ACI 318-19 Code Cases A CI has received written requests for clarification of the intent or application of the provisions for special structural walls as stated in ACI CODE-318-19: Building Code Requirements for Structural Concrete and Commentary. Requests were submitted by the Structural Engineers Association of Washington (SEAW), Structural Engineers Association of Northern California (SEAONC), and Los Angeles Tall Buildings Structural Design Council (LATBSDC). In response, ACI Committee 318, Structural Concrete Building Code, has developed, balloted, and approved three code cases to clarify the relevant Code sections. The code cases are listed in the following text by organizational submittal: Code Case 318-19 Submitted by SEAW Subject: Strength reduction factor, ϕ, for use with Eq. (18.10.3.1) Background: ACI 318-19, Section 21.2.4.1, notes that for any member designed to resist earthquake-induced forces E, ϕ for shear shall be 0.6 if the nominal shear strength of the member is less than the shear corresponding to the development of the nominal moment strength of the member. Otherwise, ϕ for shear shall be 0.75 per Table 21.2.1 item (b). Section 18.10.3.1 requires that the design shear force Ve for shear walls shall be computed as the shear demand Vu, amplified by the overstrength factor Ωv, as computed per Table 18.10.3.1.2. Per this table, for walls with aspect ratios greater than 1.5, Ωv is taken as the larger of either 1.5 or the ratio of the probable moment strength to the moment demand. This calculation effectively results in the wall being designed such that the nominal shear strength of the member exceeds the shear corresponding to the development of the nominal moment strength of the member, satisfying the requirement of Section 21.2.4.1. Section 18.10.3.1 also provides an upper limit for the amplification factor on Vu as 3.0 per Eq. (18.10.3.1). Questions: 1. This code case requests clarification that whenever a value of Ωv is computed exceeding 1.0, including when this upper limit of 3.0 is used, that ϕ for shear may be taken as 0.75 as the intent of shear amplification per Section 21.2.4.1 has been satisfied. 2. Similarly, Section 18.10.8.1(a) requires that qualifying wall piers shall have their design shear force amplified, but this value need not exceed Ω0, which is the ASCE 7-161 overstrength factor and different from Ωv from Section 18.10.3.1. The intent of the amplification factor is the same, namely that the walls can remain elastic in shear. This code case also requests clarification that ϕ for shear may be taken as 0.75 for wall piers when the shear demands have been amplified by Ω0, and that both Ω0 and Ωv do not need to be applied to Ve at the same time. Interpretations: 1. The intent of Section 21.2.4.1 is that, if Ωv ≥ 1.5, f for shear shall be permitted to be taken equal to 0.75 at the critical section and at all sections. 2. According to Section 18.10.8.1, wall piers are required to be designed either for the shear corresponding to the development of Mpr, at the top and bottom of the wall pier (capacity design approach), accounting for the axial force in the pier, or for the shear from structural analysis amplified by W0. For either case, f = 0.75 is intended, and Ωv need not be applied in addition to Ω0. Subject: Clarification about calculation methods for Mpr and Mu Background: For walls with a height-to-length ratio greater than 1.5, the overstrength factor Ωv is calculated as the greater of Mpr /Mu or 1.5, where Mpr is the probable flexural strength of the member and Mu is the factored moment at the section. Because the calculation of the axial-flexural strength for a wall section can be complicated, additional clarification about these parameters would be helpful. Questions: 1. For ductile coupled walls, or special structural walls otherwise separated into separate design segments by coupling beams, clarify if Mpr and Mu are intended to reference the individual design segments of the wall, or the overall wall as a whole. Note that for an overall wall as a whole, separated by coupling beams, the strain in the concrete and nonprestressed reinforcement is not proportional to the distance from the neutral axis as required by ACI 318-19, Section 22.2.1.2. 2. Please clarify the load combinations and loading conditions intended to be used for the calculation of Mpr and Mu. Due to the large number of load combinations, many values of Mpr and Mu are considered during the design of a special structural wall, and a typical design would have calculated ratios that don’t control the design of the section that exceed 3 or more. As a suggestion, should it be clarified that Mu be calculated using the load combination of ACI 318-19, Eq. (5.3.1e) for the load combination with the maximum seismic moment? 3. Is the calculation of Mpr using the critical capacity method acceptable? The critical capacity method minimizes the www.concreteinternational.com | Ci | JUNE 2023 55 where the seismic flexural demand is largely an axial behavior. Interpretations: 1. The intent of Section 18.10.3.1.2 is to treat structural walls in coupled wall systems as individual walls when determining Mpr and Mu at critical sections for shear amplification requirements. 2. The intent of Table 18.10.3.1.2 footnote [1] is to only use load combinations that include earthquake effect E. 3. ACI 318-19, Section 18.10.3.1.2, does not specify which method shall be used; the licensed design professional may exercise judgment in using any reasonable approach. Fig. 1: Edited schematic figure of critical capacity method taken from spColumn v7.00 manual distance between the ultimate load point and the point on the capacity curve (Fig. 1). Use of this method would more accurately represent the available overstrength in coupled walls where axial forces increase together with seismic moments, or Subject: Use of the redundancy factor when calculating amplified forces Background: ASCE 7-16 requires the use of load combinations, including an earthquake force multiplied by an overstrength factor Ω0 to approximate the maximum seismic load for the design of critical elements. ASCE 7-16, Section 12.3.4.1, states that the redundancy factor ρ is intended to be 1.0 for load combinations that include this overstrength factor. The last sentence of Commentary Section R18.10.3.1 states, “The application of Ωv to Vu does not preclude the application of a redundancy factor if required by the general building code.” Anyone. Anytime. Anywhere. Instantly Verify an individual’s ACI Certification. Download the ACI Certification Verify App now! To learn more or download the Verify App, visit concrete.org/verify. 56 JUNE 2023 | Ci | www.concreteinternational.com Question: 1. Please clarify this commentary sentence. Is the intent of this commentary that the redundancy factor ρ per ASCE 7-16 is allowed to be 1.0 when using Eq. (18.10.3.1), similar to the design of critical elements in other structural systems? Interpretation: 1. The intent of Section 18.10.3.1 is that, where a redundancy factor of 1.3 is applied according to ASCE 7-16, Section 12.3.4, Ve, due to lateral forces, need not exceed three times the factored shear obtained from elastic analysis of the structure under code-prescribed seismic forces with a redundancy factor of 1.0. Code Case 318-19 Submitted by SEAONC Subject: Use of mechanical splices for Grade 80 in structural walls Background: Per Section 18.2.7.2 (Fig. 2), Type 2 mechanical splices for Grade 80 are not permitted within 2D from a critical section of the wall, because it is expected that reinforcement will yield in this region. This provision is in contradiction with Section 18.10.2.3(c), which, for lap splices, states that yielding of the reinforcement is expected in height equal to hsx above and ℓd below the critical section (Fig. 3). The second paragraph of the commentary provides exception if testing data show that coupler successfully meets performance requirements. This process will require using alternative means and methods, and hence can complicate the design, and will be subjective to authority having jurisdiction (AHJ) on how the commentary is interpreted and what tests, how many specimens, and what the required performance is. This part should be codified so that when test data is presented, it shall be accepted. Questions: ACI 318-19 extends the use of high-strength reinforcement in seismic regions. It is expected that engineers will use Grade 80 more often to avoid congestion problems in the wall boundary elements. ACI 318-19 further introduces significant restrictions on lap and mechanical splices. Section 18.2.7.2 on mechanical splices appears to be written primarily for moment frame elements and then was extended to structural walls. As such, it is inconsistent with definition of yielding region in Section 18.10. 1. We seek confirmation that the mechanical splices should be only restricted from the same zones as lap splices. 2. We also ask to include into the Code part minimum performance requirements on mechanical splices for Grade 80, so they can be used in locations of expected yielding, and what type of testing and how many successful tests are required. Interpretations: 1. ACI 318-19 specifies different heights over which restrictions apply to lap splices and mechanical splices of longitudinal reinforcement, as follows: (a) According to Section 18.10.2.3 (refer to Fig. R18.10.2.3), lap-splices of longitudinal reinforcement are not permitted above (by one story height) and below (by ℓd) a wall critical section. (b) According to Sections 18.2.7.2 and 18.2.8.1, respectively, mechanical couplers of longitudinal reinforcement (except for Type 2 on Grade 60 reinforcement) and welded splices of CODE COMMENTARY Fig. 2: Excerpt of ACI 318-19, Section 18.2.7.2 www.concreteinternational.com | Ci | JUNE 2023 57 Fig. 3: Clarification of “No splice region” for lap splices (ACI 318-19, Fig. R18.10.2.3) longitudinal reinforcement, are not permitted within a distance equal to twice the member depth of a critical section, where yielding of the reinforcement is likely to occur. Commentary Sections R18.2.7 and R18.10.2.3 both refer to these (different) lengths in (a) and (b) as potential yielding regions. The Committee will consider clarifying this issue as new business. 2. ACI Committee 318 has not evaluated test data that would enable developing minimum performance requirements for mechanical splices for Grade 80 reinforcement. The Committee will consider this as new business. Subject: Shear wall web ties Background: ACI 318-19, Section 18.10.6.4(i), requires 135-135 degree web ties or hoops (Fig. 4). The vertical extent of the web ties is the same as the extent of the special boundary element (SBE) per Section 18.10.6.2. However, Section 18.10.6.4 applies to walls with the SBE determined by either of Sections 18.10.6.2 or 18.10.6.3. However, Section 18.10.6.2 is intended only for higher-aspect-ratio walls. The 58 JUNE 2023 | Ci | www.concreteinternational.com Fig. 4: Excerpt from ACI 318-19, Section 18.10.6.4(i) code language is not clear on whether the web ties are required only for walls with the SBE required by Section 18.10.6.2. (Additional note: Section 18.10.6.2(b)(i) should reference Section 18.10.6.4(j) for limits of extent of the SBE). Question: 1. ACI 318-19 introduces web ties to prevent the loss of axial load-carrying capacity. The tests used as reference in commentary focused mostly on high-aspect-ratio walls where (a) (b) Fig. 5: Excerpts from ACI 318-19, Section 18.10.3: (a) Table 18.10.3.1.2; and (b) Section 18.10.3.1 the compressive stresses at the inside face of the SBE can be quite high. On the other hand, the stress trigger in Section 18.10.6.3 for requirement of the SBE is relatively low, and hence the web crossties may not be justified. We seek confirmation that web ties are only required for walls with the SBE per Section 18.10.6.2. If that is not the case, we seek confirmation that the vertical extent of web ties need not exceed the height of the SBE. We suggest reevaluation of the requirements on vertical and horizontal extent of the web ties for the walls. Interpretation: 1. ACI 318-19, Section 18.10.6.1, indicates that, if SBEs are required by either Section 18.10.6.2 or 18.10.6.3, the requirements of Section 18.10.6.4 apply. As indicated by Section 18.10.6.4, all subsections ((a) through (k)) must be satisfied. Therefore, all subsections of Section 18.10.6.4 apply to walls designed according to either Section 18.10.6.2 or 18.10.6.3, if the SBE is required. For walls designed according to Section 18.10.6.2, the height of the SBE is specified in Section 18.10.6.2(b)(i), whereas for walls designed according to Section 18.10.6.3, the SBE may be discontinued when the stress trigger drops below 0.15 fc′. The requirements of Section 18.10.6.4 apply only over the height of the SBE; therefore, the web crossties need not be used above the height of the SBE. Note that Section 18.10.6.2(b)(i) referencing Section 18.10.6.4(i) is an erratum that has been identified and corrected (to Section 18.10.6.4(j)). Subject: Wall shear amplification Background: ACI 318, Section 18.10.3, introduces shear amplification on shear walls. The shear amplification consists of two parts: flexural overstrength and dynamic amplification. We found points herein that are open to interpretation and should be clarified. 1. The flexural overstrength is based on horizontal critical section (Fig. 5(a)). However, the Code specifies that design shear force Ve is calculated as amplified shear (Fig 5(b)). While unlikely, this can be interpreted as not only horizontal shear forces but also vertical design forces on coupling beams. 2. The load case for calculating flexural amplification is not clear. Current language in footnote [1] of Table 18.10.3.1.2 requires load combination that produces maximum value of Mpr/Mu. This can imply calculating this ratio at nonseismic load combination that would produce very large overstrength because the Mu value is low. Questions: We seek confirmation: 1. That amplification of shear is only required for horizontal shear; and 2. On the load case that is to be used for calculation of flexural overstrength. Interpretations: 1. The shear amplification of Section 18.10.3.1 is not required for design of coupling beams. 2. Footnote [1] in Table 18.10.3.1.2 indicates that the overstrength factor Ωv is calculated for the load combination producing the highest value of Ωv. Load combinations are specified in ACI 318-19, Section 5.3. The intent is that the overstrength factor Ωv is calculated only for the load combinations that include load effect E—that is, Table 5.3.1 load combinations (5.3.1e) and (5.3.1g). Subject: Transverse reinforcement configurations Background: A large part of Section 18.10.6.4 was revised for ACI 318-19. The revisions include enhanced detailing based on tests of flexural (large aspect ratio) walls. We found that some of the requirements are unclear (1) on whether 135-135 are always required. While the code language seems to allow it (see our interpretation in Fig. 6), the commentary and example figure in commentary contradict it. Given that the special moment frame (SMF) columns can use 135-90 degree crossties, we seek confirmation that the 135-90 degree crossties can also be used in SBE as long as the spacing of vertical bars supported by a seismic hook meets the code requirement. We seek confirmation that alternative transverse reinforcement configurations, such as “uni-ties,” that are in general agreement with the Code can be used instead of overlapping hoops and crossties (2) or headed bars instead of crossties (3). In addition, we suggest re-evaluation of the requirements on enhanced detailing (enhanced from ACI www.concreteinternational.com | Ci | JUNE 2023 59 (a) (b) Fig. 6: Per our interpretation of Section 18.10.6.4(f), both of the following are acceptable: (a) SBE transverse reinforcement of two cross sections above each other using 135-90 degree crossties having vertical bars laterally supported by a seismic hook or bend of a hoop at 14 in. on-center; and (b) SBE transverse reinforcement with 135-135 degree crossties having vertical bars laterally supported by a seismic hook or bend of a hoop at 14 in. on-center (a) (b) Fig. 7: Excerpts from ACI 318-19: (a) Section 18.10.6.4(e) and (f); and (b) Fig. R18.10.6.4 318-14 requirements) for walls with SBE that are expected to experience low stress and strain levels (4). Questions: 1. ACI 318-19 Commentary Fig. R18.10.6.4 and Commentary Section 18.10.6.4 suggest that all crossties in SBE should have 135-135 degree hooks (Fig. 7). However, Section 18.10.6.4(e) references SMF column sections that do not require that and Section 18.10.6.4(f) requires that vertical bars spaced lesser than 14 in. and 2/3 of SBE width are supported by a seismic hook. It seems that if the bars are 60 JUNE 2023 | Ci | www.concreteinternational.com spaced at 7 in., only every other bar would require a seismic hook. The Code should explicitly clarify whether each crosstie needs to be 135-135 degrees or under which circumstances that would be the case. 2. ACI 318-19, Section 18.10.6.4(e) and (f), requires an exterior hoop or overlapping hoops depending on SBE lengthto-width ratio with additional crossties. These requirements provide appropriate restraint for vertical bars and confinement. Similar confinement and restraint can also be achieved by using continuous wound ties (“serpentine ties” or “uni-ties”). However, it is unclear whether uni-ties meet the exterior hoop requirement. Similarly, this applies to Section 18.7.5.2 for moment frame columns and Section 18.10.6.4(i) for web crossties. 3. Headed bars appear to be a viable alternative to crossties with seismic hooks in providing required confinement. Is the head of the headed bar conforming to ACI 318-19, Section 20.2.1.6, equivalent to a seismic hook? 4. ACI 318-19, Section 18.10.6.4(e) and (f), requires exterior hoop or overlapping hoops depending on SBE length-to-width ratio with additional crossties. The overlapping hoops are required to improve the confinement and are based on tests for high-aspect-ratios walls undergoing large inelastic strains in SBEs. Given the low stress limit requirement on SBE in Section 18.10.6.3, it is not expected that all walls would undergo high compressive strains. As such, ACI should clarify whether the overlapping hoops are required for all walls with SBE or only for walls with high rotational or stress demands. Interpretations: 1. The intent of Section 18.10.6.4(f) is that all crossties within the SBE shall have a seismic hook at both ends, regardless of the horizontal spacing between supported longitudinal bars. 2. According to ACI 318-19, Section 25.7.4, continuously wound bars or wires can be considered as ties; therefore, provided that the aspect ratios of the hoops created by the continuously wound tie do not exceed 2.0, and overlap as required, they satisfy the intent of Section 18.10.6.4(f). Similarly, continuously wound ties can meet the intent of Section 18.7.5.2 for confining reinforcement in columns of SMFs and Section 18.10.6.4(i) for confining reinforcement in webs (regions between SBEs) of special structural walls. 3. ACI 318 only defines the use of crossties with seismic hooks at one end and a bend at least 90 degrees on the other end, or in the situation identified in Section 18.10.6.4(f), seismic hooks at both ends. ACI Committee 318 has not adopted the use of headed reinforcement for crossties because of concerns about whether the heads can be effectively interlocked with adjacent reinforcement and whether that interlocking can be maintained during concrete placement. Because of these concerns, Section 25.7.4 explicitly prohibits the use of interlocking headed bars to make up hoops. 4. ACI 318-19, Section 18.10.6.4, requires the same detailing provisions for walls designed using either Section 18.10.6.2 or 18.10.6.3; therefore, overlapping hoops are required for SBEs of walls designed using either Section 18.10.6.2 or 18.10.6.3 if the hoop aspect ratio exceeds 2, as required by Section 18.10.6.4(f). Code Case 318-19 Submitted by LATBSDC Questions: 1. The amplification factors Wv and wv amplify the entire demand Vu determined from ASCE 7-16. Is it the intent that Vu should be separated into portions due to nonseismic (if appropriate) and lateral seismic, and only the portion of shear demand associated with horizontal earthquake loading Eh be amplified? 2. Is it the intent that Vu not be amplified in Section 18.10.3.1 for horizontal wall segments (including coupling beams) and wall piers because other Provisions 21.2.4.1 (18.10.7) and 18.10.8 address these cases? 3. The maximum amplification factor Wvwv is 3.0. It is unclear why this is not limited to W0 in ASCE 7-16 and how the redundancy factor r should be treated. Would the intent of Section 18.10.3.1 be satisfied if Ve is taken equal to WvVu with redundancy factor taken as 1.0, as is allowed in overstrength load combinations of ASCE 7, Section 12.4.3? 4. Is it the intent that only load combinations with E be considered to determine the ratio of Mpr/Mu according to footnote [1] in Table 18.10.3.1.2? 5. If only load combinations with E are considered in the calculation of Mpr/Mu, is it the intent that Mpr can be determined for the expected axial load, for example, 1.0D + 0.25Lu or as specified in ASCE 7-16? 6. For coupled walls and particularly for core walls subjected to biaxial demands, the calculation of Mpr/Mu is overly complicated and uncertain. We ask for clarification on how this should be accomplished. If using an expected axial load is acceptable (Q5), and given the complication and uncertainty, is use of Mpr/Mu = 1.5 sufficient? We ask because it appears that a lot of effort is required to determine a Mpr/Mu that is likely to be between about 1.25 and 1.75. Also, for a value of wv = 1.5, the value of Mpr/Mu is not required to be taken greater than 2.0 (to reach Wvwv = 3.0). If the upper limit is set as Wvwv = W0 in ASCE 7-16 (Q2), then, for wv = 1.5, the value of Mpr/Mu is not required to be taken greater than 1.67 (to reach Wvwv = W0 = 2.5). 7. For coupled walls, is it the intent that the amplified shear can be based on the average (or gravity) axial load for the coupled walls because amplifying shear for each pier (tension, compression; compression, tension) including the worst-case axial load due to overturning for both ±Eh would produce an unreasonably high shear demand for each pier? Or, can an average value be used for each direction of loading (which would be similar to using gravity load)? Again, setting Mpr/Mu = 1.5 (or some value) would eliminate this complication. 8. The dynamic amplification factor wv in Eq. (18.10.3.1.3) appears to be based on using the equivalent lateral force (ELF) procedure of ASCE 7-16, Section 12.8, based on a review of the original paper and NZS 3101.2 Where a modal response spectrum procedure is used, is it the intent that the use of an alternative equation is appropriate (as noted in the SEAOC Blue Book3), because use of modal analysis includes at least some portion of the dynamic amplification factor? 9. If Wv is taken greater or equal to 1.5, is it the intent that the f-factor for shear be taken as 0.75? 10. The requirement for overlapping hoops at wall boundaries in Section 18.10.6.4(f) is based on the studies by www.concreteinternational.com | Ci | JUNE 2023 61 Segura and Wallace4 and Abdullah and Wallace.5 These studies indicate that overlapping hoops are required to improve the deformation capacity (lateral instability of the compression zone) of relatively thin wall boundaries subjected to significant compression (and shear) demands. Section 18.10.6.4(f) could be interpreted to require overlapping hoops for cases where the SBE is required within a wall flange or around the perimeter of a core wall. Is it the intent that overlapping hoops need not be provided for walls with flanges that provide lateral support to the compression zone? Interpretations: 1. The intent of Section 18.10.3.1 is that only the factored shear force from load combinations (5.3.1e) and (5.3.1g) in Table 5.3.1 associated with horizontal seismic load effect Eh need be amplified. 2. The intent of Section 18.10.3.1 is that Vu is not amplified for horizontal wall segments (including coupling beams) and wall piers because other Provisions 21.2.4.1 (18.10.7) and 18.10.8 address these cases. 3. The intent of Section 18.10.3.1 is that, where a redundancy factor of 1.3 is applied according to ASCE 7-16, Section 12.3.4, Ve due to lateral forces need not exceed three times the factored shear obtained from elastic analysis of the structure under code-prescribed seismic forces with a redundancy factor of 1.0. Therefore, the intent of Section 18.10.3.1 is not satisfied if Ve is taken equal to W0Vu with redundancy factor taken as 1.0. The Committee will consider this possibility as new business. 4. Footnote [1] in Table 18.10.3.1.2 indicates that the overstrength factor Ωv is calculated for the load combination producing the highest value of Ωv. Load combinations are specified in ACI 318-19, Section 5.3 (Table 5.3.1). The intent is that the overstrength factor Ωv is calculated only for the load combinations that include load effect E—that is, Table 5.3.1 load combinations (5.3.1e) and (5.3.1g). 5. See response to Item 4. The intent of the footnote [1] in Table 18.10.3.1.2 would not be satisfied using expected axial load. The Committee will consider this as new business. Career Center Advance Your Career The ACI Career Center, specifically targeted to the concrete industry, brings together great job opportunties and great candidates. Featuring hundreds of job postings across the country and around the world, ACI’s Career Center is the right solution for your job search needs. www.concrete.org/careercenter 62 JUNE 2023 | Ci | www.concreteinternational.com 6. The intent of Section 18.10.3.1 (Table 18.10.3.1.2) is that Wv be taken as the greater of Mpr/Mu and 1.5, unless a more detailed analysis demonstrates a smaller value; however, Ωv shall not be taken less than 1.0 (refer to Table 18.10.3.1.2, footnote [2]). Therefore, the intent of Section 18.10.3.1 is not satisfied if Mpr/Mu equal to 1.5 is used as an upper bound. The Committee will consider simplifying this requirement as new business. 7. The intent of Section 18.10.3.1.2 is to treat structural walls in coupled wall systems as individual walls when determining Mpr and Mu at critical sections for shear amplification requirements. However, ACI 318-19, Section 18.10.3.1.2, does not specify how to calculate Mpr/Mu for coupled walls; therefore, the licensed design professional may exercise judgment in using any reasonable approach. 8. If a dynamic analysis procedure (for example, response spectrum analysis) is used to compute Vu, the intent of Section 18.10.3.1.3 is satisfied using the following expression for dynamic amplification in the SEAOC Blue Book3 ꞷv = 1.2 + ns / 50 The Committee suggests an alternative, simplified expression that also considers differences in story heights between those used in the original study for buildings in New Zealand and for buildings more typical of the U.S. practice ꞷv = 1.0 + 0.09hn1/3 where hn is the structural height from the base to the highest level of the seismic force-resisting system of the structure, in feet, where the base is the level at which the horizontal seismic ground motions are considered to be imparted to the structure. 9. The intent of Section 21.2.4.1 is that, if Ωv ≥ 1.5, f for shear shall be permitted to be taken equal to 0.75 at the critical section and at all sections. 10. The intent of Section 18.10.6.4(f) is that overlapping hoops are not required for the SBE located where a wall web and flange intersect. References 1. ASCE 7-16, “Minimum Design Loads for Buildings and Other Structures,” American Society of Civil Engineers, Reston, VA, 2017, 800 pp. 2. NZS 3101-2006—Concrete Structure Standard, Part 1: The Design of Concrete Structures: Part 2: Commentary on the Design of Concrete Structures, Standards New Zealand, 2006, 754 pp 3. SEAOC Seismology Committee, “SEAOC Blue Book: Seismic Design Recommendations,” Structural Engineers Association of California (SEAOC), Sacramento, CA, 2009, 296 pp. 4. Segura, C.L. Jr., and Wallace, J.W., “Impact of Geometry and Detailing on Drift Capacity of Slender RC Walls,” ACI Structural Journal, V. 115, No. 3, May 2018, pp 885-895. 5. Abdullah, S.A., and Wallace, J.W., “Drift Capacity of Reinforced Concrete Structural Walls with Special Boundary Elements,” ACI Structural Journal, V. 116, No. 1, Jan. 2019, pp 183-194. Selected for reader interest by the editors.
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )