Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Power System Protection for Engineers Transmission Line Distance Protection Part 2 Copyright © SEL 2004 Technical papers supporting this section: 6022.pdf, Z = V/I Does Not Make a Distance Relay by J. Roberts; A. Guzman; E.O. Schweitzer, III 6063.pdf, Innovative Solutions Improve Transmission Line Protection (WPRC '97) by Daqing Hou; Armando Guzman; Jeff Roberts 6010.pdf, Distance Relay Element Design by Jeff Roberts; Dr. Edmund O. Schweitzer III 6065.pdf, Application Guidelines for Ground Fault Protection by Joe Mooney, P.E.; Jackie Peer Transmission Line Distance Prot II_r8 1 1 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Transmission Line Distance Protection (Part 2) Objectives l Discuss the Effect of Fault Impedance on Distance Relays l Discuss the Load Encroachment Problem in Distance Relays l Describe the Effect of Magnetic Mutual Coupling on Ground Distance Relay Performance l Describe and Compare Distance Relay Polarizing Methods Transmission Line Distance Prot II_r8 2 2 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Distance Protection Problems l Infeed l Fault Resistance l Unequal Measured Impedances During Faults l Evolving Faults l Load Encroachment Transmission line protection is complex. Problems such as infeed, fault resistance, unequal measured impedances during faults, load encroachment, and mutual coupling affect the apparent impedance of distance relays. Fault resistance and mutual coupling may also affect ground directional overcurrent relays. These problems may be complicated by the evolving character of many faults. Transmission Line Distance Prot II_r8 3 3 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Distance Protection Problems l Mutual Coupling l Simultaneous Faults l Cross-Country Faults l Power Swings l Three-Terminal Lines All these problems may affect distance and directional overcurrent relays. Cross-country faults, simultaneous faults, and CT saturation may also present a problem for differential schemes. Transmission Line Distance Prot II_r8 4 4 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Distance Protection Problems l Reactor-Compensated Lines l Short Lines l CT Saturation l CCVT Transients l Series-Compensated Lines Three-terminal lines and short lines also have special protection requirements. The ringdown at subharmonic frequency resulting from compensation reactors may also create protection problems. Series-compensated lines are extremely difficult to protect. All protection principles may have problems, because of the possibility of voltage and current inversions. If the series-compensation capacitors are carefully selected, the possibility of current inversions can be eliminated. In such a case, a differential protection scheme may be the best option. In this presentation, we will examine transmission line protection problems that exclude CT saturation, CCVT transients, series-compensated lines, three-terminal lines, short lines, and reactor-compensated lines. Transmission Line Distance Prot II_r8 5 5 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Fault Resistance l l Phase Faults t Arc resistance t Other components (trees, etc.) Ground Faults t Arc resistance t Tower and tower footing t Ground return path t Other components (trees, etc.) Fault resistance affects all protection principles to some extent. For phase faults (threephase, line-line) fault resistance results largely from the resistance of the arc between the faulted conductors. If the fault is initiated by a tree or something else in the line, its resistance should also be considered. Ground fault resistance includes the resistance of the arc between the conductor and the tower, the tower and tower footing resistance, and the ground return path resistance. Ground faults may also involve other objects such as trees. Ground fault resistance values are typically much greater than phase fault resistances. For transmission line faults involving trees, for example, the fault resistance may be on the order of hundreds of ohms. In distribution lines, an important component of ground fault resistance is the contact resistance between the fallen conductor and ground. For a conductor falling on dry asphalt, for example, the fault resistance could be close to infinity. The detection of fallen conductors in overhead distribution systems is a very complex protection problem. Transmission Line Distance Prot II_r8 6 6 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Arc Resistance 440 × L R arc = W I L: Arc Length in Feet I: Arc Current in Amperes Arc resistance is quite variable. A commonly accepted value for currents between 70 A and 20,000 A is an arc voltage drop of 440 V per phase, independent of current magnitude. Transmission Line Distance Prot II_r8 7 7 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Arc Resistance 28710 × L Rarc = Ω 1.4 I L: Arc Length in Meters I: Arc Current in Amperes This is another empirical expression for arc resistance with the arc length in meters (instead of feet). Observe that there is a 1.4 exponent in the current in this expression. Transmission Line Distance Prot II_r8 8 8 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Effect of Fault Resistance l Reduces Fault Current Values l Reduces Voltage Sag in the Faulted Phase l Increases Measured Impedance Values l Limits Protection Sensitivity The general effect of fault impedance is reduction in protection sensitivity. Fault impedance reduces the fault current values and the voltage sag in the faulted phases. Fault impedance also increases the value of the impedance measured by distance relays. Fault resistance limits the sensitivity of all protective relay types. Transmission Line Distance Prot II_r8 9 9 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Fault Resistance Radial Lines V mZL R I F 21 Z = V I = mZ L + R F Fault Resistance Produces Relay Underreach The figure shows the effect of fault resistance on the impedance a distance element measures in a radial system. The distance element measures the fault loop impedance, including the fault resistance. The result is a distance estimate greater than the real distance to the fault. This inaccurate distance estimate makes the distance element underreach. Transmission Line Distance Prot II_r8 10 10 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Fault Resistance Looped Lines V mZL I RF IF 21 V = I mZL + IFRF Z = V I = mZ L + IF I RF An additional problem in looped lines is the infeed effect in the fault impedance. The relay does not measure the current contribution to the fault from the remote-end source. As a result, RF in the impedance estimate is multiplied by an infeed effect factor IF / I. The effect of this factor is twofold. The infeed effect increases the value of the apparent fault resistance (the magnitude of the factor is greater than unity). The infeed effect factor is, in general, a complex number, so the apparent fault impedance is no longer purely resistive. Transmission Line Distance Prot II_r8 11 11 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Impedance Plane Diagram X IF I RF mZL Z R In this impedance plane representation, the effect of fault resistance in looped lines can be seen. The distance element should measure an impedance mZL. However, the measured impedance is Z. Observe that the infeed effect factor, IF / I, increases the value and produces a phase shift in the fault resistance RF. Transmission Line Distance Prot II_r8 12 12 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II System Single-Line Diagram E Ðd I BUS S ZS (1-m)•ZL m•ZL RELAY E Ð0 BUS R RF ZR IF Z1S = 2 Ð 80° Z1L = 8 Ð 80° Z1R = Z1S Z0S = 3•Z1S Z0L = 3•Z1L Z0R = Z0S The power system model shown will be used to study the effect of RF and the power angle, d, on the apparent fault impedance. For simplicity, a homogeneous system (all source and line impedances have the same angle) will be considered. Transmission Line Distance Prot II_r8 13 13 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Effect of RF and δ RF (W sec.) 8 d = -60° 6 d = -30° 4 2 d = 0° X d = +30° d = +60° Z1L Reactance (W sec.) 10 Im (V/I) 0 -2 -2 0 2 4 6 8 X =0 =1 =4 =8 Re (V/I) 10 12 14 Resistance (W sec.) This figure shows the effect of RF and d on the impedance estimate. For bolted faults, the distance element measures the correct impedance value. An increase in the value of RF increases the measured impedance and produces relay underreach. In radial lines, or when d = 0, the apparent impedance is purely resistive. A reactancetype characteristic would avoid relay underreach. However, for d ¹ 0, even a reactance element may overrreach (d > 0) or underreach (d < 0). In other words, the direction of the pre-fault power flow will determine the reactance element behavior. Transmission Line Distance Prot II_r8 14 14 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Measured Impedances During Faults mZL V IF I 21 ZX C = I IF A distance protection scheme has six basic relay elements. For the phase elements, the line-line voltages and the differences of the line currents are used as input signals. Ground distance elements receive the phase voltages and the compensated line currents as input signals. The zero-sequence current is used to compensate the line current inputs of ground distance elements. These connections ensure that the fault-loop element(s) correctly measure the fault-loop impedance. For example, for an ABG fault, three distance elements correctly estimate impedance: AB, AG, and BG elements. The question is, what impedances do the other three elements measure for this fault? These elements need to measure impedances with values no lower than the fault-loop impedance. This ensures that the distance elements that measure the correct impedance value will make the tripping decision. The simple power system shown in the figure can be used for an analytical study of the impedances measured by the different distance elements during faults. The idea is to derive the expressions of the measured impedance using symmetrical component techniques. In the figure, mZL is the impedance of the protected line section. The positive-sequence value of this impedance, mZL1, is the correct value that the distance elements measure. ZX is an impedance including mZL and the source impedance behind the relay. The factor C expresses the infeed effect in the fault resistance. Transmission Line Distance Prot II_r8 15 15 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Measured Impedances Relay Element Fault Type ABC AB m Z L1 + BC m Z L1 + CA m Z L1 + BC RF C1 m Z L1 + 3 Z X 1Ð -90° + RF m Z L1 + C1 RF C1 RF C1 Ð -60° RF C1 m Z L1 + 3 Z X 1Ð90° + RF C1 Ð60° This table shows the expressions of the impedances phase distance elements measure for two types of phase faults (ABC and BC faults). For ABC faults, all three elements measure the loop impedance value, which unfortunately includes the fault impedance term. For BC faults, only the fault-loop element BC correctly measures the impedance. The other two elements (AB and CA) estimate higher impedances. This means that the BC element will make the tripping decision for zone-end faults. Transmission Line Distance Prot II_r8 16 16 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Measured Impedances Relay Element Fault Type ABC AG m Z L1 + BG m Z L1 + CG m Z L1 + BC RF ¥ C1 RF C1 RF C1 m Z L1 + Z X1 R Ð -90° + F Ð -30° 3 3C1 m Z L1 + Z X1 R Ð90° + F Ð30° 3 3C1 This table shows the expressions of the impedances measured by ground distance elements for two types of phase faults. For ABC faults, all three elements measure the fault-loop impedance. In other words, ground distance elements may respond to three-phase faults unless, for example, their operation is supervised with a zero-sequence overcurrent element. This tendency to operate is also present for other system balanced conditions such as normal load or power swings. For phase-to-phase faults, the ground distance elements measure impedance values greater than the fault-loop impedance. The effect of ground faults on ground distance elements is not presented in this analysis. The result is the same as for the phase elements. That is, the fault-loop element correctly measures the impedance, and the healthy phase elements estimate impedance values greater than the fault-loop impedance. Transmission Line Distance Prot II_r8 17 17 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Example Power System m (per-unit of ZL) ZS ZL Relay SOURCE S ZL1 = 8 Ohms ZL0 = 24 Ohms ZS1 = 1 Ohm ZS0 = 3 Ohms FAULT Digital simulation is an excellent tool for studying the impedances that distance elements measure during faults in complex power systems. The figure shows a power system model that will be used for digital simulation studies. Transmission Line Distance Prot II_r8 18 18 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Close-In Phase A-to-Ground Faults Variable RF X Line Angle Reach = 300%•Z1L Characteristics Self-Polarized Expanded 4 CG 0 0 BG 2 4 AB 0 AG 0 R CA 4 4 The figure shows the impedances all distance elements measure for a close-in A-phaseto-ground fault for different RF values (0 to 4 ohms). Two mho-element characteristics are shown, a self-polarized mho characteristic (crosses through the origin of coordinates) and a cross-polarized mho characteristic. As will be seen in a future presentation, the effect of mho element polarization is to expand the characteristic backwards in relation to the origin of coordinates for forward faults. Polarization ensures mho element directionality for close-in bolted faults. The figure indicates that only the AG distance element correctly measures the impedance for this AG fault. It is also clear from the figure that a self-polarized mho element may not see the fault. For a polarized mho element, the fault is well within the characteristic. Other distance elements such as AB, CG, and CA may operate for this fault, so distance element operation cannot be relied on to make single-pole tripping decisions. In this case, for example, a three-pole trip would be issued instead of a single-pole trip for a singleline-to-ground fault. Transmission Line Distance Prot II_r8 19 19 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Phase A-to-Ground Faults Variable RF and Fault Location X AB Line Angle Reach = 300%•Z1L 100% 100% 50% CA AG 50% CG 0 0 0 R 0 50% 50% 100% 100% BG The figure shows the effect of displacing the fault location along the protected line. The result is the appearance of fault areas in the impedance plane. The impedance each distance element measures will lie inside the corresponding fault area. The position for the measurement depends on fault location and fault resistance. The sides of the fault areas marked with dots are the locii of the measured impedances for bolted (RF = 0) faults. The straight lines parallel to those sides are the locii of the measured impedances corresponding to the maximum RF value (4 ohms.) The basic conclusion is the same as for the previous figure: there are several distance elements prone to operate for a single line-to-ground fault. For single-pole tripping, the tripping decisions of the distance elements cannot be used. A separate algorithm is needed to determine the fault type for single-pole applications. Transmission Line Distance Prot II_r8 20 20 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II BCG Fault at Remote Terminal X 15 CA 1 7 CG 7 -10 -5 NO LOAD 1 5 -15 Line Impedance 1 BC AB 7 BG 5 7 10 15 CASE 1 2 3 4 5 6 7 RF 0.00 W 0.25 W 0.50 W 1.00 W 2.00 W 5.00 W 10.00 W R This figure shows the impedances the distance elements measure for a BCG fault at the remote end of the relay reach. The dots on each fault locus represent different values of fault resistance (0 to 10 ohms). For bolted faults, three distance elements (BC, BG, and CG) see the fault exactly at the end of the reach corresponding to each element. When the fault resistance increases, the impedance the CG element measures moves away from the relay characteristic. On the other hand, the BC impedance penetrates the relay characteristic. This element overreaches, so it must be blocked from operation for this fault. For simplicity, the effect of the fault resistance on the BC element impedance is not shown. It is clear, however, that this impedance also leaves the operation characteristic. Transmission Line Distance Prot II_r8 21 21 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Measured Impedances During Faults l Distance Elements Measure Different Impedances l Ground Elements Can Overreach for Line-LineGround Faults l Phase Elements Can Operate for Close-in Line-Ground Faults In summary, distance elements measure different impedances for unbalanced faults. Phase elements can operate for close-in, line-to-ground faults, and ground elements can overreach for line-to-line-to-ground faults. A separate algorithm is needed to determine the fault type. The information on the fault type can be used to decide on single-pole tripping and to block the operation of ground distance elements for line-to-line-to-ground faults. Transmission Line Distance Prot II_r8 22 22 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Evolving Faults l Variable RF and IF l The Fault Type Changes (AG®ABG ®ABCG) l It Is Difficult to Detect Fault Inception and Fault Type Changes Evolving faults present problems for all protection principles. Many faults evolve in some way. The fault resistance RF may vary with time. As a result, the fault current is variable. Another common type of fault evolution is a change of fault type. Many faults initiate as line-to-ground faults and evolve into line-to-line-to-ground faults and/or threephase-to-ground faults. For evolving faults, it is generally difficult to detect fault inception and fault type changes. Transmission Line Distance Prot II_r8 23 23 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Measured Impedance for Load Conditions V I P, Q 21 In Per-Unit: SÐj = VIÐj = P + jQ V V2 Z = = Ðj = Ðj I S I V Both phase and ground distance elements measure impedance for normal load conditions. As can be seen in the figure, the measured impedance depends on the load flow conditions. An increase in the apparent power, S, transferred over the line reduces the magnitude of the measured impedance Transmission Line Distance Prot II_r8 24 24 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Load Impedance Regions X Maximum Load Load OUT Load IN R The impedance angle depends on the direction of P and Q. For positive values of P and Q (both P and Q flowing into the line), j is between 0° and 90° and the measured impedance lies on the first quadrant of the impedance plane. A negative Q value brings the impedance to the fourth quadrant. Accordingly, a negative P value will move the measured impedance to the other two quadrants: to the second quadrant for a positive Q value and to the third quadrant for a negative Q value. The figure shows the possible regions of the measured impedance for normal load conditions. For positive P values (Load OUT in the figure), the impedance is in the first or fourth quadrants. For negative P (Load IN), the impedance is in the second or third quadrants. Transmission Line Distance Prot II_r8 25 25 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Load Encroachment X R Checks for load encroachment problems can be performed by superimposing relay and load characteristics on the impedance plane. In the figure, it can be seen that certain load conditions result in penetration of the impedance in the relay characteristic. A traditional solution to avoiding distance element misoperation is to shape the relay characteristic to exclude the load impedance regions. A drawback of this solution is that it limits the fault resistance coverage of the distance element. A new solution is to create a relay load element having the same shape as the load impedance regions. This new element may be used to block the distance element. In this case, only a small section of the relay characteristic is lost. Transmission Line Distance Prot II_r8 26 26 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Power Swings Example Fault on Line A-B A B p L1 q The relay is supposed to be protecting line L1, and its location is at Bus P. The fault occurs on line A-B. Transmission Line Distance Prot II_r8 27 27 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Power Swings No Relay Misoperation Second Clearing t=t2 X First Clearing t=t1 t=0+ Fault q L1 p t=t3 L1 Relay at p Post-Fault Power Swing Pre-Fault t=0R The figure shows the impedance measured by a distance relay for an external fault. As expected, the apparent impedance moves to an external point. After the fault clears, the apparent impedance does not return instantaneously to the load equilibrium point, but there is a post-fault “slow” oscillation, or swing. The characteristics of the oscillation depend on many parameters of the power system. The case shown in the figure shows that the oscillation does not produce any relay misoperation. Transmission Line Distance Prot II_r8 28 28 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Power Swings Relay Could Misoperate Second Clearing t=t2 X First Clearing t=t1 t=0+ Fault q L1 p t=t3 L1 Relay at p Post-Fault Power Swing Pre-Fault t=0R The figure shows a case where the post-fault power swing enters into the relay first zone operation characteristic. This will produce an undesired operation of the relay. Transmission Line Distance Prot II_r8 29 29 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Power Swing Blocking Traditional Scheme X + B B 21 tD T LOAD tB AUXT 21 52/TC AUX R l For a Fault, tD-tB Is Almost Zero l For an Oscillation, tD-tB is Relatively Large l Time Relay “T” Is Set to Block the Tripping (21 Over 52/TC) Transmission Line Distance Prot II_r8 30 30 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Parallel Lines - Mutual Coupling Parallel lines is a very common case in transmission systems. The magnetic field produced by a faulted line influences the behavior of the voltages and currents of a neighboring line. This influence is called mutual coupling between lines. Transmission Line Distance Prot II_r8 31 31 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Zero-Sequence Mutual Coupling I0M Z0M IR, I0 Relay The figure illustrates mutual coupling. For a ground fault on one of two double-circuit lines, the zero-sequence current flowing at each line induces a voltage in the other line. This effect modifies the voltage ground distance elements measure. If the mutually coupled current flows in the same direction as the relay current, the measured voltage will increase and the distance element will tend to underreach. On the other hand, if the mutual current direction is opposite to that of the relay current, the relay element will measure a lower voltage and tend to overreach. Transmission Line Distance Prot II_r8 32 32 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Magnetic Mutual Coupling l Occurs in Double-Circuit Lines l Affects the Zero-Sequence Network l Z0M= 50–70% of Z0 l Very Low Coupling in the Positive and Negative-Sequence Networks (5–7%) Magnetic mutual coupling between multiple-circuit lines affects distance and directional ground relays. Typical values of the zero-sequence mutual coupling impedance, Z0M, are on the order of 50 percent to 70 percent of the zero-sequence impedance, Z0. Very low coupling occurs in the positive-sequence and negative-sequence networks. Transmission Line Distance Prot II_r8 33 33 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Effect on Ground Distance Relays ( ) V a = m Z1L I a + k 0 I res + m Z0 M I 0 M Z= Va I a + k 0 I res = m Z IL + m Z0 M I0 M I a + k 0 I res Relay Underreaches When I0M and I0 Flow in the Same Direction These expressions show the effect of mutual coupling on the impedance ground distance elements measure. I0M is assumed to be positive when it flows in the same direction as Ires. The result is an increase in the apparent impedance, Z, and a relay underreach. A negative value of I0M reduces the measured impedance, and the relay element overreaches. Transmission Line Distance Prot II_r8 34 34 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Parallel Lines With Mutual Coupling C D mZ (1-m)ZL L B A Z 2 ZL ZC ZL ZA ZB 0 0.2 0.4 0.6 0.8 1.0 m The figure shows the ground distance element behavior for a ground fault on a doublecircuit transmission line with both lines connected in parallel. For simplicity, it is assumed that the system is energized at one end only. In the lower figure, the impedances ground distance elements measure at locations A, B, and C are shown as a function of the distance, m, to the fault from location A. For relay elements A and C, the apparent impedances, with mutual coupling, are represented by full lines, and dotted lines are used to represent the measured impedances without mutual coupling. The latter case gives the correct impedance values and serves as a reference for analysis. For relay element B, the measured impedance plot without mutual coupling would be a straight line from ZB = ZL at m = 0, to ZB = 0 at m = 1. The effect of mutual coupling in this case is that none of the ground distance elements correctly measure the distance to the fault. For relay elements A and C, the mutually coupled current flows in the same direction as the relay current. These elements measure higher impedance values and tend to underreach. For relay element B, the mutual current flows opposite to relay current. The result is a lower apparent impedance value and a tendency for the relay element to underreach. Transmission Line Distance Prot II_r8 35 35 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Zero-Sequence Mutual Coupling Compensation ( ) Va = mZ1L Ia + k0 Ires + mZ0M I0M æ ö Z0 M ç I0 M ÷ V a = m Z1L I a + k 0 I res + ç ÷ Z1L è ø I relay = I a + k 0 I res + k 0 M I0 M k 0 M = Z0 M Z1L The mutual-coupling error may be compensated for by providing the faulted-line relay element with information on the mutually coupled current. These equations show that an additional compensation term, k0M I0M, is needed in the relay current of the ground distance element. The compensation factor, k0M, equals the ratio of the zero-sequence impedance to the positive-sequence impedance of the protected line. Several commercial distance relays have an additional current input for the mutually coupled current. Transmission Line Distance Prot II_r8 36 36 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Mutual Coupling Compensation Limitations l Provides Compensation Only to the Faulted Line Relays l I0M is not Always Available at the Relay Location A limitation of mutual coupling compensation is that it eliminates the distance measurement errors only for the faulted-line ground elements. In the parallel-line case that was presented before, compensation works for relays at locations A and B and fails for the relay at C. The problem with the relay at C is that the level of compensation needed depends on the fault location, m. Another limitation of mutual coupling compensation is that I0M is not always available at the relay location. Transmission Line Distance Prot II_r8 37 37 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Difficult System Arrangements for Zero-Sequence Compensation This figure shows cases in which the mutually-coupled current I0M is not available at the relay location. Transmission Line Distance Prot II_r8 38 38 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Case Where Compensation Fails Experience shows that the first zone setting for the relay should be reduced to avoid overreaching for severe cases of zero-sequence mutual coupling. In some cases, the first zone may need to be reduced by 60 percent. Transmission Line Distance Prot II_r8 39 39 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Introduction to Distance Relay Polarizing Transmission Line Distance Prot II_r8 40 40 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Basic Distance Element Signal V I S1 Phase Forming Signal Trip Comparison S2 Forming S1 = -V + Zr I S2 = V Operating Quantity Polarizing Quantity ( ) Operation Condition: l1 £ arg S1 S 2 £ l 2 Transmission Line Distance Prot II_r8 41 41 Power System Protection for Engineers – PROT 401 42 Section 21 - Transmission Line Distance Protection - Part II Mho Characteristic Mho Circle Threshold: ( ) arg ( Z r - Z ) Z = ± 90 X B Zr Zr-Z 90o Z A R It is convenient to use an impedance plane to represent the distance element operating characteristic. There are three traditional distance elements: impedance-type, reactance-type, and mho-type distance elements. The figure shows the operation equation and the operating characteristic of the mho distance element. The characteristic is the locus of all apparent impedance values for which the relay element is on the verge of operation. The operation zone is located inside the circle, and the restraint zone is the region outside the circle. The mho characteristic is a circle passing through the origin of the impedance plane. The mho element operates for impedances inside the circle, which is basically oriented toward the first quadrant. This is the case for forward faults. For reverse faults, the apparent impedance lies in the third quadrant of the impedance plane and represents a restraint condition. The fact that the circle passed through the origin of coordinates is an indication of the inherent directionality of the mho elements. However, close-in bolted faults produce deep voltage sags. The mho element may lose the voltage polarizing signal for close-in faults. This fact needs to be considered in selecting the appropriate mho element polarizing quantity. There are only two settings in a mho element: the characteristic diameter, ZM, and the angle of this diameter with respect to the R axis, jMT. This is equivalent to the maximum torque angle of a directional element: the mho element presents the highest reach (highest sensitivity) when the apparent impedance angle j coincides with jMT. The value jMT should be set close to the protected line impedance angle. By doing this, it ensures maximum relay sensitivity for faults and minimum relay sensitivity for load conditions, in which j < j MT. The other two conventional distance elements lack directionaly. The impedance-type characteristic is a circle whose center is at the origin of coordinates. The reactance-type characteristic is a straight line parallel to the R axis. Impedance-type elements need an additional directional element. Reactance-type elements need a directional element and a resistance element to limit the reach on both sides of the element characteristic. Transmission Line Distance Prot II_r8 42 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Concept of Polarizing Quantity X F4 S1 = - V + Z r I F3 S2 = V S1 Phase Changes S2 Phase Does Not Change F1 F2 Transmission Line Distance Prot II_r8 R 43 43 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Loss-of-Polarization for Close-In Bolted Faults X I V F2 F1 F1 21 F2 V = 0, S2 = 0 Transmission Line Distance Prot II_r8 44 R 44 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Polarization Alternatives l Self-Polarization l Dual-Polarization t Addition of healthy phase voltage l Cross-Polarization l Positive-Sequence l Memory t Transmission Line Distance Prot II_r8 Three-phase faults, voltage reversals 45 45 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Polarized Mho Relay S1 = - V + Z r I Self-Polarization: S 2 = V Dual Polarization: S 2 = V + k p V p (Healthy Phases) Cross Polarization: S 2 = k p V p (Healthy Phases) Positive-Sequence Polarization: S 2 = k p V p Transmission Line Distance Prot II_r8 46 46 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Polarized Mho Relay Characteristic S1 = - V + Z r I S2 = V + k p V p æ Z - Zr ö ÷£p 0 £ argç çZ+Z ÷ p ø è A = -Z p = - k p V p I Transmission Line Distance Prot II_r8 47 B = Zr 47 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Relay Characteristic: Forward Fault m ZL 1 F 2 3 3 X B Zr Z r 2 A' Transmission Line Distance Prot II_r8 A R 1 48 48 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Relay Characteristic: Reverse Fault m ZL 1 F 3 2 3 X B A'' Zr 2 A R 1 Transmission Line Distance Prot II_r8 49 49 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Polarization Alternatives Summary l Self-Polarization l Healthy-Phase Cross Polarization (With and Without Memory) l Positive-Sequence Polarization (With Memory) Transmission Line Distance Prot II_r8 50 50 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Phase Element Self-Polarization S1 = - V bc + Zr Ibc S 2 = V bc l No Characteristic Expansion l Unreliable for Zero-Voltage Faults l Directionally Insecure for Reverse Bus Faults During High Load. Requires Additional Directional Element Transmission Line Distance Prot II_r8 51 51 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Ground Element Self-Polarization ( S1 = - Va + Zr Ia + k 0 I0 ) S2 = Va l No Characteristic Expansion l Unreliable for Zero-Voltage Single Line-to-Ground Faults l Requires Directional Element Transmission Line Distance Prot II_r8 52 52 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Phase Element Cross Polarization S1 = - V bc + Zr Ibc S2 = - j Va l Good Expansion for Phase-to-Phase Faults l Unreliable for Zero-Voltage Three-Phase Faults l Requires Directional Element Transmission Line Distance Prot II_r8 53 53 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Ground Element Cross Polarization ( S1 = - Va + Zr I a + k 0 I 0 ) S 2 = j Vbc l Good Expansion l Reliable Operation for Zero-Voltage Single Line-Ground Faults l Requires Directional Element l Single-Pole Trip Applications Require Study for Pole-Open Security Transmission Line Distance Prot II_r8 54 54 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Phase Element Cross Polarization With Memory S1 = - Vbc + Zr Ibc S2 = -j Va,mem l l l l Transmission Line Distance Prot II_r8 Good Expansion Reliable Operation for Zero-Voltage Three-Phase Faults Requires Directional Element Single-Pole Trip Applications Require Study for Pole-Open Security 55 55 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Phase Element Positive-Sequence Polarization With Memory S1 = - Vbc + Zr Ibc S2 = -j Va1,mem l Greatest Expansion l Reliable Operation for Zero-Voltage Three-Phase Faults l Requires Directional Element l Best Single-Pole Trip Security Transmission Line Distance Prot II_r8 56 56 Power System Protection for Engineers – PROT 401 Section 21 - Transmission Line Distance Protection - Part II Ground Element Positive-Sequence Polarization With Memory ( S1 = - Va + Zr Ia + k 0 I0 ) S2 = Va1,mem l Greatest Expansion l Reliable Operation for Zero-Voltage Faults l Requires Directional Element l Best Single-Pole Trip Security Transmission Line Distance Prot II_r8 57 57
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )