Installing ProView 4.0.1 on your PC
1. Insert the ProView 4.0.1 CD-ROM into your CD-ROM Drive. The Install Shield Wizard
should run automatically. If it does not, click Start then Run. Enter D:\setup.exe in the field
that appears. (Note: Replace “D” with the letter of your CD-ROM drive if not the correct
drive identifier for your PC.)
2. Follow the on-screen prompts.
3. IMPORTANT: When prompted, accept the default Installation directory.
Using the ProView 4.0.1 Upgrade Wizard
Cooper
Ò
During the installation process several icons were created and placed onto your desktop.
Locate the icon labeled “ProView 4.0.1 F6-F6TS Upgrade Wizard”. Use your mouse to
position the cursor over the icon and double-click with the left mouse button.
NOTE: The ProView 4.0.1 Upgrade Wizard is intended for use with Standard
ProView 4.0 Form 6, Form 6 T/S, Form 6-LS and Form 6 T/S-LS control schemes. It
is NOT intended for use with any other control or relay schemes.
NOTE: The upgrade wizard converts ProView 4.0 Form 6 schemes to ProView 4.0.1.
The wizard will not convert Form 6 schemes created in earlier versions of ProView.
NOTE: Workbench modifications that include global variables in the logic may not
convert correctly. If the conversion fails, contact the Switchgear Support Group.
The Upgrade Wizard consists of three options:
1. The first option will convert a ProView 4.0 scheme file that is located in
the following directory on your personal computer (PC): C:\Program
Files\Cooper\Proview40\Form6 and then saves the converted
scheme file to C:\Program Files\Cooper\Proview401\Form6.
2. The second option upgrades the ProView 4.0 firmware on a Form 6
control to ProView 4.0.1 and then loads a ProView 4.0.1 scheme into
the Form 6 control. Note that the scheme file must be located in the
following directory on your PC:
C:\Program Files\Cooper\Proview401\Form6
3. The third option connects to the Form 6 control and extracts a ProView
4.0 scheme file. It then upgrades the firmware in the control to ProView
4.0.1, converts the uploaded scheme to ProView 4.0.1 and then
downloads the converted scheme into the Form 6 control.
IMPORTANT: Do not remove power from the Form 6 control at any time during
the Upgrade Wizard Process.
Questions?
Contact the Switchgear Support Group at (800) 497-5953
or email to SSG@cooperpower.com
B280-06022 • September 2006 • Supersedes 08/2006
1
OPTION 1
1. From the Upgrade Wizard Mode selection box, click the top button labeled, “Convert a
Form 6 V 4.0 scheme file into a Form 6 V 4.0.1 scheme file”.
9
2. When the “Select a Scheme to convert to
4.0.1” dialog is displayed, use your
mouse to select the ProView 4.0 file to be
converted. Highlight the file by clicking it
and then click the “Open” button.
3. The selected scheme is loaded into
RAM and converted into the ProView
4.0.1 format.
When the “Save As” dialog is displayed,
accept or change the File name: then
click the Save button.
The newly converted file is located in the
following directory:
C:\Program Files\Cooper\Proview401\Form6
IMPORTANT: After completing the Scheme file conversion, proceed with the
recommended Scheme Verification process at the end of this document.
B280-06022 • September 2006 • Supersedes 08/2006
2
OPTION 2
IMPORTANT: Before proceeding with Option 2, open the ProView 4.0.1 scheme file and
perform a Scheme Verification as detailed at the end of this document.
1. From the Upgrade Wizard Mode selection box, click the middle button labeled “Upgrade a
Form 6 control from ProView 4.0 to ProView 4.0.1 using a Form 6 V4.0.1 scheme file
stored on disk”
9
2. When the “Select a Form 6 Version 4.0.1
Scheme to download to the control” dialog
is displayed, highlight the ProView 4.0.1
file to be downloaded by clicking it and
then click the “Open” button.
The Upgrade Wizard will launch ProView
4.0.1 and load the selected scheme.
3. When the Select Connection dialog
opens, select the Com port used by your
PC for serial communications.
NOTE: This is typically “Com 1”.
4. ProView will prompt you for a password,
enter the device password (e.g., the default
password is “Modify”) then click the OK
button. Note that this is a case-sensitive
field.
5. Three progress-bar boxes will be displayed
in the following sequence to indicate the current state of the upgrade wizard.
•
•
•
Synchronizing with Connected Device
Downloading Firmware
Preparing Scheme for Download
IMPORTANT: The Upgrade Process is not
complete until the ProView 4.0.1 message
box is displayed.
B280-06022 • September 2006 • Supersedes 08/2006
3
OPTION 3
1. Launch ProView 4.0; connect to the Form 6 using the “Open Scheme from Device…”
option. When the Save As dialog is displayed accept or change the File name: then click
the Save button.
RECOMMENDED VERIFICATION PROCESS:
a) Perform the steps listed under Option 1 then proceed with Option 3 or perform
Option 2.
2. Launch the ProView 4.0.1 upgrade Wizard. From the Upgrade Wizard Mode selection box,
click the third button labeled “Upgrade a Form 6 control from ProView 4.0 to ProView
4.0.1 by uploading the scheme file from the device”
9
3. When the “Select a Connection…”
dialog opens, select the Com port
used by your PC for serial
communications.
NOTE: This is typically “Com 1”.
4. ProView will prompt you for a
password, enter the device password
(e.g., the default password is “Modify”)
then click the OK button. Note that this
is a case-sensitive field.
5. Three progress-bar boxes will be displayed in the following sequence to indicate the current
state of the upgrade wizard.
a) Connecting to device…
b) Reconnecting to device…
c) Synchronizing with connected device
B280-06022 • September 2006 • Supersedes 08/2006
4
6. When the Upgrade Wizard completes
uploading the scheme, a “Save As” Dialog
will be displayed. Accept or change the
File name: then click the Save button.
Note:
If the recommended verification
process was followed at the beginning of
Option 3, the file name will already be present.
You can either save the file under a new name
or replace the existing file.
7. When the Scheme Upgrade box is displayed click YES.
NOTE: Do not cancel the Scheme Upgrade
Progress of the scheme conversion and firmware download
is indicated by the “Downloading Firmware” progress bar.
NOTE: Do not cancel the Firmware Download.
IMPORTANT: The Upgrade Process is not complete
until the following message box is displayed:
B280-06022 • September 2006 • Supersedes 08/2006
5
Recommended Scheme Verification
Newly created ProView 4.0.1 schemes or schemes converted to ProView 4.0.1
using the upgrade wizard can be verified using the following procedure.
1. Launch ProView 4.0.1 and open the scheme to be verified.
2. Select Manage from the
main menu.
When the drop-down menu
appears, select
Oscillographic Events…
A progress bar is displayed
to indicate status of the
scheme preparation process.
3. The Oscillographic Event Manager dialog
will be displayed upon a successful scheme
preparation. The scheme verification
process is complete, click the Exit button.
4. If the scheme preparation was unsuccessful, ProView displays an error message similar to
the one shown in the following example. Clicking the OK button will take you to the
Workbench where the error occurred.
Questions?
Contact the Switchgear Support Group at (800) 497-5953
or email to SSG@cooperpower.com
©2006 Cooper Power Systems, Inc., or its affiliates.