NORSOK Standard NORSOK M-004:2018 Published: 2018-12-23 Language: English Piping and equipment insulation Reference number: NORSOK M-004:2018 (en) © NORSOK 2018 ICS: 75.180.01, 913.12, 13.220.99, 29.080 Copyright protected document Unless otherwise specified, no part of this document may be reproduced or used in any form or in any way without written permission obtained in advance. This includes photocopies and electronic use, such as publishing on the Internet or an intranet. Any reproduction that violates this may lead to seizure, liability and/or legal prosecution. Requests related to reproduction are to be directed to Standard Online AS. NORSOK M-004:2018 Contents Foreword .......................................................................................................................................................................... v Introduction.................................................................................................................................................................. vii 1 Scope .......................................................................................................................................................................1 2 Normative references .......................................................................................................................................1 3 Terms and definitions.......................................................................................................................................3 4 Symbols and abbreviations.............................................................................................................................6 5 Qualification requirements ............................................................................................................................7 5.1 Qualification of personnel ................................................................................................................................. 7 5.1.1 Qualification of insulation fitters .................................................................................................................... 7 5.1.2 Qualification of supervisors, foremen and QC personnel ..................................................................... 7 5.2 Qualification of insulation system .................................................................................................................. 7 5.2.1 Class 5 and F: Fire insulation............................................................................................................................ 8 5.2.2 Class 6, 7 and 8: Acoustic insulation ............................................................................................................. 8 5.2.3 Sealing of penetrations ....................................................................................................................................... 8 5.3 Insulation procedure ........................................................................................................................................... 9 5.3.1 Insulation procedure specification (IPS)..................................................................................................... 9 5.3.2 Drawings for penetration seals .................................................................................................................... 10 5.3.3 Inspection and test plan (ITP) ...................................................................................................................... 10 6 Materials ............................................................................................................................................................. 11 6.1 Environmentally requirements .................................................................................................................... 11 6.2 Selection of insulation materials ................................................................................................................. 11 6.3 Selection of cladding ......................................................................................................................................... 13 6.3.1 Metallic cladding................................................................................................................................................. 13 6.3.2 Non-metallic cladding ...................................................................................................................................... 14 6.4 Aluminium foils ................................................................................................................................................... 15 6.5 Sealers and sealing tape and gaskets ......................................................................................................... 15 6.6 Perforated guards .............................................................................................................................................. 15 6.7 Accessories ........................................................................................................................................................... 15 7 Design engineering ......................................................................................................................................... 16 7.1 Designing for insulation .................................................................................................................................. 16 7.1.1 Class 1: Heat conservation ............................................................................................................................. 17 7.1.2 Insulation systems with vapour barrier ................................................................................................... 17 7.1.3 Insulation of valves and flanges ................................................................................................................... 17 7.2 Calculation of insulation thickness ............................................................................................................. 18 7.2.1 Class 1,2,4 and 9 ................................................................................................................................................. 18 7.2.2 Class 3 ..................................................................................................................................................................... 18 7.2.3 Class 5 or F ............................................................................................................................................................ 18 7.2.4 Class 6, 7 and 8 .................................................................................................................................................... 19 7.3 Combination of insulation classes ............................................................................................................... 19 7.3.1 General.................................................................................................................................................................... 19 7.3.2 Thermal insulation and/or personnel protection combined with fire protection ................. 19 7.3.3 Thermal insulation and/or personnel protection combined with acoustic insulation......... 19 7.3.4 Fire protection combined with acoustic insulation ............................................................................. 19 NORSOK © 2018 iii NORSOK M-004:2018 7.3.5 Thermal insulation and/or personnel protection combined with fire protection and acoustic insulation ............................................................................................................................................. 19 8 Installation and inspection .......................................................................................................................... 20 8.1 General.................................................................................................................................................................... 20 8.1.1 Workmanship ...................................................................................................................................................... 20 8.1.2 Technical requirements................................................................................................................................... 20 8.1.3 Insulation with vapour barrier ..................................................................................................................... 20 8.2 Piping insulation................................................................................................................................................. 21 8.3 Vessel insulation ................................................................................................................................................. 21 8.3.1 Vessel insulation ................................................................................................................................................. 21 8.3.2 Segment insulation of vessel ......................................................................................................................... 21 8.4 Cladding ................................................................................................................................................................. 21 8.4.1 Metallic cladding................................................................................................................................................. 21 8.4.2 Non-metallic cladding ...................................................................................................................................... 22 8.4.3 GRP ........................................................................................................................................................................... 23 8.5 Flanges and valves ............................................................................................................................................. 23 8.5.1 General.................................................................................................................................................................... 23 8.5.2 Surface material for jackets ........................................................................................................................... 23 8.5.3 Insulation materials for prefabricated boxes ......................................................................................... 23 8.5.4 Insulation boxes with vapour barrier ........................................................................................................ 23 8.5.5 Locking mechanism........................................................................................................................................... 24 8.5.6 Identification ........................................................................................................................................................ 24 8.6 Non-contact insulation..................................................................................................................................... 24 8.7 Drainage ................................................................................................................................................................. 25 8.8 Instrument insulation....................................................................................................................................... 25 8.9 Sealing of penetrations .................................................................................................................................... 25 8.10 Inspection .............................................................................................................................................................. 25 Annex A (informative) Key data for insulation ............................................................................................... 26 Annex B (normative) Qualification of new products .................................................................................... 27 B.1 General.................................................................................................................................................................... 27 B.2 Testing .................................................................................................................................................................... 27 B.3 Documentation .................................................................................................................................................... 27 Annex C (informative) Test piece for site test ................................................................................................. 28 Annex D (normative) Material Data sheets (MDSs) ...................................................................................... 29 Bibliography ................................................................................................................................................................. 37 iv NORSOK © 2018 NORSOK M-004:2018 Foreword NORSOK M-004:2018 was adopted as NORSOK Standard 2018-12-23. NORSOK M-004:2018 supersedes NORSOK R-004 Rev. 3, August 2006. NORSOK is an acronym for the competitive position of the Norwegian continental shelf and comprise petroleum industry standards in Norway. The collaboration initiative in 1993 between the authorities and the petroleum industry initiated the development of NORSOK standards. Reducing the project execution time and developing and operating cost for petroleum installations on the Norwegian shelf was the target. The intention for the Petroleum industry is to develop and use standards providing good technical and cost-effective solutions to ensure that the petroleum resources are exploited and managed in the best possible way by the industry and the authorities. The industry will actively contribute to the development and use of international standards in the global market. The NORSOK standards shall: bridge the gap based on experiences from the Norwegian continental shelf where the international standards are unsatisfactorily; replace oil company specifications where possible; be available as references for the authorities’ regulations; be cost effective; and promote the Norwegian sector as an attractive area for investments and activities. Developing new NORSOK standards and regular maintenance of existing standards shall contribute to maintain the competitiveness both nationally and internationally for the Norwegian petroleum industry. The NORSOK standards are developed by experts from the Norwegian petroleum industry and approved according to the consensus principles as laid down by the guidelines given in NORSOK A-001 N directive. The NORSOK standards are owned by the Norwegian Oil and Gas Association, the Federation of Norwegian Industries and the Norwegian Shipowners' Association. They are managed and published by Standards Norway. Historically, piping and equipment insulation has been under the formal responsibility of NORSOK EG R Mechanical. Due to transfer of responsibility from NORSOK EG R Mechanical to NORSOK EG M Materials, the standard is re-issued as NORSOK M-004:2018, edition 1. The re-issuance of the standard also reflects a major revision and update of the standard itself. The update is based on industry experience over the last years. The major changes are listed as follows: - - the standard has been re-structured and rewritten. o Qualification requirements are included in a separate section. o Material requirements are included in a separate section. o Design engineering requirements are included in a separate section. o Installation and inspection requirements are included in a separate section. criteria for fire testing has been aligned with requirements in S-001 and best practise in the industry; NORSOK © 2018 v NORSOK M-004:2018 - - a sketch showing test piece for site test has been included as Annex C (informative annex); material data sheets for insulation materials, incl. GRP cladding, have been established and included as Annex D (normative); all references to relevant international standards have been reviewed and changed where convenient. Several changes are made; requirements for aerogel insulation materials have been included; requirements for polymer-based fire protection have been included; temperature definitions applicable for assessing personnel protection, material selection and vapour barrier are added; IPT requirements have been deleted; in general, selection criteria and selection possibilities are included in tables where convenient, and not as free text; reference to “Insulation Handbook” is removed. vi NORSOK © 2018 - - Annex A and C are informative. Annex B and D are normative. NORSOK M-004:2018 Introduction NORSOK M-004:2018 has been established by a working group nominated by NORSOK EG M (expert group for materials). The working group was represented by insulation suppliers, engineering and fabrication contractors, institutes and operators. The standard has been established based on consensus and covers Norwegian Petroleum industry requirements. The standard shall be used by the onshore and offshore Norwegian Petroleum industry. The standard specifies good technical and cost-effective solutions. The standard is relevant for: • • • • insulation suppliers – providing insulation systems complying with the standard; certification bodies, test laboratories –personnel qualifications and insulation system testing and qualifications; engineering and fabrication contractors – detail engineering and facilitating of insulation systems; operators – purchasing and maintenance of insulation systems. The standard covers insulation for piping and equipment for the following insulation purposes: • • • • thermal purposes; fire protection; acoustic protection; personnel protection. Additionally, the standard covers penetration seals through cellar decks, bulkheads, etc., for fire protection and explosion purposes. Corrosion under insulation (CUI) is a major challenge for onshore and offshore installations. In all life cycle phases, it is important to have high focus on how to minimize CUI, from design to decommission. NORSOK M-004 has strong relationship to NORSOK C-002, NORSOK M-001, NORSOK M-501, NORSOK S001 and NORSOK S-002. Where this standard refers to these standards, this standard shall be read and understood in conjunction with these standards. The corresponding annexes A and C are informative. Annexes B and D are normative. Normative text contains the requirements of the standard. Informative text is only guidance to the reader. All text in foreword, introduction and notes is informative text. Note to entries in section 3 and annexes to the document may be either normative or informative. The bibliography lists standards, norms, laws, regulations and other literature that may be relevant to the use of this document. NORSOK © 2018 vii NORSOK Standard NORSOK M-004:2018 Piping and equipment insulation 1 Scope This NORSOK standard covers the minimum requirements for insulation of pipes, equipment, vessels, tanks, valves, flanges, instrument tubing and penetrations for offshore/onshore installations. This standard covers thermal insulation, personnel protection, fire protection and acoustic protection. This standard is not intended for subsea installation. This NORSOK standard does not cover refractory or HVAC (heating, ventilation and air condition) related items. 2 Normative references The following referenced documents contain text which fully or in part is part of the requirements in the document. For dated references, only the edition cited applies. For undated references, the latest edition of the cited document applies (including amendments). NORSOK C-002, Architectural components and equipment Material selection NORSOK M-001, Surface preparation and protective coating NORSOK S-001, NORSOK S-002, Working environment ISO 178, Plastics- Determination of flexural properties NORSOK M-501, ISO 37, ISO 527, Technical Safety Rubber, vulcanized or thermoplastic – Determination of tensile stress-strain properties Plastics- Determination of tensile products ISO 834, Fire-resistance tests – Elements of building constructions – (all parts) ISO 5660-1, Reaction-to-fire tests – Heat release, smoke production and mass loss rate – Part 1: Heat release rate (cone calorimeter method) and smoke production rate (dynamic measurement) ISO 8497, Thermal insulation – Determination of steady-state thermal transmission properties of thermal insulation for circular pipes ISO 9865, Textiles – Determination of water repellency of fabrics by the Bundesmann rain shower test ISO 12944-9, Paints and vanishes – Corrosion protection of steel structures by protective paint systems – Part 9: Protective paint systems and laboratory performance test methods for offshore and related structures ISO 15665, Acoustics – Acoustics insulation for pipes, valves and flanges (including Corrigendum 1) ISO 9364, NORSOK © 2018 Continuous hot-dip aluminium/zinc-coated steel sheet of commercial, drawing and structural qualities 1 NORSOK M-004:2018 ISO 20340:2009, Paints and varnishes – Performance requirements for protective paint system for offshore and related structures ISO 80079-36, Explosive atmospheres – Part 36: Non-electrical equipment for explosive atmospheres – Basic method and requirements EN 823, Thermal-insulating products for building applications – Determination of thickness ISO 22899-1, Determination of the resistance to jet fires of passive fire protection materials – Part 1: General requirements EN 822, Thermal-insulating products for building applications – Determination of length and width EN 1363-2, Fire resistance test. Alternative and additional procedures EN 1608, Thermal-insulating products for building applications – Determination of tensile strength parallel to faces EN 10346, Continuously hot-dip coated steel flat product for cold forming EN 1604, Thermal-insulating products for building applications – Determination of dimensional stability under specified temperature and humidity conditions EN 1609, Thermal insulating products for building applications – Determination of shortterm water absorption by partial immersion EN 12086, Thermal insulating products for building applications – Determination of water vapour transmission properties. EN 12667, Thermal performance of building materials and products – Determination of thermal resistance by means of guarded hot plate and heat flow meter methods – Products of high and medium thermal resistance EN 12939, Thermal performance of building materials and products – Determination of thermal resistance by means of guarded hot plate and heat flow meter methods – Thick products of high and medium thermal resistance EN 13468, Thermal insulating products for building equipment and industrial installations – Determination of trace quantities of water-soluble chloride, fluoride, silicate, sodium ions and pH EN 13471:2001, Thermal insulating products for building equipment and industrial installations – Determination of the coefficient of thermal expansion EN 13472, Thermal insulating products for building equipment and industrial installations – Determination of short-term water absorption by partial immersion of preformed pipe insulation EN 13501-1:2007+A1 Fire classifications of construction products and building elements – Part 1: Classification using data from reaction to fire test EN 14303, Thermal insulation products for building equipment and industrial installations – Factory made mineral wool (MW) products – Specification EN 14305, Thermal insulation products for building equipment and industrial installations – Factory made cellular glass (CG) products – Specification EN 14707, Thermal insulating products for building equipment and industrial installations – Determination of maximum service temperature for preformed boxes EN 14304, Thermal insulation products for building equipment and industrial installations – Factory made flexible elastomeric foam (FEF) products – Specification EN 14706, Thermal insulating products for building equipment and industrial installations – Determination of maximum service temperature 2 NORSOK © 2018 NORSOK M-004:2018 EN 60332-1-1 Tests on electrical and optical fibre cables under fire conditions – Part 1-1 Tests for vertical flame propagation for a single insulated wire or cable – Apparatus EN 60332-1-3 Tests on electrical and optical fibre cables under fire conditions – Part 1-3 Tests for vertical flame propagation for a single insulated wire or cable – Procedure for determination of flaming droplets/particles EN 60332-1-2 EN ISO 12241, EN ISO 13787, ASTM C-201, Tests on electrical and optical fibre cables under fire conditions – Part 1-2 Tests for vertical flame propagation for a single insulated wire or cable – Procedure for 1 kW pre-mixed flame Thermal insulation for building equipment and industrial installations – Calculation rules Thermal insulation products for building equipment and industrial installations – Determination of declared thermal conductivity Standard Test Method for Thermal Conductivity of Refractories ASTM C1728, Standard Specification for Flexible Aerogel Insulation DNVGL-CP-0165, Cable and pipe penetrations ASTM-E662, IACS UR S14, IMO 2010 IMO 2010 IMO 2010 IMO 2010 NES 713, Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials Testing procedures of watertight compartments FTP Code Part 1 Non- combustibility test FTP Code Part 2 Smoke and toxicity test FTP Code Part 3 Test for "A", "B" and "F" Class Divisions FTP Code Part 5 Test for surface flammability Toxicity Test Apparatus Regulations Marine Equipment Directive, Directive No. 2014/90/EU PSA, The Facilities Regulations (Innretningsforskriften) PSA, EC, 3 Technical and Operational Regulations (Teknisk og operasjonell forskrift for landanlegg) Regulations No. 1272/2008 Terms and definitions In this document, the following terms and definitions apply. 3.1 shall (requirement) expression in the content of a document conveying objectively verifiable criteria to be fulfilled and from which no deviation is permitted if compliance with the document is to be claimed Note 1 to entry: clause 7.2 Table 3. NORSOK © 2018 Requirements are expressed using the verbal forms specified in ISO/IEC Directives, Part 2 3 NORSOK M-004:2018 3.2 should (recommendation) expression in the content of a document conveying a suggested possible choice or course of action deemed to be particularly suitable without necessarily mentioning or excluding others Note 1 to entry: Recommendations are expressed using the verbal forms specified in ISO/IEC Directives, Part 2 clause 7.3 Table 4. Note 2 to entry: In the negative form, a recommendation is the expression that a suggested possible choice or course of action is not preferred but it is not prohibited. 3.3 may (permission) expression in the content of a document conveying consent or liberty (or opportunity) to do something Note 1 to entry: clause 7.4 Table 5. Permissions are expressed using the verbal forms specified in ISO/IEC Directives Part 2 3.4 can (possibility and capability) 1: expression in the content of a document conveying expected or conceivable material, physical or causal outcome. 2: expression in the content of a document conveying the ability, fitness, or quality necessary to do or achieve a specified thing Note 1 to entry: Possibility and capability is expressed using the verbal forms specified in ISO/IEC Directives, Part 2 clause 7.5 Table 6. 3.5 temperature definitions Normal operating temperature: temperature during normal operation, including normal variations. Maximum operating temperature: maximum temperature including plant operation at unstable condition. Unstable condition includes start-up/ shutdown, control requirements and process upsets. Ambient temperature; temperature of the air surrounding the product to be insulated. The product might be a pipe, valve, vessel, etc. In this standard, the following temperature definitions applies: • personnel protection: normal operating temperature, Tn, shall be used for evaluation of the need for personnel protection; • vapour barrier: normal operating temperature, Tn, shall be used for evaluation of the need for vapour barrier. Material selection: maximum operating temperature, Tm, shall be used for insulation and cladding material selection. 3.6 indoor mechanically ventilated rooms 3.7 Company operating company, normally a company, ship/rig owner, contractor or subcontractor that is responsible for the facility 4 NORSOK © 2018 NORSOK M-004:2018 3.8 Insulation Class 1: Heat conservation The purpose is to reduce heat losses and to maintain temperatures for the efficient operation of the process. 3.9 Insulation Class 2: Cold medium conservation The purpose is to maintain low temperature and control heat input to the process. 3.10 Insulation Class 3: Personnel protection Protection of personnel from surfaces with temperatures below -10 °C or above 70 °C in normal operating conditions. 3.11 Insulation Class 4: Frost protection Insulation to prevent freezing, precipitation and inside condensation. 3.12 Insulation Class 5 and F: Fire protection The purpose is to reduce the heat input and secure that the temperature on piping, vessels and equipment is below the specified critical temperature when exposed to the specified fire scenario for the actual area of installation. Class F is used only for protection of pressurized flange connections if adjoining piping or equipment is not insulated, otherwise Class 5 alone shall be used. 3.13 Insulation class 6, 7 and 8; Acoustic insulation Acoustic insulation is specified in order to ensure that noise emission from piping, valves, flanges and equipment meets the area noise requirements for the working environment. The definition of the classes of acoustic insulation is as given in ISO 15665, Clause 4. This standard specifies the minimum insertion loss for each class related to the diameter of the pipe on which it is to be applied. Class 6 Minimum insertion loss shall be in accordance with the definition given in ISO 15665 for class A. Valves and flanges shall be insulated when and as required by Company. Class 7 Minimum insertion loss shall be in accordance with the definition given in ISO 15665 for class B. Flanges to be insulated. Valves to be insulated when and as required by Company. Class 8 Minimum insertion loss shall be in accordance with the definition given in ISO 15665 for class C. Valves and flanges shall be insulated. 3.14 Insulation Class 9: External condensation and icing protection The purpose is to prevent outside condensation on piping and equipment with normal operating temperatures below ambient. NORSOK © 2018 5 NORSOK M-004:2018 4 Symbols and abbreviations For this document, the following symbols and abbreviations apply. AG Aerogel AES Alkali Earth Silicate CG Cellular Glass ASTM CL CUI c/c DN EG M EG R EVA FEF FROSIO GRP HSE IACS IMO IPS American Society for Testing and Materials symbol of the declared level of soluble chlorides Corrosion under insulation centre/centre Diameter Nominal Expert Group Materials Expert Group Mechanical Ethylene-Vinyl Acetate Flexible Elastomeric Foam Faglig Råd for Opplæring og Sertifisering av Inspektører innen Overflatebehandling Glass fibre Reinforced Polyester Health, Safety and Environment International Association of Classification Societies (e.g. DNVGL, Lloyds, TÜV) International Maritime Organisation Insulation Procedure Specification ISO International Organization for Standardization MW Mineral Wool ITP Inspection and Test Plan OD Outer Diameter of Cladding PBFP Polymer Based Fire Protection P&ID PSA Piping & Instrument Diagram Petroleum Safety Authority (Petroleumstilsynet – PTIL) EN European Standard ST Service Temperature QC Tn Quality Control Normal operating temperature Tm Maximum operating temperature Wp symbol of the declared level for short-term water absorption Wlp pH RH 6 symbol of the declared level of long-term water absorption potential of Hydrogen Relative Humidity NORSOK © 2018 NORSOK M-004:2018 5 Qualification requirements 5.1 Qualification of personnel 5.1.1 Qualification of insulation fitters All operators shall be qualified. For each work team, minimum 50 % workers shall be qualified to tradesman level. Operators shall be qualified to tradesman level as insulation fitter. The remaining operators shall as minimum be qualified by a theoretical examination and practical site test, as given below. The test scheme shall be subject to Company approval. Company is entitled to be present during the test. Notification shall be sent min five working days in advance. Insulation contractors shall have a list of personnel that have passed the test, and this shall be available for the Company. The site test shall be carried out for each Contract or Project and shall reflect the actual scope of work. Guidance note: If agreed by Company, the site test can be omitted provided documented relevant site test. Prior to the theoretical examination test, the unskilled/semi-skilled operators shall have undergone relevant theoretical training, e.g. by class lessons. The theoretical examination test shall demonstrate relevant knowledge of health and safety hazard, use of protection equipment, insulation materials, application of insulation materials, insulation systems surface requirements, how to avoid corrosion under insulation and prevent ingress of moisture. The practical test shall be supervised by a qualified supervisor and examined by qualified QC personnel. The test shall be carried out with project specific insulation classes and materials according to IPS, on relevant parts of the test piece in Annex C. An examination certificate, with photo identification, shall be issued if the candidate passes the theoretical examination test and the practical test. The theoretical training, examination and practical test shall be documented. Inspection personnel shall have access to training, examination and practical test procedures. 5.1.2 Qualification of supervisors, foremen and QC personnel Personnel carrying out inspection or verification shall be qualified FROSIO Inspector level III, within insulation. FROSIO Inspector level II, may carry out the inspection work under the supervision of an inspector level III. Supervisors and foremen shall be qualified to tradesman level and shall have documented minimum 3 years’ experience with insulation work corresponding to work described in this standard. All QC- and supervision personnel shall be familiar with the requirements in this NORSOK standard. 5.2 Qualification of insulation system The insulation systems for the following applications shall be tested, documented and when required Type Approved/certified prior to any use: Class 5 and F: The selected fire protection system shall be tested and documented as described in Sec. 5.2.1; Class 6, 7 and 8: All materials shall be tested, and documented as described in Sec. 5.2.2; NORSOK © 2018 7 NORSOK M-004:2018 sealing penetrations in fire divisions shall be tested and Type Approved as described in Sec. 5.2.3. 5.2.1 Class 5 and F: Fire insulation Selected fire insulation system (including any removable jackets or boxes) shall be tested and properly documented in accordance with relevant requirements, e.g.: PSA requirements as stated in the Facilities Regulations (Innretningsforskriften) and the Technical and Operational Regulations (Teknisk og operasjonell forskrift for landanlegg) and NORSOK S-001 Technical Safety; pool fire testing – the testing shall be performed according to the method described in ISO 834-1. For a hydrocarbon pool fire, the standard time-temperature curve described in EN 1363-2 shall be used. Design criteria relevant for evaluation of acceptable fire resistance is given in the Design Accidental Load specification; jet-fire testing - insulation used for passive fire protection against a jet-fire shall be tested in accordance with the method described in ISO 22899-1. Depending upon the heat flux described in the Design Accidental Load specification modification of the heat load method might be necessary. Design criteria relevant for evaluation of acceptable fire resistance is given in the Design Accidental Load specification; explosion testing – there is no standardised method or system for explosion testing. However, explosion testing shall be carried out to document that the passive fire insulation systems resist the design accidental loads to which they may be exposed. The explosion testing should be instrumented to measure: o o o NOTE overpressure; flame arrival time; explosion loading response using strain gauges, displacement transducers, etc. Materials and systems already tested according to OTI 95634 can be accepted if agreed with Company Fire testing of pipe insulation, boxes and removable jackets shall ensure that all important design details are covered, e.g. inspection hatches, drains, end caps, joints and section overlaps. Tests shall be carried out on complete insulation system installed on a test piece on a relevant dimension, if not otherwise agreed with Company. 5.2.2 Class 6, 7 and 8: Acoustic insulation All systems shall be tested, and the insertion loss documented in accordance with the measurement procedure outlined in ISO 15665, Clause 10. 5.2.3 Sealing of penetrations Penetrations in fire divisions shall not reduce the fire and explosion integrity, stability or the temperature limitations of such divisions. 8 NORSOK © 2018 NORSOK M-004:2018 The installed penetration seal shall have an approved and valid certificate issued by recognized accredited registrar and classification society such as DNVGL or Lloyds. For A, B and F class additionally in accordance with the Marine equipment directive. Penetration seals shall be tested in same direction as intended installed. To be installed in both bulkhead and deck applications, the penetration seals shall be tested in both type of divisions. Additionally, separate testing is required for single pipes, multiple pipes and cable penetrations. The following requirements apply: penetration sealings for a hydrocarbon fire, “H” Class Division, shall be tested according to the method described in IMO 2010 FTP Code, part 3 with the following modifications: o o standard time-temperature curve found in EN 1363-2; acceptance criteria for hydrocarbon fire divisions are found in the Facilities Regulations. penetration sealings for a cellulosic fire shall be tested for compliance with IMO 2010 FTP Code Part 3 Test for "A", "B" and "F" Class Divisions; penetration sealing materials shall be tested for compliance with IMO 2010 FTP Code Part 2 and 5 or EN 13501-1:2007+A1. The following requirements apply (when relevant): jet fire testing according to ISO 22899-1 (see Guidance Note in 5.2.1); blast requirements specified in the Design Accidental Load specifications; water tightness according to DNVGL-CP-0165 Sec. 4.3 and IACS UR S14, Sec. 4.3. 5.3 Insulation procedure 5.3.1 Insulation procedure specification (IPS) A detailed IPS shall be established based on the requirements of this NORSOK standard, in addition to relevant project requirements. The IPS shall be approved by Company prior to installation. The IPS shall as a minimum contain following documents: detailed sketches, which shows the system build-up for each insulation class, including necessary details needed to fulfil the work (also for combination of systems); product data sheet for all type of materials; detailed drawings and necessary documentation for all type of removable insulation jackets or boxes for flanges and valves; for accessories such as rivets, adjustable ex-centre locks, bands, wires, clips, and breather springs etc., materials, thicknesses, dimension, type shall be specified. The IPS shall be followed during all insulation work. The following changes in the insulation application parameters requires the IPS to be re-approved: NORSOK © 2018 9 NORSOK M-004:2018 any change of insulation material and/or type of cladding; change of system build-up; change type/manufacture of removable insulation solutions. 5.3.2 Drawings for penetration seals Penetration seal manufacturer shall prepare typical installation drawings that show any required installation restrictions determined during the laboratory approval testing. These drawings shall be referenced on the type approval certificate. The seals shall be installed in accordance with these drawings. Drawings shall be included in the IPS and penetration dossier. According to NORSOK C-002 a penetration dossier shall be developed and include penetration for all areas on the installation. The drawings shall as a minimum contain the following information unless otherwise agreed with Company: fire rating A0/A60/H0/H60 etc; minimum and maximum frame (sleeve) dimensions; installation symmetry; maximum operation temperature; minimum and maximum pipe diameter; minimum distance between pipes (multiple); minimum distance between pipes and frame (sleeve); fire exposure side; relevant valid certificate references; any deviation from certificate; any requirement for insulation coat-back. 5.3.3 Inspection and test plan (ITP) Insulation contractor shall establish both an inspection and test plan (ITP) and an inspection log for the insulation works. The ITP shall reflect work during production, at delivery and all other pertinent phases. The ITP shall be approved by Company. 10 NORSOK © 2018 NORSOK M-004:2018 6 Materials 6.1 Environmentally requirements The insulation materials shall fulfil the following requirements: shall be tested according to IMO 2010 FTP Code Part 1 or EN 13501-1:2007+A1, for fire classification. Requirements for fire classification for different insulation materials are given in MDS for the materials; additional requirements regarding non-combustibility and prohibited substances and products are given in NORSOK S-001 and NORSOK S-002. 6.2 Selection of insulation materials In general, selection of insulation materials shall be in accordance with Table 1. Alternative insulation system and materials may be used if the proposed materials and methods satisfy the technical requirements in this NORSOK standard, see Annex B. All insulation material is subject to Company approval. Selection of insulation materials for instrument tubing from DN 10 to and including DN 32 is given in Table 2. Instrument tubing sizes above 32 mm shall be insulated as piping. Piping tubing shall be insulated as piping. Manufacturer of pre-insulated instrument tubes may be used pending approval by Company. Material data sheets for the following insulation materials are given in Annex D: Aerogel (AG); Alkali Earth Silicate (AES); Cellular Glass (CG); Flexible Elastomeric Foam (FEF); Mineral Wool (MW). NORSOK © 2018 11 NORSOK M-004:2018 Table 1 – Selection of insulation material Insulation class Normal operating Temperature Insulation material 1 - Aerogel, AES fibre, cellular glass or mineral wool 1), 2) 3 70 °C < Tn ≤ 150 °C Insulating coating or perforated guards 2 - 3 Tn ≥ 150 °C 4 Aerogel3) or Cellular glass Aerogel, AES fibre, cellular glass or mineral wool 1), 2) - Aerogel, cellular glass or mineral wool 1), 2) 6, 7, 8 - 9 - Aerogel, AES fibres, cellular glass or mineral wool 1, 2) as per qualified system 5 - Notes 1) 2) 3) Insulation/fire protection material in accordance with qualified system. Systems with mineral wool or AES fibres shall comply with note 1 Aerogel or cellular glass At Tn temperatures < 180 °C Mineral wool and AES fibres shall only be used as part of a non-contact insulation system or used as a secondary (outer layer) insulation material applied over e.g. aerogel or cellular glass. In dry rooms with no sprinkler/deluge system, mineral wool may be used directly on pipes/vessels with a normal operating temperature above +40 °C. Indoor areas with regular water cleaning or testing of seawater deluge system are not considered dry. For low temperature application, long term fit for use documentation relevant for onshore/offshore applications in Norway is not available. For low temperature applications, special consideration should be made. Not recommended for cryogenic (<- 80°C) temperatures. Table 2 – Selection of insulation material for instrument tubing (DN 10 mm to DN 32 mm) Normal operating Temperature Tn ≤ 110 °C 110 °C < Tn ≤ 180 °C Tn > 180 °C Notes 1) 2) 12 Insulation material FEF Mineral wool (MW) Cladding material Non-metallic cladding Non-metallic or metallic cladding Metallic cladding Surface temperature on heat tracing cables is to be checked prior to deciding material types for insulation of instrument tubing. Non-metallic cladding may be either separately applied onto the insulation material on site or may be factory applied to the insulation material. NORSOK © 2018 NORSOK M-004:2018 6.3 Selection of cladding Selection of cladding materials shall be in accordance with Table 3. Table 3 – Table 3 – Selection of cladding material Insulation class All, except class 5 or F Application Offshore SS316 Aluminium alloy AlMn1 GRP Non-metallic1) other than GRP Onshore 5 or F Notes 1) 2) Cladding material SS316 Aluminium alloy AlMn1 GRP Non-metallic1) other than GRP Aluzinc, AZ185 2) All Cladding to be tested and documented as part of the system Types of non-metallic cladding shall be subject to Company approval. Aluzinc is accepted for onshore applications providing: - No risk for corrosive environment/ atmosphere - Company approval. 6.3.1 Metallic cladding 6.3.1.1 Stainless steel Stainless steel metal cladding shall be type SS316, 2D finish and thickness according to table 4. Table 4 – Cladding thickness, SS316 Dimension, cladding SS316 2D sheet < OD 250 0,5 mm OD 250 – OD 900 0,7 mm > OD 900 0,9 mm 6.3.1.2 Aluminium alloy Aluminium alloy cladding shall be type AlMn1 (AA 3103) or equal corrosion resistance and thickness according to table 5. Table 5 – Cladding thickness, aluminium. Dimension, cladding Aluminium sheet NORSOK © 2018 ≤OD 450 0,7 mm > OD 450 0,9 mm 13 NORSOK M-004:2018 6.3.1.3 Aluzinc Aluzinc cladding shall be type hot dip coated steel with an alloy of zinc and aluminium to ISO 9364. Coating weight shall be 185 g/m². Thickness according to table 6. Table 6 – Cladding thickness, Aluzinc Dimension, cladding Aluzinc sheet ≤ OD 300 0,6 mm OD 300 – OD 1500 0,8 mm > OD 1500 1,0 mm 6.3.2 Non-metallic cladding Requirements in Table 7 shall be fulfilled for non-metallic cladding, except GRP. Table 7 provide minimum requirements for non-metallic cladding (flexible/soft or rigid/hard types) in terms of fire properties and aging. The table does not define mechanical properties, as these will depend on the actual product type. Mechanical properties such as tensile strength, elongation, tear resistance etc. as well as water vapour transmission/permeability shall be documented for the relevant product, and it is for the Company to decide if the material is fit for purpose for the actual application. GRP is covered by MDS GRP, see annex D. Table 7 – Table 7 – Requirements for non-metallic cladding. Property Test method Heat release ISO 5660-1 Smoke and toxicity IMO 2010 FTP code part 2 Flame spread/surface flammability Aging resistance Mechanical properties of material, including joint Water vapour transmission Decomposition Requirement Results to be provided for fire risk assessment IMO 2010 FTP code part 5 Pass IMO 2010 FTP code part 52) ISO 20340:2009/ISO 12944-9:2018, 4200 hours cyclic aging (UV, Salt spray and freezing)1 It shall be documented that the material (including system for joining) will maintain min. 90 % of its tensile strength/elongation properties after the accelerated aging EN 12086 Notes Pass IMO 2010 FTP code part 22) Shall be documented Shall be documented The material including system for joining shall not decompose at temperatures from –20 °C to 70 °C. 1) ISO 20340:2009 is withdrawn and is replaced by ISO 12944-9. Previous tests according to ISO 20340:2009 are acceptable. 2) Criteria for Bulkhead, wall and ceiling linings 14 NORSOK © 2018 NORSOK M-004:2018 Any possible shrinkage or temperature instability of the non-metallic cladding shall be documented. For factory applied non-metallic cladding used on FEF on instrument tubing (see Table 2), the tensile strength shall be minimum 4 MPa, tear strength shall be minimum 5 N/mm and elongation at break shall be minimum 150 %. 6.4 Aluminium foils For vapour barrier applications, the following shall apply: minimum aluminium foil thickness shall be 25 µm; minimum 10 µm polymer coating shall be applied on both sides of the aluminium foil; minimum total thickness shall be 45 µm. For heat tracing and/or coating protection and heat distribution applications, the following shall apply if aluminium foil is required by the electro discipline: minimum aluminium foil thickness shall be 45 µm. For wrapping of insulation materials used in insulation boxes and jackets, aluminium foil with polymer coating shall be used, minimum total thickness shall be 45 µm. 6.5 Sealers and sealing tape and gaskets Joint sealers and sealing tape and gaskets shall be permanently flexible through a relevant temperature range and shall be capable of withstanding repeated expansion and contraction. 6.6 Perforated guards Stainless steel perforated metal cladding shall be of type SS316 with 5 or 8 mm hole diameter and 8 or 12 mm hole pitch. Thickness shall be according to table 4 and the finish shall be 2B or 2D. Distance holders shall be made of polytetrafluorethylene (PTFE) or rubber. Minimum numbers of distance holders shall be three per circumferential location. Distance holders shall be installed with c/c maximum 300 mm in both longitudinal and circumferential direction. As an alternative to perforated guards, Company approved insulating coating can be applied. The application shall be in accordance with NORSOK M-501 and supplier's recommendation. 6.7 Accessories All metal accessories shall be of type SS316, except grommets for reinforced drain holes in tailor made jackets, which may be of brass. For aluminium cladding, special considerations shall be made. Stainless steel wire for securing of insulation shall be minimum 1.0 mm thick. NORSOK © 2018 15 NORSOK M-004:2018 Table 8 – Steel banding and locking clips Equipment Piping and equipment Vessels Notes Band width x thickness [mm x mm] 12 x 0,4 19 x 0,4 Clips length x width x thickness [mm x mm x mm] 1) 20 x 13 x 0,7 20 x 20 x 0,7 1) Clip type shall be Stainless Steel Closed Seals 7 Design engineering 7.1 Designing for insulation The extent of insulation and heat tracing shall be clearly shown on P&ID’s and piping isometrics. Insulation class and/or combination classes shall be denoted on the line label, according to the Company ENS (engineering numbering system). In case where multiple insulation classes cannot be shown in line label, the most stringent ones shall be given in line label. Additional classes may be denoted by note on the P&ID. All design shall allow for necessary space for insulation. Particular care shall be taken in piping design to ensure sufficiently long straight pipe runs around e.g. branches, bends, valves and supports, to enable proper installation of insulation. Insulation adjacent to flanges in piping and equipment shall be terminated to allow removal of bolts without damage to insulation. Minimum free space from the flange to the nearest part of the insulation shall be equal to the bolt length +25 mm. The termination of the weather protection shall not allow ingress of water. Insulated pipes and insulation boxes shall have a minimum 100 mm clearance from surroundings (parallel insulated/non-insulated lines, bends, tees, structural steel, cable and instrument tubing trays etc.). When a rigid type of insulation is used, provision shall be made for longitudinal expansion and contraction. Vessels of diameter 1 500 mm and smaller shall be insulated as piping when it comes to: support rings, ref. Sec. 8.3.1; cladding, ref. Sec. 8.4.1; steel band, ref. Sec. 6.7. However, the vessel shall have insulation installed to allow for inspection of doubling plates, ref. Sec. 8.11. Bolts on flanges on liquid nozzles from large vessels, more than 4 tons of hydrocarbon should be fire protected, see NORSOK S-001. Requirement for coating under insulation is given in NORSOK M-001. The coating system and application requirement shall be as specified in NORSOK M-501. 16 NORSOK © 2018 NORSOK M-004:2018 7.1.1 Class 1: Heat conservation For heat conservation class 1, except for steam services or when otherwise specified, the following shall not be insulated: vessel manhole, handhole covers, nozzles and flanges; exchanger nozzles and flanges; valves and piping flanges; control valves, line valves and fittings, which are to be removed periodically; expansion and rotation joint, slide valves and similar equipment. If the line has heat tracing the heat tracing cable must be protected in places without insulation. 7.1.2 Insulation systems with vapour barrier All insulation systems with normal operating temperatures below ambient shall have vapour barrier. Ambient temperature shall be calculated for each project. If normal operating temperature is alternating below and above ambient temperature, the requirement of vapour barrier shall be evaluated based on exposure time and temperature. To protect the vapour barrier, where metal sheet cladding is used, it shall be applied an additional layer of insulation/spacers. Minimum thickness of the insulation/spacers shall be the length of the screws/pop rivets or similar + 10mm. The type of insulation/spacers to be used is subject to Company approval. 7.1.3 Insulation of valves and flanges When choosing between removable insulation solutions, close attention must be paid to the geometry of the equipment, weather condition, mechanical impact, high pressure washing, use of chemicals, flare, available space and size. Tailor made jackets are only permitted for indoor applications, and only for insulation systems without vapour barrier. Tailor made jackets shall not be used for valves and flanges above DN400. Using jackets where there are sharp edges leads to wear and tear of the jacket. Bolts should be covered by plastic caps to protect the jackets. Removable insulation for flanges and valves, prefabricated insulation boxes, fire protection systems for bolts and nuts or tailor-made jackets shall be suitable for quick removal and reinstallation. For class 5 or F fire protection systems for bolts and nuts may be used, given that the flanges are part of system with emergency depressurisation capability and the fire protective properties are tested and documented in accordance with the depressurisation rate. Prefabricated insulation boxes, which shall be frequently subject for inspection or maintenance, shall be provided with an inspection hatch with toggle latches and gasket between the hatch and the cladding. The insulation shall be easily removable under the hatch. Inspection hatches shall be located where required by Company and shall be indicated on the fabrication isometric. Insulation boxes for valves and flanges etc. in vertical lines shall be designed with the “roof tile” principles on the upper section to prevent water ingress. For valves above DN 900 in all classes, except insulation systems requiring vapour barrier, insulation boxes with inspection hatches/doors shall be used. NORSOK © 2018 17 NORSOK M-004:2018 7.2 Calculation of insulation thickness 7.2.1 Class 1,2,4 and 9 For all thermal insulation classes, class 1,2,4 and 9, the insulation thickness shall be calculated in accordance with EN ISO 12241, and based upon project requirements for heat loss, energy input, etc. For thermal calculations on non-contact insulation systems, the annular gap/void provided by the spacer system shall be included as part of the outer pipe diameter in the calculations (pipe diameter for calculation = actual pipe diameter + 2 x gap/void). For flat surfaces the contribution of the gap/void can be ignored. 7.2.2 Class 3 Class 3 shall only be installed if the pipe or equipment are closer than 2,1 m vertically and 0,8 m horizontally to walkways and normal working areas. Guards as perforated SS316 plate, or alternatively insulating coatings, shall be used for normal operating temperatures between 70 °C and 150 °C. Insulation, as class 1, shall be used for normal operating temperatures above 150 °C. If perforated guards are used, the length of distance holders shall be according to Table 9. Table 9 – Length of distance holders Nominal pipe size (DN) Normal operating temperature (°C) 70˚C ≤ Tn ≤ 150˚C and Tn˂ -10 °C DN < 80 DN≥ 80 30 mm 50 mm Where insulating coating is used, the thickness shall be according to manufacturer documentation and recommendation. If insulation is used the insulation thickness shall be calculated in accordance with EN ISO 12241 based upon project design conditions to secure a surface temperature below 70 ˚C. 7.2.3 Class 5 or F For class 5 or F insulation, required insulation thickness, and combination of insulating materials, shall be determined based on relevant fire testing. The following shall be taken into consideration: extrapolations of test results are generally not acceptable. New systems or combination of materials shall be subject to relevant fire tests prior to acceptance. Extrapolation in the section factor dimension, i.e. material thickness versus surface area, is possible if the calculation model accounts for heat capacity in test specimen, and proper correlation between calculation model and tested results can be documented; type and duration of fire and explosion scenarios; properties of pipe work and vessel material (critical temperatures in piping materials); content of pipe work and vessel (critical temperature, operating temperature); depressurization time for the exposed system; properties of the insulating material. 18 NORSOK © 2018 NORSOK M-004:2018 For fire scenarios consisting of several fire loads (e.g. jet-fire or hydrocarbon-fire) the most stringent fire condition shall be used for selecting the fire protection solution. The most stringent fire condition is defined as that condition where the test specimen experiences the highest temperature rise for its respective fire load and duration. For combination of fire loads (e.g. jet-fire and hydrocarbon-fire) the total temperature rise can be estimated from a transient calculation model under the following circumstances: documentation of a proper correlation between calculated temperature and test results for at least two sampling points for all relevant fire loads; heat capacity in insulation materials are accounted for in calculation model; calculation model is to be approved by Company. 7.2.4 Class 6, 7 and 8 For acoustic insulation, the insulation thickness shall be according to the system tested. 7.3 Combination of insulation classes 7.3.1 General The guidelines below are given for insulation systems where insulation shall serve more than one purpose. Within the same installation one shall try to limit the number of pipe insulation systems by choosing alternative that provide combinations of sufficient personnel protection, heat insulation, cold medium conservation, fire protection and noise insulation when and as required. 7.3.2 Thermal insulation and/or personnel protection combined with fire protection Use the build-up for fire protection and if necessary increase the thickness of the insulation to fulfil the requirement for thermal insulation. If the thermal insulation requires vapour barrier, vapour barrier shall be added. 7.3.3 Thermal insulation and/or personnel protection combined with acoustic insulation Use the build-up for acoustic insulation and if necessary increase the thickness of the insulation to fulfil the requirement for thermal insulation. If the thermal insulation requires vapour barrier, vapour barrier shall be added. 7.3.4 Fire protection combined with acoustic insulation The build-up shall fulfil both the requirement for acoustic insulation and fire protection. 7.3.5 Thermal insulation and/or personnel protection combined with fire protection and acoustic insulation The build-up shall fulfil both the requirement for acoustic insulation and fire protection. If necessary increase the thickness of the insulation to fulfil the requirement for thermal insulation. If the thermal insulation requires vapour barrier, vapour barrier shall be added to the build-up. NORSOK © 2018 19 NORSOK M-004:2018 8 Installation and inspection This section covers general insulation requirements for the different insulation systems. For specific insulation materials, additional installation requirements are given in applicable Material Data Sheets, see Annex D. 8.1 General Piping and equipment shall be insulated according to the insulation classes, normal operating temperature and insulation thickness defined in the P&ID, piping isometric, data sheets and IPS. 8.1.1 Workmanship All insulation materials shall be stored in dry areas, and all insulation work shall be performed in dry conditions. All surfaces to be insulated shall be clean and dry. For application of sealers, tape and glue/ adhesive all surfaces shall be clean and dry, and surface temperature shall be min. 3°C above dew point. The insulation materials and the external cladding shall be installed in such a way that water does not enter the insulation material or between the insulation and the pipe/equipment surface during design life. Insulation on valves shall leave the packing gland accessible, except for class 5 or F where Company would specify the need for protection. Special attention shall be given for valves with vapour barrier. Class 5 and F shall be installed such that the fire performance is not affected by the specified design explosion loads. If insulation is applied prior to testing of pipe work, welds and joints shall be left un-insulated to allow inspection during testing. In cases where the insulation may be exposed to weather or dirt/moisture during this period, the insulation terminations at the joints shall be properly protected with temporary cladding until the insulation work is finalized. Insulation shall be installed to allow for inspection, i.e. typical inspection points (tag plates, welds on doubling plates on vessels etc.). Discontinued insulation work shall be properly covered to avoid damage and keep the insulation clean and dry. 8.1.2 Technical requirements All insulation shall be installed with tightly fitted and staggered joints. Voids within the insulation are not acceptable. Sharp edges are not allowed. 8.1.3 Insulation with vapour barrier Aluminium foils joint overlaps shall be minimum 50 mm. It is of vital importance that the vapour barrier is smoothly and firmly applied to the insulation such that it forms a fully vapour tight layer. For insulation class 2, items with complicated shape or areas with poor access, where a proper application of the aluminium foil used for vapour barrier cannot be obtained, a layer of mastic shall be applied on the outside of the insulation to ensure tightness of the vapour barrier. The mastic shall overlap the aluminium foil by at least 50 mm. Type of mastic shall be specified in IPS. 20 NORSOK © 2018 NORSOK M-004:2018 In order to avoid frost formation or condensation on pipe supports or protrusions/penetration the following apply: insulated prefabricated pipe supports shall be used; insulation and vapour barrier shall be extended with minimum length of 3 times insulation thickness on to the support/protrusion. 8.2 Piping insulation Insulation joints shall be butted firmly together, and the insulation shall be secured with glass fibre reinforced tape or stainless-steel band. Insulation shall be secured with bands over the outer layer at each side of radial joints and at the centre of each section and minimum c-c 250mm. Insulation on long vertical pipe runs shall be supported with rings spaced on 3 600 mm maximum centres installed on the piping. Width of rings shall be half the thickness of the insulation material and min 30 mm. On piping with vapour barrier, insulation covering on rings shall be minimum 2/3 of the insulation thickness. The rings shall be fastened to the piping as described in IPS. 8.3 Vessel insulation 8.3.1 Vessel insulation Insulation of all vessels shall be supported on rings with a distance of 900 mm c/c installed on the vessel. Rings shall also be provided around nozzles above DN 200 mm. The rings shall be fastened according to IPS. Insulation on vessel heads shall be fastened with bands spaced not more than 300 mm c/c. The bands shall be fixed to the fixing ring installed on the vessel. 8.3.2 Segment insulation of vessel No adhesive shall be used to bond segment insulation to the vessel. 8.3.2.1 Insulation with vapour barrier Where required, manholes and handholes shall be provided with removable covers of the same insulation thickness as the shell insulation. Covers shall be secured to the shell insulation and sealed to provide vapour tightness. Joint sealer shall be applied on all segment edges and in accordance with the manufacturer's recommendations. Termination of insulation on all layers, including contact surfaces where removable insulation covers are installed, shall be vapour sealed. 8.4 Cladding 8.4.1 Metallic cladding All cladding seams shall be installed by "roof tile" principle and the application of joint sealer shall be inside the cladding. NORSOK © 2018 21 NORSOK M-004:2018 Longitudinal seams of metal cladding on horizontal or sloping pipelines shall be located maximum 60 degrees away from the lowest point of the circumference. Longitudinal seams shall be overlapped 30 mm for OD < 150 mm, for OD ≥ 150 mm seams shall be overlapped 50 mm. Circumferential seams of metal cladding on horizontal or sloping pipelines shall be overlapped minimum 50 mm. Circumferential seams shall be crimped 50 mm from the edge on one side. For bends and vessel zeppelin, over and under crimps shall be used in the overlap. Metallic cladding for vessel insulation shall be edge crimped and overlapped 75 mm on longitudinal and circumferential seams. For hot insulation with operating temperature above 180 °C, the overlap shall be 100 mm. Head covers on vessels shall overlap shell covers by 100 mm. All seams on metallic cladding shall be provided with a sealant in between the overlap. Cladding shall be terminated with a fold, min 5 mm fold out, and gasket to prevent water ingress and galvanic corrosion. For terminations where there is no risk of water ingress (e.g. on the underside of vertically installed valve/flange boxes), terminations without fold and gaskets are acceptable. However, if the piping is uninsulated, a fold out with gasket is required to protect coated pipe from the 316 cladding of the box. The gap in the cut outs shall be 5-10 mm before gasket is installed and 3-5 mm after gasket is installed. Metallic cladding shall be built with a slope on top of vertical vessels and square tanks/containers with flat roof, min 10° incline. The bottom heads of skirt-supported vessels may be covered with flat metallic cladding. Removable insulation covers shall be provided for removable vessels heads. Metallic cladding shall be fastened with stainless steel bands. Only for difficult details (e.g. bends, T-pieces etc.) pop rivets or screws may be used. In cases where pop rivets are used, the rivet holes shall be predrilled prior to installation of cladding. If pre-drilling is impossible, the length of the drilling bit shall not exceed 6 mm. On vessel cladding, breather springs shall be used on bands, if required, for expansion. On vertical vessels and piping, "S" clips, minimum 0,7 mm, shall be used to keep the cladding sheets from sliding. Minimum four clips per seam. 8.4.2 Non-metallic cladding Use of combustible non-metallic cladding in enclosed areas shall be subject to written approval by Company related to HSE aspects. Application of non-metallic cladding shall be done in accordance with vendor's recommendations. Terminations against piping with a temperature above the maximum design temperature for the nonmetallic cladding shall be metallic cladding with sufficient length to avoid overheating of the nonmetallic cladding. 22 NORSOK © 2018 NORSOK M-004:2018 8.4.3 GRP GRP cladding shall be fastened with stainless steel bands as for metallic cladding. 8.5 Flanges and valves 8.5.1 General Insulation boxes and jackets mounted more than 2.5 meters above deck levels shall be secured by steel banding. Tailor made jackets shall fit the actual valve/flange/equipment and secure minimum 100 mm overlap to incoming insulated pipe. Valve and flange boxes in systems with vapour barrier shall be insulated without any air gaps between object and insulation, and fully sealed with a continuous vapour barrier. 8.5.2 Surface material for jackets Jacket surface material shall prevent water being absorbed by the insulation material. The material shall be suitable for use against design temperatures and shall have an adequate wear resistance to withstand frequent handling and normal tear and wear. It shall be tested for flame spread according to IMO 2010 FTP Code 5 equal to self-extinguishing properties, and for smoke and toxic gases according to IMO 2010 FTP Code 2. The cover, including seams, shall be weather tight according to ISO 9865. Guidance note: Materials already tested according to IACS UR S 14.4.4.3 can be accepted if agreed with Company Precautions shall be implemented in the design and fabrication of the jackets to prevent the insulation material from sagging causing reduction of the insulation properties. Jackets for flanges and valves shall be formed such that it sheds water. 8.5.3 Insulation materials for prefabricated boxes Precautions shall be implemented in the design and fabrication of the prefabricated boxes to prevent the insulation material from sagging causing reduction of the insulation properties. All insulation materials shall be totally wrapped in aluminium foil and fastened to the cladding when used in insulation boxes. 8.5.4 Insulation boxes with vapour barrier Due to the various shapes and design of valves and flanges, special attention shall be drawn towards the performance of the insulation work. The build-up of insulation shall be identical to the insulation on straight pipes. Where a perfect fit between the insulation and the valve is not possible, the void shall be filled with mineral wool. All cut outs shall be properly sealed and completely airtight. Insulation boxes shall have a fixed neck fastened to the box and secured around the pipe with band. NORSOK © 2018 23 NORSOK M-004:2018 8.5.5 Locking mechanism The locking mechanism of the tailor-made jackets shall be hook-and loop fastener type, minimum width 50 mm. The flat fastener type locking mechanism shall be located minimum 10 mm from the outer edge of any overlaps. Minimum width of overlap shall be 100 mm longitudinally for jackets applied on valves/flanges larger than DN 80, and 50 mm for jackets applied on valves/flanges DN 80 and smaller. Jackets for thermal-/acoustic insulation may be fastened to the pipe with nylon straps or equal, except in escape route areas where stainless steel bands shall be used. Jackets for fire insulation shall be secured with stainless steel bands. When steel bands are used for securing the jacket the steel band shall be protected to avoid cutting into the jackets. Adjustable and lockable ex-centre locks shall have safe working load of minimum 900 N, and each part of the lock to be fastened with minimum two pop rivets. Ex-centric locks shall be secured with safety pin. 8.5.6 Identification Each removable part of an insulation cover shall be provided with an identification plate in SS316 with the following information: vendor name; line number; tag number when relevant; part number and total number of parts, (e.g. part 1 of 3); design requirement (insulation class, fire requirements etc.). The identification number system shall be easily read prior to and after installation. The font shall be engraved with black colour and be UV resistant. The vendor shall identify each cover on drawings and store this information as retain documentation. If other cladding than SS316 is used, special consideration must be made to avoid galvanic corrosion. 8.6 Non-contact insulation The spacer system shall ensure an annular gap/void of min 12 mm between the steel surface and the insulation. Guidance note: In selection of material of spacers, both the risk of mechanical damage to the coating system and heat tracing and galvanic corrosion shall be considered. The spacers shall be installed according to the installation manual from Manufacturer and approved by Company. 24 NORSOK © 2018 NORSOK M-004:2018 8.7 Drainage For all insulation systems and insulation classes for piping and equipment there shall be minimum 10 mm diameter drain holes in all low points, and a minimum of one hole every 3 m on horizontal runs. Drain holes shall penetrate the whole insulation system (except for classes with vapour barrier). Necessary precaution shall be taken to avoid damage to the surface protection on the piping and heat tracing cables. For classes with vapour barrier, drain holes shall only be in the cladding. The drainage in class 5 or F shall be of approved type. For instrument tubing insulated with FEF drain holes are not required. Tailor made jackets and pre-shaped boxes shall be provided with drainage at its lowest point. 8.8 Instrument insulation For insulation of instruments, insulation boxes with inspection window should be used. 8.9 Sealing of penetrations Penetration seals installed, including the materials and method of assembly, shall be equal to detail drawings referred to in the approval test certificates. Penetration seals shall be installed in the same orientation as tested. To be installed in both bulkhead and deck application, the penetration seal shall be tested in both type of divisions and, in addition, for both single pipe and multiple pipe and cable penetrations. The minimum and maximum size (length x width, cross sectional area or diameter) shall not exceed the restrictions specified in the test certificate. Steel frame (sleeve) may be of carbon steel, galvanized steel or stainless steel regardless of type of steel used in laboratory test. Steel frame (sleeve) that was welded to the test assembly shall be welded. When bolted to the test assembly it may be either bolted or welded. Penetration seals shall be installed in the same manner and with the same type of insulation on the seal that was used in the type approval certificate. However, the insulation applied to the bulkhead or deck being penetrated to make a fire division may be of any approved insulation, which meets the fire requirements. Penetration seals that were tested with the sealing located entirely on the exposed/unexposed side shall be installed in the same way. Steel frame (sleeve) that was tested symmetrically shall be installed with approximately equal parts on each side of the division. 8.10 Inspection Work during production, at delivery and all other pertinent phases, shall be duly inspected and documented with an inspection log. This log shall be available for the Company. Personnel carrying out inspection or verification shall have access to workshop and personnel. Inspection shall be carried out at each stage of the work, but as a minimum before the second layer is installed, after installation of vapour barrier, plus before and after cladding is applied. NORSOK © 2018 25 NORSOK M-004:2018 Annex A (informative) Key data for insulation Insulation class Insulation materials Cladding Material 3),4) Class 1 Heat conservation Aerogel, AES fibre, cellular glass mineral wool 1) SS316, aluminium AlMn1, GRP or non-metallic (other than GRP) Class 3 Personnel protection At Tn≤ 150ºC Perforated guards or insulating coating. At Tn > 150ºC as class 1. Where relevant as class 1. Class 5 or F Fire protection Insulation/fire protection In accordance with the material in accordance qualified system with qualified system. Class 2 Cold medium conservation Class 4 Frost protection Class 6, 7 and 8 Acoustic insulation Class 9 External condensation and icing protection Aerogel Cellular glass Other comments SS316, aluminium AlMn1, Vapour barrier, see 6.4 and 7.1.2. GRP or non-metallic (other than GRP) Aerogel, cellular glass mineral wool 1) SS316, aluminium AlMn1, Vapour barrier, see 6.4 and 7.1.2. GRP or non-metallic (other than GRP) Aerogel, AES fibres, cellular glass or mineral wool 1) as per qualified system SS316, aluminium AlMn1, Shall be installed in accordance with GRP or non-metallic the tested/qualified system (other than GRP) in accordance with the qualified system Aerogel, cellular glass The system selection is dependent on the actual protection requirement and shall be accepted in writing by client for each case. SS316, aluminium AlMn1, Vapour barrier, see 6.4 and 7.1.2. GRP or non-metallic (other than GRP) Notes 1) 2) 3) 4) 26 At Tn < 180 °C Mineral wool and AES fibres shall only be used as part of a non-contact insulation system, or used as a secondary (outer layer) insulation material applied over e.g. aerogel or cellular glass. In dry rooms with no sprinkler/deluge system, mineral wool may be used directly on pipes/vessels with a normal operating temperature above +40 °C. Indoor areas with regular water cleaning or testing of seawater deluge system are not considered dry. Use of non-metallic cladding shall be subject to Company approval Aluzinc, AZ185, cladding material may be used onshore, see 6.3 NORSOK © 2018 NORSOK M-004:2018 Annex B (normative) Qualification of new products B.1 General This clause lists additional requirements for testing and documentation for qualifying of new products developed for piping and equipment insulation purposes. B.2 Testing B.2.1 Testing of technical properties All products shall be tested for technical properties by an external third-party institute or accredited laboratory. The test shall be relevant and in accordance with insulation classes described in this NORSOK standard. B.2.2 Life cycle test All products shall be tested for life cycle properties by an external third-party Institute or accredited laboratory. Test methods and acceptance criteria shall be agreed with Company. The test shall be relevant and in accordance with the products strain and stress exposure and in relevance to products expected life cycle. B.3 Documentation The supplier shall prove that the products technical properties (see Table B.1) are in accordance with, and fulfil, requirements described for insulation classes in this NORSOK standard, or another specific project requirements. Table B.1 — Declaration of technical properties Property Requirement Test method Length Always declare nom. incl. tolerance EN 822 Thickness Always declare nom. incl. tolerance EN 823 Width Dimensional stability Reaction to fire Maximum ST (+) Thermal conductivity, λD Always declare nom. incl. tolerance Rel. dimensional changes < 1 % Always declared Always to be declared Determined and verified in accordance with EN ISO 13787 EN 822 EN 1604 EN 13501-1:2007+A1 or IMO 2010 FTP Code Part 1 EN 14706 / EN 14707 EN 12667, EN 12939 or ISO 8497 Tensile strength parallel to faces (handling property) ≥ 2 x weight of product EN 1608 Trace quantities of water soluble ions and the pH-value CL: to be declared pH: neutral to slightly alkaline EN 13468 Water absorption (Wp) < 1 kg/m2 EN 1609 / EN 13472 The documentation shall be in written format, i.e. rapport, from an external third-party Institute or accredited laboratory. NORSOK © 2018 27 NORSOK M-004:2018 Annex C (informative) Test piece for site test 28 NORSOK © 2018 NORSOK M-004:2018 Annex D (normative) Material Data sheets (MDSs) The materials shall be delivered in accordance with the standard referred to in the MDS’. In addition, the MDS’ specify the selected options in the referred standard and additional requirements which shall be added or supersede the corresponding requirements in the referred standard. Provided the MDS’ do not specify any additional requirements all the requirements of the referred standard apply. The latest edition of the referred standard shall apply unless a specific year of issue is specified by the purchaser. NORSOK © 2018 29 NORSOK M-004:2018 MATERIAL DATA SHEET MDS AES Rev. 1 TYPE OF MATERIAL: Alkali Earth Silicate (AES) General Products Application Standard This specification describes the minimum requirements for AES materials. Products shall meet the requirements for bio-soluble fibres in Note Q of Regulation (EC) No. 1272/2008. AES insulation products are supplied in slabs and blankets. AES can be used for all classes, except class 2 and 9. NA MATERIAL DATA AND PROPERTIES Thermal conductivity Shall be measured and declared according to ASTM C-201 or EN 12667 and fulfil the requirement in the table below. Thermal conductivity, λD (max value) temp. °C λD - W/mk Reaction to fire Max. service temperature EN 14706 200 0,05 400 0,09 1 kg/m2 Trace quantities of water soluble CL EN 13468 < 10 mg/kg pH-value: EN 13468 INSTALLATION REQUIREMENTS General 0,19 1000 0,25 Maximum service temperature, ST (+), shall be declared EN 1609 EN 13471:2001 0,13 800 Class A1 according to EN 13501-1:2007+A1 or non-combustible according to IMO 2010 FTP Code Part 1. If supplied with surface covering the cover shall meet the requirements according to IMO 2010 FTP Code Part 5. Short-term water absorption: Coefficient of thermal expansion, 600 TE: < 1 % Neutral Installation according to installation manual from Manufacturer and project specific requirements. For classes 5, 6, 7 and 8, installation shall be done as described in the relevant test reports/installation instructions for the qualified systems. 30 NORSOK © 2018 NORSOK M-004:2018 MATERIAL DATA SHEET MDS AG Rev. 1 TYPE OF MATERIAL: Aerogel (AG) General This MDS specifies the selected options in the referred standard and additional requirements which shall be added or supersede the corresponding requirements in the referred standard. Products Blankets Application Aerogel can be used for all insulation classes. Standard ASTM C1728 MATERIAL DATA AND PROPERTIES Acceptance criteria Type I: Grade 1B Type III: Grade 1A and 2A Additional requirements Reaction to fire: Min Class B-s1, d0 according to EN 13501-1:2007+A1, or non-combustible according to IMO 2010 FTP Code Part 1. General Installation according to installation manual from Manufacturer and project specific requirements. Installation requirements For classes 5, 6, 7 and 8, installation shall be done as described in the relevant test reports/installation instructions for the qualified systems. NORSOK © 2018 31 NORSOK M-004:2018 MATERIAL DATA SHEET MDS CG Rev. 1 TYPE OF MATERIAL: Cellular glass (CG) General Products Application Standard This MDS specifies the selected options in the referred standard and additional requirements which shall be added or supersede the corresponding requirements in the referred standard. Cellular glass insulation products are supplied as prefabricated piping and equipment elements/sections. The product shall be delivered with anti-abrasive coating if used directly on piping/equipment. CG can be used for all insulation classes. For temperature above +180 °C an outside reinforcement mesh/coating shall be used. EN 14305 MATERIAL DATA AND PROPERTIES Thermal conductivity Ref. EN 14305 Sec. 4.2.1. The following thermal conductivity shall apply: Thermal conductivity, λD (max value) Temp. °C -180 °C -150 °C -120 °C λD - W/mk 0.020 Reaction to fire Other requirements 0.022 EN 14305 Sec. 4.2.4. EN 14305 Sec. 4.3.2 32 0.041 +40 °C 0.046 +80 °C 0.054 +120 °C +180 °C +240 °C 0.061 0.075 0.090 Class A1 according to EN 13501-1:2007+A1, or non-combustible according to IMO 2010 FTP Code Part 1. Maximum service temperature, ST (+), shall be declared Water vapour diffusion resistance: μ ≈ ∞ INSTALLATION REQUIREMENTS CG with non-metallic cladding 0.040 +10 °C EN 14305 Sec. 4.3.11 EN 14305 Sec. C.6 Vessel 0.034 +0 °C Minimum service temperature, ST (-), shall be declared EN 14305 Sec. 4.3.12 Piping 0.029 -40 °C EN 14305 Sec. 4.3.3 EN 14305 Sec. 4.3.10 General 0.025 -80°C Short term/long term water absorption: Wp and Wlp Trace quantities of water soluble chlorides (Cl): ≤ 2 mg/kg and the pH-value shall be neutral to slightly alkaline Coefficient of thermal expansion/contraction to be declared Installation according to installation manual from Manufacturer and project specific requirements. For classes 5, 6, 7 and 8, installation shall be done as described in the relevant test reports/installation instructions for the qualified systems. Anti-abrasive coating shall be used to prevent damage to cellular glass and coating systems. The anti-abrasive coating shall be completely dry before the insulation material is mounted. The anti-abrasive coating shall be suitable at maximum operation temperatures. Amount of wet applied anti-abrasive coating shall be used to effectively ensure sufficiently smooth surface finish. CG shall be prefabricated as pipe insulation elements according to dimensions and shape. To cover fittings and other irregular surfaces, sections may be cut and fitted on site. Min. thickness up to DN150 shall be 30 mm. Above DN150, min. thickness shall be 40 mm. CG vessel (DN200) segments shall be mechanically fastened and tightened with metal bands. For ≤DN150 segments glass fibre reinforced tape shall be used. Prefabricated CG with factory applied non-metallic cladding shall be joint sealed with suppliers recommended sealant. NORSOK © 2018 NORSOK M-004:2018 MATERIAL DATA SHEET MDS FEF Rev. 1 TYPE OF MATERIAL: Flexible Elastomeric Foam (FEF) General This MDS specifies the selected options in the referred standard and additional requirements which shall be added or supersede the corresponding requirements in the referred standard. Products Flexible Elastomeric Foam products with or without factory -applied non-metallic cladding are delivered in prefabricated pipe section, rolls and slabs. Application FEF can be used for instrument tubing with diameter DN≤ 32 mm for all insulation classes, for temperatures ≤ 110 °C. Standard EN 14304 MATERIAL DATA AND PROPERTIES Thermal conductivity Ref. EN 14304 Sec. 4.2.1. The following thermal conductivity values shall apply: Thermal conductivity λD (Max value) Mean temp. °C -50 -30 Reaction to fire EN 14304 Sec. 4.2.4 FEF Reaction to Fire (RtF) to be declared depending on type of FEF and factory applied surface covering. Tubes: DL-s3-d0 Additional requirements EN 14304 Sec. 4.3.2 Maximum service temperature ST (+) shall be declared EN 14304 Sec. 4.3.5 Water vapour diffusion resistance: λ - W/mK 0.035 EN 14304 Sec. 4.3.3 EN 14304 Sec. 4.3.6 INSTALLATION REQUIREMENTS General 0.038 -20 0.038 0 0.040 10 0.041 20 0.042 40 0.045 70 0.051 85 0.048 Minimum service temperature ST (-) shall be declared T ≤ 10 ⁰C: μ > 4000 T > 10 ⁰C: μ > 2000 Trace quantities of water soluble ions (Cl- to be declared) and the pH-value shall be declared Installation according to installation manual from Manufacturer and project specific requirements. For classes 5, 6, 7 and 8, installation shall be done as described in the relevant test reports/installation instructions for the qualified systems. NORSOK © 2018 33 NORSOK M-004:2018 MATERIAL DATA SHEET MDS MW Rev. 1 TYPE OF MATERIAL: Mineral wool (MW) General Products Standard Application This MDS specifies the selected options in the referred standard and additional requirements which shall be added or supersede the corresponding requirements in the referred standard. Products shall meet the requirements for bio-soluble fibres in Note Q of Regulation (EC) No. 1272/2008. Mineral wool products are supplied as mandrel wound pipe sections, wired mats, mats and slabs. Wired mats shall be supplied with stainless steel (SS304) stitching wire and mesh. EN 14303 All insulation classes except class 2 and 9. At temperatures < 180⁰C MW shall only be used as part of a non-contact insulation system or used as a secondary (outer layer) insulation material, applied over e.g. cellular glass or aerogel. MATERIAL DATA AND PROPERTIES Thermal conductivity Ref. EN 14303 Sec. 4.2.1. The following thermal conductivity values shall apply: Thermal conductivity, λD (max value) temp. °C λD - W/mk 10 0.038 50 0.043 100 0.047 150 0.057 200 0.070 300 400 0.100 0.154 Reaction to fire EN 14303 Sec. 4.2.4 Additional requirements EN 14303 Sec. 4.3.2 Maximum service temperature ST (+) shall be declared EN 14303 Sec. 4.3.7 Trace quantities of water soluble chloride (Cl-) shall be < 10 mg/kg2, and the pH-value shall be neutral to slightly alkaline. EN 14303 Sec. 4.3.5 INSTALLATION REQUIREMENTS General Class A1 according to EN 13501-1:2007+A1 or non-combustible according to IMO 2010 FTP Code Part 1. With surface covering: Class A2-s1, d0, according to EN 13501-1:2007+A1 or according to IMO 2010 FTP Code Part 2 and 5. Short-term water absorption, Wp Installation according to installation manual from Manufacturer and project specific requirements. For classes 5, 6, 7 and 8, installation shall be done as described in the relevant test reports/installation instructions for the qualified systems. 34 NORSOK © 2018 NORSOK M-004:2018 MATERIAL DATA SHEET MDS GRP Rev. 1 TYPE OF MATERIAL: Weather resistant glass fibre reinforced polyester (GRP) cladding General This specification describes the minimum requirements for a GRP for cladding purposes. Standard NA Products Application Laminate based on glass fibre reinforced polyester and/or vinyl ester resins. The material can be supplied as prefabricated shells or as wet material by curing on site. GRP is used for external areas subjected to mechanical loads or where a water tight cladding is required. MATERIAL DATA AND PROPERTIES General requirements Maximum material temperature resistance: ≥ 90⁰C Layer thickness: ≥ 1,5 mm ISO 178 Bending strength: ≥ 130 MPa ISO 527 Elongation at break: ≥ 1 % ISO 527 Reaction to fire Aging test Additional requirements General Notes 1) Tensile strength: ≥ 50 MPa Shall meet the requirements for surface flammability and smoke and toxicity according to IMO 2010 FTP Code Part 2 and Part 5. Part 5 of this test should be conducted over a relevant insulation substrate in order to demonstrate system performance. ISO 12944-9 (cyclic test) It shall be documented that the material (including system for joining) will maintain min. 90 % of its tensile strength/elongation properties after the accelerated aging. The GRP can be tested with or without a UV durable topcoat. Depending on design life and risk for direct sunlight exposure, GRP may be required protected by a UV durable topcoat, with quality in line with topcoat in system 1 (NORSOK M-501). The coating can be pre-applied to the prefabricated shells or site applied. GRP shall be antistatic and fulfil the requirements in ISO 80079-36 Annex D (except high voltage spray electrode test) 1). Installation according to installation manual from Manufacturer and project specific requirements. Material already tested according to EN13463-1 can be accepted if agreed with Company NORSOK © 2018 35 NORSOK M-004:2018 MATERIAL DATA SHEET MDS Polymer-Based Fire Protection (PBFP) Rev. 1 TYPE OF MATERIAL: Flexible EVA Polymer General Products Flexible polymer-based fire protection supplied on rolls, sheets, or in extruded/moulded form Application PBFP can be used for insulation Class 5 or F, or any other insulation classes in combination with Class 5 or F Standard NA MATERIAL DATA AND PROPERTIES Reaction to fire A polymer that utilizes endothermic reaction processes to change state from a flexible polymer in to a micro-porous ceramic state Flame propagation shall be tested according to EN 60332-1-1. Accept criteria according to NEK-EN 60332-1-2, Annex A. Flaming droplets/particles shall be tested according to NEK-EN 60332-1-3. Accept criteria according to NEK-EN 60332-1-3, Annex A. Additional requirements Maximum continuous service temperature ST (+) shall be declared. For higher continuous operating temperatures, a thermal layer is required underneath the PBFP in order to reduce the temperature to ST (+). Minimum continuous service temperature ST (-) shall be declared. For lower temperatures, a thermal layer is needed underneath the PBFP in order to increase the temperature to ST (-). EN 1609 Below 0,05 for both semi/fully submerged NES 713 Toxicity Index reading below 1,2 ASTM E662 INSTALLATION REQUIREMENTS General Piping Vessels 36 Above 85% Installation according to installation manual from Manufacturer and project specific requirements. For Class 5 or F, or combined insulation including Class 5 or F, installation shall be done as described in the relevant test reports/installation manuals for the qualified systems. SS316 metal cladding shall be used on top of PBFP and fastened with metal banding and pop rivets, according to tested system. SS316 metal cladding shall be used on top of PBFP and fastened with metal banding and pop rivets, according to tested system. NORSOK © 2018 NORSOK M-004:2018 Bibliography Standards and norms [1] [2] OTI 95634:1996, Jet-fire resistance test of passive fire protection materials EN 13463-1:2009, Non-electrical equipment indented for use in potentially explosive atmospheres NORSOK © 2018 37 This NORSOK standard is developed with broad petroleum industry participation by interested parties in the Norwegian petroleum industry and is owned by the Norwegian petroleum industry represented by the Norwegian Oil and Gas Association, the Federation of Norwegian Industries and the Norwegian Shipowners’ Association. Please note that whilst every effort has been made to ensure the accuracy of this NORSOK standard, neither the Norwegian Oil and Gas Association, the Federation of Norwegian Industries nor the Norwegian Shipowners’ Association, or any of their members will assume liability for any use thereof. Standards Norway is responsible for the administration and publication of this standard. Standards Norway P.O. Box 242 NO-1326 Lysaker Norway Standard Online AS P.O. Box 252 NO-1326 Lysaker Norway petroleum@standard.no salg@standard.no Tel. +47 67 83 86 00 Tel. +47 67 83 87 00 www.standard.no/petroleum Visiting address: Mustads vei 1 NO-0283 Oslo
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )