A of-electrical installation design B -- General General rules design Regulations Installed power 4 Power loading of an installation B15 B - General design - Regulations Installed power 4 Power loading of an installation A17 B15 In In order order to to design design an an installation, installation, the the actual actual maximum maximum load load demand demand likely likely to be to be imposed the power-supply system be assessed. imposed on theonpower-supply system must must be assessed. To To base base the the design design simply simply on on the the arithmetic arithmetic sum sum of of all all the the loads loads existing existing in in the the installation installation would would be be extravagantly extravagantly uneconomical, uneconomical, and and bad bad engineering engineering practice. practice. In order to design an installation, the actual maximumtaking load demand likely to diversity be The The aim aim of of this this chapter chapter is is to to show show how how some some factors factors taking into into account account the the diversity imposed on the power-supply must beofassessed. (non simultaneous operation of ofsystem all appliances appliances given group) group) and and utilization utilization (e.g. (e.g. (nonsimultaneous operation all of aa given an motor is generally its capability, etc.) To base the design simply on theoperated arithmeticat of all the loads existing in all the an electric electric motor is not not generally operated atsum its full-load full-load capability, etc.) of of all existing and be projected can be assessed. The values given are based installation extravagantly uneconomical, bad engineering practice. existing andwould projected loadsloads can be assessed. Theand values given are based on on experience records taken from actual installations. In account addition to providing experience andand on on records from actual installations. addition to providing The aim of this chapter is totaken show how some factors takingIninto the diversity basic data circuits, the basic installation-design installation-design dataofon on individual circuits, the results results will provide a global (nonsimultaneous operation allindividual appliances of a given group)will andprovide utilization (e.g. avalue for is the installation, from which requirements of asystem supply forvalue the installation, from which the requirements of a supply anglobal electric motor not generally operated at the its full-load capability, etc.) ofsystem all (distribution or set) can (distribution network, HV/LV transformer, or generating generating set)given can be be specified. existing and network, projectedMV/LV loads transformer, can be assessed. The values arespecified. based on experience and on records taken from actual installations. In addition to providing basic installation-design data on individual circuits, the results will provide a global value for the installation, from which the requirements of a supply system 4.1 Installed (kW) or generating set) can be specified. (distribution network, power HV/LV transformer, The installed power is the sum of the nominal powers of all power consuming devices devices in the powerconsuming in the installation. installation. This is not the power to be actually supplied in The installed power is the sum of the nominal in practice. practice. powers of all powerconsuming devices in the installation. This is not the power to be actually supplied in practice. Most Most electrical electrical appliances appliances and and equipments equipments are are marked marked to to indicate indicate their their nominal nominal power power rating rating (Pn). (Pn). 4.1 Installed The power the the The installed installed power is ispower the sum sum of of(kW) the nominal nominal powers powers of of all all power-consuming power-consuming devices devices in in the the installation. installation. This This is is not not the the power power to to be be actually actually supplied supplied in in practice. practice. This the for motors, where rating refers the output This is iselectrical the case caseappliances for electric electricand motors, where the the power rating refers to to thenominal output power Most equipments arepower marked to indicate their at its driving shaft. input will evidently be greater. power at its driving shaft. Thepower input consumption power consumption will evidently be greater rating (Pn). The The installed power is the sum of the nominal powers of all power-consuming Fluorescent and discharge lamps associated with stabilizing ballasts, Fluorescent and discharge lamps associated with stabilizing ballasts, are are other other devices the installation. is not the power to be actually practice. cases which the power indicated on lamp is than cases in inin which the nominal nominalThis power indicated on the the lamp is less lesssupplied than the theinpower power This is the by case electric where the power rating refers to the output consumed lamp and its consumed by the thefor lamp and motors, its ballast. ballast. power at of its assessing driving shaft. The input power consumption will evidently be greater Methods the actual power Methods of assessing the actual power consumption consumption of of motors motors and and lighting lighting Fluorescent and discharge lamps associated with stabilizing ballasts, are other appliances are given in Section 3 of this Chapter. appliances are given in Section 3 of this Chapter. cases in which the nominal power indicated on the lamp is less than the power The The power power demand demand (kW) (kW) is is necessary necessary to to choose choose the the rated rated power power of of aa generating generating set set consumed by the lampthe and its ballast. of a prime mover have to be considered. or or battery, battery, and and where where the requirements requirements of a prime mover have to be considered. Methods of assessing the actual power consumptionor of motors and lighting For For aa power power supply supply from from a a LV LV public-supply public-supply network, network, or through through aa MV/LV HV/LV transformer, transformer, appliances are given in Section 3 of this Chapter. the the significant significant quantity quantity is is the the apparent apparent power power in in kVA. kVA. The power demand (kW) is necessary to choose the rated power of a generating set or battery, and where the requirements of a prime mover have to be considered. For a power supply from a LV public-supply network, or through a HV/LV transformer, (kVA) 4.2 Installed apparent power the significant quantity is the apparent power in (kVA) kVA. The The installed installed apparent apparent power power is is commonly commonly assumed assumed to to be be the the arithmetical arithmetical sum sum of of kVA individual loads. The maximum estimated kVA suppliedhowever howeveris thethe kVA of of individual loads. The maximum estimated kVA totobebesupplied 4.2 Installed apparent is equal total installed kVA.power (kVA) notnot equal to to thethe total installed kVA. The The apparent-power apparent-power demand demand of of aa load load (which (which might might be be aa single single appliance) appliance) is is The installed power is commonly assumed to be the arithmetical sum for of obtained from its power rating ifif necessary, as obtained fromapparent its nominal nominal power rating (corrected (corrected necessary, as noted noted above above the kVA etc.) of individual loads. The maximum estimated kVA to be supplied however is for motors, etc.) application of the following coefficients: motors, andand thethe application of the following coefficients: not equal to the total installed kVA. η η == the the per-unit per-unit efficiency efficiency = = output output kW kW // input input kW kW The apparent-power demand of a load (which might be a single appliance) is cos cos ϕ ϕ == the the power power factor factor = = kW kW // kVA kVA obtained from its nominal power rating (corrected if necessary, as noted above for The apparent-power demand the load The apparent-power kVA demandofof ofthe thefollowing load motors, etc.) and the kVA application coefficients: Pa Pa = = Pn Pn /( /(η η xx cos cos ϕ ϕ)) η = the per-unit efficiency = output kW / input kW (1) From value, the full-load current From this value, thefactor full-load current (A)(1) taken taken by by the the load load will will be: be: cos ϕ this = the power = kW / kVA IIaa (A) The apparent-power kVA demand of the load Pa x 103 c Ia = b Pa = Pn /(ηVx cos ϕ) for single phase-to-neutral connected load From this phase-to-neutral value, the full-load current Iaload (A)(1) taken by the load will be: for single connected 3 Pa x 10 3 Pa x 10 c II a c a= = 3xU b 3xU three-phase balanced load where: for three-phase single phase-to-neutral connected for balanced load where: load V = phase-to-neutral voltage (volts) 3 Pa x 10 V = phase-to-neutral voltage (volts) I aphase-to-phase = c U= voltage (volts) U = phase-to-phase voltage (volts) 3xU It may be noted that, strictly speaking, the total kVA of apparent power is not the Itformay be noted balanced that, strictly speaking, the total kVA of apparent power is not the three-phase load where: arithmetical sum of the calculated kVA ratings of individual loads (unless all loads arithmetical sum of the calculated kVA ratings of individual loads (unless all loads are V = phase-to-neutral voltage (volts) are at the same power factor). at the same power factor). U = phase-to-phase (volts) It is common practicevoltage however, to make a simple arithmetical summation, the result ItIt is common practicestrictly however, to makethe a simple arithmetical summation, thethe result bewill noted speaking, total of apparent power is not ofmay which givethat, a kVA value that exceeds the kVA true value by an acceptable “design of which will give a kVA value that theof true value byloads an acceptable arithmetical sum of the calculated exceeds kVA ratings individual (unless all “design loads margin”. margin”. are at the same power When some or all of thefactor). load characteristics are not known, the values shown in It is common practice however, to make a simple arithmetical summation, the result Figure B9 next page may be used to give a very approximate estimate of VA of which will give a kVA value exceeds true by an acceptable demands (individual loads are that generally toothe small tovalue be expressed in kVA or“design kW). (1) For greater precision, account must be taken of the factor margin”. The estimates for lighting loads are based on floor areas of 500 m2. of utilization as account explained below 4.3 of the factor (1)maximum For greater precision, must be in taken When some or all of the load characteristics are not known, the values shown in of maximum utilization as explained below in 4.3 Figure B9 next page may be used to give a very approximate estimate of VA Schneider Electric installation guide 2016 Schneiderdemands Electric -- Electrical Electrical installation guide 2005 (individual loads are generally too small to be expressed in kVA or kW). 2 © Schneider Electric - all rights reserved The installed apparent power is commonly assumed to be the arithmetical sum of the kVA kVA of individual loads. The maximum estimated kVA kVA to to be be supplied supplied however however is is not not equal equal to the The apparent power is commonly to theinstalled total installed total installed kVA. kVA. assumed to be the arithmetical sum of the kVA of individual loads. The maximum estimated kVA to be supplied however is not equal to the total installed kVA. A - General rules of electrical installation design A18 When some or all of the load characteristics are not known, the values shown in Figure A9 may be used to give a very approximate estimate of VA demands (individual loads are generally too small to be expressed in kVA or kW). The estimates for lighting loads are based on floor areas of 500 m2. Fluorescent lighting (corrected to cos ϕ = 0.86) Type of application Estimated (VA/m2) Average lighting fluorescent tube level (lux = lm/m2) (1) with industrial reflector Roads and highways 7 150 storage areas, intermittent work Heavy-duty works: fabrication and 14 300 assembly of very large work pieces Day-to-day work: office work 24 500 Fine work: drawing offices 41 800 high-precision assembly workshops Power circuits Type of application Estimated (VA/m2) Pumping station compressed air 3 to 6 Ventilation of premises 23 Electrical convection heaters: private houses 115 to 146 flats and apartments 90 Offices 25 Dispatching workshop 50 Assembly workshop 70 Machine shop 300 Painting workshop 350 Heat-treatment plant 700 (1) example: 65 W tube (ballast not included), flux 5,100 lumens (Im), luminous efficiency of the tube = 78.5 Im / W. Fig. A9: Estimation of installed apparent power 4.3 Estimation of actual maximum kVA demand All individual loads are not necessarily operating at full rated nominal power nor necessarily at the same time. Factors ku and ks allow the determination of the maximum power and apparent-power demands actually required to dimension the installation. © Schneider Electric - all rights reserved Factor of maximum utilization (ku) In normal operating conditions the power consumption of a load is sometimes less than that indicated as its nominal power rating, a fairly common occurrence that justifies the application of an utilization factor (ku) in the estimation of realistic values. This factor must be applied to each individual load, with particular attention to electric motors, which are very rarely operated at full load. In an industrial installation this factor may be estimated on an average at 0.75 for motors. For incandescent-lighting loads, the factor always equals 1. For socket-outlet circuits, the factors depend entirely on the type of appliances being supplied from the sockets concerned. For Electric Vehicle the utilization factor will be systematically estimated to 1, as it takes a long time to load completely the batteries (several hours) and a dedicated circuit feeding the charging station or wall box will be required by standards. Schneider Electric - Electrical installation guide 2016 4 Power loading of an installation A19 Diversity factor - Coincidence factor (ks) It is a matter of common experience that the simultaneous operation of all installed loads of a given installation never occurs in practice, i.e. there is always some degree of diversity and this fact is taken into account for estimating purposes by the use of a factor (ks). This factor is defined in IEC60050 - International Electrotechnical Vocabulary, as follows: b Coincidence factor: the ratio, expressed as a numerical value or as a percentage, of the simultaneous maximum demand of a group of electrical appliances or consumers within a specified period, to the sum of their individual maximum demands within the same period. As per this definition, the value is always y 1 and can be expressed as a percentage b Diversity factor: the reciprocal of the coincidence factor. It means it will always be u 1. The determination of ks factors is the responsibility of the designer, since it requires a detailed knowledge of the installation and the conditions in which the individual circuits are to be exploited. For this reason, it is not possible to give precise values for general application. Note: In practice, the most commonly used term is the diversity factor, but it is used in replacement of the coincidence factor, thus will be always <= 1. The term "simultaneity factor" is another alternative that is sometimes used. The factor ks is applied to each group of loads (e.g. being supplied from a distribution or sub-distribution board). The following tables are coming from local standards or guides, not from international standards. They should only be used as examples of determination of such factors. Diversity factor for an apartment block Some typical values for this case are given in Figure A10, and are applicable to domestic consumers without electrical heating, and supplied at 230/400 V (3-phase 4-wires). In the case of consumers using electrical heat-storage units for space Number of downstream consumers 2 to 4 5 to 9 10 to 14 15 to 19 20 to 24 25 to 29 30 to 34 35 to 39 40 to 49 50 and more 6 consumers 36 kVA 3 rd floor 4 consumers 24 kVA 2 nd floor 5 consumers 30 kVA 1st floor 6 consumers 36 kVA ground floor 4 consumers 24 kVA Fig. A10: Example of diversity factors for an apartment block as defined in French standard NFC14-100, and applicable for apartments without electrical heating 0.78 heating, a factor of 0.8 is recommended, regardless of the number of consumers. Example (see Fig. A11): 5 storeys apartment building with 25 consumers, each having 6 kVA of installed load. The total installed load for the building is: 36 + 24 + 30 + 36 + 24 = 150 kVA The apparent-power supply required for the building is: 150 x 0.46 = 69 kVA From Fig. A11, it is possible to determine the magnitude of currents in different sections of the common main feeder supplying all floors. For vertical rising mains fed at ground level, the cross-sectional area of the conductors can evidently be progressively reduced from the lower floors towards the upper floors. These changes of conductor size are conventionally spaced by at least 3-floor intervals. In the example, the current entering the rising main at ground level is: 0.63 0.53 0.49 150 x 0.46 x 103 0.46 400 3 = 100 A the current entering the third floor is: (36 + 24) x 0.63 x 103 Fig. A11: Application of the diversity factor (ks) to an apartment block of 5 storeys 400 3 = 55 A Schneider Electric - Electrical installation guide 2016 © Schneider Electric - all rights reserved 4th floor Diversity factor (ks) 1 0.78 0.63 0.53 0.49 0.46 0.44 0.42 0.41 0.38 A - General rules of electrical installation design A20 Rated Diversity Factor for distribution switchboards The standards IEC61439-1 and 2 define in a similar way the Rated Diversity Factor for distribution switchboards (in this case, always y 1) IEC61439-2 also states that, in the absence of an agreement between the assembly manufacturer (panel builder) and user concerning the actual load currents (diversity factors), the assumed loading of the outgoing circuits of the assembly or group of outgoing circuits may be based on the values in Fig. A12. If the circuits are mainly for lighting loads, it is prudent to adopt ks values close to unity. Type of load Assumed loading factor Distribution - 2 and 3 circuits 0.9 Distribution - 4 and 5 circuits 0.8 Distribution - 6 to 9 circuits 0.7 Distribution - 10 or more circuits 0.6 Electric actuator 0.2 Motors y 100 kW 0.8 Motors > 100 kW 1.0 Fig. A12: Rated diversity factor for distribution boards (cf IEC61439-2 table 101) Diversity factor according to circuit function ks factors which may be used for circuits supplying commonly-occurring loads, are shown in Figure A13. It is provided in French practical guide UTE C 15-105. Circuit function Diversity factor (ks) Lighting 1 Heating and air conditioning 1 Socket-outlets 0.1 to 0.2 (1) Lifts and catering hoist (2) b For the most powerful motor 1 b For the second most powerful motor 0.75 b For all motors 0.60 (1) In certain cases, notably in industrial installations, this factor can be higher. (2) The current to take into consideration is equal to the nominal current of the motor, increased by a third of its starting current. © Schneider Electric - all rights reserved Fig. A13: Diversity factor according to circuit function (see UTE C 15-105 table AC) Schneider Electric - Electrical installation guide 2016 motor 1 c For the second most powerful motor 0.75 c For all motors 0.60 (1) In certain cases, notably in industrial installations, this factor can be higher. (2) The current to take into consideration is equal to the nominal current of the motor, oncreased by a third of its starting current. 4 Power loading of an installation A21 Fig. B13 : Factor of simultaneity according to circuit function 4.4 Example of application of factors ku and ks 4.4 Example of application of factors ku and ks An example in the estimation of actual maximum kVA demands at all levels of an An examplefrom in theeach estimation of actual maximum demands at all levels of an installation, load position to the point ofkVA supply (see Fig. B14 opposite installation, from each load position to the point of supply is given Fig. A14. page). In In this this example, example, the the total total installed installed apparent apparent power power is is 126.6 126.6 kVA, kVA, which which corresponds corresponds to value at at the the LV LV terminals transformer to an an actual actual (estimated) (estimated) maximum maximum value terminals of of the the MV/LV HV/LV transformer of of 65 65 kVA kVA only. only. Note: in order to select cable sizes for the distribution circuits of an installation, the Note: in order to select cable sizes for the distribution circuits of an installation, the current I (in amps) through a circuit is determined from the equation: current I (in amps) through a circuit is determined from the equation: kVA x 103 I= U 3 where kVA kVA is is the the actual actual maximum maximum 3-phase 3-phase apparent-power apparent-power value value shown shown on on the the where diagram for for the the circuit circuit concerned, concerned, and and U U is is the the phase phasetodiagram to- phase phase voltage voltage (in (in volts). volts). 4.5 Diversity factor The term diversity factor, as defined in IEC standards, is identical to the factor of Level 2in 4.3. In some English-speaking Level 3 Level 1 guide, as described simultaneity (ks) used in this countries however (at the time of writing) diversity factor is the inverse of ksApparent i.e. it is Apparent Utilization Apparent Diversity Apparent Diversity Apparent Diversity always power factor power u 1. factor power factor power factor power Utilization Workshop A Lathe (Pa) kVA max. demand demand Schneider Electric - Electrical installation guide 2005 max. kVA kVA no. 1 5 0.8 4 no. 2 5 0.8 4 no. 3 5 0.8 4 14.4 Socketoulets 3.6 Lighting circuit 0.8 4 2 0.8 1.6 no. 2 2 0.8 1.6 18 1 18 0.2 30 fluorescent lamps 3 1 3 1 Workshop B Compressor 3 socketoutlets 10/16 A 15 0.8 12 1 10 fluorescent lamps 1 1 1 Workshop C Ventilation no. 1 2.5 no. 2 2.5 no. 1 no. 2 10.6 0.4 5 socketoutlets 10/16 A 20 fluorescent lamps Workshop A distribution box 0.9 18.9 3 Main general distribution board MGDB Power circuit 12 Socket- Workshop B 4.3 1 oulets distribution box 1 1 2.5 1 2.5 Distribution box 15 1 15 15 1 15 18 1 18 0.28 5 oulets Lighting 2 1 2 1 2 circuit LV / MV 15.6 65 0.9 Lighting circuit 1 1 Oven Power circuit 0.75 5 10.6 demand kVA Distribution box no. 4 Pedestalno. 1 drill 5 socketoutlets 10/16 A demand kVA 0.9 Workshop C distribution 35 Powver box circuit 0.9 37.8 Socket- © Schneider Electric - all rights reserved Fig A14: An example in estimating the maximum predicted loading of an installation (the factor values used are for demonstration purposes only) Schneider Electric - Electrical installation guide 2016 A - General rules of electrical installation design A22 B20 B - General design - Regulations Installed power B20 B - General design - Regulations Installed power 4 Power loading of an installation 4.5 Choice of loading transformerof rating 4 Power an installation When an installation is to be supplied directly from a MV/LV transformer and the maximum apparent-power loading of the installation has been determined, a suitable rating for the transformer can be decided, taking into account the following c Installation constraints (temperature...) standard transformer ratings considerations (see Fig. A15): b The possibility of improving the installation (see chapter L) by: The nominal full-load current In onpower the LVfactor side of of the a 3-phase transformer is given b Anticipated3extensions to the installation Pa x 10 constraints (e.g. temperature) bI nInstallation = b Standard U 3transformer c Installation constraintsratings. (temperature...) standard transformer ratings where The nominal full-load current IIn on the the LV LV side side of of aa 3-phase 3-phase transformer transformer is is given given by: by: The nominal full-load current n on c Pa P =akVA rating of the transformer 3 x 10 cI nU== phase-to-phase voltage at no-load in volts (237 V or 410 V) U 3 c In is in amperes. where where b Pa = kVA rating of the transformer c Pa = kVA rating of the transformer b U = phase-to-phase voltage at no-load in volts (237 V or 410 V) c IUna=issingle-phase phase-to-phase voltage at no-load in volts (237 V or 410 V) For b in amperes. transformer: c In is in amperes. For a single-phase transformer: Pa x 103 In = For a single-phase transformer: V where where cV terminals at at no-load no-load (in (in volts) volts) b V= = voltage voltage between between LV LV terminals Pa x 103 cI nSimplified equation for 400 V (3-phase load) = SimplifiedVequation for 400 V (3-phase load) c In = kVA x 1.4 b In = kVA x 1.4 where The IEC standard for power transformers is IEC 60076. The IEC standard for power transformers is IEC(in 60076. cV= voltage between LV terminals at no-load volts) c Simplified equation for 400 V (3-phase load) c In = kVA x 1.4 © Schneider Electric - all rights reserved 4.7 Choice ofpower power-supply sources The IEC standard for transformers is IEC 60076. The study developed in E1 on the importance of maintaining a continuous supply Apparent power In (A)plant. The choice and characteristics raises the question of the use of standby-power kVA 237 V 410 V of these alternative sources are described in E1.4. 4.7 Choice of power-supply sources 100 244 141 For the main source of supply the choice is generally between a connection to the 160 390 225 HV the LV network in of E1 theon power-supply utility. Theorstudy developed the importance of maintaining a continuous supply 250 609 352 raises the question of the use of standby-power plant. Thewhere choicethe and characteristics In practice, connection to be necessary load exceeds 315a HV source may 767 444 of these alternative sources are described in E1.4. (or is planned eventually to exceed) a certain level - generally of the order of 400 974 563 250 kVA, or ifsource the quality of service required is greaterbetween than available For the main of 500 supply the choice is 1218 generally connection to the 704 thatanormally from LV LV network. HV ora the network of630 the power-supply utility. 1535 887 Moreover, the installation to cause disturbance towhere neighbouring In practice,ifconnection to a is HVlikely source may 1949 be necessary the load exceeds 800 1127 consumers, when connected to a LVanetwork, the supply authorities (or is planned eventually to exceed) certain level - generally of the may orderpropose of 1000 2436 1408 a HVkVA, service. 250 or if the quality of service required3045 is greater than 1250 1760that normally available from a LVatnetwork. 1600 3898 2253 Supplies HV can have certain advantages: in fact, a HV consumer: Moreover, if the installation is likely to cause disturbance tocase neighbouring 2000consumers, 4872 2816 c Is not disturbed by other which could be the at LV consumers, when connected the supply authorities may propose 2500 to a LV network, 6090 3520 c Is free to choose any type of LV earthing system a HV service. 3150 7673 4436 c Has a wider choice of economic tariffs Supplies at HV can have certain advantages: in fact, a HV consumer: c Can accept very large increases in load c IsA15: not disturbed by otherpowers consumers, which could be the case at LV Fig. Standard apparent It should be noted, however, that:for MV/LV transformers and related nominal output currents c Is free to choose any type of LV earthing system c The consumer is the proprietor of the HV/LV substation and, in some countries, c Has a wider choice of economic tariffs he must build and equip it at his own expense. The power utility can, in certain c Can accept very large increases in load circumstances, participate in the investment, at the level of the HV line for example It A should bethe noted, however, that: c part of connection costs can, for instance, often be recovered if a second consumer is connected to the HV of line a certain timeand, following the countries, original c The consumer is the proprietor thewithin HV/LV substation in some consumer’s own he must build andconnection equip it at his own expense. The power utility can, in certain circumstances, in only the investment, at the level of the HVaccess line for to example c The consumerparticipate has access to the LV part of the installation, the HV to the utility (meter reading, operations, etc.). c A part part being of thereserved connection costs can,personnel for instance, often be recovered if a second However, countries, the line HV protective circuittime breaker (or fused load-break consumer in is certain connected to the HV within a certain following the original switch) can be operated by the consumer consumer’s own connection c The type and location of theonly substation are agreed the consumer and consumer has access to the LV part of thebetween installation, access to the the HV utility part being reserved to the utility personnel (meter reading, operations, etc.). However, in certain countries, the HV protective circuit breaker (or fused load-break switch) can be operated by the consumer c The type and location of the substation are agreed between the consumer and the utility Schneider Electric - Electrical installation guide 2016 4 Power loading of an installation A23 4.6 Choice of power-supply sources The importance of maintaining a continuous supply raises the question of the use of standby-power plant. The choice and characteristics of these alternative sources are part of the architecture selection, as described in chapter D. For the main source of supply the choice is generally between a connection to the MV or the LV network of the power-supply utility. In some cases main source of supply can be rotating generators in the case of remote installations with difficult access to the local Utility public grid (MV or LV) or where the reliability of the public grid does not have the minimum level of reliability expected. In practice, connection to a MV source may be necessary where the load exceeds (or is planned eventually to exceed) a certain level - generally of the order of 250 kVA, or if the quality of service required is greater than that normally available from a LV network. Moreover, if the installation is likely to cause disturbance to neighbouring consumers, when connected to a LV network, the supply authorities may propose a MV service. © Schneider Electric - all rights reserved Supplies at MV can have certain advantages: in fact, a MV consumer: b Is not disturbed by other consumers, which could be the case at LV b Is free to choose any type of LV earthing system b Has a wider choice of economic tariffs b Can accept very large increases in load It should be noted, however, that: b The consumer is the owner of the MV/LV substation and, in some countries, he must build equip and maintain it at his own expense. The power utility can, in certain circumstances, participate in the investment, at the level of the MV line for example b A part of the connection costs can, for instance, often be recovered if a second consumer is connected to the MV line within a certain time following the original consumer’s own connection b The consumer has access only to the LV part of the installation, access to the MV part being reserved to the utility personnel (meter reading, operations, etc.). However, in certain countries, the MV protective circuit breaker (or fused load-break switch) can be operated by the consumer b The type and location of the substation are agreed between the consumer and the utility. More and more renewable energy sources such as photovoltaic panels are used to supply low-voltage electrical installations. In some case these PV panels are connected in parallel to the Utility grid or these PV panels are used in an autonomous mode without connection to the public grid. Conversion from d.c. to a.c. is then necessary as rated voltage of these PV panels are higher and higher (few hundreds volts) and also because PV panels produce d.c. currents. See also chapter P "Photovoltaic installations" Schneider Electric - Electrical installation guide 2016
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )