ENGINEERING STANDARD Design Criteria for Plant Layout 3PI01001 Rev.3 Page 1 of 10 Uncontrolled copy unless a distribution list is included in this document: Print Date: 28 April 2025 Complete Revision: EPS-01131950 1. PURPOSE 1.1 This engineering standard defines the basic design requirements for plant layouts. 2. SCOPE 2.1 This standard applies to all plants designed, owned, and operated by Air Products. Cylinder fill activities are not covered by this guideline. 2.2 This standard applies to sale of equipment, unless the customer's requirements are more stringent. 3. MINIMUM TECHNICAL REQUIREMENTS 3.1 Plant layout shall be the optimum combination of economy, operability, and basic safety considerations. 3.2 Process vents shall be located in accordance with 3PI25010 “Venting of Nontoxic and Nonflammable Substances” and 3PI25011 “Venting of Buoyant Flammable Gases”, unless local regulations are more stringent, or specific regional codes apply. 3.3 Climatic Conditions: 3.3.1 Vents shall be located to prevent carryover onto residential property or other zoned areas, and onto platforms, stairs, building openings and air intakes, and operating areas within the facility. 3.3.2 Cooling towers shall be located so that the prevailing wind does not carry the drift onto the plant or into areas in which it could cause icing, accelerate external corrosion of plant structure or equipment, or where visibility impairment could be hazardous (such as, causing fog on neighboring roads). The concern for fogging also applies to ambient vaporizer back-up systems. The cold vapor caused by normal operation causes a dense low-level fog, which can drift for considerable distances causing poor visibility hazards both within the site boundary and across adjacent sites and roadways. 3.3.3 Cooling towers, air compressor houses, and air separation units shall be located so that flammable and/or corrosive gases and atmospheric particulates from neighboring process plants, boiler chimneys, and other sources are not carried into the air intakes by the prevailing wind. 3.4 Equipment, Utility, and Building Location 3.4.1 All equipment in Air Separation Plants shall have separation distances according to 3ES60101 “Safety Distance Criteria for Air Separation Plants”. 3.4.2 All equipment in HYCO and Gaseous Hydrogen Plants shall have separation distances according to local regulations (e.g. NFPA) for flammable and toxic gases. This shall be determined on a case by case basis. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 2 of 10 3.4.3 Heat exchangers shall be located to minimize connecting process lines and to use common utility mains. 3.4.4 Storage systems separation distances shall comply with STD-ENG-ES012 “Separation Distances for Storage Systems and Process Equipment” for North America plants. 3.4.5 Compression equipment shall be located to minimize interconnecting piping distances from cold boxes or other equipment. 3.4.6 Deep water wells and waste water wells locations and siting shall be determined on a case-bycase basis, and shall comply with local regulations. 3.4.7 Electrical equipment shall have minimum clearances listed in Table 1 in areas where the NFPA 70 code is applicable. Where the NFPA 70 code is not applicable, electrical equipment shall have minimum clearances in accordance with applicable local electrical code. 3.4.8 Ambient Vaporizers shall be spaced according to manufacturer’s recommendations. See Table 2 for required spacing around the outside of vaporizer banks. 3.5 Minimum personnel and equipment minimum safety clearances shall be according to Table 1 3.6 If lifting areas or wells are used, they shall be large enough for the largest piece of equipment that will have to pass through them, and should be kept free of piping, cables, and other minor equipment that could impede their proper use. 3.7 Roads 3.7.1 Layout of roads shall allow for both present and specified future traffic densities. 3.7.2 Primary roads shall not infringe on hazardous area classifications 3.7.3 Emergency access shall be provided to all areas of the process plant. Adequate access for firefighting and other emergency service vehicles shall be provided in accordance with local laws. 3.7.4 The number of road junctions, rail crossings, 90-degree turns, dead ends, and ramps should be minimized. Turnaround or spur roads shall be provided at dead ends for vehicle turning. 3.7.5 Requirements for roads are contained in Table 3. 3.7.6 Areas in which a number of articulated vehicles will be loading or discharging at one time should have a minimum depth of 36 m (120 ft) for angle parking, and a minimum of 44 m (145 ft) for square parking, to allow vehicles to maneuver. The parking area dimensions and shapes shall be determined on a case by case basis, according to parking frequencies and road conditions. 3.7.7 A level area and a minimum straight length shall be provided at the approach and exit of each scale. 3.7.7.1 For plants within the United States, state regulations require that level areas extend a minimum 3m (10 ft) from the scale, and the straight length minimum shall be equal to the length of the scale load platform. 3.7.7.2 For plants outside the United States, the local department of transportation should be consulted for minimum level area length and straight length. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 3 of 10 3.8 The consequences of all probable plant emergencies shall be considered in the overall plant layout. 3.9 All appropriate emergency equipment (for example, safety showers, eye wash stations, and air packs) must be in safe, accessible locations that are as close to their anticipated use areas as possible. 4. REQUIRED SAFETY ENHANCEMENTS FOR AIR PRODUCTS FACILITIES No. Name Category/ Reason Code Safety 4.1 Cooling Tower Stand Pipe Clearance Cooling tower stand pipes shall be considered a gaseous-effluent source. A minimum 6 m (20 ft) horizontal clearance to adjacent platforms is required, excluding access areas provided with the tower. See Table 1 4.2 Safety Flares and Flammable Vents Location The impact of radiant heat on personnel and in-plant equipment shall be studied by the safety engineer, and the results of the analysis shall be used to locate flares and flammable vents within the site. 4.3 Safety Separation from Neighboring Third Part Plants Equipment, buildings, and utility stations located in Air Products facilities shall be separated from neighboring customers or third party plants in accordance with the recommendations of the project hazard and operability study, and in accordance with the appropriate safety distances for the separation of hazardous materials located outside of the battery limit. Safety Cryogenic Leak/Spill Prevention 4.4 Cryogenic liquid shall be prevented from exiting the site or entering the public drainage systems. This can be accomplished by utilization of any combination of the following: Central location of the storage tanks(s), pumps and piping systems on the site Sloping of finished grade to direct flow Site drainage/retention systems such as swales, and ponds Flow containment details such as curbs and sluice gates 4.5 Safety Equipment Layout for Noise Attenuation Equipment layout shall be used to reduce the noise impact at fence lines and at work areas within the plant. Storage tanks, cold boxes, and structures shall be used to shield equipment that emits noise. Work areas include control room, terminal, and maintenance area. 4.6 Road Protection Near Vulnerable Plant Installations Safety If roads pass near vulnerable plant installations (for example, corrosive liquid tanks and pipe bridge trestles), crash barrier protection such as standard highway guardrails shall be provided. 4.7 Tanker Loading Position- No Reversing Required Safety The position of tankers during loading shall be such that they can exit the plant without reversing after loading. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 4 of 10 No. Name Category/ Reason Code Safety 4.8 Main-gate Setback Main-gate setback shall permit trucks to clear public roadways while waiting for gates to open. Main gate setback shall be at least one trailer length according to selected trailer model. Typically, this is 21 m (70 ft) for a liquid trailer. 4.9 Car Parking Location 4.9.1 Car parking shall be segregated from trailer parking and from operating areas. Also, separation of truck and car traffic shall be considered when locating car parking areas. 4.9.2 Employee parking shall be separated from the plant production areas with a fence with employees walking through an access control point. 4.10 Air Products Security Safety Safety Review Global EH&S Standards 22-0008 “Perimeter Barriers” through 22-0015 “Facility Vehicle and Pedestrian Entrances and Exits” for engineering related security standards. All Air Products owned and operated plants shall comply with the global security standards. Safety 4.11 Perimeter Fence or Barrier 4.12 According to EHS document 22-0008 “Perimeter Barriers”, the complete process plant, storage, office, parking, vehicle maintenance area, vehicle refueling area, and truck scale shall be surrounded by a chain link fence or other barrier. The perimeter fence shall be a minimum of 2 m (8 ft) from the property line. Safety Main Access Gate Remote Operation The main access shall have lockable gates that can be operated from a remote position. The main gate shall be visible or capable of being monitored from its point of operation (for example, a camera monitor located in the main control room). 4.13 Shipping and Receiving Points Near Perimeter Safety Shipping and receiving points shall be located near or on the perimeter, thereby limiting the amount of non-Air Products traffic on the property and through process areas. 5. OPTIONS FOR ENHANCEMENTS No. 5.1 Name In-line Layout Category/ Reason Code Operability An in-line layout, in which equipment is arranged according to the process flow sequence, should be used for air separation process equipment and large chemical plants to optimize interconnection materials and to facilitate operation and maintenance. 5.2 Constructability Similar Equipment Grouping Layout A similar equipment grouping layout combines like equipment such as utilities, major process, or compression equipment and storage. This approach should be used to minimize cost and enhance operability, by combining platform, building, crane, and utility requirements. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 5 of 10 No. 5.3 Name Functional-equipment Arrangement Layout Category/ Reason Code Operability The functional-equipment arrangement consists of equipment with similar electrical or hazardous classifications being grouped together. 5.4 Future Expansion Space Constructability Future expansion might require that adequate space is provided adjacent to some areas in the plant. Cooling towers and storage areas can often be located to allow for future expansion at no initial cost penalty. 5.5 Tower and Large Vessel Arrangement Operability Towers and large vessels should be arranged in rows with their centerlines on a common line, if they are of similar diameters. If they are of differing diameters, they may be aligned to a common face. 5.6 Maintainability Heat Exchanger Maintenance Structure Horizontal, shell-and-tube heat exchangers may be stacked. The centerline of the top heat exchanger shall not exceed 4.0 m (12 ft) from grade without providing a permanent maintenance structure. 5.7 Cooling Tower Alignment Operability Cooling towers up to 61.0 m (200 ft) long should be aligned parallel to the prevailing summer wind, to minimize recirculation of the humid exhaust air. They should also be located away from the plant boundaries and with a solid end wall toward the nearest boundary, since the low frequency noise generated by a cooling tower is very difficult to attenuate and is directional. 5.8 Buildings near In-Plant Roads Control, electrical, and analyzer buildings should be located near in-plant roads. 5.9 Compression Equipment Grouping Operability Constructability When multiple units have similar building requirements, consideration should be given to grouping and housing them in a single building. Grouping compression equipment can also minimize electrical and cooling water runs, as well as allow sharing of deck or platform steel. 5.10 Product Storage and Trailer Loading Efficiency Product storage and trailer loading should be located in a common area. The location of product pumps, transfer pumps, and pressure build-up (P.B.) coils should be immediately adjacent to storage tanks. 5.11 Equipment Requiring Regular Maintenance Maintainability Large equipment that requires regular (once per year) maintenance should be accessible from a floor or a permanent working platform. When this is not possible, adequate space should be left for erecting scaffolding. Adequate space should also be provided when platforming is not furnished for equipment maintenance that is required more often than once per year. 5.12 Equipment Requiring Dismantling or Replacement Maintainability Equipment that needs to be dismantled or replaced frequently (once every six months or more frequently) should be positioned so that other equipment will not have to be disturbed. A clear area for parts lay-down should be provided. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 6 of 10 No. 5.13 Name Equipment Requiring Moving or Servicing Category/ Reason Code Maintainability Heavy or large items of equipment that need to be moved from the plant for servicing should be placed to facilitate crane access, loading onto transport vehicles, and reinstallation. If these items are located in a building, crane access should be facilitated by removable roof panels. 5.14 Additional Space for Withdrawal of Serviceable Items Maintainability Space should be provided for withdrawal of such items such as heat exchanger tube bundles and filter cartridges. See Table 2 Maintainability 5.15 Additional Space for Equipment Maintenance See Table 2 for recommended equipment clearances. 5.16 Operability Liquid Production Plant Truck Traffic Flow For liquid production plants, a one-directional flow of truck traffic through the loading cycle is recommended. 5.17 Garage and Vehicle Washing Facilities Maintainability Garages, when specified, should be located in the main traffic pattern on the primary road and away from the process area. Vehicle washing facilities should be located near the garage and be accessible to a sanitary sewer or process water disposal system. 5.18 Vehicle Refueling Operability Vehicle refueling should be located between the main gate and the truck scale. Installation must provide for two-way traffic during refueling. Efficiency 5.19 Load-on Scales for Liquid Producing Facilities 5.20 Load-on scales should be considered for liquid-producing facilities. Load-on scales with automatic trailer filling allow tankers to fill the maximum allowable road weight and eliminate over or under filling of trailers. Load-on scales reduce plant traffic and support one-directional traffic flow through the facility, thereby providing a safer and quicker turnaround. Operability Single Truck Scale Location Location for a single truck scale should be along the primary road between the fueling point and the loading area. 5.21 Operability Two-way Traffic on Truck Scale Installation Truck scale installation should provide for two-way traffic with the scale occupied. 5.22 Weather Proofed Scale Readout The scale readout should be housed indoors or be suitably weatherproofed. Reliability 5.23 Scale Located to Prevent Vehicles Reversing or Turning Operability The scale should be located so that vehicles may drive onto and away from it without reversing or turning and to avoid cross traffic. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 7 of 10 Table 1 Personnel and Equipment Safety Clearances Length units, m (ft) Horizontal Operating Clearances, m (ft) Minimum Preferred In structures 0.75 (2.5) 1.0 (3) On vessels 0.75 (2.5) 1.0 (3) Stairways 0.75 (2.5) width 1.0 (3) Cooling Tower Stand Pipes 6 (20) Access between wall and process equipment 0.75 (2.5) 1.0 (3) Horizontal Operating Clearances, m (ft) Front (Minimum*) Front (Preferred) Rear (Minimum*) Rear (Preferred) Based on voltage. See NFPA 70 2.0 (6) 0.762 (2’6”) 1.50 (4) Main Control Panel Switchgear-high voltage (600 to 13,800 volts) 1.50 (5) - 0.762 (2’6”) 0.9 (3) Switchgear-low voltage (up to 600 volts) 1.0 (3’ 6”) 1.25 (4) 0.762 (2’6”) 0.9 (3) Motor starters: 2.3 kV 1.25 (4) - - - Motor Starters: 4.16 kV 1.25 (4) 1.50 (5) - - 480 volt motor control centers 1.0 (3’ 6”) - - Between Instrument Racks - - - 2.0 (6) * Minimum clearances are based on NFPA 70 National Electrical Code (NEC) condition 2: Exposed live parts on one side of the working space and grounded parts on the other side of the working space. Energized parts on both sides (condition 3) will require additional clearances. For locations outside the United States, clearances shall follow local electrical codes and regulations. Vertical Overhead Clearances*, m (ft) Minimum Preferred Passageways, walkways, platforms 1.8 (6) 2.30 (7.5) Aisles, aisleways 2.30 (7.5) Accessways 3.0 (10) Secondary plant roads 4.1 (13.5) Primary plant roads 5.5 (18.0) Under main pipeways, pipe racks 6.0 (20) 3.0 (10) Electric panels 2 (6.5) Instrument panels 0.15 (0.5) 0.75 (2) * as measured to the lowest point of member or line, including but not limited to, insulation, flanges, fittings, and supports © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 8 of 10 Table 2 Equipment Clearances Length units, m (ft) Equipment Clearances Note: Distances are based on large equipment items. Judgment should be applied when locating smaller items typically encountered in air separation plants. Tube bundle removal Bundle length, plus 1.0 (3) Piston rod removal Rod length, plus 0.75 (2.5); 1.25 (4) side clearance Agitator shaft removal Shaft length plus 1.25 (4) preferred (where agitator is "top or bottom entering" within a closed structure, an individual analysis shall be made) In front of exchanger channel and cover ends 1.25 (4) outdoor; 0.75 (2.5) indoor Access to pumps 1.0 (3) both sides preferred; 0.75 (2.5) minimum Access between pumps and wall 1.25 (4) Access between two rows of pumps 2.0 (6) outdoor; 1.25 (4) indoor Access around outside of ambient vaporizer banks 0.75 (2.5), 2 (6) preferred Maintenance Equipment Clearances 10 to 20 U.S. ton loads 5.5 (18) minimum width, 4.25 (14) minimum height, 7.3 (24), minimum length [ or 22’ x 22’] 21 to 100 U.S. ton loads 7.62 (25) minimum width, 4.25 (14) to 4.9 (16) minimum height (, 8.5 (24) minimum length [Typical 100 ton crane have outrigger spread of 25 wide x 28’ long.] 101 to 300 U.S. ton loads 9.1 (30) minimum width, 5.0 (16) to 5.50 (18) minimum height, 9.1 (30) minimum length [Typical 300 ton crane have outrigger spread of 30 wide x 30’ long.] Note: Table 2 equipment clearances are only mandatory when options 5.14 and 5.15 are selected; therefore, these are not mandatory. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 9 of 10 Table 3 Roads (Road Classification) Road Characteristic Primary Secondary Service Maintenance Other* Vehicle type 2 or 3 axle, heavy 2 axle, light Any Any Heavy cranes Application Product/Raw material Service Service Maintenance Construction Number of lanes 2 2 1 1 Variable Width, m (ft) 6 (20)*** 5.0 (16) 4.0 (12) 4.0 (12) Variable as required by Construction Surface All-weather surface All-weather surface All-weather surface Stone Stone Head room, m (ft)** 5.5 (18) 4.5 (14) 4.5 (14) 4.5 (14) As required Inside radius, m (ft) 15.0 (50) 7.5 (25) --- --- --- Frequency of use Daily Daily --- --- --- Notes: * When possible, roads shall be initially designed for other use. ** Measured from the crown of the road. *** A hard shoulder 1 m (3'-0") wide is required both sides of the roadway. Table 3.Road requirements are mandatory for Air Products owned and operated plants only. © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited. Design Criteria for Plant Layout 3PI01001, Ошибка! Используйте вкладку "Главная" для применения Revision к тексту, который должен здесь отображаться., Page 10 of 10 6. RELATED INFORMATION 6.1 Air Products Engineering Documents 3PI25010 Venting of Nontoxic and Nonflammable Substances 3PI25011 Venting of Buoyant Flammable Gases 3ES60101 Safety Distance Criteria for Air Separation Plants 3EL64550 Spacing Criteria for Oil-filled Transformers and Oil-filled AutoTransformers 3EQ93012 Minimum Requirements for Standard Bulk Gaseous Hydrogen Customer Installations 3EQ12002 Requirements for Gaseous Hydrogen Tube Trailer Filling Locations STD-ENG-ES012 Separation Distances for Storage Systems and Process Equipment EP-9.1 Safety Review Plan EP-9.3 Environmental Strategy About this document (for Air Products Internal Use Only) Version History (for Air Products Internal Use Only) 6.2 6.3 Global EH&S Standards: 25-010912 Siting and Design of Occupied Plant Buildings for Overpressure Protection 22-0003 Air Products Chemicals of Concern List for Product Security Management 22-0008 Perimeter Barriers 22-0009 Facility Internal Security Barriers 22-0010 Facility Closed-Circuit Television Systems 22-0011 Facility Intrusion Monitoring Systems 22-0012 Contracted Uniform Guard and other Protective Services 22-0013 Facility Security Lighting 22-0014 Facility Access Control Systems 22-0015 Facility Vehicle and Pedestrian Entrances and Exits National Fire Protection Association (NFPA) National Fire Code © 2018 Air Products and Chemicals, Inc. All information herein is the property of Air Products unless another source is shown. This document is classified as Air Products Internal Use Only, is subject to return on demand and must not be disclosed or reproduced without prior written consent. This information may be subject to export controls. Disclosure contrary to U.S. law is prohibited.
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )