies to the actuator, check its response (output air pressure). Check the setting of the air lock relay on the actuator. Service the actuator. Failure of Auto control of Auxiliary damper 1. 2. 3. 4. 5. 6. 7. 1.3.2.6 Failure of Fuel air dampers. 1. 2. 3. 4. 1.3.2.7 Check the furnace to WB diff pressure transmitters for proper functioning. Check for high mismatch between measured values. Confirm that ALL the dampers are responding properly and the damper position in all corners of the same elevation are matching. Check the response of the DP when dampers are manually adjusted. Adjust the bias to get suitable DP demand. Check the healthiness of reference signal used to generate DP demand ( boiler load index) Check for any over riding interlocks. Check the secondary air system for proper status. Check that no override commands are present. Check that the reference input ( e.g PA flow) is OK. Check the damper operation in manual. Tune the parameters to suit the firing regime. Failure of Over fire dampers 1. 2. 3. 4. Check that no override commands are present. Check that the reference input ( boiler load) is OK. Check the damper operation in manual. Tune the parameters to suit the firing regime.
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )