Submarine Power Cable Current Rating Calculations • • • • • • • • • • • • Current Rating Calculations Submarine Cable Design Bonding of Offshore Cable Systems Modelling Submarine Cables Armour Loss Calculations Fundamentals Landfall – Design and Modelling Dynamic Ratings J-tube – Design and Modelling Seabed – Design and Modelling 2 K Criterion Calculation Examples including Live Software Demo • Submarine Installation • J-tube Installation Conclusions and Recommendations Examples ELEK Cable HV Software • Accurate and validated software for cable current rating calculations. • Suitable for any AC voltage and HVDC cables. • Complies with the IEC 60287 standards, the main authority for cable rating calculations. • Performs current rating calculations for custom cables under specific installation conditions. The accuracy of the calculations is validated with CIGRE TB 880. Download a Free Trial from elek.com 2 IEC 60287 Current Rating Calculations • The IEC Standard (60287) series provides analytical equations for calculating cable current ratings. • The IEC standards continue to be widely adopted because they: • 1. Are adapted for common cable types and installation methods. • 2. Are reasonably accurate, which leads to reliable, current ratings for new and existing cable circuits. • 3. Ensure consistency and comparability of current ratings determined by different bidders, providers, or suppliers for stakeholders. • The IEC standard calculations are somewhat complicated to implement and ambiguous in parts. 9 parts to IEC 60287 3 Submarine Power Cables Design • • • • • Conductors: – Usually copper. Some projects use sections of Cu and Al. – Deep water uses Aluminium for its lighter weight during installation and retrieval. Insulation: XLPE for AC or DC is the first choice. Sheath: Around each core. Lead is standard due to its flexibility. Armour: Single or double layer (shore landing sections). Provides strength during installation and mechanical protection during operation. – Galvanised or stainless steel (nonmagnetic with low losses). – SS grade 316 is recommended over 304 but is very expensive. Outer serving: Polypropylene yarn. Dry design cables – Sheath is welded separate lead (SL) or aluminium (SA). Wet design – Sheath is replaced with screen made of wires, tapes, or braid. Cheaper & used for short lengths. Lead sheath: The European Union's REACH regulation classifies lead as a substance of Very High Concern, potentially restricting future cable use. 4 Bonding of Offshore HV Submarine Cables Solidly Bonded HV AC Cables For practical reasons, the metal layers (screen, sheath, and armour) in offshore AC cables are solidly bonded. 30 kV Submarine Cable The current rating is 920A at 90˚C Sheath circulating current: 85 A Notes: 1. 3-core AC cables have lower electrical losses than single-core cables. 2. Increasing conductor size has diminishing benefits due to increased sheath losses. 5 Modelling Submarine Power Cables • • Requirements: – Cable construction. – Material properties. – Layer dimensions. Challenges: – Incomplete information. – Combined layers. – Lay length factors unknown. • Standard values: 1.01 for cores, 1.05 for armour – Back calculations required. – Matching AC resistance. – Custom layers. – Material selection (matching). 6 Example of Modelling Submarine Cable 7 Thermal Resistance of Fillers • • • • Three-core submarine cables typically have an additional jacket around each core. An additional thermal resistance between the sheath and the armour (T2’) value is calculated (not included in IEC 60287). The dry thermal resistance of the filler and armour bedding must be used. The water inside fillers with voids is ignored. Jacket around each individual phase conductor. The thermal properties of water-filled voids is ignored. The filler is assumed to have uniform thermal resistivity matching the filler insulating material. 8 Magnetic Armour Loss Considerations • • Magnetic armour wires will electrically influence the skin and proximity effects in the cable conductors. – IEC 60287 ignores this – which is incorrect. – CIGRE TB 880 proposes multiplying factor of 1.5. A multiplication factor of 1.5 is applied to the circulating loss factor for SL cables with separate lead sheaths. – May not always provide conservative results [CIGRE TB 908]. • Conductor AC resistance: • Sheath circulating current loss factor for separate lead sheath cables: Steel wire armour 1.5 x multiplying factors 9 Armour Loss Factor (λ2) Calculations • • • Three core cables with non-magnetic wire armour λ2 = 0. Reduction of armour losses due to sheath losses for SL cables. Additional considerations according to CIGRE TB 908: – Applicable for cables with a single armour of round metal wires. – Suggests 1.5 x factor to conductor AC resistance is conservative. – Considers the effect of magnetic armour on sheath eddy current losses. – Considers lay direction of armour wires - Unilay or Contralay. – Considers complex magnetic relative permeability of armour. CIGRE TB 908 Implications 1. Conductor and sheath/screen losses considerably increase. 2. Armour losses significantly reduce. 3. Current rating improves significantly (typically by 10 %). 10 Accurate Armour Loss Calculations 30 kV Submarine Array Cable. 3 x 630 mm2 IEC/TB 880 with galvanised steel wire armour. TB 908 830 A 920 A IEC/TB 880 Method TB 908 Method Difference (%) Conductor loss 88.78 W/m 104.84 W/m ↑ 18.08 Sheath loss 14.45 W/m 19.105 W/m ↑ 32.214 Armour loss 37.34 W/m 7.77 W/m ↓ -79.19 Current rating 838.33 A 920.18 A ↑ 9.76 11 Critical Sections for Cable Ampacity • (1) Landfall, (2) J-tube, (3) Seabed. 3 2 1 12 Landfall Sections – Design • • • • • • • Open cut trench or HDD. HDD is difficult in gravel-based and rocky soils. Typical burial depth 10 – 15 m. TR of soil at landfall is higher than at the seabed. The ducts may be filled with pumpable grout that does not solidify over time. Soil drying out above the water table is a concern. HDD ducts have a diameter of 1.5 – 2.5 times the cable OD. Typically, the landfall area is the thermal bottleneck for wind farm cable systems. Limiting soil dry out zone Single-point bonding in the landfall section can reduce losses by 20-25 % Top image source: R. Spice, M. Hird, and J. Dix, "Dynamic cable rating with partial drying of soil," CIGRE Session Paper B1-11329, 2024. Bottom image source: Olsen, E., Hovde, M., Pilgrim, J., & Williams, D. (2022). Single Point Bonding of 3-core Submarine Cables. CIGRE Session 2022, B1 - Insulated Cables, PS2 / Future functionalities and applications, Paper ID 10961. 13 Landfall Sections – Modelling • Current rating () is substantially • proportional to depth of burial (d) and soil resistivity (ρ): 𝐼∝ • 1 𝑙𝑛. 𝑑 Soil drying out at depths above the water table. 1 𝐼∝ 𝜌 Consider sections with buried water-filled or air-filled ducts. Water -filled Air/Solidfilled Dry soil zone • Multiple export cables in pipe. → Requires FEM calculation. Pipe • Use calculated soil temperature at significant depths (> 3 m): Ducts Meshing & Temperature Plot (ELEK Software) 14 Dynamic (Efficient) Ratings of Export Cables • • • • The export cable sizing can be optimised by considering the actual wind load generation. Landfall export cables that are deeply buried have a long thermal time constant of months or even years. A multiple step dynamic rating provides a method based on IEC 60287 and IEC 60853 to assess the worst-case load event during the cable life. In a real-world example: rating of deeply buried 220 kV export cable increased by 8.4 %. The long-term root mean square current (RMS) is typically 50-70 % of the full load rating. Several years of wind data K (τ) Multi-step profile (worst-case) Cable temperature response T. Kvarts, I. Arana, R. Olsen, and P. Mortensen, "Systematic description of dynamic load for cables for offshore wind farms: 15 Method and experience," 2016. J/I-tube Sections – Design • • • • • J-tube: – Open-ended, J-shaped section of metal pipe. – Attached to an offshore unit. – Bellmouth for cable entry. Tube bends range between 1545 degrees. Inner diameter should be not less than 2.5 times cable OD. Bending radius should not be less than 20 times cable OD. Multiple tubes should have horizontal separation ≥ 1 m. With bell mouths ≥ 2 m. Image source: Elia Group Tube can be made from multiple sections with vertical gaps to facilitate air circulation 16 J/I-tube Sections – Modelling • • • • An analytical approach is based on heat transfer principles. The hottest temperatures within the J-tube are observed inside the air-filled section. Open to airflow at the top which allows convective heat transfer. Airflow is not circulating since the tube is blocked at the bottom due to the water. Multiple cables or a single cable (heat sources) are modelled. Thermal model includes heat transfer by: Conduction inside/outside the tube. Convection inside/outside the tube. Radiation between cables and inner tube walls. Heat rise from solar radiation. A new IEC standard for ampacity of cables in J-tubes is being prepared by WG 19. 17 J-tube Sections – Factors Affecting Ampacity Significant factors: • Length of air-filled section. • Ambient air temperature. • Tube diameter. Small diameter means higher ampacity. • Solar radiation intensity. • Wind speed. Wind speed Air-filled section length Cables in separate J-tubes - 34 % Cables combined in J tubes - 34.16 % Major Solar radiation Standard values for sun-exposed area are 50% and 32%. The 50% assumes half-day shading, while 32% is from Cress and Moltis's 1991 paper on risers. Cables in separate J-tube - 9.37 % Cables combined in a J-tube - 11.98 % Minor Cables in separate J-tubes - 14.61 % Cables combined in a J-tube - 14.96 % Moderate 18 Seabed Sections – Design • • • • • • • The cable can be buried during laying or Direct burial in the seabed. laid and then buried using a plough Typical burial depth 1 – 4 m. Nominal depth is 2 m. At shore areas or places where ploughing is not practical then concrete mattresses or cable covers are used. At J-tube entries rock dumping Exceptionally is often adopted. high and likely TR tests are performed along caused by organic content. the cable route. Typical soil resistivity at sea are between 0.4 and 1.4 K.m/W. Typical soil temperatures are between 5 and 15 ℃ (Note). Note: Seabed temperatures are highly variable and should be averaged using several years of data. 19 Seabed Sections – Modelling • • • • Cables completely in water (natural or forced convection, varying salinity). Cables partially buried in the seabed. Cables fully buried under the seabed (standard IEC buried calculation). Cables buried in ducts. How does marine growth affect ampacity? Water convection model Partially-buried model Marine growth model [BS 10009 (draft)] 20 Underwater – Factors Affecting Ampacity Typical ocean range Dynamic cable systems: Water velocity 𝐼 ∝ ΔΘ Water temperature Current rating () is substantially proportional to the difference between conductor temperature and ambient temperature (Δϴ). Tropical regions – 20-30 ℃, Temperate regions – 5-20 ℃ (with seasonal variations) Image (top-left) source: Prysmian Ocean water range Typical ocean water velocities – 0.1-2.5 m/s Gulf Stream – 2.5 m/s, Deep ocean – 0.1 m/s Salinity Ocean water – 30-50 g/kg Estuaries and inland seas – 0.5-30 g/kg 21 Environmental Impact: The 2 K Criterion • • Guideline established by the German Federal Agency for Nature Conservation, requiring that temperatures above a buried submarine cable 200 mm below (or 300 mm1) the seabed must not exceed 2 ℃ to protect marine life. 2K criterion Submarine cables cause local temperature increases, affecting benthic2 organisms. The burying of cables can lead to deoxygenation and the formation of black spots on the seabed, necessitating careful cable design and installation. (1) (2) (1) At rated current 2053 A, the soil temperature rises above 2 ℃ up to 0.17 m depth. (2) To comply with the 2 K criterion (such that soil temperature is not increased above 2 ℃ within 300 mm from the seabed) the current of the cables must be reduced to 1579 A. Footnote 1: This limit is even stricter in sensitive areas like the Wattenmeer National Park in Germany. Footnote 2: Anything associated with or occurring on the bottom of a body of water, such as oceans, lakes, or rivers 22 Calculation Examples Now that we’ve explored the background, let’s model some examples! 23 Submarine Installation IN WATER PARTIALLY BURIED HVDC INTER-ARRAY CABLE WATER-FILLED DUCT EXPORT CABLE 24 J-tube Installation 25 Conclusions and Recommendations IEC 60287 is used for accurate ampacity calculations. Submarine cable construction is complicated. Solid sheath bonding is used for submarine cable systems. The landfall is the most critical section (thermal bottleneck) of an offshore wind farm. • The J/I-tubes are another critical thermal bottleneck. • The underwater sections have a higher rating but may be significantly constrained by the 2 K criterion. Recommendations: 1. Use the dynamic rating for deeply buried export cables by considering the actual/predicted wind load data. 2. Use CIGRE TB 908 for accurate 3-core armour loss calculations that will increase ratings by approximately 10 %. 3. Use the finite element method (FEM) for complicated installations including multiple cable circuits inside pipes. • • • • 26 Free Trial of ELEK Cable HV Software Download a Free Trial from elek.com 27
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )