Lecture 9: Transformer Department of Electrical Engineering National Institute of Technology Rourkela EE1000: Basic Electrical Engineering 1 / 93 Outline 1. Goals of the lesson 2. Introduction 2 / 93 Goals of the lesson After going through the lesson, you shall get a broad idea of the following: • two winding ideal transformer, its properties and working principle under no load condition as well as under load condition. • How to draw phasor diagram under no load and load conditions. 3 / 93 Introduction • The transformer is a device, or machine, that transfers electrical energy from one electrical circuit to another electrical circuit through the medium of magnetic field and without a change in the frequency. • The electric circuit which receives energy from the supply mains called primary winding and the other circuit which delivers electric energy to the load is called secondary winding. • If the secondary winding has more turns than the primary winding, then the secondary voltage is higher than the primary voltage and the transformer is called a step-up transformer. • In case the secondary winding has less turns than the primary winding, then the secondary voltage is lower than the primary voltage and the transformer is called a step-down transformer. 4 / 93 A typical Transformer Figure 1: A typical Transformer 5 / 93 Principle of Transformer Action • A transformer works on the principle of electromagnetic induction. According to this principle, an emf is induced in a coil if it links a changing flux. • The primary winding P is connected to an alternating voltage source, therefore, an alternating current Iϕ starts flowing through N1 turns. • The alternating mmf N1 Iϕ sets up alternating flux ϕ which is confined to the high permeability iron path as indicated in the Fig. • The alternating flux induces voltage E1 in the primary P and E2 in the secondary S. If the load is connected across the secondary, a load current starts flowing. 6 / 93 Ideal Transformer In the beginning, a transformer is assumed to be a ideal one. For a transformer to be ideal one, the various assumptions are as follows • Primary and secondary windings has no resistance. • All the flux produced by the primary links the secondary winding i,e., there is no leakage flux. • Permeability µr of the core is infinitely large. In other words, to establish flux in the core vanishingly small (or zero) current is required. • Core loss comprising of eddy current and hysteresis losses are neglected. 7 / 93 Analysis of Ideal Transformer • Let the voltage V1 applied to the primary of a transformer, with secondary open circuited, be sinusoidal. • Then the current Iϕ , due to applied voltage V1 , will also be a sine wave. Then mmf N1 Iϕ and therefore, the core flux ϕ will follow the variations of Iϕ very closely. • Therefore, if the applied voltage V1 has sine waveform, the flux ϕ must also have a sine waveform. Let the sinusoidal variation of flux ϕ be expressed as ϕ = ϕmax sin ωt, where ϕmax is the maximum value of the magnetic flux in weber and ω = 2πf , is the angular frequency in rad/sec and f is the supply frequency in Hz. Figure 2: Ideal Transformer 8 / 93 Analysis of Ideal Transformer • The emf e1 in volts, induced in the primary N1 turns by the alternating flux is given by dϕ dt = −N1 ωϕmax cos ωt e1 = −N1 = N1 ωϕmax sin(ωt − π π ) = E1max sin(ωt − ) 2 2 where E1max = N1 ωϕmax . • RMS value of emf E1 induced in primary winding is given by E1max E1 = √ 2 2πfN1 ϕmax √ = 2 √ = 2πfN1 ϕmax 9 / 93 Analysis of Ideal Transformer • The current Iϕ in the primary is assumed to flow along the path abcda. The emf e1 induced in N1 turns must be in such a direction as to oppose the cause, i.e., Iϕ ; as per Lenz’s Law. • Therefore, the direction of e1 is as shown by the arrows in the primary N1 turns and it is seen to oppose v1 . Since primary winding resistance is negligible, e1 at every instant, must be equal and oppositive to v1 . v1 = −e1 = N1 dϕ dt orV1 = −E1 10 / 93 Analysis of Ideal Transformer • The emf induced in the secondary is dϕ dt = −N2 ωϕmax cos ωt e2 = −N2 = N2 ωϕmax sin(ωt − π π ) = E2max sin(ωt − ) 2 2 where E2max = N2 ωϕmax . • RMS value of emf E2 induced in secondary winding is given by E2max E2 = √ 2 2πfN2 ϕmax √ = 2 √ = 2πfN2 ϕmax 11 / 93 Analysis of Ideal Transformer • E1 N1 = E2 N2 √ E1 E2 ∴ = = 2πf ϕmax N1 N2 ∴ emf per turn in primary= emf per turn in the secondary • Assuming no loss, V2 V1 = N1 N2 V1 N1 = =k V2 N2 12 / 93 Analysis of Ideal Transformer ∴ V2 = V1 k k < 1 ⇒ step-up transformer and k > 1 ⇒ step-down transformer. when a load is connected across the secondary winding, a current I2 flows. In an ideal transformer losses are neglected and a transformer is considered to be 100% efficient. Hence primary and secondary volt-amperes are equal, i.e., V1 I1 = V2 I2 I2 N1 V1 = = =k ∴ V2 I1 N2 The rating of transformer is stated in terms of the volt-amperes that it can transform with out overheating. Transformer rating is either V1 I1 or V2 I2 (where I2 is the full-load secondary 13 / 93 Example Problem • An ideal transformer has turns ration 8 : 1 and the primary current is 3 Amp when it is supplied at 240 volt. Calculate the secondary voltage and current. 14 / 93 Example Problem • A 5 kVA, 1ϕ transformer has turns ration 10 : 1 and is fed from a 2.5kV supply. Neglecting losses, determine (1) the full-load secondary current (2) the minimum load resistance which can be connected across the secondary winding to give full load kVA. (3) primary current at full load kVA. 15 / 93 Phasor Diagram of Ideal Transformer • Iϕ and ϕ they are in same phase. • Here N1 and N2 are assumed equal for convenience and therefor E1 = E2 . • From the equations, they are lagging behind the current Iϕ by 90◦ . • The applied voltage V1 is equal and opposite to E1 and it is drawn opposite to E1 . Figure 3: Phasor diagram 16 / 93 No Load Phasor Diagram for a Practical Transformer • The no load current I0 , taken by the primary consists of two components: • A reactive or magnetizing component, Im , producing the flux and therefore in phase with the ϕ. • An active or power component, Ic , supplying the hysteresis and eddycurrent losses in the core and the negligible I 2 R loss in the primary winding. Component Ic is in phase with the applied voltage, i.e.Ic V1 = core loss. This component is usually very small compared with Im , so that the no-load power factor is very low. • Power factor on no load is cos ϕ0 = IIc . Figure 4: Phasor diagram 0 17 / 93 Example Problem • The emf per turn for a single phase, 2310/220V, 50 Hz transformer is approximately 13V. Calculate (a) the number of primary and secondary turns (b) the net cross-sectional area of core, for a maximum flux density of 1.4T. 18 / 93 Transformer under loaded condition • In Fig., if the switch S is closed, a load impedance ZL gets connected across the secondary terminals. Since the secondary winding resistance is zero, V2 = E2 . • When load is connected at secondary side, due to induced voltage, E2 current I2 will flow and it can be determined by the magnitude and phase angle of the impedance ZL . • As soon as current I2 starts flowing in the secondary current, by the Lenz’s law the induced current opposes the cause that produces it. That is, it will establish a flux which is opposite to the flux ϕ established by the coil 1. Figure 5: Magnetic circuit 19 / 93 Transformer under loaded condition • As a result of which, the total flux linking coil 1 will become ϕm = ϕ1 − ϕ2 . The total flux linking coil 1 will reduce. Hence E1 will reduce. • For an ideal transformer, V1 = −E1 and, therefore, mutual flux ϕm in the core must remain constant. • However there is no impedance between the applied voltage and the coil. There will be current I1 drawn from the source of such magnitude so that the induced voltage E1 of coil 1 always balances the applied voltage V1 . • ϕm = ϕ1 − ϕ2 ⇒ N1 I´1 = N2 I2 ( To keep the net flux ϕm constant). • Here I´1 is called the load component of primary current I1 . • Assuming I2 to lag behind V2 by an angle θ2 , the phaser diagram under load for an ideal transformer can be drawn as shown in Fig. 20 / 93 Transformer under loaded condition • Since F1 and F2 tend to magnetize the core in opposite directions, they are shown in phase opposition. • The total primary current I1 is the phasor sum of I´1 and Iϕ , i.e., I1 = I´1 + Iϕ . • The power factor on the primary side of ideal transformer is cos θ1 . • If the magnetizing current Iϕ is neglected, the following can be written I1 N1 = I2 N2 . • I1 = ( N2 )I2 = I´2 =Reflected Load Current N1 21 / 93 Transformer under loaded condition Figure 6: Phasor Diagram 22 / 93 Phasor diagram for a loaded transformer • With this assumption, it follows that the secondary terminal voltage V2 is the same as the e.m.f. E2 induced in the secondary, and the primary applied voltage V1 is equal to the e.m.f. E1 induced in the primary winding. Also, if we again assume equal number of turns on the primary and secondary windings, then E1 = E2 . • Let us consider the general case of a load having a lagging power factor cos ϕ2 ; hence the phasor representing the secondary current I2 lags V2 by an angle ϕ2 . Figure 7: Phasor diagram for a loaded transformer having negligible voltage drop in windings 23 / 93 Phasor diagram for a loaded transformer • Phasor I´2 represents the component of the primary current to neutralize the demagnetizing effect of the secondary current and is drawn equal and opposite to I2 . Here I´2 is described as ‘I2 referred’; I0 is the no-load current of the transformer. • The phasor sum of I´2 and I0 gives the total current I1 taken from the supply, and the power factor on the primary side iscos ϕ1 , where ϕ1 is the phase difference between V1 and I1 24 / 93 Modelling of a Practical Transformer The behaviour of a transformer may be conveniently considered by assuming it to be equivalent to an ideal transformer, i.e. a transformer having no losses and no magnetic leakage and a ferromagnetic core of infinite permeability requiring no magnetizing current. Now allowing for the imperfections of the actual transformer by means of additional circuits or impedances inserted between the supply and the primary winding and between the secondary and the load. Winding resistances: Since the windings consist of copper conductors, it immediately follows that both primary and secondary will have winding resistance. The primary resistance R1 and secondary resistance R2 act in series with the respective winding. 25 / 93 Equivalent Circuit of a Transformer considering only winding resistance Figure 8: Equivalent Circuit considering only winding resistance 26 / 93 Equivalent Circuit of a Transformer considering leakage reactance • In practical transformer, the flux of each limb has to return through air. Since the flux of each limb is linked only with the winding by which it is produced, it is referred to as leakage flux and is responsible for inducing an e.m.f. of self-inductance in the winding with which it is linked. 27 / 93 Equivalent Circuit of a Transformer considering leakage reactance Figure 9: Equivalent Circuit considering only winding resistance 28 / 93 Equivalent Circuit of a Transformer considering leakage reactance • Let ϕℓ1 and ϕℓ2 are the leakage flux in the primary and secondary coil respectively. • Total flux linking in coil 1: ϕ1 = ϕm1 + ϕℓ1 − ϕm2 . • Similarly, total flux linking coil 2: ϕ2 = ϕm1 − ϕm2 − ϕℓ2 . • Voltage induced in coil 1: N1 d dϕℓ1 dϕ1 = N1 (ϕm1 − ϕm2 ) + N1 dt dt dt dϕℓ1 = e1 + N1 dt • Voltage induced in coil 2: N2 dϕ2 dϕℓ2 = e2 − N2 dt dt 29 / 93 Equivalent Circuit of a Transformer considering leakage reactance • Considering N1 I1 Rℓ1 N2 I2 ϕℓ2 = Rℓ2 ϕℓ1 = • We can write dϕℓ1 di1 N 2 di1 = 1 = ℓ1 dt Rℓ1 dt dt 2 dϕℓ2 N di2 di2 N2 = 2 = ℓ1 dt Rℓ2 dt dt N1 Here, N12 = ℓ and N22 = ℓ are the leakage inductance at primary and secondary 30 / 93 Equivalent Circuit of a Transformer considering leakage reactance • Using these di1 dϕ1 = e1 + ℓ1 dt dt dϕ2 di2 N2 = e2 − ℓ2 dt dt N1 • Finally, considering the winding resistance and leakage inductances di1 + e1 dt di2 e2 = v2 + R2 i2 + ℓ2 dt v1 = R1 i1 + ℓ1 31 / 93 Equivalent Circuit of a Transformer: winding resistance and leakage inductances Figure 10: Equivalent Circuit 32 / 93 Equivalent Circuit of a Transformer considering leakage reactance • The no-load current of the transformer I0 consists of two components: i) Magnetization current Im produces flux in the transformer core ii) Core loss current Ic to make up the hysteresis and eddy current losses. • The magnetizing current Im ∝ V1 and lagging V1 by 90◦ . It can be modelled by a reactance X0 connected across the V1 . • Core loss current Ic ∝ V1 in phase with V1 . It can be modelled as resistance R0 connected across the V1 . 33 / 93 Equivalent Circuit of a Transformer Figure 11: Equivalent Circuit 34 / 93 Phasor Equations V1 = R1 I1 + jX1 I1 + E1 = I1 Z1 + E1 E2 = R2 I2 + jX2 I2 + V2 = I2 Z2 + V2 V2 = ZL I2 E1 Im = jX0 E1 Ic = R0 N2 E2 = E1 N1 N2 I´2 = I2 N1 35 / 93 Phasor Diagram Figure 12: Phasor diagram for lagging power factor of the load 36 / 93 Equivalent Circuit of a Transformer • Circuit model of transformer shown in Fig. 11 is not suitable for applying any known circuit analysis technique since the ideal transformer is present between primary and secondary. • Hence we cannot write the KVL/KCL considering the entire loop of the transformer, since we don’t know the voltage drop across the ideal transformer. • Therefore, it will be more convenient if we eliminate this ideal transformer and this can be done by referring the secondary of the ideal transformer to the primary or referring primary of the ideal transformer to the secondary. 37 / 93 Equivalent Circuit of a Transformer: referring the secondary of the ideal transformer to the primary • By referring , we mean that we want to connect an equivalent circuit across the terminals of the ideal transformer at primary side such that the current drawn by the equivalent ′ circuit is same as I2 as it is for ideal transformer. • The current I2 = E2 ZL + R2 + jX2 ′ 2 • Now considering, I2 = N N I2 , we can write 1 ′ I2 = N2 N1 E2 2 2 N1 (N N1 ) N2 E2 = ZL + R2 + jX2 ZL + R2 + jX2 E1 = N ( N1 )2 (ZL + R2 + jX2 ) 38 / 93 Equivalent Circuit of a Transformer (Contd..) • The last equation indicates that the voltage across the two terminals of the primary side ′ is E1 and the current drawn from this terminals is I2 . ′ 1 2 • The same current I2 will flow provide the impedance of ( N N2 ) (ZL + R2 + jX2 ) is connected across the primary side. • Referred parameters at primary side: ′ ′ ′ R2 = X2 = ZL = N1 N2 2 N1 N2 2 N1 N2 2 R2 X2 ZL 39 / 93 Equivalent Circuit:referring the secondary of the ideal transformer to the primary Figure 13: Equivalent Circuit 40 / 93 Is the equivalent circuit preserves the power relation? • Actual power loss in the secondary circuit is I22 R2 . The power loss with referred variables ′ ′ I22 R2 . We can write N2 ′ I2 = I2 N1 2 N1 ′ R2 = R2 N2 ′ ′ • ∴ I22 R2 = I22 R2 . Hence power relationship is preserved. 41 / 93 Is the equivalent circuit preserves the kVA relation of load circuit? ′ • Referred secondary voltage V2 ′ ′ ′ V2 = I2 ZL = = ′ N2 N1 I2 N1 N2 2 ZL N1 V2 N2 ′ N1 2 • Now I2 = ( N N )I2 and V2 = ( N )V2 . Therefore, 1 ′ ′ 2 • Therefore, V2 I2 = V2 I2 . So the kVA consumed by the referred load circuit is same as the KVA original load circuit. 42 / 93 Equivalent Circuit:referring the primary of the ideal transformer to the secondary Figure 14: Equivalent Circuit 43 / 93 Equivalent Circuit:referring the primary of the ideal transformer to the secondary • The secondary voltage E2 = I2 (ZL + R2 + jX2 ) ′ ′ ′ ′ E2 = V1 − I1 (R1 + jX1 ) ′ ′ ′ ′ 1 • Therefore, I2 (ZL + R2 + jX2 ) = V1 − I1 (R1 + jX1 ). Multiplying both side by ( N N ), 2 N1 N1 ′ ′ N1 ′ − I (R + jX1 ) = I2 (ZL + R2 + jX2 ) N2 N2 1 1 N2 2 N1 ′ ′ N2 N1 N1 ′ ′ (ZL + R2 + jX2 ) V1 − I1 (R1 + jX1 ) = I2 N2 N2 N1 N2 h ′ i ′ ′ ′ = I2 ZL + R1 + jX1 ) = E1 = V1 − I1 (R1 + jX1 ) ′ V1 44 / 93 Equivalent Circuit:referring the primary of the ideal transformer to the secondary • Now, comparing N1 N2 ′ V1 − N1 N2 ′ ′ ′ I1 (R1 + jX1 ) = V1 − I1 (R1 + jX1 ) ′ ′ N1 2 • from the above, the following relation can be written V1 = N V1 or V1 = N N V1 ′ ′ ′ 2 1 • Power consumed by R1 and R1 must be same I12 R1 = I12 R1 . This will be ensured if N1 ′ I1 = I1 N2 2 N1 ′ R1 = R1 N2 2 ′ N1 • Similarly, X1 = N X1 . 2 45 / 93 Equivalent Circuit:referring the primary of the ideal transformer to the secondary 2 2 R0 0 • Power balance to be maintained at the shunt branches E2′ = ER1 or R0 = E2 N2 E1 = N1 . ′ • R0 = N2 N1 ′ E2 E1 2 R0 . But 2 R0 . 2 ′ N2 • Similarly, X0 = N X0 . 1 ′ ′ ′ N1 N1 1 • Also, I0 = N I , I = I and I = 0 c c m N2 N2 N2 Im 46 / 93 Summary Secondary referred to primary ′ • I2 = N2 N1 I2 ′ 1 • V2 = N N2 V2 2 ′ 1 • R2 = N R2 N2 2 ′ 1 • X2 = N X2 N2 2 ′ 1 • ZL = N ZL N2 Primary referred to Secondary ′ 2 I1 and V1 = N N1 V1 ′ ′ N1 1 • I0 = N = I and I 0 c N2 N2 Ic ′ 1 • Im = N N2 Im 2 ′ 2 • R1 = N R1 N1 2 ′ N2 • X1 = N X1 1 2 ′ 2 • X0 = N X0 N1 2 ′ 2 • R0 = N R0 N1 ′ • I1 = N1 N2 47 / 93 Problem Figure 15: Single Phase Transformer 48 / 93 Problem Figure 16: Equivalent Circuit Find V2 , I2 , I1 , I0 . 49 / 93 Solution Figure 17: 50 / 93 Solution Figure 18: Equivalent Circuit referred to primary 51 / 93 Solution Figure 19: Thevenin’s Equivalent Circuit 52 / 93 Few Salient Features of Equivalent Circuit • Applied Voltage is 230∠0◦ and VTH = 229.1∠0◦ . Is this very different from the applied voltage? • The actual impedance at primary is 0.75Ω + j0.8Ω. The Thevenin’s equivalent resistance is ZTH = 0.7461 + j0.7978. • Therefore, it is possibly make sense in order to reduce the computational complexity to obtain this Thevenin’s equivalent circuit simply omitting the parallel path and connecting across the supply voltage. In fact that is done in most practical cases. Now, the exact equivalent circuit is simplified by approximate equivalent circuit. 53 / 93 Approximate equivalent circuit: Secondary Referred to primary Figure 20: Approximate equivalent circuit Figure 21: Approximate equivalent circuit 54 / 93 Approximate equivalent circuit: Primary Referred to Secondary 2 ′ ′ 2 • Req = N Req = R2 + R1 = N1 2 N2 R2 + N R1 1 2 ′ ′ N2 • Xeq = N Xeq = X2 + X1 = 1 2 2 X2 + N X1 N1 2 2 ′ ′ N2 N2 • R0 = N R ; X = X0 0 0 N1 1 ′ ′ N2 1 • V1 = N V1 ; V2 = N N V2 1 ′ 2 ′ N2 1 • I1 = N N I1 ; I2 = N I2 2 1 Figure 22: Approximate equivalent circuit 55 / 93 Testing of Single Phase Transformer • The transformer equivalent circuit whether represented by secondary referred to primary or primary referred to secondary, useful only if one knows the values of the parameters. • Now, therefore it is important to be able to determine transformer equivalent circuit parameter either from design data or carry out certain test/ experiment. • It is possible to estimate the parameters of the transformer from the dimensions and the design data. However, most cases the users will not have access such design data and also the design data gives a first approximation of the parameters. In order to get the accurate values, user must conduct certain test on transformer. • There are two tests normally used to find out the equivalent circuit parameters of the transformer. • No load Test: which finds out the shunt branch paraments R0 , X0 . • Short Circuit Test: which finds the series branch parameters Req , Xeq . 56 / 93 No Load Test/ Open Circuit Test • In order to do the no load test, a voltmeter, wattmeter and an ammeter are connected on the low voltage side of the transformer. • The high voltage side is left open circuited. • The variac is started from zero voltage position and the voltage supplied by the variac is slowly raised till the voltmeter connected across the primary reads the rated volatge of L.V. winding. For example 110/220 Volt transformer, LV side voltage 110 volt and HV side voltage 220 volt. • Under this condition, take the readings: V1 , I0 and W0 . Where voltmeter readings gives V1 gives LV side applied voltage, ammeter reading I0 gives no load current and wattmeter reading W0 gives core loss or iron loss. • Now, how to use no load test data to find out shunt branch parameters? 57 / 93 Circuit diagram for open circuit test Figure 23: Circuit diagram for open circuit test 58 / 93 At no load the transformer equivalent circuit and phasor diagram Figure 24: equivalent circuit Figure 25: Phasor diagram 59 / 93 No Load Test/ Open Circuit Test From equivalent circuit, V1 • R0 = VI 1 = I cos ϕ (using phasor diagram) c 0 0 V1 • X0 = VI 1 = I sin ϕ0 (using phasor diagram) m 0 • Now, W0 = V1 I0 cos ϕ0 . ∴ cos ϕ0 = VWI0 and sin ϕ0 = 1 0 p 1 − cos2 ϕ0 . • Therefore R0 = X0 = V1 V2 = 1 I0 cos ϕ0 W0 V1 ; sin ϕ0 = I0 sin ϕ0 s 1− W02 . V12 I02 • As the test is performed at L.V. side, the values of R0 and X0 will be referred to L.V. side. 60 / 93 Short Circuit Test • Using this test we can find out the series branch parameters Req , Xeq . • The low voltage side of the transformer is short circuited and the instruments are placed on the high voltage side. • The applied voltage is adjusted by variac, to circulate rated current in the high voltage side. 61 / 93 Circuit diagram for short circuit test Figure 26: Circuit diagram for short circuit test 62 / 93 Short Circuit Test • How do we find out the series branch parameters from the short circuit test. Let us draw the approximate equivalent circuit for short circuit test. • Even Vs is at rated voltage , I0 is 5 to 7% of the rated current, Is . • Therefore, when we reduce Vs in order to have Is and short the L.V. side and f Is is restricted to its rated value , the voltage Vs is required to send I0 will be very small/ negligible current. • Hence, magnetization branch is neglected during short circuit test. 63 / 93 Approximate equivalent circuit of short circuit test Figure 27: Equivalent Circuit and phasor diagram 64 / 93 Short Circuit Test • Then we have very simple relation: Zs = q |Vs | 2 + X2 = Req eq |Is | • The power loss during short circuit test is entirely due to the series resistance. Therefore, Ws = Is2 Req Ws Req = 2 I qs 2 Xeq = Zs2 − Req • These values are referred to HV side. 65 / 93 Problem • A 20kVA, 2500/250V, 50Hz, single phase transformer gave the following test result • Open circuit test (on LV side): 250V, 1.4 A, 105 watts • Short circuit test (on HV side): 104V, 8A, 320 watts Compute the parameters of the approximate equivalent circuit referred to high-voltage and low voltage sides. Also draw the exact equivalent circuit referred to low-voltage side. 66 / 93 Solution 67 / 93 Efficiency of transformer • Certain performance parameters are important from users point of view. For transformer, Power the efficiency(η) is defined as η = Output Input Power . • Now, why there will be difference in output power and input power? It is due to losses. • In a practical transformer we have seen mainly two types of major losses namely core and copper losses occur. These losses are wasted as heat and temperature of the transformer rises. Therefore output power of the transformer will be always less than the input power drawn by the primary from the source. • Core Loss: These are hysteresis and eddy current losses. Core loss is constant for transformer operated at constant voltage and frequency. • Copper Loss (I 2 R-Loss): This loss occurs in winding resistances when the transformer carries the load current. Copper loss varies as the square of the loading expressed as ratio of the full load. • Major Losses i) Core loss (or Iron Loss)⇒ Pi = constant loss. ii) Copper loss ⇒ Pcu = variable loss. 68 / 93 Efficiency of transformer • For practical transformer, efficiency(η) is defined as: Output power in KW Output power in KW + Losses Output power in KW = Output power in KW + Core Loss+ Copper Loss η= • It can be shown that from no load to the full load condition the core loss, Pi remains practically constant since the level of flux remains practically same. • On the other hand we know that the winding currents depend upon the degree of loading and copper loss directly depends upon the square of the current and not a constant from no load to full load condition. 69 / 93 Efficiency of transformer ′ • Copper loss in the two windings are: Cu-Loss = (I2 )2 R1 + (I2 )2 R2 . !2 ′ I ′ 2 R1 I22 (I2 ) R1 + (I2 )2 R2 = R2 + 2 I2 " 2 # N2 R1 I22 = R2 + N1 ′ = Req I22 ′ Here, Req is the equivalent resistance referred to secondary. • Let, x = I I2 , where I2,fl is the full load current at secondary side. 2,fl • I2 = xI2,fl . (full load is meant the load (obviously, on secondary) which would make transformer transfer it’s rated power from primary to secondary.) ′ ′ 2 R ′ = x2 P . Where P 2 • Now, copper loss=Req (xI2,fl )2 = x2 I2,fl cu cu = I2,fl Req = full-load eq cu-loss. Pcu is the wattmeter reading during short-circuit test. 70 / 93 Efficiency of transformer • Output power of the transformer = V2 I2 cos ϕ = xV2 I2,fl cos ϕ = xPfl where Pfl = V2 I2,fl cos ϕ= full load output. Efficiency at any fractional load x, xPfl xPfl + Pi + x2 Pcu x(kVA)RATED cos ϕ = x(kVA)RATED cos ϕ + Pi + x2 Pcu ηx = • Here, Pi is the wattmeter reading during no load test. 71 / 93 When Efficiency will be maximum? • For efficiency to be maximum, d(Denominator) is set to zero and we get dx d Pi Pfl + + xPcu = 0 dx x Pi − 2 + Pcu = 0 x Pi x2 = Pcu q • The fractional load at which the efficiency will be maximum x = PPi . Thus we see that cu for a given q power factor, transformer will operate at maximum efficiency when it is loaded to core Pi Pcu (kVA)RATED . • For transformers intended to be used continuously at its rated kVA, should be designed such that maximum efficiency occurs at x = 1. That is, core-loss=cu-loss. Power transformers fall under this category. 72 / 93 Discussion • However for transformers whose load widely varies over time, it is not desirable to have maximum efficiency at x = 1. Distribution transformers fall under this category and the typical value of x for maximum efficiency for such transformers may between 0.75 to 0.8. • Figure shows a family of efficiency Vs. degree of loading curves with power factor as parameter. It canq be seen that for any given power factor, maximum efficiency occurs at a loading of x = Pi Pcu . • Efficiencies ηmax1 , ηmax2 andηmax3 are respectively the maximum efficiencies corresponding to power factors of unity, 0.8 and 0.7 respectively. • It can easily be shown that for a given load (i.e., fixed x), if power factor is allowed to vary then maximum efficiency occurs at unity power factor. 73 / 93 Efficiency VS degree of loading curves Figure 28: Efficiency VS degree of loading curves 74 / 93 Voltage Regulation • In a single phase transformer, the supply voltage at primary is constant with constant frequency. In most cases the load is like to see the a constant voltage across the load which is independent of load current I2 . • However, in a practical transformer usually it is not the case. There will be some variation in load voltage depending on load current. • This can be predicted from the approximate equivalent circuit which we referred to load side (secondary). ′ • Obviously, V2 will not be same as V1 for all values of I2 because there will be internal voltage drop in the series leakage impedance of the transformer and the magnitude of which will depend upon the degree of loading as well as on the power factor of the load. 75 / 93 Approximate equivalent circuit: Primary referred to secondary Figure 29: Approximate equivalent circuit 76 / 93 Voltage Regulation • The knowledge of regulation gives us idea about change in the magnitude of the secondary voltage from no load to full load condition at a given power factor. • This can be determined experimentally by direct loading of the transformer. To do this, primary is energized with rated voltage and the secondary terminal voltage is recorded in absence of any load and also in presence of full load. • Suppose the readings of the voltmeters are respectively V2,0 and V2,f ℓ . Therefore change in the magnitudes of the secondary voltage is V2,0 –V2,f ℓ . This change is expressed as a percentage of the full load secondary voltage to express regulation. • Lower value of regulation will ensure lesser fluctuation of the voltage across the loads. If the transformer were ideal regulation would have been zero. 77 / 93 Voltage Regulation • Definition: The voltage regulation of transformer is defined as the net change in the secondary terminal voltage from no-load to full load, expressed as a percentage of its rated voltage. • % voltage regulation= V2,0V–V2,f ℓ × 100. 2,f ℓ • where V2,0 = secondary voltage when load is thrown off (i.e., V2,0 = E2 ). • and V2,f ℓ = Full-load secondary voltage ( it is assumed to be adjusted to the rated secondary voltage. • voltage regulation is figure of merit of transformer. For an ideal transformer voltage regulation is zero. • smaller is the voltage regulation, better is the operation of the transformer. • In order to calculate the % of regulation, we can neglect the shunt branch of the approximate equivalent circuit referred to secondary. The equivalent circuit for the calculation of % regulation is shown next 78 / 93 Approximate equivalent circuit: Primary referred to secondary Figure 30: Approximate equivalent circuit 79 / 93 Case-I: Unity Power Factor Load Figure 32: Phasor diagram 80 / 93 Case-II: Lagging Power Factor Load Figure 33: Phasor Diagram 81 / 93 Case-II: Lagging Power Factor Load 82 / 93 Case-II: Lagging Power Factor Load Figure 35: Phasor diagram Figure 34: equivalent circuit 83 / 93 Case-III: Leading Power Factor Load 84 / 93 Solved Numerical Problem A single-phase transformer has 1000 turns on the primary and 200 turns on the secondary. The no-load current drawn is 3A at a power factor 0.2 lagging. Calculate the total primary current and power factor at primary when the secondary is loaded to a current of 280 A at a power factor of 0.8 lagging. Assume the voltage drop in the windings to be negligible. 85 / 93 Solution 86 / 93 Problem A 4kVA, 200/400V, 50Hz, single phase transformer gave the following test result • Open circuit test (on LV side): 200V, 0.7 A, 35 watts • Short circuit test (on HV side): 30V, 10A, 90 watts a) Compute the parameters of the approximate equivalent circuit referred to high-voltage and low voltage sides. b) Calculate the efficiency at 100% of the load with 0.8 power factor. c) Calculate the efficiency at 50% of the load with 0.8 power factor. 87 / 93 Solution 88 / 93 Problem • A 500 kVA transformer has an efficiency of 95 % at full-load, and the same efficiency also at 60 % of full-load; both loads at upf (unity power factor) . a) Compute the iron and copper losses of the transformer. b) Determine the efficiency of the transformer at 3/4th of full-load. 89 / 93 Solution 90 / 93 Problem 91 / 93 Solution 92 / 93 The End 93 / 93
0
You can add this document to your study collection(s)
Sign in Available only to authorized usersYou can add this document to your saved list
Sign in Available only to authorized users(For complaints, use another form )